Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange



Similar documents
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Inverter and programmable controls in heat pump applications

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

Energy savings in commercial refrigeration. Low pressure control

Why and How we Use Capacity Control

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

GPC. How do I call up the bid text for a selected unit? Why does the GPC calculate the surface reserve and not the capacity reserve?

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

Research on the Air Conditioning Water Heater System

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

DAikin Altherma low temperature heat pump. end user leaflet

5-21kW. Ecotel Indoor Range. - 21kW. > Ecotel Indoor Range. Typical Applications

Basic Technology Series

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Integrated solutions for ground source heat pumps

How to choose a heat pump and use it wisely

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

Development and testing of a multi-type air conditioner without using AC inverters

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System


ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ROTEX Gas-Hybrid-Heat Pump

Cooling kw Heating kw

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

Low GWP Replacements for R404A in Commercial Refrigeration Applications

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Natural gas heating versus split system heating and the current and future viability of the Natural gas network

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Daikin Altherma. hybrid heat pump. The natural combination

your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.

AUTOMOTIVE AIR CONDITIONING SYSTEM.

Domestic Heating Energy Savings with Better Controls

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity

Transcritical CO2 booster system How to control the system

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction

Waste Heat Recovery through Air Conditioning System

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

Simple and Convenient Individual Control

User manual. Application program for pco 1, pco 2, pco 3. Standard Chiller Modular HP 1/4 Generic /Bitzer screw compressor and CAREL valve

Hot Water. Heat pump water heaters. Residential and Commercial R410a

ROTEX gas hybrid heat pump. A strong team.

Screw Compressors ESM Fixed Speed & VS Variable Speed

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

ELECTRICAL ENERGY REDUCTION IN REFRIGERATION AND AIR CONDITIONING Ken Landymore, Director of Operations, Smartcool Systems Inc.

Daikin Altherma hybrid heat pump. The natural combination

The natural ombination

Increasing the evaporation temperature with the help of an internal heat exchanger

The natural ombination

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

The natural ombination

Heating, ventilation and air conditioning (HVAC) equipment. A guide to equipment eligible for Enhanced Capital Allowances

For every mission, there is a Vector. VECTOR

BOGE AIR. THE AIR TO WORK. CONTROLS

pco 2 Standard Application Pack Control Code: FLSTDMFC0A Version 1.2 s manual

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

SMM. Installation Operation Maintenance

Screw Compressors 11-22kW

Experimental Analysis of a Variable Capacity Heat Pump System Focusing on the Compressor and Inverter Loss Behavior

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

AIR-COOLED CHILLERS APPLIED SYSTEMS. EUWA*5-24KAZW - EUWY*5-24KAZW -

AircoSaver Energy Savings for At&t Mobility San Diego

Drives and motors. A guide to using variable-speed drives and motors in retail environments

Portable Compressors MOBILAIR M 270 With the world-renowned SIGMA PROFILE Free air delivery 20.0 to 26.9 m³/min.

A Cover HVAC ENERGY EFFICIENT

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

News in Data Center Cooling

HEATING, VENTILATION & AIR CONDITIONING

Tech Byte 27: Small Computer Room and IT Closet Cooling

Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests

How To Save Energy With High Pressure Control

Federation of European Heating, Ventilation and Air-conditioning Associations

Creating Efficient HVAC Systems

Natural geothermal energy.

Silicagel-water adsorption cooling prototype system for mobile air conditioning

Computer Controlled Capacity Control Methods in Refrigeration, with SCADA and PID Control THARA2C/1

Vitocaldens 222-F Compact Gas-Hybrid appliance

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges

INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling ,000 kw

Hiwall Hiross for Telecom. High Performance Air Conditioning

Secondary Loop Chilled Water In Super High-Rise

WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS

LG Electronics AE Company, Commercial Air Conditioning

Chapter 3.4: HVAC & Refrigeration System

Test Report issued under the responsibility of:

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

UNIT 2 REFRIGERATION CYCLE

Unico Inverter. Unique and efficient.

How does solar air conditioning work?

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER

Field test of a novel combined solar thermal and heat pump system with an ice store

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

Transcription:

Intelligent control system with integrated electronic expansion valves in an air-conditioning system operating at a Telecom telephone exchange ING. TOMMASO FERRARESE Thermodynamics Laboratory Engineer - CAREL S.p.A. ING. BIAGIO LAMANNA Thermodynamics Laboratory Manager - CAREL S.p.A. ING. GIANLUIGI BACILIERI Energy System Area Manager - TELECOM ITALIA S.p.A ABSTRACT In the control of the air-conditioning systems for mobile and fixed line telephone exchanges, given the cooling capacities involved, the priority is now focused on intelligent and integrated systems that can ensure perfect ambient temperature control and reduced electricity consumption of the air-conditioners. From this viewpoint, a complete system was developed for the control and monitoring of the direct expansion air-conditioners installed at a fixed line telephone exchange operated by Telecom Italia, for the purpose of achieving a reduction in power consumption and better control over the ambient temperature compared to traditional technology. To do this, the eight air-conditioners (total capacity 120 kw) were fitted with controllers operating in master-slave mode that through centralised intelligence ensure constant temperature control with the minimum number of compressors operating at any one time. Moreover, each air-conditioner was fitted with an electronic expansion valve managed by the control system that maximises the efficiency of the unit, especially during operation in winter. The performance of this system was monitored and compared against the existing control system based on a zone PLC and air-conditioners fitted with thermostatic expansion valves. The system was monitored over the period from January to July 2006, and based on the results a model was established for estimating the annual power consumption of the system in question.

1. INTRODUCTION Energy saving is now more and more important in all air conditioning applications where energy consumption is a large portion of the total running cost. A typical example is the air-conditioning of telephone exchanges, where both low energy consumption and precise temperature control are key issues to be achieved with the most efficient control system. For this reason, Carel and Telecom planned a joint to monitor the power consumption and cooling efficiency of a direct expansion air conditioning installation in a fixed line telephone exchange in the north of Italy, and to compare the existing traditional control system against a new complete and integrated solution. The installation consists of 8 air conditioners made by 2 different manufacturers, with a total cooling capacity of 120kW, reciprocating compressors and remote condenser with fan speed control (phase cutting). The air conditioners are configured to ensure a constant temperature of 29.5 C in the room with a constant load of 950A@53.3Volt (51kW) due to the telephone equipment, 43x36W (1.5kW) due to lighting system and variable load due to outside air infiltration and solar radiation. 2. CONTROL SYSTEMS Before the beginning of the monitoring period, all the air conditioners were restored to the design working configuration by replacing the old thermostatic expansion valves with new ones and refilling the refrigerant to the nominal charge. Carel integrated solution Carel has developed a complete and integrated control system based on a Master-Slave communication: the Master controller can share data with the other 7 Slave controllers and manage the activation of all the compressors and fans using an intelligent algorithm.. By using a PID control algorithm with a room temperature set point of 29.5 C, the Master controller measures the average room temperature and performs a real time calculation of the exact cooling capacity required. In this way, the number of fans and compressors operating is continuously adapted to the changes in load, avoiding periods with excessive cooling capacity (inefficient frequent on-off duty) or periods with insufficient cooling capacity. Each air conditioner is fitted with a electronic expansion valve installed together with the existing thermostatic mechanical valve in two parallel liquid lines that can be activated alternatively using solenoid valves. The valve driver is connected to the main controller to ensure the full integration of the system. Existing controllers The installation is controlled by a PLC that can enable or disable each air conditioner following a concept based on activation bands referred to the room temperature. Each unit is permanently assigned to a precise band.

This means that some units are always on (first band), some are enabled in the first control band (28-29 C), others in the second control band (29-30.5 C) and the last is enabled in the event of a temperature alarm (>30.5 C). Overall, the PLC controller can not ensure a constant room temperature, as it does not feature integral control and its logic is fixed and not adaptable to load changes. Consequently, there are some periods with a room temperature lower than needed, with excessive cooling capacity and frequent on-off duty of the air conditioners (winter), and some periods where the room temperature is higher than the setpoint. During PLC control, all the air conditioners are forced to work with thermostatic expansion valves for complete comparison between the two solutions. 3. ENERGY SAVING DUE TO THE INTEGRATED SOLUTION Advanced Master-Slave control ensures a stable room temperature around the required setpoint with the exact number of units running calculated by the master controller. This means that on-off cycles are limited and the air conditioners can work for longer periods with nominal COP. The PLC control system (or stand alone units in general) easily lets the units run with frequent on-off cycles, giving a lower average COP due to poor performance in the first few minutes after the compressor starts. The integration with the electronic expansion driver can also lower the period required to reach the nominal duty of the unit, setting the exact valve position at unit start-up. A Master-Slave architecture is also more reliable thanks to the multi-master procedure that allows each unit to become a Master in the event of malfunctions. Furthermore, stress on mechanical components (mainly compressors) is reduced and unit rotation can equalise working duties. The use of the electronic expansion valve controlled by a sophisticated PID algorithm can increase the units COP by optimising the refrigerant flow in the evaporator (lower average superheat compared to a mechanical thermostatic valve). Thanks to the wide control range (10-100%), it also brings a reduction in energy consumption due to lower condensing temperature control when the outside temperature conditions are suitable. The compressor performance in terms of cooling efficiency and COP is in fact higher, with a lower pressure difference between the inlet (evaporating) and outlet (condensing). The superheat will be always controlled at the nominal setpoint both in summer, with a high condensing temperature (up to 21 bar), and in winter (down to 10 bar). Thermostatic valves normally force the unit controller to maintain the nominal conditions both in winter and summer, due to the limited working range and the poor adaptability of the mechanics. As a result, the condensing pressure will be controlled at a constant 17 bar setpoint irrespective of the outside temperature.

4. TEST CONDITIONS The purpose of the monitoring test is to compare the two different technologies, and was performed by automatically switching all the units from the system to PLC-TEV control every 24 hours. In this way, each technology statistically worked in every condition for the same amount of time. Cooling demand is represented by the constant contribution of the electronic equipment and the variable contribution of the outside weather conditions that affect room temperature and the air conditioner condensing pressure and COP. The test is based on the power consumption measurement using a power meter connected to the real time monitoring system. The installation was monitored from January to July 2006. The power consumption for the rest of the year was calculated using a model based on the outside temperature provided by the nearest weather station and on the measured data referred to the related working conditions. 5. TEST RESULTS From the data gathered we first of all saw better room temperature control with the system (Figures 1 and 2), due to the PID algorithm that allows stable and precise control around the required 29.5 C. The simple PLC proportional band control brings both an uncertain average temperature in the room and often poor stability due to the continuous start-stop behaviour of the air conditioners, especially when room cooling demand is low. Secondly (Figure 3), we measured constant differences in superheat and generally air conditioner performance when using the electronic expansion valves: both unit stability and average cooling capacity were normally higher compared to the data measured using thermostatic valves in each period of the year. Figure 4 and 5 show both the recorded data (January to July) and the extrapolated data of energy consumption and energy saving achieved with this technology. 6. DETAILS ON ENERGY SAVING ISSUES To separately evaluate the contribution associated with Master-Slave control and the user of the electronic expansion valve in the total energy saving, we considered that generally the better cooling efficiency of the air conditioning units is due to the use of electronic valves. We calculated the unit cooling efficiency by measuring the temperature difference between the evaporator air inlet and outlet with constant air flow. We considered 4 units (2 made by each manufacturer) and we measured the air temperature difference in the same outside and inside ambient conditions for both electronic and thermostatic mechanical expansion valves. The difference in shown in Table 1, for certain outside temperature conditions: as already explained, with lower outside temperature, the

contribution of the electronic expansion valve reaches its maximum value of energy saving, due to the reduced compressor operation. It can be observed that with the same condensing pressure, electronic expansion valves are still 3-4% more efficient due to better evaporator control (lower superheat and more stable evaporation) We assumed that this difference directly affects the power consumption of the system, considering that the room temperature is the same in both technologies, and better efficiency means lower consumption to reach the same temperature setpoint. The contribution of Master-Slave control relates to the difference from the total energy saving. Figure 6 shows the profile of energy savings as a percentage during the year for both contributions, compared against the traditional system.. 7. CONCLUSIONS After six months of monitoring the installation, we estimated an average annual energy saving of 28%, with maximum values reached during winter (36%) and minimum values in summer (21%). The Master-Slave system gives an almost constant contribution (16%) by operating the air conditioners for longer periods at maximum efficiency and in more stable conditions. Electronic expansion valves further contribute to energy saving through precise superheat control and adaptability to lower condensing pressures during night and winter, with maximum values in winter (20%) and minimum in summer (4%). With a total cooling demand of 120kW and a total annual power consumption of 280,000 kwh with traditional technology, we found a total energy saving of 75,000 kwh per year, equal to a saving in running costs of 7,000 (at an energy cost of 0.09 /kwh ) and a consequent reduction in CO2 emissions of 38,000 kg per year. Final considerations: Integrated Master-Slave controllers (pco 3 series) can improve: Room temperature stability and control Air conditioner reliability by unit rotation, multi-master management and lower start-stop stress Energy saving of up to 16% constantly throughout the year Electronic expansion valves (E 2 V series) and drivers (EVD series) can improve: Air conditioner cooling capacity, COP, stability and reliability in general. Adaptability of the system to load changes both due to outside or inside conditions Energy saving from 4% (summer) to 20% (winter).

PLC+TEV pco + E 2 V Room temperature Compressor and fan duty Fig. 1 Comparison between room temperature management with both technologies. Room temperature Compressor and fan duty Fig. 2 Room temperature stability with Carel integrated control system (1 month).

Electronic expansion valve Thermostatic expansion valve Superheat Evaporation Fig. 3 Air conditioner superheat control with both technologies. 48 kw 44 kw 40 kw pco+eev PLC+TEV Average power consumption 36 kw 32 kw 28 kw 24 kw 20 kw 16 kw 12 kw 8 kw 4 kw 0 kw January February March April May June July August September October November December Fig. 4 Average annual power consumption profile with both technologies.

Power consumption 12000 kwh 11000 kwh 10000 kwh pco+eev PLC+TEV 9000 kwh 8000 kwh 7000 kwh 6000 kwh 5000 kwh 4000 kwh 3000 kwh 2000 kwh 1000 kwh 0 kwh -11 C -7 C -3 C 1 C 5 C 9 C 13 C 17 C 21 C 25 C 29 C Outside ambient temperature profile Fig. 5 Power consumption for annual temperature profile with both technologies. Energy saving 44% 40% 36% 32% 28% 24% 20% 16% 12% 8% 4% EEV saving Master-Slave management saving Total saving 36.0% 34.1% 31.2% 35.2% 31.9% 27.9% 26.8% 24.6% 22.8% 21.7% 22.0% 21.9% 0% January February March April May June July August September October November December Fig. 6 Carel system energy saving profile compared to the traditional system.

Outside ambient temperature TEV working condensing pressure EEV working condensing pressure EEV cooling capacity increment 5 17 11 17.5% 11 17 13 13.5% 22 17 17 4.0% 26 19 19 3.5% 31 21 21 3.4% Tab. 1 Increased cooling efficiency due to electronic expansion valves (EEV) against thermostatic expansion valves (TEV).