Large Energy Savings Per Installation VFDs for Large Chillers



Similar documents
Evaporative Cooling for Residential and Light-Commercial

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

Chapter 3.4: HVAC & Refrigeration System

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Optimization of Water - Cooled Chiller Cooling Tower Combinations

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment

Printing and Publishing Energy Savings Guide

Creating Efficient HVAC Systems

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

HVAC Systems: Overview

Appendix C. Minimum Equipment Efficiency Standards

*At the AHRI Standard flow rate of 3 gpm/ton, using today s efficient chillers, the ΔT is 9.3 F rather than the 10 F often assumed.

Why and How we Use Capacity Control

HVAC Efficiency Definitions

HVAC Made Easy - Selection Tips for Chiller Compressors

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

How To Design A Building In New Delhi

Heat Recovery In Retail Refrigeration

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

3/29/2012 INTRODUCTION HVAC BASICS

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

Tim Facius Baltimore Aircoil

Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement

Drives and motors. A guide to using variable-speed drives and motors in retail environments

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: Date: december 03, 2015 Supersedes: new Date: new

32VFD Variable Frequency Drives for Centrifugal Chillers

Modeling Guide for Daikin VRV in EnergyPro 6

Commissioning - Construction Documents (Page 1 of 6)

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Optimization of Industrial Refrigeration Plants: Including a Case Study at Stonyfield Farm Yogurt

How To Design A Refrigeration System

HVAC System Selection Criteria. RTSPco Technical department M.dadkhah

Thermal Coupling Of Cooling and Heating Systems

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

By Steven C. Severini, P.E., Member ASHRAE

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

Energy Efficiency Best Practice Guide Industrial Refrigeration

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

4. HVAC AND REFRIGERATION SYSTEM

Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc

Air Conditioning Clinic

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

8. Refrigeration. 4. Liquid. Refrigerant. 4. Liquid Refrigerant. Figure 8.1 Refrigeration system layout (single stage)

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

TRAINING, EXAMINATION AND CERTIFICATION

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

Optimizing Design & Control Of Chilled Water Plants Part 5: Optimized Control Sequences

Energy Efficiency: Integrated Design and HVAC Systems HEALTHCARE - TOP 5 GREEN BUILDING STRATEGIES

Open Cycle Refrigeration System

Research on the Air Conditioning Water Heater System

VACUUM REFRIGERATION SYSTEMS

Defining Quality. Building Comfort. Precision. Air Conditioning

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE ? SLIDE 1

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Making a world of difference. Turbocor centrifugal compressors for air-conditioning systems

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

Introduction. Motor Types

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

2015 C&I HVAC RETROFIT APPLICATION FOR PRESCRIPTIVE REBATES

Heating, Ventilation and Air Conditioning Rebate Catalog Saving energy for a brighter future

Centrifugal Fans and Pumps are sized to meet the maximum

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping

Data Center Environments

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Impact of Control System Technologies on Industrial Energy Savings

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Unidrive M Energy Savings

White Paper #10. Energy Efficiency in Computer Data Centers

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Hines Property Management, NYC

Second Place: Industrial Facilities or Processes, New

Dharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

Xcel Business Customers: Program and Rebate Summary

Heating & Cooling Efficiency

Drives and motors. A guide to using variable-speed drives and motors in data centres

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Variable-Speed Fan Retrofits for Computer-Room Air Conditioners

Transcription:

This article was published in ASHRAE Journal, June 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.tiaxllc.com. This article may not be copied nor distributed in either paper or digital form by other parties without ASHRAE s permission. For more information about ASHRAE, visit www.ashrae.org. Large Energy Savings Per Installation VFDs for Large Chillers This third column in a five-part series on variable frequency drives will cover application of VFDs to large chillers in commercial building air-conditioning systems. By John Dieckmann, Member ASHRAE; Kurtis McKenney; Matthew Guernsey; and James Brodrick, Ph.D., Member ASHRAE U sing variable frequency drives (VFDs) for compressor motors in large chillers is a newer application than using VFDs with blowers (discussed in last month s column). VFDs are being used with centrifugal compressors and screw compressors, the two major compressor categories for large chillers. Applying a variable speed drive to the compressor provides energy-efficient capacity modulation. While the focus of this series has been on using VFDs for induction motors, high-speed brushless dc motors are an important class of motors. Such motors generally are used to directly drive high-speed centrifugal compressors. Large tonnage chillers generally are capable of capacity modulation, which enables the chiller to run continuously while delivering constant-temperature chilled water as the cooling load varies from maximum to minimum design load. The traditional methods of capacity modulation have been: For centrifugal compressors, prerotation vanes, also called inlet guide vanes, reduce capacity while avoiding surge, down to around 40%. Hot gas bypass (directing compressor discharge gas to the evaporator) is used to reduce capacity further. Screw compressors have been equipped with slide valves that simultaneously vary the inlet displacement and the discharge displacement, maintaining a relatively constant built-in volume compression ratio, typically modulating down to about 30% of full load before hot gas bypass is needed for further capacity reduction. Staged operation of multiple compressors (or multiple chillers) has been used with both types of chillers, as well as with chillers that use other compressor types, such as scroll or reciprocating. Two metrics commonly used to rate the efficiency of chillers are full-load steady state performance and the integrated part load value (IPLV). The IPLV metric is intended to approximate typical seasonal performance as the load on the chiller varies. Figure 1 shows the air or water temperature entering the condenser versus load that is used to determine the IPLV for air-cooled and water-cooled chillers. In each case, reduced load is assumed to correlate with lower outdoor wet- and dry-bulb temperature, resulting in lower temperature of the cooling medium entering the condenser. The IPLV is a widely accepted metric for comparing the seasonal average performance of chillers. However, in actual applications, chillers operate over a much wider range of loads and condenser temperatures than the IPLV rating load-condenser temperature curves. Reasons for operation at low load percentage and higher condenser temperatures include high ambient wet or dry-bulb temperature coupled with low building occupancy or low solar loading and the general tendency to oversize building cooling equipment. Reasons for operation at high load percentage and lower condenser temperatures include high load during chiller start-up after an unoccupied period and operation of one of a set of multiple chillers to handle the building part load. The combination of chiller plant oversizing and the variation of the factors driving the cooling load (some of which can be highly variable, namely weather) can result in almost any combination of chiller load level and condenser temperature. Estimates suggest that more than 90% of water-cooled chiller plant installations include multiple chillers, with two being the most common number. 1 In multiple chiller plants, operation of any chiller below 50% load is unusual, with a large percentage of operating time occurring around the 75% load point or higher. 1 For multiple chiller plants, equipping each compressor with VFD may provide the greatest energy savings and/or operational flexibility, but it may be more economical (or at least less capital intensive) to apply VFD to the base load chillers or chillers expected to operate at part-load ( swing chillers ). Chillers that operate the most hours with reduced condenser water temperatures (i.e., reduced lift) and/ or reduced load will offer the greatest energy cost savings potential. Several factors account for the improvement in the IPLV provided by variable speed drives. Variable speed operation significantly reduces, if not eliminates altogether, the use of hot gas bypass for continuous operation at low load. In centrifugal chillers, variable speed combined with prerotation vanes enables operation 5 8 A S H R A E J o u r n a l a s h r a e. o r g J u n e 2 0 1 0

Advertisement formerly in this space.

100 F Temperature Entering Condenser 90 F 80 F 70 F 60 F 50 F Water-Cooled Air-Cooled IPLV Weighting: 12% 45% 42% 1% 40 F 0% 25% 50% 75% 100% Load Figure 1: Temperature of cooling air or water entering the condenser versus load and weighting factors for IPLV determination. Advertisement formerly in this space. closer to maximum compressor efficiency across a wide range of operating conditions. With screw compressors, it is possible to eliminate the slide valve, using speed variation to cover the full operating range at higher efficiency. There are many variables involved in determining seasonal energy performance. However, based on informal conversations with industry engineers, the typical energy savings over a cooling season provided by applying a VFD to a chiller is approximately 25%. 2 Additional benefits include improved power factor and soft starting of the chiller motor, reducing both impulse loading on the motor and large in-rush currents. Energy Saving Potential Space cooling in U.S. commercial buildings consumed 2.3 quadrillion Btus (quads) of primary electric energy in 2006. Of this, an estimated 0.3 quads are attributable to centrifugal and screw chillers in commercial and institutional buildings. If we assume, for the sake of simplicity, that VFDs are not widely implemented in large chillers, and that VFDs result in 25% average energy savings over conventional single-speed chillers, then VFD offers a technical energy savings potential for large chillers of approximately 0.1 quads. However, one manufacturer claims that VFDs are more prevalent now, indicating that 80% of centrifugal chillers with a VFD option available ship with a VFD. 2 This is a relatively low national energy savings potential relative to other VFD applications. However, the number of buildings with central chiller plants is only on the order of 100,000, 4 indicating there is a large amount of energy savings potential per installation. In large commercial buildings, the central chiller plant is often one of the main energy end uses, and therefore 25% savings on the chiller energy can represent a significant reduction in the building s overall operating costs. The 25% savings should not be assumed for any given application. For the reasons mentioned, the actual energy savings from using VFDs in chillers will vary widely from one installation to the next. Some applications with significant off-design operation may see energy reductions greater than 6 0 A S H R A E J o u r n a l J u n e 2 0 1 0

Advertisement formerly in this space.

35%, while applications with multiple chillers operating near design conditions, may experience energy savings of less than 15%. 2 Energy savings estimates for a single installation should rely on locationspecific factors, particularly weather. Chiller energy savings should only be modeled with respect to total chiller plant energy savings, which would also consider plant ancillary equipment. In a typical water-cooled chiller plant, the chiller accounts for approximately 85% of the system energy. 5 Market Factors Variable speed drives can offer significant energy savings when applied to the right chiller applications. Also, chillers with VFDs can exhibit improved reliability and life as a result of an improved power factor and soft starting of the chiller motor. However, real energy savings tend to be application-specific. VFDs can give the perception of energy savings when the IPLV formula is applied, particularly in buildings with multiple chillers, which is generally the case. 1 High-load operating points are noticeably more important than the IPLV metric may indicate. 1 Therefore, a more involved modeling process is necessary to determine the cost effectiveness of installing one or more VFDs in a chiller plant. The cost of VFD technology has dropped substantially over the past 30 years, and in many new designs, VFD technology is included in the base-unit design. 2 Several geographic regions offer rebates for the application of VFD technology. 2 Advertisement formerly in this space. References 1. Geister, R. and M. Thompson. 2009. A closer look at chiller ratings. ASHRAE Journal 51(12):22 32. 2. Communication with Johnson Controls. 3. Energy Efficiency and Renewable Energy. 2010. 2009 Buildings Energy Data Book. U.S. Department of Energy. http:// buildingsdatabook.eere.energy.gov/. 4. EIA. 2003. Commercial Building Energy Consumption Survey, Table B40. Energy Information Administration, U.S. Department of Energy. http://tinyurl.com/cbecs2003. 5. Furlong, J. and F. Morrison. Optimization of water-cooled chiller cooling tower combinations, CTI Journal 26(1):12 19. http://tinyurl.com/ctifurlong. 6. AHRI Standard 550/590-2003, 2003 Standard for Performance Rating of Water-Chilling Packages Using the Vapor Compression Cycle. 7. 2008 ASHRAE Handbook HVAC Systems and Equipment. Chapter 44, Motors, Motor Controls, and Variable-Speed Drives. John Dieckmann is a director, Kurtis McKenney is an associate principal, and Matthew Guernsey is a senior technologist in the Mechanical Systems Group of TIAX LLC, Cambridge, Mass. James Brodrick, Ph.D., is a project manager with the Building Technologies Program, U.S. Department of Energy, Washington, D.C. 6 2 A S H R A E J o u r n a l J u n e 2 0 1 0