Pilot-wire differential relay for lines with two or more terminals



Similar documents
Current and voltage measuring relays

Bus differential relay REB phase 1MRK BEN Page 1 Issued: September 2006 Revision: C Data subject to change without notice

Busbar differential protection

Voltage Regulator SPAU 341 C. Product Guide

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

Type SA-1 Generator Differential Relay

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Trip circuit supervision relay. Type RXTCS

Capacitor Protection Relay SPAJ 160 C. Product Guide

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Transmission Protection Overview

Circulating Current Relay. Type IRXm

T Substation Maintenance and Commissioning Test Equipment

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

Disturbance Recoder SPCR 8C27. Product Guide

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty Safety notes Policy Warranty.

Modular I/O System Analog and Digital Interface Modules

Power transformers. Special transformers Railway

Current Transformers Ratio / Polarity / Types

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

40 Series - Miniature PCB/Plug-in relays A. Features

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Safety technique. Emergency stop module BO 5988 safemaster

Product Guide. Low voltage grounding system. Answers for industry.

Manual Motor Starter MS 116 up to 16 A Technical Data

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Unified requirements for systems with voltages above 1 kv up to 15 kv

FREJA 300 Relay Testing System

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Power Meter Series 700

Generator Differential Relay Electrical Apparatus

Electronic overload relay EF65, EF96 and EF146

Circuit Breakers. NRC Series. NRC Series

15LINE PROTECTION WITH PILOT RELAYS

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Hyperlinks are Inactive

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Sentron Series Circuit Breakers

Permissible ambient temperature Operation Storage, transport

38 Series - Relay interface modules A

Relay mounting systems

Remote Monitoring and REC 501 Control Unit Product Guide

E-STOP relays, safety gate monitors

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Electronic overload relay EF19 and EF45

Vario-Series Accessories

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Eaton s E-Series protective relay family

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Properties of electrical signals

RM4TG20 three-phase network control relay RM4-T - range V

R.C.C.B. s two-pole LEXIC

Local Back-up Protection for an Electric Power System

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Three-phase monitoring relay CM-PFE

Wiring diagrams. Compact NSX. Contents

Bimetallic Overload Relay Specifications

Safety automation solutions

38 Series - Relay interface modules A

Contact expansion modules

Instrument Transformers Application Guide

Power Plant Electrical Distribution Systems

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Contact expander modules

Fundamentals of Power

Energy Management Energy Meter Type EM23 DIN

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

60 Series - General purpose relays 6-10 A. Features

Thermistor motor protection

3466 Building Energy Management Training Systems

E-STOP relays, safety gate monitors

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

S&C BankGuard PLUS Control

E-STOP relays, safety gate monitors

49 Series - Relay interface modules A. Features

5SV Residual Current Protective Devices

SECTION VARIABLE FREQUENCY DRIVES

Kit Watt Audio Amplifier

Actuator-Sensor-Interface

Section D..General Auto Electrical Corporation

Auxiliary Relay. Type P8n, PQ8n, PN8n

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits.

Transcription:

Pilot-wire differential relay for lines with two or more terminals Page 1 Issued: March 2003 Revision: A Data subject to change without notice Pilot-wire differential relay with RXHL 401 Features Phase and earth fault protection for cable and overhead lines Protect lines with High-speed operation (1-2 cycle) Stability ensured for external faults All line ends trip for fault current from single end Pilot-wire voltage limited to 60 V permits use of low cost communication wires (100V) 5 kv basic insulation level and 15 kv with pilot-wire isolating transformers 1000 ohms and 2 µf pilot-wire capacitance 2000 ohms and 0,7 µf with pilot-wire isolating transformers Direct trip contacts and trip flag indicator Test switch included Options: - Over current monitoring and back-up - Pilot-wire supervision - Three-phase/+earth overcurrent back-up functions (3 RXIDK 2H or RXHL 401/411) - Three-phase thermal overcurrent function (using RXHL 411) - Breaker failure current back-up function (using RXHL 411) - Reclosing up to four shots (option with RXHL411) Application The pilot-wire relays are used for protection of short to medium length cable or overhead lines. The relays use a dedicated metallic pilot-wire pair. The wire can be a normal low cost twisted pair communications wire. The shield may be aluminum laminated or copper wire type. The pilot-wire loop resistance is matched to 1000 or 2000 ohms. The standard relay can be applied to circuits with more than two line ends. Therefore three or more terminal applications are possible. The maximum length of a protected circuit is related to the total line charging current.the leakage current to ground must be limited to 10% of the rated primary current. The earthleakage current for a cable may be in the order of 5-15A per km, depending on network voltage and the type and size of cable. The most sensitive earth-fault detection of the relay is 25% of rated current. This may be fed from one end only, or divided between line ends. The three-phase fault sensitivity is 72% when fed from one end, or 36% when fed symmetrically from two ends. All line ends trip for a fault fed from a singleend. This makes the relay suitable for applications with weak infeed, since tripping of weak end is automatically performed.

Page 2 The relay is secure against power surges, outof-step and emergency loading conditions as it uses a balanced bridge principle for measurements. The operating principle offers also the advantage of one cycle (50/60Hz) operation. versions with current level monitoring relays are used to avoid tripping on load current when there is an open or defective pilot-wire. The current level monitoring relays are also used to provide additional relay functions. There are three alternative standard schemes available in the ordering table; 1. RXIDK 2H - three single phase elements. The overcurrent starting contacts provide monitoring of the differential relay tripping. The time-overcurrent and instantaneous overcurrent functions provide back up to the differential relay. 2. RXHL 401 - three-phase and earth overcurrent relay functions. Three levels of starting, time and instantaneous trip functions. 3. RXHL 411 - three-phase and earth overcurrent relay functions with three setting levels for phase and earth and thermal replica overload, breaker failure and optional reclosing relay functions. Optional pilot-wire supervision provides alarms for open, short-circuited or reversed pilot-wires. A simple transfer trip of a remote breaker can be obtained by opening of the s pilot-wires. The operation of the two relays then becomes half of the normal operating values, i.e. in the range 12.5-63 % of the CT rating, and depends on the type of the through going fault or load current. E 2max 20 i r (R CT +R L +Z 2 +5/i r 2 ) where: i r = main CT secondary rated current R CT = main CT secondary winding resistance R L = resistance in the wires between the main CT and the summation transformer in Z 2 = impedance of other relays and loads connected to the same CT core For systems with high resistance earthing, the R L value is taken for a single length of the wire used and for low resistance or solidly earthed systems the R L value is for the double length of the wire. In an isolated or high impedance, resistive earthed network main CT s are only required in two phases if a separate protection is used for detecting earth faults. 1000/2000 Ohms & 5/15kV pilot-wires The can operate over pilot-wires having 1000 ohms loop resistance, 2 µf shunt capacitance and 5 kv difference in earth potential between the terminals. The 5 kv limit can be increased to 15 kv by an isolating transformer (ratio 1:1) at both ends. With a 15 kv transformer of ratio 1:1.7, a 2000 ohm 0,7 µf pilot-wire can be used. Multi-terminal applications It is possible to use the standard relays for lines having more than two ends. The standard relays are used with pilot-wirpadded to 500 ohms per leg. ABB provides more details and application schematics for applications with multi terminal lines. Current Transformer requirements The CT s at each terminal do not need to have the same ratio. Ratio matching can be done with auxiliary CT s or the summation CT. The demands on the main CT s are small because the voltage in the pilot-wire circuit is limited to about 60V by zener-diodes. The protection is fully stable during external faults provided that the main CT s are approximately the same and the secondary limiting e.m.f. (E 2max ) fulfil the requirement:

Page 3 Sending end unit (SE 900631) Receiving end unit (SE99261) xx02000477 Fig. 1 pilot-wire supervision equipment Design The differential system compares the magnitude and phase angle of the currents entering and leaving the protected circuit via a pilot-wire. Zener diodes within the relay limit the voltage across the pilot- wires to 60 V and the current to 60 ma. The pilot-wire resistance is always padded to 1000 Ohms for two terminal applications. For multi-terminal applications, each pilot-wire leg is padded to 500 Ohms (as seen from relay to a pilot-wire midpoint). The calibration of the sensing relay is 10mA corresponding to about 10V at the relay. The basic two-terminal versions of the consist of: RTXP 18 test switch RXDHL 4 measuring module(fig. 2) SLCE 8 three-phase summation (Fig. 3) transformer The RXDHL 4 measuring relay includes the full wave rectifying diode bridge for the sensing relay, the flag indicator, voltage limiting zener diodes and padding resistors. The indicator flag is located in the front of the relay and has a hand reset knob. The flag indicator also has a voltage operated reset coil that can be activated via a remote push-button. An essential differential relay system principle is that the pilot-wire circuit is always padded to 1000 ohms regardless of its actual value via a tapped resistor in the RXDHL 4 unit. Adjusting resistance (ohms) Connect COMBIFLEX leads to terminals 0 426-422 and 313-316 33 426-422 and 313-315 66 426-422 and 313-314 100 426-423 and 313-316 133 426-423 and 313-315 166 426-423 and 313-314 200 426-424 and 313-316 233 426-424 and 313-315 266 426-424 and 313-314 300 426-425 and 313-316 333 426-425 and 313-315 366 426-425 and 313-314 400 426-426 and 313-316 433 426-426 and 313-315 466 426-426 and 313-314 499 426-426 and 313-311 The padding resistance is accessed from the rear of the terminal base. A wire is provided for connection via normal 10A COMBIFLEX sockets, see Fig. 6. The summation current transformer, designed for 5 kv test voltage, see Fig. 3, may be furnished loose for separate mounting. The transformer converts the input currents to a single-phase current which is applied to the pilot- wires

Page 4. 4 kohm resistor in the remote end supervision unit. The total loop resistance for the supervision circuit is therefor about 6 kohm. Fig. 2 pilot-wire relay RXDHL 4 Fig. 3 Summation CT type SLCE 8 Pilot-wire supervision (See Fig. 1) The pilot-wire supervision equipment consists of one unit at the sending end, and one unit at the receiving end. The dc current measuring unit RXCLK 2 is used in the pilot-wire supervision sending end to detect and indicate short-circuited and open-circuited pilot- wires. Interchanged connections of two pilot-wire ends are also detected. The sending end unit has two flags indicating the status of the pilotwires. The alarms are normally delayed a few seconds using the RXKA 1 timer. The timer range is 0,1-320 seconds. The pilot- wire supervision equipment also works according to the balanced bridge principle. One side of the bridge consists of the internal resistance of the relay, the pilot- wire resistance and an additional (XX02000527) (SE970868) The other side of the bridge is a variable 6,3 kohm resistor in the dc supply at the pilotwire supervision feeding end. The bridge is balanced with this resistor at commissioning. The bridge is supplied with 0 and +/-12V DC from the power supply unit RXTUB 2. 15kV insulation and 2000 Ohm pilot-wires The RXCLK 2 relay operates when the current exceeds 1 ma. The standard insulation test voltage is 5 kv 50-60 Hz. By feeding the unit from a 15kV isolation transformer it is possible to increase the total insulation level to 15kV. Pilot isolation transformers are required only when the longitudinally induced voltages in the pilot circuit is likely to exceed 5kV. This may be the case when the system voltage is above 36kV or of sufficient length. The isolation transformers are also used to extend the range of line-lengths possible to protect with pilot-wire relays. A resistance of 2000 Ohms is the limit and maximum capacitance of 0.7 µ F, can be handled with the standard relays. The 15kV insulated pilot- wire supervision equipment assembly may be housed in another enclosure than the differential relay. For a mounting example of this equipment, please refer to Fig. 4. All equipment is mounted on an insulating back-plane and the enclosure may be made from non-conducting insulating material e.g. fiberglass. In the assembly shown in Fig. 4, there are three 15kV insulation transformers type SLCE 8 used. One of these transformers isolate the pilot- wire system from the relay. The other two are used to provide additional isolation for the supervision equipment. One of these transformers increases the insulation level of the power supply to 15kV. The second provides 15kV isolation for the alarm signal to the "ground" level.

Page 5 The 15 kv pilot-wire insulation transformer type SLCE8 comes in two versions with ratio 1:1 or 1:1.7. Fig. 4 Example of a fiberglass enclosure for 15 kv insulation. Fig. 5 15kV pilot-wire isolation transformer SLCE 8 Technical data Rated current, I r 1 or 5 A Ac burden 3 VA, total for three-phase Continuous overload capacity 2. I r Frequency 50-60 Hz Sensitivity: earth faults phase faults 2-terminals 25-42% of I r 64-126% of I r 3-terminals 40-66% 100-200% 4-terminals 60-100% 150-300% Operating time 20 ms at 1,5 I pick-up Maximum pilot-wire resistance 1000 ohms (2000 ohms with isolating transformer ratio 1:1,7) Maximum pilot-wire capacitance 2,0 µf (0,7 µf with isolating transformer ratio 1:1.7) Dielectric tests: current circuits pilot-wire remaining circuits Impulse voltage test Disturbance Tests: Power frequency test Fast frequency test 1 MHz burst test Flag relay auxiliary voltage Trip outputs 50 Hz, 2,5 kv, 1 min 50 Hz, 5,0 kv, 1 min 50 Hz, 2,0 kv, 1 min 1,2/50 µs, 5 kv, 0,5 J 50 Hz, 0,5 kv, 2 min 4-8 kv, 2 min 2,5 kv, 2 s 24-55 V or 110-250 V 2 make contacts capable of closing 30A dc for 200ms

Page 6 Diagrams Fig. 6 Terminal diagram for RXDHL 4

- Pilot-wire differential relay for lines with Page 7 1) 101 7434 209-EA 9A 101 3A L1 (R) L2 (S) L3 (T) d 10A d 4A 5A 36C 101 107 125 2) (+) 3) 4) (-) 101 17A 125:114 125:211 125:212 125:213 RESET FLAG + 101 2A 1A 18A 6A 4U 101 RTXP 18 TEST SWITCH 107 TRANSFORMER UNIT 125 RXDHL 4 MEASURING UNIT + + - UL 1) PILOT-WIRES 2) RESETTING 3) TRIPPING ETC. 4) ALARM ETC. Fig. 7 Terminal diagram No. 7434 209-EAA. Basic version. Fig. 8 Circuit diagram No. 1MRK 001 358-AA. Pilot-wire supervision, sending end unit..

Page 8 Sample specification Three phase pilot-wire relay for phase and earth fault protection. The relay shall have 5 kv insulation and not impose more than 60V (120V) onto the pilot-wires. The relay shall operate in 1-2 cycles and trip both call ends during single-end infeed of fault current to permit use in weak infeed applications. Pilot-wire supervision equipment, when specified, shall detect shorted, opened and reversed pilot-wires and provide alarm outputs. The relay shall handle a 1000 (or 2000) ohms pilot-wire resistance and have a minimum of 5 (or 15) kv insulation level. A minimum of two output trip contacts and trip indication shall be provided. Current supervision and back up functions including thermal overload and breaker failure functions and auto reclosing elements are to be included as integral functions in the same assembly, when specified for the application. Ordering Specify: Quantity Ordering number according to table Rated current 1 A 5 A Auxiliary voltage UL 24 V 48 V 110 V 125 V 220 V 250 V Ordering number selection table for two terminals application Pilot-wire relay Dimensions Weight Terminal diagram Ordering No. Basic version (includes summation CT SLCE 8 and test switch RTXP 18) 4U 36C 5,2 kg 7434 209-EAA RK 612 001-EA Basic version + output relay RXME 1 4U 42C 5,7 kg 7434 209-GAA RK 612 001-GA Basic version + output relay RXMS 1 4U 42C 5,7 kg 7434 209-HAA RK 612 001-HA Basic version with summation CT furnished loose 4U 18C 3,0 kg 7434 209-ACA RK 612 001-AC Basic version with summation CT furnished loose + output relay RXME 1 Basic version with summation CT furnished loose + output relay RXMS 1 Pilot-wire supervision equipment: Sending end unit Receiving end unit SLCE 8-15 kv Pilot-wire isolation transformer Ratio 1:1 for 1000 Ohm pilot-wire Ratio 1:1,7 for 2000 Ohm pilot-wire As spare part 4U 24C 5,3 kg 7434 209-BCA RK 612 001-BC 4U 24C 5,4 kg 7434 209-DAA RK 612 001-DA 4U 48C 4U 18C 6,5 kg 2,0 kg 3,6 kg 1MRK 001 358-AAA 7434 211-CA 1MRK 001 357-AA 7434 210-CA 4785 040-AUP 4785 040-BAL RXDHL 4 loose relay 1) RX4 1,5 kg Fig. 6 RK 612 010-EA SLCE 8 summation CT 5 A 1 A 3,6 kg 3,6 kg Fig. 6 Fig. 6 4785 040-SY 4785 040-SV 1) Please note that terminal base RX4 is not included.

Page 9 Versions with additional fault detectors Specify: Quantity Ordering number according to table Rated current 1 A 5 A AC inputs for RXHL 401 and RXHL 411 Rated phase current I r = 1 A, rated neutral current IN r = 0.1 A Rated phase current I r = 1 A, rated neutral current IN r = 1 A Rated phase current I r = 5 A, rated neutral current IN r = 0.1 A Rated phase current I r = 5 A, rated neutral current IN r = 1 A Rated phase current I r = 5 A, rated neutral current IN r = 5 A 1MRK 000 322-FA 1MRK 000 322-FB 1MRK 000 322-FC 1MRK 000 322-FD 1MRK 000 322-FE Ordering number selection table for two terminals application Pilot-wire relay Basic version + 3 single phase fault detectors type RXIDK 2H Basic version + 3 phase and earth fault detectors type RXHL 401 Basic version + 3 phase and earth fault detectors type RXHL 411 Dimensions Weight Terminal diagram Ordering No. 4U 60C 7,5 kg 7434 209-FBA RK 612 001-FB 4U 60C 6,5 kg 1MRK002078-AAA 1MRK002077-AA 4U 60C 6,5 kg 1MRK002078-AAA 1MRK002077-AB Options for RXHL 411 Automatic reclosing function with intentional overreach trip function included Binary I/O module (inputs 4/outputs 4) 1MRK 000 200-BA 1MRK 000 322-ET Mounting and testing details and the pilot-wire supervision equipment are delivered mounted on apparatus bars. Depending on the type of final mounting required, i.e. 19 rack-mounting, or various forms of panel mounting, additional equipment is required. On request the 15 kv pilot-wire transformer, can be mounted on an apparatus plate or in a suitable casing.

Page 10 Reference Users guide COMBIFLEX mounting hardware details COMBITEST test equipment details RXIDK 2H current monitoring relay RXHL 401current monitoring relay RXHL 411current monitoring relay RXME 1 intertrip auxiliary relay RXMS 1 intertrip auxiliary relay 1MRK 507 004-UEN 1MRK 513 003-BEN 1MRK 512 001-BEN 1MRK 509 002-BEN 1MRK 509 062-BEN 1MRK 509 049-BEN 1MRK 508 015-BEN 1MRK 508 015-BEN Manufacturer ABB Automation Technology Products AB Substation Automation SE-721 59 Västerås Sweden Telephone +46 (0) 21 34 20 00 Facsimile +46 (0) 21 14 69 18 Internet: www.abb.com/substationautomation