Thermistor motor protection relays CM-MSS.22 and CM-MSS.23



Similar documents
Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Three-phase monitoring relay CM-PFE

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.43

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

Thermistor motor protection

Analog signal converters CC-E I/I Current / current isolators

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF19 and EF45

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

Grid feeding monitoring according to VDE-AR-N 4105 and BDEW CM-UFD.M31

38 Series - Relay interface modules A

38 Series - Relay interface modules A

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

Type: DILM32 10(24V50HZ) Article No.:

Fixed - Over/Under voltage limits, ( ) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

MasterINTERFACE 39 Series - Relay interface modules

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM50(230V50HZ,240V60HZ) Article No.:

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

MasterINTERFACE 39 Series - Relay interface modules

RM4TG20 three-phase network control relay RM4-T - range V

Manual motor starter MS116

Type: DILM9 10(24VDC) Article No.:

Three-phase monitoring relays Product group picture

Relés e Contatores de Estado Sólido SIRIUS

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

48 SERIES Relay interface modules 10 A

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

Pluggable interface relays CR-P Pcb relays

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

Safety technique. Emergency stop module BO 5988 safemaster

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Catalog. Modular DIN rail components Installation contactors

80 Series - Modular timers 16 A. Features

15 Series - Electronic step relay and dimmer. Features SERIE

STRATO LED Drivers 70W, Single output

49 Series - Relay interface modules A. Features

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

93.68/ Time scale: from 0.1s to 6h Multi-function For use with (EMR) and (SSR) relays. Screw terminal and push-in terminal

R.C.C.B. s two-pole LEXIC

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/2

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/2x15DC/1

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Power Supplies 3. SDN-P DIN Rail Series

80 Series - Modular timers 16 A. Features

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket

Technical catalogue. Modular DIN rail components Installation contactors

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

ZS25 Screw Clamp Terminal Blocks Feed-through

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x , 2CDG 110 1xx R0011

Technicaldata General

Bimetallic Overload Relay Specifications

E-STOP relays, safety gate monitors

Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M Schaffhausen 1 / 10

Trip circuit supervision relay. Type RXTCS

Waveguide Access Point WGA631. Product Guide

Signal converters Index

Digital input modules

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2CDG1101xxR0011

Telephone- and leased line modem for industrial applications TD-36

Rack mounted telephone- and leased line modem for industrial applications

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

System pro M compact Miniature Circuit Breaker S 200/S 200 M

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

EMR measuring and monitoring relays

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Signal converters Index

mecotron Safety relay ESTOP-2 For emergency stop monitoring

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

LOGO!Power. Power supply. LOGO!Power. Overview. Description, device design, dimension drawing. Mounting/Disassembly 2

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RY2 miniature industrial relays

Thermal-Magnetic Circuit Breaker M1-..

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D E 0 VD00

40 Series - Miniature PCB/Plug-in relays A. Features

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

ZS10 Screw Clamp Terminal Block

Transcription:

Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating, overload and insufficient cooling. The devices are available with two different terminal versions. You can choose between the proven screw connection technology (double-chamber cage connection terminals) and the completely tool-free Easy Connect Technology (push-in terminals). 2CDC 251 009 V0014 Characteristics 1 measuring circuit Reset button Auto, manual or remote reset configurable Overvoltage protected supply and measuring inputs Increased interference immunity acc. to EN 62061 with evaluation criterion "Fail-Safe" According to the latest version of the product standard IEC 60947-8 Screw connection technology or Easy Connect Technology available Housing material for highest fire protection classification UL 94 V-0 Tool-free mounting on DIN rail as well as demounting 22.5 mm (0.89 in) width Approvals A UL 508, CAN/CSA C22.2 No.14 C GL R EAC K E CCC Marks a b CB scheme CE RCM Order data Type Rated control supply voltage Output contacts Connection technology Order code CM-MSS.22P 24 V AC/DC * 2 c/o (SPDT) contacts Push-in terminals 1SVR740700R0200 CM-MSS.22S Screw terminals 1SVR730700R0200 CM-MSS.23P 110-130 V AC, 220-240 V AC Push-in terminals 1SVR740700R2200 CM-MSS.23S Screw terminals 1SVR730700R2200 * Supply and measuring circuits not electrically isolated

Connection technology Maintenance free Easy Connect Technology with push-in terminals Type designation CM-xxS.yyP Approved screw connection technology with double-chamber cage connection terminals Type designation CM-xxS.yyS 2CDC 253 026 F0011 2CDC 253 025 F0011 Push-in terminals Tool-free connection of rigid and flexible wires with wire end ferrule according to DIN 46228-1-A, DIN 46228-4-E Wire size: 2 x 0.5-1.5 mm², (2 x 20-16 AWG) Easy connection of flexible wires without wire end ferrule by opening the terminals No retightening necessary One operation lever for opening both connection terminals For triggering the lever and disconnecting of wires you can use the same tool (Screwdriver according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in)) Constant spring force on terminal point independent of the applied wire type, wire size or ambient conditions (e. g. vibrations or temperature changes) Opening for testing the electrical contacting Gas-tight Double-chamber cage connection terminals Terminal spaces for different wire sizes: fine strand with/without wire end ferrule: 1 x 0.5-2.5 mm² (2 x 20-14 AWG), 2 x 0.5-1.5 mm² (2 x 20-16 AWG) rigid: 1 x 0.5-4 mm² (1 x 20-12 AWG), 2 x 0.5-2.5 mm² (2 x 20-14 AWG) One screw for opening and closing of both cages Pozidrive screws for pan- or crosshead screwdrivers according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in) Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage connection terminals have the same connection geometry as well as terminal position. 2 - Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet

Functions Operating controls 1 Test / Reset button Reset - only possible if measured value < switch-on resistance 2 Indication of operational states with LEDs U: green LED - Status indication of control supply voltage V Control supply voltage applied F: red LED - Fault message 1 2CDC 251 009 V0014 2 Application / Monitoring function The thermistor motor protection relay CM-MSS monitors the winding temperature and thus protects the motor from overheating, overload and insufficient cooling in accordance to the product standard IEC 60947-8, control units for built-in thermal protection (PTC) for rotating electrical machines. Operating mode The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 are used to monitor the temperature of motors or generators equipped with PTC resistor sensors type A. The sensors are built-in into the motor windings, measuring the motor heating. In case of an increase of the temperature in the motor, the resistance of the PTC sensors will increase as well. If the motor heats-up excessively (>2.7 kh) the output relays de-energize and the corresponding LED displays the overtemperature. A reset is only possible after cooling down of the motor (<1.2 kh). Reset After rectification of a fault, the device has to be reset. This reset can be made manually by the Reset button, automatically by jumpering S1-T2 or externally by a remote reset between S1-T2. Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23-3

Electrical connection A1 11 21 T2 T1 T1 A1 11 21 A1 A2 Control supply voltage 24 V AC/DC 11 12/14 1st c/o (SPDT) contact 21 22/24 2nd c/o (SPDT) contact S1 T2 (jumpered) Automatic reset T1 T2 Measuring circuit S1 ϑ T2 A2 12 14 22 24 24 22 S1 14 12 A2 2CDC 252 019 F0014 Connection diagram CM-MSS.22 S1 A1 A3 T1 ϑ A1 A3 11 21 T2 T1 11 21 A1 A2 Control supply voltage 220-240 V AC A2 A3 Control supply voltage 110-130 V AC 11 12/14 1st c/o (SPDT) contact 21 22/24 2nd c/o (SPDT) contact S1 T2 (jumpered) Automatic reset T1 T2 Measuring circuit T2 A2 12 14 22 24 24 22 S1 14 12 A2 2CDC 252 021 F0014 Connection diagram CM-MSS.23 4 - Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet

Function diagrams A1/A3-A2 2700 Ω 1200 Ω R [Ω] Reset S1-T2 11-14 / 21-24 11-12 / 21-22 1 3 2 1 Tripping caused by overtemperature 2 Control supply voltage interrupted 3 Reset (resets fault) - manually with front-face Test / Reset button or - externally by a remote reset between terminal S1-T2 2CDC 252 048 F0214 CM-MSS.22, CM-MSS.23 Manual reset A1/A3-A2 2700 Ω 1200 Ω R [Ω] S1-T2 11-14 / 21-24 11-12 / 21-22 1 2 1 Tripping caused by overtemperature 2 Control supply voltage interrupted 2CDC 252 050 F0214 CM-MSS.22. CM-MSS.23 Auto reset Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23-5

Example of application Circuit diagrams V+ A1 11 21 T1 M 3~ t T2 24 22 Reset 14 V- S1 A2 12 2CDC 252 026 F0014 CM-MSS.22 V+ A1 or A3 11 21 T1 M 3~ t T2 24 22 Reset 14 V- S1 A2 12 2CDC 252 027 F0014 CM-MSS.23 6 - Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet

Technical data Data at T a = 25 C and rated values, unless otherwise indicated Input circuit Supply circuit CM-MSS.22 CM-MSS.23 Rated control supply voltage U s A1-A2 24V AC/DC 220-240 V AC A2-A3-110-130 V AC Rated control supply voltage U s tolerance -15...+10 % Rated frequency 50-60 Hz Typical current / power consumption 24 V AC/DC 38 ma / 0.65 VA - 110-130 V AC - 24 ma / 3 VA 220-240 V AC - 10 ma / 2.2 VA Electrical insulation between supply circuit and measuring circuit no yes Power failure buffering time 20 ms Measuring circuit / Sensor circuit T1-T2 Number of sensor circuits 1 Sensor type PTC type A (DIN/EN 44081, DIN/EN 44082) Max. total resistance of sensors connected in series, cold state < 750 h Overtemperature monitoring switch-off resistance (relays de-energize) 2.7 kh w 5 % switch-on resistance (relays energize) 1.2 kh w 5 % Maximum voltage in sensor circuit 1.33 kohm 2.5 V 4 kohm 3.7 V y kohm 5.5 V Maximum current in sensor circuit 3.7 ma Maximum sensor cable length 2 x 100 m at 0.75 mm ², 2 x 400 m at 2.5 mm ² Accuracy within the rated control supply voltage tolerance 5 % Accuracy within the temperature range 0.5 %/K Repeat accuracy (constant parameters) on request Reaction time of the safety function <100 ms Hardware fault tolerance (HFT) - Control circuit S1-T2 Control function manual reset yes auto reset adjustable remote reset adjustable Maximum no-load voltage (S1-T2 open) 5.5 V Max. current (S1-T2 jumpered) 1.2 ma Maximum cable length 2 x 100 m at 0.75 mm ², 2 x 400 m at 2.5 mm ² User interface Indication of operational states Control supply voltage U: green LED V: control supply voltage applied Fault message F: red LED V: overtemperature Operating controls Reset front-face button Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23-7

Output circuit Kind of output 11-12/14 relay, 1st c/o (SPDT) contact 21-22/24 relay, 2nd c/o (SPDT) contact Operating principle closed-circuit principle Contact material AgNi alloy, Cd free Rated operational voltage U e (IEC/EN 60947-1) 250 V AC Minimum switching voltage / Minimum switching current 24 V / 10 ma Maximum switching voltage / Maximum switching current See Load limit curves on page 11 Rated operating current I e (IEC/EN 60947-5-1) AC-12 (resistive) at 230 V 4 A AC-15 (inductive) at 230 V 3 A DC-12 (resistive) at 24 V 4 A DC-13 (inductive) at 24 V 2 A AC Rating (UL 508) utilization category (Control Circuit Rating Code) B 300 maximum rated operational voltage 250 V AC maximum continuous thermal current at B 300 4 A maximum making/breaking apparent power at B 300 3600/360 VA Mechanical lifetime 30 x 10 6 switching cycles Electrical lifetime at AC12, 230 V AC, 4 A 0.1 x 10 6 switching cycles Maximum fuse rating to achieve short-circuit protection n/c contact 10 A fast-acting n/o contact 10 A fast-acting General data MTBF on request Duty time 100 % Dimensions (W x H x D) product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in) packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in) Weight Screw connection technology Easy Connect Technology (push-in) net weight CM-MSS.22 0.132 kg 0.121 kg CM-MSS.23 0.174 kg 0.163 kg gross weight CM-MSS.22 0.155 kg 0.145 kg CM-MSS.23 0.197 kg 0.186 kg Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool Mounting position any Minimum distance to other units 10 mm (0.394 in) if switching current > 2 A 10 mm (0.394 in) if switching current > 2 A Material of housing UL 94 V-0 Degree of protection housing IP50 terminals IP20 Electrical connection Screw connection technology Easy Connect Technology (push-in) Wire size fine strand with(out) wire end ferrule 1 x 0.5-2.5 mm² (1 x 20-14 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) rigid 1 x 0.5-4 mm² (1 x 20-12 AWG) 2 x 0.5-2.5 mm² (2 x 20-14 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) Stripping length 8 mm (0.32 in) Tightening torque 0.6-0.8 Nm (5.31-7.08 lb.in) - Wire end ferrule according to DIN 46228-1-A, DIN 46228-4-E 8 - Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet

Environmental data Ambient temperature ranges operation -25 C...+60 C storage -40 C...+85 C Damp heat, cyclic (IEC/EN 60068-2-30) 6 x 24 h cycle, 55 C, 95 % RH Climatic category (IEC/EN 60721-3-3) 3K5 (no condensation, no ice formation) Vibration, sinusoidal (IEC/EN 60255-21-1) Class 2 Shock (IEC/EN 60255-21-2) Class 2 Isolation data CM-MSS.22 CM-MSS.23 Rated insulation voltage U i Supply circuit / Measuring circuit 1) n/a 300 V AC (IEC/EN 60947-1, IEC/EN 60664-1) Supply circuit / Output circuits 300 V AC Measuring circuit 1) / Output circuits 300 V AC Output circuit 1 / Output circuit 2 300 V AC Rated impulse withstand voltage U imp Supply circuit / Measuring circuit 1) n/a 4 kv / 6 kv (IEC/EN 60947-1, IEC/EN 60664-1) Supply circuit / Output circuits 4 kv / 6 kv Measuring circuit 1) / Output circuits 4 kv / 6 kv Output circuit 1 / Output circuit 2 4 kv Basic insulation (IEC/EN 60664-1) Supply circuit / Measuring circuit 1) n/a 600 V AC Supply circuit / Output circuits 600 V AC Measuring circuit 1) / Output circuits 600 V AC Output circuit 1 / Output circuit 2 300 V AC Test voltage, routine test Supply circuit / Measuring circuit 1) n/a 2.5 kv, 50 Hz, 1 min. (IEC/EN 60255-27, IEC/EN 61010-1) Supply circuit / Output circuits 2.5 kv, 50 Hz, 1 min. Measuring circuit 1) / Output circuits 2.5 kv, 50 Hz, 1 min. Test voltage, type test Supply circuit / Measuring circuit 1) n/a 6 kv / 1.2-50 µs (IEC/EN 60255-27) Supply circuit / Output circuits 6 kv / 1.2-50 µs Measuring circuit 1) / Output circuits 6 kv / 1.2-50 µs Output circuit 1 / Output circuit 2 6 kv / 1.2-50 µs Protective separation Supply circuit / Measuring circuit 1) no yes, up to 300 V (IEC/EN 61140, IEC/EN 50178) Supply circuit / Output circuits yes Measuring circuit 1) / Output circuits yes Output circuit 1 / Output circuit 2 no Pollution degree (IEC/EN 60664-1) 3 Overvoltage category (IEC/EN 60664-1) III 1) Potential of measuring circuit = potential of control circuit Standards Product standard IEC/EN 60255-1; IEC/EN 60947-8 Low Voltage Directive EMC directive RoHS directive 2006/95/EC 2004/108/EC 2011/65/EC Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23-9

Electromagnetic compatibility Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2 electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kv contact discharge, 8 kv air discharge radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 10 V/m (1 GHz), 3 V/m (2 GHz), 1 V/m (2.7 GHz) electrical fast transient / burst IEC/EN 61000-4-4 Level 3, 2 kv / 5 khz surge IEC/EN 61000-4-5 Level 3, Installation class 3, supply circuit and measuring circuit 1 kv L-L, 2 kv L-N conducted disturbances, induced by radio-frequency IEC/EN 61000-4-6 Level 3, 0.15-80 MHz, 10 V, 80 % AM (1kHz) fields voltage dips, short interruptions and voltage variations IEC/EN 61000-4-11 Class 3 harmonics and interharmonics IEC/EN 61000-4-13 Class 3 Additional interference immunity according to product standard EN 60255-1 (reference on EN 60255-26_2011) radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 10 V/m (80 MHz - 3 GHz) conducted disturbances, induced by radio-frequency IEC/EN 61000-4-6 10 V at stated frequencies fields damped oscillatory waves IEC/EN 61000-4-18 Signal lines, symmetric coupling: 1 kv peak voltage Power supply, asymmetric coupling: 2.5 kv peak voltage, Increased interference immunity acc. to EN 62061 for safety with the evaluation criterion IEC/EN 61000-6-1, IEC/EN 61000-6-2 "Fail-Safe" against electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kv contact discharge, 8 kv air discharge radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 20 V/m (1 GHz), 6 V/m (2 GHz), 3 V/m (2.7 GHz) electrical fast transient / burst IEC/EN 61000-4-4 Level 3, 4 kv / 5 khz surge IEC/EN 61000-4-5 Level 3, Installation class 3, supply circuit and measuring circuit 2 kv L-L, 4 kv L-N conducted disturbances, induced by radio-frequency IEC/EN 61000-4-6 Level 3, 10 V fields voltage dips, short interruptions and voltage variations IEC/EN 61000-4-11 Class 3 harmonics and interharmonics IEC/EN 61000-4-13 Class 3 Interference emissions IEC/EN 61000-6-3, IEC/EN 61000-6-4 high-frequency radiated IEC/CISPR 22, EN 55022 Class B high-frequency conducted IEC/CISPR 22, EN 55022 Class B high-frequency radiated Germanischer Lloyd increased requirements in the emergency call frequency band 10 - Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet

Technical diagrams Load limit curves V V 300 200 V V 300 200 100 80 60 50 40 30 100 80 60 50 40 30 20 10 0.1 0.2 0.5 1 2 4 6 10 I A 2CDC 252 194 F0205 20 10 0.1 0.2 0.5 1 2 4 6 10 I A 2CDC 252 193 F0205 AC load (resistive) DC load (resistive) 1.0 0.9 Switching cycles F 0.8 0.7 0.6 250 V resistive load 0.5 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ 2CDC 252 192 F0205 Switching current [A] 2CDC 252 148 F0206 Reduction factor F for inductive AC load Contact life time / number of operations N 220 V 50 Hz 1 AC, 360 operations/h Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23-11

Dimensions in mm and inches 113.4 4.47 105.9 4.17 22.5 0.89 85.6 3.37 103.7 4.08 2CDC 252 009 F0011 Accessories in mm and inches 22.5 0.89 8 0.32 4.8 0.19 6.5 0.256 62.5 2.461 60 2.362 70 2.756 10 11.5 0.394 0.453 20 0.787 2CDC 252 008 F0010 3A11 20 0.787 8 0.315 2CDC 252 186 F0005 68 2.68 front to back 110.5 4.31 2CDC 252 010 F0011 ADP.01 Adapter for screw mounting MAR.01 Marker label for devices without DIP switches COV.11 Sealable transparent cover Further documentation Document title Document type Document number Electronic products and relays Technical catalogue 2CDC 110 004 C02xx Operating and installation instructions CM-MSS.12, CM-MSS.13, CM-MSS.22, CM-MSS.23 Instruction manual 1SVC 730 630 M0000 You can find the documentation on the internet at http://new.abb.com/low-voltage/products/epr/monitors/thermistor-motor-protection-relays CAD system files You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com/portal/portal/abb-control-products -> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls -> Thermistor Motor Protection Relays. 12 - Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet

Contact us ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Document number 2CDC 112 220 D0201 (12/2014) Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2014 ABB All rights reserved