Engineers Newsletter. HVAC Refrigerants: A Balanced Approach. providing insights for today s hvac system designer. volume 40 2. Refrigerant History



Similar documents
The phase out of R22. Phase out of HCFCs

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

RS-44 (R424A) : Q & A

R-32. The next generation refrigerant for air conditioners and heat pumps

Replace Your CFC Air Conditioning Chiller

Industry insight. Refrigerant gases: an industry in transition.

HCFC phase-out has started.

It s Your Choice Retrofitting Your Car s A/C System 1EPA. 2 Printed on paper that contains at least 20 percent postconsumer fiber.

Part A: Fluid properties

The EC Ozone Regulation. Legislative Update and Strategies for HCFC Phase-out

RS-24 (R426A): Q & A

Air-cooled Chillers with High Speed Centrifugal Compressors

HFCS, REFRIGERATION AND AIR-CONDITIONING: MINIMISING CLIMATE IMPACT, MAXIMISING SAFETY

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight Temperature glide o C Boiling point (1 atm)

Low-GWP Refrigerants for Air Conditioning and Refrigeration Applications. Samuel F Yana Motta

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

Administrator Lisa P. Jackson Environmental Protection Agency Ariel Rios Building 1200 Pennsylvania Avenue, N.W. Washington, DC

Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity

EU f-gas regulation EN 517/2014.

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

Guidance for Stationary Refrigeration & Air- Conditioning

ADVANCING FLAMMABLE REFRIGERANT ADOPTION IN NORTH AMERICA

THE F-GAS REGULATION AND ITS IMPLICATIONS IN FIRE SUPPRESSION APPLICATIONS

Refrigerants for Residential and Commercial Air Conditioning Applications

2010 Report of the Refrigeration, Air Conditioning and Heat Pumps Technical Options Committee (RTOC)

Calculating HFC and PFC Emissions from the Manufacturing, Installation, Operation and Disposal of Refrigeration & Airconditioning

How To Know If Cfc 12 Is Still Needed

Guidance for Stationary Refrigeration & Air-Conditioning

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

R-32. The next generation refrigerant for air conditioners and heat pumps. Superior energy efficiency and low GWP

Substitute Aerosol Solvents and Propellants Under SNAP as of August 10, 2012 SNAP Information:

Refrigeration and Air Conditioning with Reduced Environmental Impact

Environmental perspective in intelligent products and processes

7. COST AND EMISSION REDUCTION ANALYSIS OF HFC EMISSIONS FROM REFRIGERATION AND AIR-CONDITIONING IN THE UNITED STATES INTRODUCTION...

NYU Safety Policy Manual

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

Refrigerant Update and Beyond. Stephen Niles Refrigeration/Commercial Sales Manager

THE REPLACEMENT OF R-22

Refrigerants for residential and commercial air conditioning applications

Refrigerant Compliance Policy

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois Information compiled by Frank Prah, CMS

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment

USC CFC Leak Repair and Recordkeeping Procedures

Refrigeration, Air-conditioning and Heat Pump Sector. The Environmental Protection Agency

History of Chlorofluorocarbons

F-Gas Compliance. To provide a process for F-Gas Leak Testing in accordance with legislative requirements.

EU F-Gas Regulation Guidance Information Sheet 5: Stationary Air-conditioning and Heat Pumps

Planning for the ban on R22 in building air conditioning

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

Tim Facius Baltimore Aircoil

Guidance for Mobile Air Conditioning (MAC) Sectors. Guidance: F Gas and Ozone Regulations Information Sheet MAC 3: Key Obligations

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Federal Clean Air Act Section 609 Training Manual & Exam

Guide to good leak testing

How Do Smart Buildings Make A Building Green?

Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance

DEVELOPMENT OF THE GHG REFRIGERATION

TECHNICAL ANNEX. Alternatives to HCFCs/HFCs in unitary air conditioning equipment at high ambient temperatures. November 2014

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Certification Training Manual

Calculating Greenhouse Gas Emissions

CHILLER EMISSIONS PROGRAM Region 8 Sustainability & Environmental Management System

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN?

Administrator Regina McCarthy Environmental Protection Agency Ariel Rios Building 1200 Pennsylvania Avenue, N.W. Washington, DC

Protection of Stratospheric Ozone: Update to the Refrigerant Management Requirements

The Development of Heat Pump Water Heaters Using CO 2 Refrigerant

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

REFRIGERANT REFERENCE GUIDE

Residential and Commercial Air Conditioning and Heating

Certification in the safe and efficient use of alternative refrigerants

Heating and Cooling Technology and Global Solutions for Food Distribution:

Refrigerant identification and equipment issues in relation to HCFC phase-out. Ole Reinholdt Nielsen

Extracts from the FINAL REPORT. Denis CLODIC, Stephanie BARRAULT, Sabine SABA. tonnes. CO2 Eq. Emissions. CFC HCFC HFC Others 1 200

International Refrigerant Standards and their Influence on the Global HVAC Industry and Refrigerant Replacement

AHRI Begins Second Phase of Low-GWP AREP Testing AHRI Completes Four Research Projects in 2014

Environmental Guideline for Ozone Depleting Substances (ODS s) and Halocarbon Alternatives

Thermo Scientific Ultra-Low Temperature TSX Series Freezers

The Importance of Mobile Air Conditioning to Climate Protection. Stephen O. Andersen US EPA

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications

Certification Training Manual

Chapter 7: Greenhouse gases and particulate matter

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

University of South Florida Greenhouse Gas Emissions Inventory FY

Roche Basel/Kaiseraugst

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Environmental Benefits of Thin Computing A comparison of the environmental impacts of conventional desktop and thin computing

Production of R-134a

Background. Page 1. Table 1. Environmental impacts of MVAC refrigerants. Global warming potential

Guide to updated EU f-gas regulation (517/2014).

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

As supermarkets look to lessen

R441A An EPA- Approved Multi-blend Pure Hydrocarbon Refrigerant

P08 Köldmedier med låg växthuseffekter

Protection of Stratospheric Ozone: Listing of Substitutes for Ozone-Depleting Substances

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

Fujitsu General New Zealand Ltd

2. Environmental indicators

White Paper: Revisiting Flammable Refrigerants

Transcription:

providing insights for today s hvac system designer Engineers Newsletter volume 40 2 HVAC Refrigerants: A Balanced Approach One of the constant themes throughout the history of the HVAC industry is the search for a better refrigerant. When considering alternative refrigerants, manufacturers need to balance efficiency with environmental impact to determine the optimal replacement. This EN will provide a brief history of refrigerants used in the HVAC industry and the developing regulations. From there, we ll discuss considerations for new and existing equipment, along with refrigerant replacement options and risks. Refrigerant History In the early years, the primary focus of the HVAC industry was simply on finding a refrigerant that would provide effective cooling. Many of the early refrigerants such as sulfur dioxide, methyl chloride and ammonia met that objective but posed safety hazards due to their toxicity or high flammability potential. In the 1930s, chlorofluorocarbon (CFC) refrigerants were introduced as safe alternatives to the chemicals used before them. CFCs came to dominate first refrigeration and later HVAC because of their safety and efficiency. Hydrochlorofluorocarbons (HCFCs) were added to the portfolio of refrigerant alternatives in the 1950s. In the 1970s, environmental concerns came into play. Scientists discovered that CFCs and to a lesser extent HCFCs were contributing to the depletion of the ozone layer. Montreal Protocol. Global concern about depletion of the ozone layer resulted in the Montreal Protocol, an international treaty that established phase-out dates for the use and production of ozone-depleting substances. It went into effect in 1987, first targeting CFCs, then HCFCs. CFCs were replaced with HCFCs, which have lower ozone-depletion potential (ODP), or with hydrofluorocarbons (HFCs), which have zero ODP. The CFC phaseout was completed in 1996. Due to their low ODP, the phase-out dates for HCFCs were set out later from 2004 to 2030 (2040 in developing countries). Kyoto Protocol. In the 1990s, concerns grew that the refrigerants being phased in because of their favorable ODP were contributing to global warming. The global-warming potential (GWP) of refrigerants now became a factor. These concerns with global climate change led to the Kyoto Protocol, created in 1997. Kyoto set reduction targets for greenhouse gases, including HFCs, in developed countries. Because CFCs and HCFCs were already covered under the Montreal Protocol, they were not included in the Kyoto Protocol. Where we are today. Both protocols allow each participating country to control its own reductions of the refrigerants to meet their compliance obligations. In the United States, the U.S. Environmental Protection Agency (EPA) issued regulations under the Clean Air Act to phase out the 2011 Trane, a business of Ingersoll Rand. All rights reserved. 1

production and import of CFCs and HCFCs. Figure 1 provides a summary of the major actions involving refrigerants in developed and developing countries. The dates on the chart are for the United States and Canada (dates in other countries vary). The Montreal and Kyoto protocols have set dates to ensure long-term availability. When production of a refrigerant stops, the time lines allow for the recycled, recovered and stockpiled supplies to continue to be used without restriction. For example, production of CFCs ended in 1996, but inventory of these refrigerants is still readily available. What s ahead. Policy pressure impacting nearly all commercially viable refrigerants available today has accelerated the development of alternatives.the next family of refrigerants, known as hydrofluoroolefins (HFOs), have properties similar to HCFCs and HFCs but with minimal direct environmental impact. The first HFO on the market has been developed to replace R-134a for automotive applications and will begin implementation this year in Europe. Implementation of HFOs will lag in the HVAC industry as manufacturers develop and test new alternatives, and global regulators decide on a future path. A Balanced Approach When considering refrigerant alternatives for the future, policy makers, the public, and manufacturers must balance direct environmental concerns (ODP, GWP, leak rates), indirect environmental concerns (energy efficiency), safety and performance. Direct versus indirect impact. The direct environmental impact of an HVAC system is dependent on the ODP and GWP of the refrigerant and the rate of refrigerant leakage into the environment. Figure 1. Legislative actions involving refrigerant Montreal Protocol signed All CFC production stopped (R -11,R-12) in developed countries Kyoto Protocol went into effect No CFCs for developing countries 1990 2000 2010 2020 2030 2040 2050 No R-134a use in new model automobiles in Europe Today continued use of recycled CFCs While leakage rates can vary widely among different HVAC products, good design and servicing can keep leakage to a minimum. (See the sidebar on p. 4.) Years ago, when chillers used CFCs and service practices were less concerned with minimizing emissions, leak rates were 2½ to 10 times what they are today. Due to advances in technology and the use of refrigerants with significantly lower GWP, the direct environmental impact from HVAC equipment is now from 20 to 600 times lower than the older CFC chiller designs. These reduced leak rates, coupled with newer refrigerants, bring the direct global warming impact to under 5 percent of the application s total global warming impact. For hermetic systems, up to 95 percent of the total environmental impact is the indirect impact the energy used to power HVAC systems. According to the U.S. Department of Energy, 83 percent of the primary power consumed in the U.S. is generated by the burning of fossil fuels, which emits greenhouse gases. No new R-22 for service in US, Canada No new equipment with R-123 in developed countries No new R-123 for service in developed countries, no HCFCs in new equipment in developing countries No new equipment with R-22 in US, Canada continued use of recycled R-22 No HCFC production in developing countries continued use of recycled R-22, R-123 for developing countries continued use of recycled R-123 Note: Included in the use of recycled refrigerants is also the use of stockpiled supplies of the refrigerant produced before the phase-out date. In addition, there is no restriction on the importation of recycled and recovered supplies of refrigerant. When considering both the direct and indirect environmental impact, HCFCs and HFCs, because of their high energy efficiency, can be the most environmentally responsible and appropriate refrigerants available today for many HVAC applications. Evaluating alternatives. Let s take a look at the refrigerants that are currently available, taking into consideration their efficiency, direct and indirect environmental impact, and safety. Figure 2 compares the ODP, GWP and energy efficiency of today s commercial refrigerants and potential future refrigerants. While there is no perfect refrigerant, the chart shows that HCFC-123 (R-123), HFC-152a (R-152a) and HFC-32 (R-32) strike a good balance between ODP, GWP and efficiency. However, the use of R-152a and R-32 is limited because of flammability. Refrigerants such as CO 2, hydrocarbons and ammonia have zero ODP and a very low GWP. Let s take a closer look. 2 Trane Engineers Newsletter volume 40 2 providing insights for today s HVAC system designer

Carbon dioxide. CO 2 has potential as a low-temperature refrigerant in refrigeration applications. However, it has very low efficiency in HVAC applications, more than 20 percent below the efficiency of R-22 and R-410A, due to operation above the critical point of CO 2 in these applications. Today s equipment would therefore consume at least 20 percent more energy with CO 2 to get the same cooling tonnage, compared to the existing HCFCs and HFCs used today. Switching from fluorocarbons to CO 2 to reduce direct environmental impact (5 percent), while significantly increasing the indirect impact (95 percent), would not be a good tradeoff. Hydrocarbons. Hydrocarbons may perform well in stationary air conditioning applications, but they present safety issues in application, service and recovery because they are highly flammable. Ammonia. Ammonia has been used for years and has potential for lowtemperature and process chiller applications in remote locations or where people density is low. Its flammability and high toxicity strictly limit its broader use. Maintaining a balance between the lowest possible refrigerant emissions and the best possible energy efficiency is the key to being both environmentally and economically responsible. Achieving this balance in a cost effective manner is critical in order to make these new designs affordable for the end user. Green building and refrigerant selection Green building rating systems such as USGBC s LEED (Leadership in Energy and Environmental Design) and GBI s Green Globes take refrigerant usage into consideration. The current LEED rating system uses a formula to calculate the impact of ozone depletion, global warming, equipment life, leakage rate, and refrigerant charge. The Green Globes rating system accounts for ozone depletion, global warming and leak detection. By following the criteria in the rating systems, the selected refrigerants can help the project achieve points toward green building status. For example, most centrifugal chillers (both R-123 and R-134a) can achieve the refrigerant points for LEED Energy and Atmosphere credit 4. Many split systems, due to the large volume of refrigerant, cannot. For more information, see www.usgbc.org or www.thegbi.org. Figure 2. Overview of the environmental impact of current refrigerants Energy efficiency COP (at typical chiller conditions) 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 ODP GWP (R-11=1.0) (CO 2 =1.0) (000s) 1.0 0.8 0.6 0.4 0.2 0 2 4 6 8 10 12 CFC-11 CFC-12 HCFC-22 HCFC-123 HFC-134a HFC-410A HFC-32 HFC-152a HFC-245fa HFO-1234yf R-290 (propane) R-600a (isobutane) R-744 (CO 2 ) R-717 (ammonia) lower efficiency some flammability some flammability some flammability flammability flammability flammability & toxicity higher 3 Trane Engineers Newsletter volume 40 2 providing insights for today s HVAC system designer

Options for Existing Equipment So, what do we do with existing equipment containing refrigerants that will be phased out? There is no definitive answer. However, there are options and a logical progression to determine the best solution for each project. Options: Maintain existing refrigerant Replace the refrigerant Replace the equipment Evaluate existing equipment The first step is to evaluate the current inventory of equipment. When tracking the current inventory, obtain records that document the energy performance and refrigerant leakage rate of existing equipment. Track leakage rate of equipment. The U.S. Clean Air Act requires that leakage rate data records be kept for all equipment with more than 50 lbs of refrigerant charge. These records should be available either from the owner's maintenance records or from the records of the servicing contractor. If records are unavailable, then record keeping should begin immediately to understand the state of the existing equipment. As of January 2011, for equipment with more than 50 lbs of refrigerant charge, the U.S. EPA s maximum allowable leakage rates over a 12-month period are: Commercial refrigeration: 35 percent Industrial process refrigeration: 35 percent Comfort cooling: 15 percent Venting is prohibited for any equipment, regardless of size. A note regarding equipment using HFCs: There are no specific recordkeeping requirements or maximum leakage rates for this equipment, but due to direct global warming, venting of these chemicals is also prohibited. In the future, maximum leakage rates will most likely cover the HFCs as well. Track the equipment performance. The performance data of the equipment can be provided either by the building automation system (preferred), or by the original nameplate data of the equipment. Proper service practice should be able to maintain close to original performance on most equipment, but individual equipment monitoring will provide an even better performance baseline. Evaluate refrigerant changeout Before replacing a refrigerant, determine the capacity and efficiency impact. This impact is clearly understood in some equipment types, such as centrifugal chillers, where replacements are clearly defined and several years of performance data has been accrued. For other equipment, there are many replacement options in the marketplace, and even more claims of seemingly miraculous capacity and efficiency improvements by using these replacements. Basic physical properties, as well as industry experience, have clearly shown that any refrigerant replacement in existing equipment will result in some sort of capacity and efficiency reduction. The specific reduction depends on the type of equipment and the specific replacement refrigerant. Note: When retrofitting existing equipment, do not use a flammable refrigerant in equipment that was not specifically designed for it. Replacements for the refrigerants R-11 and R-12 are relatively straightforward (R-123 and R-134a, respectively). The Use best practices to minimize environmental impact Best practices in design and servicing can keep refrigerant leaks to minimal levels. In fact, a Trane study conducted as far back as 1997 determined the annualized total loss rate for every single R-123 chiller that Trane had under service contract at the time. The study included all leaks whether from accidental discharge, servicing or normal operation. It showed that of 2768 R-123 chillers studied, only 16,229 pounds per year of charge was lost less than 0.4575 percent annual leakage rate. It's important to note that operating pressure can also impact how likely a leak is to occur and how much refrigerant will escape during a leak. In addition, innovative technologies can be employed that minimize the refrigerant charge for a given amount of refrigeration or cooling capacity, with the percent charge reduction directly reducing refrigerant emissions over the life of the equipment by the same amount. So, use of low pressure technology with reduced refrigerant charge levels can result in nearly an order of magnitude reduction in lifetime emissions compared to other higher pressure centrifugal chillers. decision gets more complex with the replacement of R-22. Many solutions are available, and it is impractical for equipment manufacturers to test and analyze all of them. Generally, these replacements incorporate the use of multi-chemical blends in order to mirror the properties of R-22. Note: Because of its higher operating pressure, R-410A cannot be used in R-22 products. Blends work in many applications, but be sure to weigh the following risks: Different leakage rates Concerns exist in the marketplace about what happens when refrigerant leaks occur. The different components in the blend could potentially leak at different rates, and therefore change the composition and performance of the equipment. When these replacement refrigerants incorporate as many as four or more chemicals in the blend, these concerns increase. 4 Trane Engineers Newsletter volume 40 2 providing insights for today s HVAC system designer

Change in oil In many cases, a refrigerant changeout requires a change in the oil needed in the system. CFCs and HCFCs are able to use mineral oil with the refrigerant. HFCs, however, generally require the use of POE or other synthetic oils. So that an oil change may not be required, many of the R-22 substitutes incorporate a small amount of hydrocarbons, such as butane, in order to improve their miscibility with mineral oil. However, the refrigerant and oil chosen must have sufficient solubility and miscibility throughout the refrigeration system which may not be the case for some R-22 substitutes and mineral oil. If in doubt, consult the unit or compressor manufacturer for the required oil type. When a refrigerant and/or oil changeout is evaluated, all the components of the refrigeration system must be scrutinized for compatibility with the refrigerant and oil. Gaskets and o-rings are of particular importance because they may shrink or expand and cause a refrigerant release. It is strongly suggested that the gaskets and o-rings be proactively replaced during a refrigerant or oil conversion. Future availability and GWP If a proprietary blend is used for an alternative refrigerant, it should be ensured that the blend will still be available in the future. In addition, many of these blends are very high in GWP. The GWP of refrigerants will likely be regulated or taxed in the coming years, making many of the alternatives unattractive. Review and assess After you have reviewed the data and evaluated the possibility of refrigerant changeout, determine the best solution for your particular application. In most cases, retaining the existing refrigerant in the equipment, or replacing the equipment altogether will make the most sense. If leakage rates with the existing refrigerant cannot be contained to a minimal level with the current refrigerant, then it is unlikely that leaks will be contained with the new refrigerant. In addition, significant investments in inefficient equipment that will result in a loss in capacity and efficiency will often not be the most attractive solution. In many cases, investment in minimizing leaks and maintaining the equipment to its peak energy performance will result in a smaller up-front investment and better life cycle cost. Summary Since the early 1900s, the HVAC industry has been faced with the challenge of constantly changing refrigerants. While change is constant, it s important to remember that the industry has successfully navigated refrigerant phaseouts in the past and can apply the lessons learned to future transitions. As an industry, the key is to carefully consider alternatives and strike a balance that is financially and environmentally responsible. Today we have good, solid refrigerant options and availability with HCFCs and HFCs. There s no need to panic. The future will bring different options, challenges, and opportunities. By Jeff Moe, director, global policy and advocacy for the Center for Energy Efficiency and Sustainability, Ingersoll Rand; Mike Thompson, global leader of refrigerant strategy, Trane; and Beth Bakkum, information designer, Trane. You can find this and previous issues of the Engineers Newsletter at www.trane.com/en. To comment, e-mail us at comfort@trane.com. 5 Trane Engineers Newsletter volume 40 2 providing insights for today s HVAC system designer

New On-Demand Courses Now Available Upgrading Existing Chilled-Water Systems. (This program provides designers with specific strategies for chiller upgrades, optimization or replacement; reusing components of a chilled water system and help you identify areas where control upgrades would be beneficial. ASHRAE 62.1 and 90.1 and VAV Systems. (GBCI LEED-specific) This program discusses the potentially conflicting requirements and design choices. ASHRAE 62.1: Ventilation Rate Procedure. This program covers the Ventilation Rate Procedure for calculating zone and system ventilation airflow, which still exists in the standard today. As a prerequisite to obtain LEED certification, this program will help viewers understand the requirements of the Standard. Visit www.trane.com/ ContinuingEducation to view or to see a complete list of courses. Engineers Newsletter LIVE! To register, contact your local Trane office. Upgrading Existing Chilled-Water Systems Now available on-demand at www.trane.com/continuingeducation June 2011 High-Performance VAV Systems October 2011 Dedicated Outdoor Air Units Trane, A business of Ingersoll Rand For more information, contact your local Trane office or e-mail us at comfort@trane.com Trane believes the facts and suggestions presented here to be accurate. However, final design and application decisions are your responsibility. Trane disclaims any responsibility for actions taken on the material presented. 6 Trane Engineers Newsletter volume 40 2 ADM-APN041-EN (June 2011)