Power Transformer Fundamentals: Design and Manufacturing



Similar documents
Transformer Design & Design Parameters

Transformer Manufacturing Processes


Power Transformers 10 to 100 MVA

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

Liquid Filled Transformers Load Tap Changing Transformers Three-Phase Voltage Regulators

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Table of Contents. TransformerIQ FAQs 1

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Unified requirements for systems with voltages above 1 kv up to 15 kv

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

Secondary Unit Substations

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Multi-tap Transformers

This section applies to the design and installation of transformers.

Engineers at Liftech designed the structure of the first container crane and have designed and reviewed thousands of container cranes since.

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

James M. Pleasants Company

Transformer Bushings for GIS

Electrical Maintenance Workshop

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

جامعة البلقاء التطبيقية

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

INSTALLATION. General. Important Note. Design. Transport

Step Voltage Regulators

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Low Voltage Transformers Sealed, General Purpose, Dry Type

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

1. The diagram below represents magnetic lines of force within a region of space.

Presentation of the France Transfo factories

THE VALUE OF POWER FACTOR TESTING

Tasarım ve Baskı: AJANSBRAND A

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

METHOD OF STATEMENT FOR STATIC LOADING TEST

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

Air Eliminators and Combination Air Eliminators Strainers

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Vehicle Design Summit Electric Hub Motor (V2) Eric Conner Harvey Tang Matthew Peddie

SECTION SUBSTATION TRANSFORMERS

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

Power transformers. Special transformers Railway

Transformer Calculations

SECTION DRY-TYPE TRANSFORMERS

WINDING RESISTANCE TESTING

Model 1210C Battery Powered Pump Shown. Description

Tamini is the leading Italian company in the world for the design and production of industrial, power and special transformers.

BLADDER SURGE CONTROL SYSTEM

Power Transmission and Distribution. Shunt reactors for medium and highvoltage. From development to use

all VAC LIFT ALL-VAC-LIFT Phone Redstart Street Fax

Effect of design parameters on temperature rise of windings of dry type electrical transformer

S Y N C H R O N O U S G E N E R A T O R S

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

Diesel Engine Driven Generators Page 1 of 6

Subminiature Load Cell Model 8417

Together we create reliable products, thus ensuring development of power industry of continents.

Cables, Cable Laying & Accessories Manual

Power Plant Electrical Distribution Systems

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva

Tutorial One: Calculation of leakage inductance of transformer using FEM MVA, 132 kv/33kv, Y/, Ampere-turns: , No.

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Transformer oil cooler ALFA A02

Product Data Bulletin

Generators TEM. for small hydroelectric power stations. Electric Machines

Current Limiting Protector For Systems rated kV and continuous currents through 5000A.

Instructions for Secondary Unit Substation Transformers KVA, Three Phase

Chapter 22: Electric motors and electromagnetic induction

T U R B I N E G A S M E T E R

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Power Transformers Small, Medium & Large

PM734F - Technical Data Sheet Winding 28

Transformers: Basics, Maintenance, and Diagnostics

OLI. Oil level indicator

COATING & WRAPPING OF UNDERGROUND PIPING

understanding medium frequency induction melting furnace and its components

SYNCHRONOUS MACHINES

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Power Cube Open Source Ecology Page 1. Power Cube. Version 4

Stilling Well Recommendations

KNOW YOUR OPTIONS: 230 KV POWER CABLES

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Gulf Cable & Electrical Ind. Co.

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)

SAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE

Development Of High Efficiency Brushless DC Motor With New Manufacturing Method Of Stator For Compressors

HV Submarine Cable Systems Design, Testing and Installation

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A

Green Thread Product Data

INTERNATIONAL STANDARD

Transcription:

Power Transformer Fundamentals: Design and Manufacturing Waldemar Ziomek, Engineering Manager CG Power Systems Canada Inc IEEE Training, Houston, Texas, Oct.8-9, 2013 1 Overview Transformer Design Transformer Types Construction and Parts Core & Coils Electrical design Losses & Impedance Thermal, Dielectric & Short Circuit Cooling & Sound Level Mechanical design Tank Oil Preservation Transformer Manufacturing Process 2

Power Transmission & Distribution The traditional power supply chain - from the central power generator to the consumer: GENERATION TRANSMISSION SUB-TRANSMISSION DISTRIBUTION DISTRIBUTED POWER 115/10 or 20 kv 500/230 230/13.8 132 345/161 161 161 230/115 132 230 230/132 115 345 69 500 34 Generator Step-Up Auto-Transformer Step-Down Pads Transformer Transformer With and without LTC 3 Specification vs. Design SPECIFICATION GIVES BASIC PARAMETERS: Voltages (kv, BIL), power rating ( MVA), impedance (IZ), DESIGNER/PRODUCER GIVES: Dielectric system Magnetic system Thermal system Mechanical system Oil flow system Sound system 4

Standards USA (ANSI) IEEE Std C57.12.00-1993, standard general requirements for liquidimmersed distribution, power and regulation transformers ~ 50 Pages ANSI C57.12.10-1988, safety requirements 230 kv and below 833/958 through 8,333/10,417 KVA, single-phase, and 750/862 through 60,000/80,000/100,000 KVA, three-phase without load tap changing; and 3,750/4,687 through 60,000/80,000/100,000 KVA with load tap changing ~ 30+ Pages (ANSI) IEEE C57.12.90-1993, standard test code for liquid-immersed distribution, power and regulating transformers and guide for short-circuit testing of distribution and power transformers ~ 107 Pages NEMA standards publication no. TR1-1993; transformers, regulators and reactors ~ 2 Pages CSA IEC 5 Simple Transformer Left coil - input (primary coil) AC Source is connected to Magnetizing current flows and establishes the flux in core Right coil - output (secondary coil) Load Magnetic circuit (core) Problems? Stray flux, transients, heating, vibrations, noise, losses, regulation, saturation, human errors, dielectrics (high voltage insulation), non-linear magnetics, fluid dynamics, material defects, contamination, etc.etc. 6

Real single phase transformer Wound leg LV winding HV winding Return core leg In order to better control the stray flux distribution, both windings are wound on same core leg 7 Equivalent Circuit Rp+jXp X m Rs+jXs R m Load Rp+Rs Xp+Xs X m R m Load 8

Transformer Design Basis Thermal Dielectric Short Circuit Quality Reliability Consistent performance Long Service life 9 Design Procedure Select Core Diameter & Area (A) Select Maximum Flux Density (Bm) Find Volts/Turn = 4.44 x Freq x Bm x A Find LV Turns = LV volts per Phase/ (V/T) Find HV Turns = HV volts per Phase/ (V/T) Select current densities LV & HV Select Conductor Area = Current / Density Select type of Winding: Helical,Disc,Center-fed,end-fed Finalize HV Axial & Radial Finalize LV Axial & Radial 10

Mass [x 1000 kg] Design Procedure Select Core - LV; LV-HV Ducts Draw Ampere - Turn diagram Find Impedance % : α 1, α 2, δ - radial dimensions of two windings and the gap l avg = π D 1-2 where D 1-2 = OD 1 +δ Check with guaranteed impedance, adjust V/T, height to get required impedance Finalize frame size- CD x WH x LC Find Iron Loss Find Load Loss u x 7.9 f Check for short circuit withstand Check for thermal withstand Check for impulse withstand x k I NT S a1 a2 k R 1 h N 2 lavg a1 a2 kr 10 h 3 3 4 % 11 Design Optimization 200 Transformer parameters as a function of core diamater Height [m] 10 180 9 160 140 Cu [ton] Fe[ton] Active part [ton] Height [m] 8 7 120 6 100 Active part 5 80 Core Height 4 60 3 Copper 40 2 20 1 0 700 800 900 1000 1100 1200 1300 Core diamater [mm] 0 12

Design Optimization Winding which are closer to each other have lower impedance. The taller the winding the lower the impedance. Impedance is changing in power two with the number of turns. Transformer impedance expressed in Ohms is independent from MVA base 13 Construction Type and Main Parts Core- or Shell Form Windings Circular for core-type, Pancake for shell-type Solid Insulation (turn-to-turn, section-tosection, winding-to winding, coil-tocore/clamp) Insulating liquid (coolant and main insulation) Tank Cooling equipment (radiators, coolers) 14

Shell Form 1. high voltage bushing 2. tank top section 3. cooling equipment 4. oil circulating pump 5. tank bottom section 17. pancake coil 18. inter-phase block 19. L.V. coil group 20. H.V. coil group 24. tank shielding 25. insulating washer 15 Core Form Concentric windings Set Winding Geometry Cooling options Cost consideration Shipping differences 16

Core Form 17 Types of Cores Type 1 Type 2 3 legs 1 wound leg 2 return legs legs and yokes not of equal cross section single-phase 2 legs 2 wound legs legs and yokes of equal cross section single-phase Type 3 3 legs 3 wound legs legs and yokes of equal cross section three-phase 18

Types of Cores cont. Type 4 4 legs 2 wound legs 2 return legs legs and yokes not of equal cross section single-phase Type 5 5 legs 3 wound legs 2 return legs legs and yokes not of equal cross section three-phase 19 Core Cutting Core Form Design Fully mitered & step lapped in corner joints improves flux distribution, minimizes losses & sound level Circular core shape provides windings with optimum radial support 20

Core Stacking Methods BUTT-LAP STACKING: Local concentration of flux higher excitation current & core loss STEP-LAP STACKING: Reduced Local flux concentration lower excitation current & core loss Core Material- Grain Oriented Silicon M - NON-LS; H - LS H ZDKH (laser scribed) ZDMH (mechanically scribed) 21 Tie-rod Based Clamping Systems 22

Tie-plates and Clamping Beams 23 Winding Types Layer / Barrel Layer / Barrel Mostly buried TV Good space factor Cooling only on vertical surfaces 24

Winding Types - Helix Helical Winding Inner windings Axial ducts allow for cooling on horizontal surface 25 Winding Types - Helix 26

Winding Types - Multistart Multistart Winding Used mainly for LTC taps Single or two layer H e lec 27 Winding Types - Multistart 28

Winding Types Tapped Disc / Helix Tapped Disc / Helix Used mainly for outer LTC or DTC windings Can be used internally, eccentric duct Two symmetrical halves Problems with impulse 29 Winding Types Tapped Disc / Helix 30

Winding Types Disc Winding Disc Winding Used for inner and outer windings 31 Winding Types Disc Winding 32

Winding Types Interleaved Disc Interleaved Disc Winding Improve impulse distribution Various forms of interleaving 33 Winding Types Shielded Disc Shielded Disc Winding Alternative to interleaving No joins in the winding conductor 34

Winding Types Shielded Disc 35 Magnet Wire, Paper Insulated 36

CTC - Epoxy Bonded, Netting Tape 37 Losses & Impedance No load losses: Hysteresis and eddy losses in transformer core Load losses: DC Losses Resistive loss in winding conductor Eddy Losses Produced by stray flux in the windings when current is drawn from the transformer Stray Losses Eddy losses in constructional parts (clamps, tank wall, etc) Impedance Dependent upon geometry, amp-turns, base power rating and frequency Effect on short circuit currents/forces 38

Eddy Losses in Conductor Eddy loss factor per unit of volume: Bm d sh sin ; ch cos d for d, then 3 2 Peddy 2 2 2 f d Bm V 6 2 Peddy Bm W 3 V 2 2 m where 2 d 2 f ; ; ; 4 10 7 H ; 20.967 10 m 9 m 39 Sound Level Magnetostriction - varying magnetic flux produces vibrations at fundamental frequency of 120 Hz for 60Hz power frequency ( or 100 Hz at 50Hz power) Sound level depends on: - core material - flux density in core - core weight - sound level increases proportionally to log (weight), - tank design and cooling system (# and type of fans, pumps) Measured at 0.3 m for core alone and at 2 m for top rating (with whole cooling equipment on) Sound level under load becoming a new requirement 40

Stray Flux Distribution CORE LV HV 41 Stray Flux Distribution Flux distribution with the tapping winding in position: (i) full rise, (ii) neutral, (iii) full buck 42

Stray flux distribution controlling the eddy loss by varying conductor size LTC Line Valve 43 Mechanical Forces in Windings Stress due to radial forces: Hoop on outer winding Buckling on inner winding Radial bending Stress due to axial forces: Compressive on keyspacer Tilting of conductors Axial bending between keyspacers Spiralling forces 44

Losses in Tank Wall 45 Losses in Constructional Parts 46

Insulation Coordination & Design Impact Withstand voltage BIL (LI) SIL Induced voltage Applied voltage Impact on design Bushings, lead structure & its clearances, winding clearances, stresses to ground, neutral point insulation External clearances, lead clearances, phase-to-phase stresses Internal winding stresses (V/T), stresses to ground, phase-to-phase stress Stresses to ground (windings, leads) 47 Electric Field Intensity in Hi-Lo Gap 48

Voltage (kv) Gradient (kv/mm) Comparison With Weidmann Curves 100 10 1 0.1 1 10 100 Distance (mm) 49 Transient Voltages in Tap Winding Across LTC, 200 kv neutral impulse, LTC 16L 350 300 Node 1 Node 26 (27) Difference 250 200 150 100 50 0 0 5 10 15 20 25 30 35 40 45 50-50 -100-150 Time (us) 50

End Insulation - Electric Field Distribution 51 Cooling Methods Cooling medium A - air cooling, O - oil cooling, K, L - cooling with synthetic fluid, W - water cooling Cooling mode N - natural cooling, F - forced cooling, D - directed cooling (directed oil flow) e.g. ONAN - oil natural, air natural ONAF - oil natural, air forced ODAF - oil directed, air forced - OA - FA - FOA 52

Directed and Non-Directed Oil Flow Directed Non - Directed 53 Cooling A) ONAN, OA - Oil natural, air natural B) ONAF, FA - Oil natural, air forced C) OFAF, FOA - Oil forced, air forced 54

Cooling D) ODAF, FOA - Oil directed, air forced - The oil is pumped and directed through some or all of windings E) OFWF, FOW - Oil forced, water forced F) ODWF, FOW - Oil directed, water forced 55 Tap Changers Load tap changers (LTC) De-energized type changers (DETC) Bridging Linear Series/parallel Delta/wye 56

DETC Typically in HV w/adjustment of ±5%, 4 steps Bridging Type Linear Type 57 LTC (On) Load Tap Changer - switching under load! L.T.C. Switches - Resistive Bridging - Current limiting resistors - Reactive Bridging - Preventative auto-transformer (reactors) On tank & In tank Vacuum or Arcing in oil 58

Resistive - Type LTC Fig. a Fig. b Position 1. The main contact H is carrying the load current. The transition contacts M1 and M2 are open, resting in the spaces between the fixed contacts. The transition contact M2 has made on the fixed contact 1, and the main switching contact H has broken. The transition resistor and the transition contact M2 carry the load current. Fig. c Fig. d The transition contact M1 has made on the fixed contact 2. The load current is divided between the transition contacts M1 and M2. The circulating current is limited by the resistors. The transition contact M2 has broken at the fixed contact 1. The transition resistor and the transition contact M1 carry the load current. Fig. e Position 2. The main switching contact H has made on the fixed contact 2. The transition contact M1 has opened at the fixed contact 2. The main contact H is carrying the load current. 59 Reactor-type LTC tap n tap n+1 tap n tap n+1 P1 P4 P1 P4 I L 2 CT V I I L 2 I L 2 CT I L 2 P2 P P3 P2 P P3 Non - Bridging Bridging 60

Mechanical Design Overview Conservator Handholes Oil level gauge Bushings Lifting Bollards/Lugs Dry air bottles Neutral ground copper bars Dehydrating breather Bushing connectors Copper bars Lightning arrestor Pressure Relief Device Radiator Gas detector relay (GDR) Impact recorder Control Box Stiffeners Jack steps Anchors Skid Ladder 61 Tank Design contain the oil and serve as supporting structure Conventional Tank Two basic types of tank construction: Conventional Tank This type of construction has a top cover as shown. Bell Tank Bell Jar Tank In this type of tank construction, the joint between the two parts is at the bottom yoke level to facilitate the inspection of core-winding assembly at site after the bell is removed. 62

Tank Design The transformer tank should be capable of withstanding the following loads: Lifting Bollard 1. Vacuum Maximum allowable deflection for the tank is 0.005 x span length Bollard Lifting Lug 2. Lifting designed to facilitate handling of the transformer. Lifting bollards/lugs are used to lift the structure by a crane Lifting Lug Lug 63 Tank Design 3. Jacking designed to facilitate handling of the transformer. used for handling the transformer in the absence of crane, especially at the site Tank Wall Gussets Jack Step Jacking pad 64

Tank Design 4. Seismic and wind load: The transformer has to be designed for a specified seismic acceleration and wind load. are very important design considerations for bushings, supporting structures of conservator and radiators. 5. Transient pressure rise When an internal fault takes place, a large volume of decomposed gases may get generated due to arcing. Under these conditions, the tank structure has to withstand a rapid rise of pressure. Sound Reduction Other consideration to take into account when designing tank is to reduce sound generation 65 Tank Design Base of Tank can be stiffened by formed channels or c-channels to reduce its thickness Designed to carry core-winding assembly weight, oil head and test pressure Skid Base Flat Base 66

Transport Wheels/Skids It is normally not practical to lift larger units by crane directly to final position. If a cast-in-rails system exist between unload area and final position, the unit may be equipped with wheels allowing it to be rolled in If no rail system exists, the unit is skided to final position Rail System with Wheels 67 Tank Design Cover of Tank Designed to withstand vacuum load Stiffened by formed channels, c-channels, or flat bars Many accessories are mounted on top of cover Type of cover: Flat, Slope, Domed Flat Cover Slope Cover Domed Cover 68

Stiffener The design of stiffeners is a very important aspect of tank design An effective stiffening arrangement can reduce the tank plate thickness. Thus, tank weight is minimum. should be able to withstand the specified loads Types of stiffeners used Formed channels Angles Bars 69 55 Vertical and Horizontal Stiffeners 540 MVA, 345/22 kv GSU 70

Oil Preservation Systems GAS-OIL SEALED Free space (nitrogen gas or dry air) is provided in the tank for oil expansion The contact of oil with the outside atmosphere is totally eliminated. A positive pressure of 0.5 to 5 psi Advantage Simple design, no conservators Disadvantage Maintenance of gas system Possibility for gas bubble generation, which reduces the dielectric strength Can only designed for a transformer up to 550 KV BIL 71 Oil Preservation Systems Conservator System Oil preservation system Connected to transformer tank by piping. Can be provided with air bag Air bag A synthetic rubber bag occupies the space above oil to prevent air from contacting the oil Internal of the bag is connected to atmosphere Breathe in air when transformer cools and the oil volume is reduced breathe out when transformer heats up. Air typically enters and exits through a desiccant-type air dryer/breather The main parts of the system are the expansion tank, air bag, breather, vent valves, liquid-level gauge, and alarm switch 72

Oil Preservation Systems Conservator System Complete oil system in transformer Expansion tank Piping Dehydrating breather, Liquid-level gauge 73 3D Transformer Design 74

Transformer Product Visualization in UG Downstream Visualization in Shop & Supplier Reduce/Eliminate 2-D Drawings Improve feedback mechanism Eliminate non value added activities on clarifications 75 Design Example HV Internal 76

Design Example LV Internal 77 Design Example HV External 78

Design Example LV External 79 Finite Element Model - Deformation 80

Finite Element Model Safety Factor 81 Finite Element Model Equivalent Stress 82

Deflection Plot Under Pressure Loading Deflection in mm 83 Manufacturing Process Core Construction Insulation Windings Core and Coil Processing Testing Tanks Shipping 84

Core Cutting Georg 1000 85 Core Parts (Legs and Yokes) Stacked 86

Core Stacking Use of temporary bolt guides for stacking 2, 3, 4 & 5 leg cores manufactured for single & three phase units 87 Core Stacking Oil ducts utilized to control temperature rise Temporary, Permanent or combination of banding 88

Coil Assembly Winding type Conductor Type Insulation components 89 Complete Winding Insulation Package 90

Coil & Core Assembly Coils lowered over core Top coil to clamp insulation Top clamps Top core inserted 91 Coil & Core Assembly Windings are clamped using external or internal tie rods to provide additional support for axial forces Leads and busbars are rigidly supported to withstand forces from shipping & short circuits Assembly moved on air cushions 92

Tank Shop Cleaned, priming and painted Inside painted white Shunt Packs 540 MVA, 345/22 kv GSU 93 Tank Covers Raised flanges Domed cover Mild steel plate w/inserts 94

Vapor Phase Core and coil assembly - kerosene vapor cycle drying Power factor & water extraction - continually monitored Kerosene is vaporized Water & Vapor drawn by vacuum into autoclave 95 Re-Pack & Tanking Re-packed, final hydraulic clamping Limited exposure time 250 ton over head crane 504 MVA, 230/115 kv Auto 96

Testing All Industry standard tests : Routine Tests Loss Measurement and Temperature Rise tests Dielectric tests Zero-phase-sequence Audible Sound Level Short-circuit tests, if required (performed at the IREQ lab) 97 Securing Transformer for Shipping Steel bars are welded to secure the transformer PacifiCorp 540 MVA, 345/22 kv GSU Securing the transformers are performed according to AAR rule AAR Association of American Railroad New document: IEEE Std C57.150 1 dia. tie rods are used to secure the transformer 98

IEEE Std C57.150-2012 Guide for transportation IEEE Guide for the Transportation of Transformers and Reactors Rated 10,000 kva or Higher major topics covered are as follows: Request for quotation and specification Design Considerations for Transport Transportation preparation (Main transformer or reactor, tank accessories) Planning for heavy haul transportation Transport (Transportation information, terminology, Barge and ocean vessels, Rail, Air cargo, Arrival at destination, dielectric fluid) Heavy haul transportation (Condition of heavy haul equipment, Inspection of equipment prior to receiving, Offloading the equipment onto heavy haul transportation equipment, Securing the load, Transportation to the destination ) Arrival (receipt) inspection 99 IEEE 57.150 six degrees of motion at sea Vessels underway at sea will experience wind and wave conditions that cause six degrees (or freedoms) of motion. Three degrees of motion are rotational: the side to side rotation is called roll,, the fore to aft rotation causing the bow to rise and fall opposite to the stern rising and falling is called pitch, while turning or rotation about the vertical axis is called yaw. Three degrees are linear or axial: In combination or separately, the vessel may experience forth to aft acceleration/deceleration called surge, sideways movement called sway, and, vertical movement called heave. 100

IEEE 57.150 design aspects The design and shipping details of new transformers and reactors should be addressed during the design phase and prior to the manufacture to address all aspects of transport from factory to final pad. The equipment should be designed to allow transportation by both rail and truck, as well as by ocean vessel, barge, or air cargo when appropriate. The core legs should have a solid support from the bottom to the top clamp to prevent sideways deformation and bulging of the outermost laminations. The core should be adequately braced to the core clamping structure, so that it cannot move in any direction. The windings should be tight to prevent movements relative to the core. The core and coil assembly and other internal components should be supported by permanent bracing to the interior of the tank. Temporary transportation braces for the core and coil should not generally be required, and should only be allowed with special approval and instructions for use formally documented. Temporary transportation supports may be required in some units (e.g. units that will be subjected to long sea voyages, shell form, or other units shipped in a laid down position), or for current transformers, leads, bushing supports, and other ancillary items. 101 Schnable Road Trailer 102

Field Assembly Unit has been skidded onto foundation fully assembled. Vacuum processed Oil filled with approx. 29,000 imperial gallons of oil 700 MVA, 345 kv, Auto Shipping Wt. 524,000 LB Total Wt. 870,470 LB 103 Thank You! 104