Transformer Manufacturing Processes
|
|
|
- Daisy Morrison
- 9 years ago
- Views:
Transcription
1 Transformer Manufacturing Processes - Ronnie Minhaz, P.Eng.
2 Most common types of power transformers: GSU s (Generator Step-Up): 2 windings HV/LV 3 windings HV/LV1/LV2 with D.T.C. in HV, typically ± 2x2.5% normally no L.T.C. Connection Wye/Delta typical LV: 10, 20, 25 kv + 5% - 5% typical HV: 33, 69, 115, 138, 161, 230, 345, 500 kv Single-phase Three-phase
3 Most common types of power transformers: Auto-Transformers: 1 winding (series + common winding) 2 windings (series + common) + tertiary winding D.T.C. in HV L.T.C. in HV or LV Single-phase or three-phase Connection: always Wye/Wye purpose of tertiary winding suppression of harmonics can be buried (no bushings brought out) sometimes brought out for station service voltage tertiary sized at 33% of rating Auto-transformer has smaller frame size e.g. Rating = 300 MVA Frame size: HV = 230 kv x 300 = 150 MVA LV = 115 kv 230
4 Most common types of power transformers: Step-down transformers: 2 winding HV/LV + D.T.C. 2 winding HV/LV + L.T.C. winding 3 winding HV1xHV2/LV + D.T.C. HV1xHV2/LV + L.T.C. winding HV/LV1xLV2 + D.T.C. HV/LV1xLV2 + L.T.C. winding D.T.C. HV L.T.C. LV D.T.C. LV or HV L.T.C. HV or LV Connection: Delta - Wye (majority) Wye - Delta Wye - Wye Three-phase
5 Core Construction Insulation Windings Core and Coil Processing Tanks Testing Shipping
6 Core Dimensions
7 Stacking Height (SH) Diameter of the core circle (DCC) Circular core cross section: Core Dimensions Steps of 5 mm for DCC Widest sheet width
8 Core stacking methods BUTT-LAP STACKING: Local concentration of flux higher excitation current & core loss. STEP-LAP STACKING: Reduced Local flux concentration lower excitation current & core loss. Core Material- Grain Oriented Silicon M - NON-LS; H - LS H ZDKH (laser scribed) ZDMH (mechanically scribed)
9 Core Cutting - Georg Automatically stacks legs & yokes Purchase uncut slit rolls of steel or pre-cut
10 Core Logs Stacked
11 Core Cutting Core Form Design Fully mitered & step lapped in corner joints improves flux distribution, minimizes losses & sound level Circular core shape provides windings with optimum radial support
12 Core Stacking Use of temporary bolt guides for stacking 2, 3, 4 & 5 leg cores manufactured for single & three phase units
13 Core Stacking Oil ducts utilized to control temperature rise Temporary, Permanent or combination of banding
14 Core Stacking
15 Coil Winding Shop Winding room separate from other manufacturing areas Positive Pressure Horizontal/Vertical winding mandrels
16 Coil Winding Windings are circular concentric type Conductor are either copper magnetic wire or continuously transposed conductor Conductor purchased pre-wrapped with thermally upgraded paper or Nomex High strength wire or epoxy bonded CTC used when high short circuit forces Winding type chosen according to voltage & application, Cont. Disc, Interleaved Disc, Helical, etc.
17 Continuously Transposed Conductor
18 CTC Thermally upgraded paper
19 CTC - epoxy bonded, netting tape
20 CTC - Perforated Nomex
21 Magnet Wire, Paper Insulated
22 Winding Types 2 main groups helical windings disc windings
23 Flat/Edge Wound Wound on flat side Edge Wound
24 Winding Types helical windings 2 main groups disc windings Boomerang Giron Equally transposed Layer and multilayer Multistart Continuous disc Interleaved Partial Interleaved Axial Interleaved Mainly LV, TV, CR and FR Mainly HV, LV, FR
25 Helical Winding
26 Helix Boomerang MW
27 Helix- Boomerang, Giron, Double Helix equally Transposed Use(Varies from Manufacturer to Manufacturer): 1 or 2 layers Up to 325 kv BIL for single-layer windings Up to 200 kv BIL for two-layer windings Axial cooling ducts in the winding or with zigzag cooling depending on what kind of helix Preferably with at least one turn between successive transpositions Advantages: Cheap winding No radial overbuild at the transpositions depends on Boomerang type Disadvantages: One brazing per transposition on Boomerang type Cannot be used for zigzag cooling without radial overbuilds on Giron and Double helix type
28 For inside windings For outside windings Manufacturing Process: Tapped helix MW / CTC Regulating winding(for LV) Easy to wind, high Cu cross-section possible Eccentric duct necessary if used as inside winding
29 Multistart MW / CTC With ZnO-discs : up to 1050 kv BIL, Without ZnO-discs : up to 450 kv BIL if impulsed and up to 950 kv BIL if not impulsed Easy to wind, Uniform Amp-turns distribution, Robust winding, especially when MW is used on the edge Medium to high paper insulation thickness needed, due to the voltage difference of 1 or 2 taps between adjacent wires. This can cause high thermal winding gradients.
30 Continuous disc Many electrical turns, up to 550 kv BIL with key spacers, above 550 kv BIL with key spacers in combination with interleaved part at impulse side Easy to wind, No brazing, High axial space factor and reduced manufacturing time for version without key spacers Partial turns can cause extra sections, Decreased radial space factor for the version without key spacers
31 Continuous disc Transposition Transposition at each cross over
32 Interleaved Many electrical turns, typically above 550 kv BIL, if necessary for impulse reasons Adjacent is standard method for interleaving, Braided interleaving method if necessary for lightning impulse High impulse withstand capability, due to improved voltage distribution Brazing necessary, and thus very time consuming with CTC, Total number of sections must be even
33 Interleaved Winding
34 Shielded Winding
35 Shielded Winding
36 Winding Selection Based on: winding voltages: (nominal, test, impulse, ) number of turns electrical clearances ZnO discs allowed? winding current: needed Copper cross-sectional area maximum allowed temperature (average and hottest spot) cooling type: axial cooling or zigzag cooling winding position in the core window
37 Lead Connection Stress ring and pick tail connected with lead
38 Upender
39 Insulation Shop Insulation Shop separate from other areas Winding cylinders and spacers are made from high density pressboard
40 Complete Winding Insulation Package
41 Coil Sizing Coil sizing force applied to check and adjust (of stabilize) the winding height
42 Coil Assembly Winding type Conductor Type Insulation components
43 Coil Assembly
44 Coil Assembly
45 Coil Assembly
46 Coil & Core Assembly Exposed edges of core are bonded with low viscosity, high strength epoxy resin which penetrates and bonds laminations. Prefabricated coil to clamp insulation is placed on bottom clamps
47 Coil & Core Assembly Coils lowered over core Top coil to clamp insulation Top clamps Top core inserted
48 Lead Braising
49 Lead Braising
50 LV Cu bus bar instead of cable for high current
51 HV Center Fed with snout and draw lead to bushing; reactor for RMV tap changer
52 Coil & Core Assembly Windings are clamped using external or internal tie rods to provide additional support for axial forces Leads and busbars are rigidly supported to withstand forces from shipping & short circuits Assembly moved on air cushions
53 LTC Lead Connection
54 DTC Lead Connection
55 DTC Lead Connection
56 Link Board: Re-connectable LV
57 ZnO Used for taps usually above 550kV impulse voltage
58 Vapor Phase Unit Complete core and coil assembly is dried using a vapor phase cycle method Power factor & water extraction are continually monitored Kerosene is vaporized & drawn by vacuum into autoclave
59 Tank Shop Designed to withstand full vacuum filling Facilities for lifting, jacking, and pulling provided
60 Tank Shop All tanks are grit-blasted cleaned before priming and painting. Inside painted white for good visibility during internal inspections. Shunt Packs
61 Tank Covers Raised flanges are provided to prevent water entry Cover is designed to prevent water collection High quality steel plate is cut by an automated waterbed plasma cutter
62 Re-Pack & Tanking After vapor phase unit is re-packed and undergoes final hydraulic clamping Maximum exposure time to atmosphere is limited to under 16 hours
63 LTC Lead Connection
64 LTC Lead Connection
65 Exciter and Series Transformer
66 Final Assembly Installation of conservator, radiators, pumps, fans, etc.
67 Final Assembly Fans bottom mounted
68 Final Assembly The surge of one pump should die down before the next pump comes-on
69 Testing All Industry standard tests : Routine Tests Loss Measurement and Temperature Rise tests Dielectric tests Zero-phase-sequence Audible Sound Level Short-circuit tests, if required (performed at the IREQ lab)
70 Factory Pretest Test Standard Section Engineering Instruction Parallel Turns No EMT Ratio,Polarity,Core meg. Std EMT R.S.G. Yes EMT Non Linear Resistors Std EMT CT's & PT's Std EMT LTC Reactor Std EMT LTC Pretest prior to tank. Std EMT
71 Factory Tests Ratio Std ANSI C Polarity Std Resistance Std Core Loss & Exciting Current Std 8.1 Load Loss & Impedance Std 9.1 Zero Sequence Impedance 9.5 Temperature OA 11 Rise Tests FA 11 Overload 11 Lightning HV 10.3 kv LIL Impulse HVN kv LIL LV kv LIL LVN kv LIL TV kv LIL Switching HV 10.2 kv SIL Impulse LV kv SIL Applied HV 10.5 kv rms Potential LV kv rms TV kv rms Induced Potential 10.7 Partial Discharge 10.8 Sound Level % Voltage Run CAN/CSA-C88-M k Core Loss after Dielectrics ANSI C CAN/CSA-C88-M k
72 Factory tests cont. Test Standard Section Engineering Instruction Dissipation Std EMT & ANSI 10.9 Core Megger Std CSA & EMT CT Resistance Std CT Ratio & Polarity Std CSA & EMT PT Ratio & Polarity Std CSA & EMT Hi-Pot: Panels, Fans, Std CSA & MI Pumps Hi-Pot: PT's & CT's Std CSA & EMT Hot Spot Calibration Std CSA & EMT Top Oil Calibration Std CSA & EMT GDR Alarm & Trip Std CSA & EMT Panel Operation Std CSA & EMT Line Drop Compensator Std CSA & MI Fan, Pump Losses;Klixon Std CSA & EMT Tapgear Operation Std CSA & EMT Pressure Tests Std CSA & MI Gas-in-Oil Samples PCB Oil Sample ADDITIONAL TESTS
73 Unit in Test
74 Paint Booth Epoxy base paint system, meets ANSI C
75 Shipping Parts
76 Shipping Transformer
77 Shipping Transformer
78
Transformer Design & Design Parameters
Transformer Design & Design Parameters - Ronnie Minhaz, P.Eng. Power Transmission + Distribution GENERATION TRANSMISSION SUB-TRANSMISSION DISTRIBUTION DISTRIBUTED POWER 115/10 or 20 kv 500/230 230/13.8
Power Transformer Fundamentals: Design and Manufacturing
Power Transformer Fundamentals: Design and Manufacturing Waldemar Ziomek, Engineering Manager CG Power Systems Canada Inc IEEE Training, Houston, Texas, Oct.8-9, 2013 1 Overview Transformer Design Transformer
Technical catalogue About KOLEKTOR ETRA has been acting as transformer manufacturer over more than 75 years. Specializing in the manufacturing of power transformers rating up to 500 MVA and 420 kv the
MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
Presentation of the France Transfo factories
Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15
Power Transformers 10 to 100 MVA
Power Transformers 10 to 100 MVA Transformer technology at a glance An extensive transmission system with efficient transformers is indispensable to ensure a reliable supply of power. Consequently Siemens
Liquid Filled Transformers Load Tap Changing Transformers Three-Phase Voltage Regulators
Liquid Filled Transformers Load Tap Changing Transformers Three-Phase Voltage Regulators Virginia Transformer is a leader in custom power transformers engineered precisely for your application and optimized
Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission
Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up
Transformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
This section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
Table of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
SECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
SECTION 16322 SUBSTATION TRANSFORMERS
SUBSTATION TRANSFORMERS PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the primary and/or secondary substation transformers as specified herein and as shown on the contract
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is
Transformers. Special transformers Reactors products
Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having
Tasarım ve Baskı: AJANSBRAND A 15.09.2014
www.kosgeb.gov.tr Tasarım ve Baskı: AJANSBRAND A 15.09.2014 THE ENERGY TRANSFERRED TO NATURE www.atstrafo.com ABOUT Having been founded in Adıyaman Organized Industrial District in 2003, ATS Trafo carries
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
The Don ts of Better Flexible Circuit Design and Manufacture By Mark Finstad Friday, 01 June 2007
The Don ts of Better Flexible Circuit Design and Manufacture By Mark Finstad Friday, 01 June 2007 Successful designs are soon forgotten but failures are remembered for years. Steering clear of these twelve
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Power Transformers Small, Medium & Large
Power Transformers Small, Medium & Large O F T H E A L T R G R O U P A N M E M B E R O ALTRON 10 State of the Art Transformer Manufacturing Facility Experience and Design Capability Powertech Transformers
3. Three phase winding technology
3. Three phase winding technology VATech Hydro, Austria Prof. A. Binder 3/1 Single layer winding Per slot only one coil side is placed. Coils manufactured as: a) Coils with identical coil span: W = τ p
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
understanding medium frequency induction melting furnace and its components
understanding medium frequency induction melting furnace and its components 9 Spruce Street, Jersey City, NJ 07306 USA [email protected] INDUCTION MELTING FURNACE AND ITS COMPONENTS The purpose
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
WINDING RESISTANCE TESTING
WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991
25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
EH-20 20m antenna. By VE3RGW
EH-20 20m antenna By VE3RGW Equivalent circuit of EH-20 (prototype 2A) antenna system. Upper cylinder Lower cylinder Ground Counter pose Phasing coil Impedance transformer and tune circuit Tune coil Feed
Flex Circuit Design and Manufacture.
Flex Circuit Design and Manufacture. Hawarden Industrial Park, Manor Lane, Deeside, Flintshire, CH5 3QZ Tel 01244 520510 Fax 01244 520721 [email protected] www.merlincircuit.co.uk Flex Circuit
THE VALUE OF POWER FACTOR TESTING
THE VALUE OF POWER FACTOR TESTING Nov 1, 2005 12:00 PM by John Bleyer and Phillip Prout, National Grid NATIONAL GRID DISCOVERED A HIGH POWER FACTOR DURING ACCEPTANCE TESTING of a new 40-MVA transformer
Power transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
Effect of design parameters on temperature rise of windings of dry type electrical transformer
Effect of design parameters on temperature rise of windings of dry type electrical transformer Vikas Kumar a, *, T. Vijay Kumar b, K.B. Dora c a Centre for Development of Advanced Computing, Pune University
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60076-11 First edition 2004-05 Power transformers Part 11: Dry-type transformers This English-language version is derived from the original bilingual publication by leaving out
Flexible Solutions. Hubert Haidinger Director PE/CAM BU Industrial & Automotive 5.June 2013. www.ats.net
Flexible Solutions Hubert Haidinger Director PE/CAM BU Industrial & Automotive 5.June 2013 www.ats.net Austria Technologie & Systemtechnik Aktiengesellschaft Fabriksgasse13 A-8700 Leoben Tel +43 (0) 3842
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
Electrical Maintenance Workshop
Electrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003 Transformer Maintenance & Testing Purpose This presentation provides an overview of the major considerations
Transformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
WIRE AND CABLE ENGINEERING GUIDE
DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a
Grounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
PI734D - Technical Data Sheet
PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
PI734B - Technical Data Sheet
PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
Basic Load Tap Changer Operation
Basic Load Tap Changer Operation Topics Basic Transformer Theory Differences from LTC s to DETC s LTC Definitions Transformer Nameplates Purpose of a Tap Changer How Does an LTC Work? Topics Reactance
Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E
SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant
Testing of Power Transformers. Routine tests, Type tests and Special tests
Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests
Figure 1 (end) Updated document to corporate requirements Added text to Paragraph 2.4
This specification covers the requirements for application of ELCON Drawer Series Connectors: True Hot Plug, Blind Mating Mixed Signal and Power Connectors. These connectors are designed for use in pluggable
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
Modeling of Transmission Lines
Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward
Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
Practical Transformers: Operation, Maintenance and Testing
Practical Transformers: Operation, Maintenance and Testing YOU WILL GAIN: 4 hour live, practical online course Saturday, 2 nd May, 2015 8.00AM WST; 10.00AM AEST An understanding of the fundamental theory
Radial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
James M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
UCI274C - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet
HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards
AMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
UCI274H - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
Active noise control in practice: transformer station
Active noise control in practice: transformer station Edwin Buikema 1 ; Fokke D. van der Ploeg 2 ; Jan H. Granneman 3 1, 2, 3 Peutz bv, Netherlands ABSTRACT Based on literature and extensive measurements
Figure 1 (end) Application Specification 114 13088 provides application requirements for MICTOR Right Angle Connectors for SMT PC Board Applications
This specification covers requirements for application of MICTOR Vertical Board to Board Plugs and Receptacles designed for pc boards. The connectors have an in row contact spacing on 0.64 [.025] centerlines.
PM734F - Technical Data Sheet Winding 28
- Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Multi-tap Transformers
Multi-tap Transformers Three-Phase Multi-tap Transformer for Electrical Submersible Applications Functional Specification Guide Functional Specification for Multi-tap Transformers for Electrical Submersible
HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR
HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new
Medium-voltage transformers
Medium-voltage transformers We make energy measurable and take care of your future www.mbs-ag.com Page 2 E-Mail: [email protected] Web: www.mbs-ag.com Contents Current transformers Technical characteristics
transformer division Convincing with outstanding solutions: Leading technology for transformer production.
transformer division Convincing with outstanding solutions: Leading technology for transformer production. With a passion for technology we at Georg have been developing inspirational solutions for generations
DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.
DC Generators DC generators are widely used to produce a DC voltage. The amount of voltage produced depends on a variety of factors. EO 1.5 LIST the three conditions necessary to induce a voltage into
SPECIFICATIONS OF STATCOM TRANSFORMER (FOR 2.5 MVAR STATCOM)
SPECIFICATIONS OF STATCOM TRANSFORMER (FOR 2.5 MVAR STATCOM) PROJECT EQUIPMENT Quantity : 2.5 MVAR STATCOM. The transformer will be used for connecting a 2.5 MVA Inverter with grid at 6.6 kv. : Transformer
KNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
An equivalent circuit of a loop antenna.
3.2.1. Circuit Modeling: Loop Impedance A loop antenna can be represented by a lumped circuit when its dimension is small with respect to a wavelength. In this representation, the circuit parameters (generally
SIL Resistor Network. Resistors. Electrical. Environmental. L Series. Thick Film Low Profile SIP Conformal Coated Resistor Networks RoHS Compliant
Resistors SIL Resistor Network Thick Film Low Profile SIP Conformal Coated Resistor Networks RoHS Compliant All parts are Pb-free and comply with EU Directive 2011/65/EU (RoHS2) Electrical Standard Resistance
MGB Chrome Bumper Conversion
MGB Chrome Bumper Conversion Installation Instructions For 1974 1/2-1980 MGB This kit requires cutting, welding, and painting. Professional installation recommended. Note: Every MGB body is slightly different
Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E
SIEMENS Siemens Energy, Inc. Power Technology Issue 106 Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos Grande-Moran, Ph.D. Principal
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
High-ohmic/high-voltage resistors
FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
ELECTRICAL ENGINEERING Vol. III - Induction Motor and Self-Excited Induction Generator - Tze-Fun Chan
INDUCTION MOTOR AND SELFEXCITED INDUCTION GENERATOR TzeFun Chan The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong, China Keywords: threephase induction motor, singlephase induction motor,
Distribution Voltage Regulators
Distribution Voltage Regulators Type JFR Single Phase 2.5 to 19.9 kv Type SFR Three Phase 13.2 to 34.5 kv Power Transmission & Distribution Siemens JFR & SFR Voltage Regulators Improving Quality of Service
ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION
ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION Ref: WG 21.06 (TB 177) JTF 21.15 (TB 210) TF B1.10 (Electra 212) Henk Geene Presentation overview Accessories function Accessory design Accessory types
SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
GUIDE FOR TESTING POWER TRANSFORMERS
GUIDE FOR TESTING POWER TRANSFORMERS Routine test 11/11/02 Pagina 1 di 10 INDEX Introduction... 3 1 Dielectric tests Separate-source voltage withstand test... 4 2 Induced voltage test... 5 3 Voltage ratio
Section 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw
,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
Subminiature Load Cell Model 8417
w Technical Product Information Subminiature Load Cell 1. Introduction... 2 2. Preparing for use... 2 2.1 Unpacking... 2 2.2 Using the instrument for the first time... 2 2.3 Grounding and potential connection...
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic