Midea Commercial Air Conditioner Malfunction Handbook



Similar documents
SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Technical service manual

Failure code manual. content

Technical service manual 2009

PANASONIC TROUBLE SHOOTING GUIDE

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM EXPLOSION VIEW 12 6.

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit

TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O

INSTALLATION MANUAL. Address card EKAC10B

14. Troubleshooting Guide

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.


SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

ECOCIAT. Domestic hot water heat recovery unit

, User s Manual

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

Repair Guideline for SANYO New Erp. DC Inverter Air Conditioner (Published in May, 2013)

Air Conditioning System

Condensing unit type EPSILON-ECHOS LE Technical information manual

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

ChapterⅠ Introduction to Products

Repair Guideline for TCL DC Inverter Air Conditioner

ABNORMAL OPERATION Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

SMM. Installation Operation Maintenance

Cool Design for Homes and Offices

AIR-COOLED CHILLERS APPLIED SYSTEMS. EUWA*5-24KAZW - EUWY*5-24KAZW -

FULL DC INVERTER SYSTEMS

DM en. Service manual MIV V5 HEAT PUMP DC INVERTER R410A MVUH252B-VA3 MVUH280B-VA3 MVUH335B-VA3 MVUH400B-VA3 MVUH450B-VA3 MVUH500B-VA3

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

Basic Technology Series

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

Service manual. The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy

Simple Self-Diagnosis by Malfunction Code

HEATER, AIR CONDITIONING AND VENTILATION

AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS

Technical Service Manual. Version One

york air-conditioning products Residential & VRF News 2015

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

CRAC Precision climate control units for data centres

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

Chilled Water Precision Air Conditioner For Critical Application

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Appendix - Controllers 179

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

How To Wire Wire Wire A Power Supply On A Powerline (Powerline) From A Powerstation To A Powerplant (Powerplant) (Powerplant) (Control Board) (Wire) (Switchboard) (Wired) (

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

10.1 Indoor Unit Error Display

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

Test Report issued under the responsibility of:

USER S MANUAL HSC-24A

D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

Split units TH with hermetic compressors

technical data air conditioning systems RXS E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

Refrigeration & Air Conditioning

Repair Guideline for TCL DC Inverter Air Conditioner

HVAC SYSTEM (HEATER, VENTILATOR, AND A/C)

SERVICE MANUAL. Model No. HSU24VHJ(DB) Wall mounted Type DC Inverter EA-Series WARNING. Haier Group. Order No.AC1101S021V0

Application Engineering

Heat Pump Water Heater IOM Manual

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

State of the Art Energy Efficient Data Centre Air Conditioning

marine/bespoke split applications

Vertical Display and Storage B SKOPE Gen2: Three Door Chiller

WATER SOURCE / GEOTHERMAL COOLING HEAT PUMP

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC

- White Paper - Data Centre Cooling. Best Practice

CoolTeg Plus Chilled Water (CW) version: AC-TCW

Haier Air conditioner

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

How To Design A Building In New Delhi

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS

AIR CONDITIONER INSTALLATION MANUAL

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

CGC s Hybrid System Loop Control

HVAC Systems: Overview

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

Transcription:

Midea Commercial Air Conditioner Malfunction Handbook May 1, 2008

Customer Service Philosophy of Midea Air Conditioner Service Target: 100% Customer Satisfaction Service Standard: 100% Earnestness Service Tenet: Customer First Forever 1

Contents I. Error Indication of MDV Indoor Units 6 II. Error Indication of MDV Digital Scroll Central Air Conditioner 8 1. Error Indication of Digital Scroll Unit D3 (D4) 8 2. MDV-D540 (560, 580, 820, 840, 860) W/S-820...12 3. MDV-D280 (220) W/S-810...15 III. Error Indication of Intelligent Variable Frequency Central Air Conditioner 18 1. Error Indication of V3 (V4, Vi) Intelligent Variable Frequency Unit 18 2

2. MDV-J280W/S-810(811) 23 3. MDV-280W/BS...26 IV. Error Indication of MDV Home Central Air Conditioner 32 1. MDV(H)-J140(120)W-510(511), MDV(H)-J160(180)W(/S)-720...32 2. MDV-D100 (120) (/S)..35 3. Error Code List for Novel M-home Series Digital Indoor Unit. 38 4. Error Code List for Novel Home Digital Water Unit.41 5. MDV-J110 ~ MDV-J160 AC Inverter 44 6. Home Central Air Conditioner with Water System Based on Frequency Conversion..52 3

7. KFR-61T2W/BP or KFR-40 2W/BP-510T2.59 V. Error Indication of Unitary Central Air Conditioner...70 1. Error Code List of Ordinary One-to-One...70 2. Error Code List of Novel Four-way cassette...74 3. Error Code List of 10HP Air Cooled Cabinet Unit 78 4. Error Indication of 20HP Medium Static Pressure Fan Coil Unit...79 VI. Error Indication of Digital Scroll Air Cooled Module...92 1. Display List of Error and Protection for 60Kw Modular Air Cooled Heat Pump Unit..92 2. Display List of Error and Protection for 200KW Large Modular Air Cooled 4

Heat Pump Unit.96 3. Code List of Error and Protection for Wire Controller on Modular Unit.97 VII. Error Indication of Water Cooled Cabinet Unit.100 VIII. Error Indication of Screw Unit 105 IX. Error Indication of Network Air Conditioner.113 5

I. Error Indication of MDV Indoor Units LED Flash RUN Indicator Flash, Slowly RUN Indicator Constantly On Pre-heating/Defrosting Indicator Constantly On Timing Indicator Constantly On RUN Indicator Flash, Quickly Definition of Error or Protection Standby Operation Anti-cooling or Defrosting Start up Timing Function Error in Any Temperature Sensor in Indoor Unit 6

Timing Indicator Flash, Quickly Pre-heating/Defrosting Indicator Flash, Quickly Alarm Indicator Flash, Quickly Alarm Indicator Flash, Slowly Communication Error between Indoor Units and Outdoor Unit Mode Conflict Water Level Alarm Outdoor Unit Error 7

II. Error Indication of Midea Digital Scroll A/C 1. Error Indication of Digital Scroll Unit D3 (D4) Display Definition of Error or Protection Content Remark E0 Communication Error between Outdoor Units Only Displayed on Principal Unit E1 Phase-sequence Protection E2 Communication Error between Indoor Units and Outdoor Unit 8

E3 T3 Tube Temperature Sensor Error E4 E5 T4 Ambient Temperature Sensor Error Digital Discharge Temperature Sensor Error E8 Outdoor Address Error H0 Mode Conflict Error (D3 R410a) H1 Communication Error between Chips H2 Reduction in the Number of Outdoors Only Displayed on 9

H3 Units Increase in the Number of Outdoor Units Master Unit Only Displayed on Master Unit P1 High-voltage Protection P2 Low-voltage Protection P3 Over-current Protection of Digital Scroll Compressor 10

P4 P5 P7 P8 Over-high Discharge Temperature Protection of Compressor High Tube Temperature Protection of Outdoor Condenser Current Protection of NO.1 Fixed Compressor Current Protection of NO. 2 Fixed Compressor 11

2. MDV-D540 (560, 580, 820, 840, 860) W/S-820 Error Indication of Outdoor Main Control Board DSP1 (Digital Tube) Display Content of Digital Tube Quantity of Indoor Unit Capability Demand of Indoor Units df Definition of Error or Protection Standby Normal Operation Defrosting 12

P1 P2 P3 P4 P5 E0 High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection of Compressor High Temperature Protection of Outdoor Condenser Communication Error between Outdoor Units 13

E1 E2 E3 E4 E5 E6 E7 Phase-sequence Error Communication Error between Indoor Units and Outdoor Unit Outdoor Tube Temperature Sensor Error Outdoor Ambient Temperature Sensor Error Discharge Temperature Sensor Error Water Level Alarm Error Inlet Temperature Sensor Error of Condenser for Master Unit 14

3. MDV-D280(220)W/S-810 Error Indication of Outdoor Main Control Board DSP1 (Digital Tube) Display Content of Digital Tube Definition of Error or Protection Standby Capability Demand of Indoor Unit df Operation Defrosting 15

P1 P2 P3 P4 P5 E1 High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection of Compressor High Temperature Protection of Outdoor Condenser Phase-sequence Error 16

E2 Communication Error between Indoor Units and Outdoor Unit E3 Outdoor Tube Temperature Sensor Error E4 Outdoor Ambient Temperature Sensor Error E5 Discharge Temperature Sensor Error E6 Water Level Alarm Error 17

III.Error Indication of Intelligent Variable Frequency Central Air Conditioner 1. Error Indication of V3 (V4) Intelligent Variable Frequency Unit Display Content E0 Definition of Error or Protection Communication Error between Outdoor Units Remark Only Displayed on Master Unit E1 Phase-sequence Error E2 Communication Error between Indoor 18

Units and Master Unit E3 or E4 Ambient Temperature or Tube Temperature Sensor Error E8 Outdoor Unit Address Error E9 Voltage Error H0 Communication Error between DSP and 780034 H1 Communication Error between 9177 19

H2 H3 P0 and 780034 Reduction in the Number of Outdoor Units Increase in the Number of Outdoor Units Temperature Protection of Top Part of Inverter Compressor Only Displayed on Master Unit Only Displayed on Master Unit P1 High-voltage Protection 20

P2 Low-voltage Protection P3 P4 Over Current Protection of Inverter Compressor Over-high DischargeTemperature Protection P5 High Tube Temperature Protection P6 Module Protection P7 Current Protection of NO.1 Fixed 21

Compressor P8 Current Protection of NO.2 Fixed Compressor 22

2. MDV-J280W/S-810(811) Display Content Definition of Error or Protection Standby Operating Frequency of Compressor df Normal Operation Defrosting P1 High-voltage Protection 23

P2 Low-voltage Protection P3 P4 P5 P6 Current Protection of Compressor Discharge Temperature Protection of Compressor High Temperature Protection of Outdoor Condenser Module Protection E1 Phase-sequence Error 24

E2 E3 E4 Communication Error between Indoor Units and Outdoor Unit Communication Error between outdoor PCB and Inverter Module Ambient Temperature Sensor Error E5 Voltage Protection E6 Water Level Alarm Error 25

3. MDV-280W/BS Spot Inspection Error Information Spot Inspection Error Content Code 99 Terminal Blocks of Wire Controller A0 A1 A2 Loop of Outlet Temperature Sensor (TD1) Loop of Outlet Temperature Sensor (TD2) Loop of Inlet Temperature Sensor (TS) 18 Loop of Outdoor Heat Exchanger Sensor (TE) 26

AA B4 1C Loop of High Pressure Sensor (Pd) Loop of Low Pressure Sensor (Ps) Interface Substrate Loop 22 High Voltage Protection Action (Sensor Pd) E6 Phase-sequence Error of Power Supply 95 Communication Loop of Indoor and Outdoor 96 Inconsistency Detection of Indoor and Outdoor Address A6 Protection Action of Outlet Temperature (TD1) 27

bb AE A7 Ab Protection Action of Outlet Temperature (TD2) Protection Action of Discharge Temperature (TD1) during Low Frequency Protection Action of Inlet Temperature Wiring Error of Pressure Sensor (Pd, Ps) 89 The capability of indoor unit connected is transfinite. 28

Spot Inspection Error Information of Indoor Unit 0b 0c Drainage System of Suction Pump Loop of Room Temperature Sensor (TA) 11 Motor Loop 12 Loop of Indoor Substrate 93 Loop of Indoor Heat Exchanger (Tc1) 94 Loop of Indoor Heat Exchanger (Tc2) 95 Outdoor Unit Communication Loop 29

97 Communication Loop of Centralized Management 98 Address Setting of Centralized Management 9A Wiring Error of Indoor Equipment, Connection Error b5 b6 b9 External Chain Display Indoor Sensor Loop 30

Spot Inspection Error Information of Frequency Converter Plate Error Content Spot Inspection Information 14 Over-current Protection of Frequency Converter 1d 1F Compressor System Loop Current Detection Loop 21 High-voltage Switch Loop of Frequency Converter Side 17 Current Transformer Loop 31

IV. Error Indication of MDV Home Central Air Conditioner 1. MDV (H)-J140(120, 80)W-510(511) and MDV(H)-J160 (180)W(/S)-720 Free Frequency Converter Error Indication of Outdoor Main Control Board DSP1 (Digital Tube) 32

LED Display E1 E2 E3 E4 E5 H0 P1 P2 Content Phase-sequence Error Communication Error between Indoor Unit and Outdoor Unit Communication Error between PCB and inverter module Outdoor Temperature Sensor Error Voltage Protection Error Mismatching Error of Indoor Units High-voltage Protection Low-voltage Protection 33

P3 P4 P5 P6 Current Protection of Compressor Discharge Temperature Protection High-temperature Protection of Condenser Module Protection 34

2. MDV (H) -D100 (120) (/S)-510 Error Code Display of Outdoor Unit LED Display Quantity of Indoor Units Capability Demand of Indoor Unit df E1 Content Standby Normal Operation Period of Defrosting Phase-sequence Protection (only 5HP unit has) 35

E2 E3 E4 E5 H0 P1 Communication Error between Indoor Units and Outdoor Unit Outdoor Tube Temperature Error Outdoor Ambient Temperature Sensor Error Discharge Temperature Sensor Error of Compressor Mismatching Error of Indoor Units High-voltage Protection 36

P2 P3 P4 P5 Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High-temperature protection of Condenser 37

3. Error Code List of Novel M-home Series Digital Indoor Unit Display (LED) Display Definition of Error Timing Indicator LED2 Flash, Quickly RUN Indicator LED1 Flash, Quickly RUN Indicator LED1 Flash, Quickly E1 E2 E3 Communication Error between Indoor Units and Outdoor Unit Room Temperrature Sensor Error Tube Temperature Sensor Error RUN Indicator LED1 Flash, E4 Tube Temperature Sensor Error 38

Quickly Alarm Indicator LED4 Flash, Quickly RUN Indicator LED1 Flash, Slowly Defrosting Indicator LED3 Flash, Quickly Alarm Indicator LED4 Flash, Slowly EE E7 E0 Ed Water Level Alarm Error EEPROM Error Model Conflict Error Outdoor Unit Error 39

Four LED Indicators Flash, Simultaneously Ed Mismatching Error of Indoor Units and Outdoor Unit 40

4. Error Code List of Novel Home Digital Water Chiller Display E0 E1 E2 E3 E4 E5 Definition of Error Detection Error of Water Flow Pahse-sequence Error Communication Error between Indoor Units and Outdoor Unit Backwater Temperature Sensor Error Outdoor Ambient Temperature Sensor Error Outlet Water Temperature Sensor Error 41

E6 E7 E8 E9 P0 P1 P2 P3 Tube Temperature Sensor Error of Condenser Temperature Sensor Error 1of Plate Exchanger Temperature Sensor Error 2 of Plate Exchanger Digital Compressor Discharge ( Dispaly E4 on Wire Controller) Current Protection of System High-voltage Protection Low-voltage Protection Discharge Temperature Protection 42

P4 P5 P6 Pb Temperature Difference Protection of Inlet and Outlet Water High-temperature Protection of System Condenser Low-temperature Protection of Plate Exchanger Anti-Freezing Protection of System Temperature Difference Protection of Inlet and Outlet Water (3 times P8 within one hour, power on anew) Dispaly P4 on Wire Controller 43

5. MDV-J110 ~MDV-J160 AC Inverter Error Indication of Outdoor Unit LED4 LED3 LED2 LED1 LED0 Definition of Error or Protection X X X X O O O X X O Normal Status (Compressor is shut down) Normal Status (Compressor is operating) X X X O Module Error X X O X Temperature Protection of Top 44

part of Compressor X O X X O X X X X O X O O X X O Room Temperature or Inner Tube Temperature Sensor Error Outdoor Temperature Sensor Error Discharge Temperature Protection High-temperature Protection of Indoor Heat Exchanger 45

X O O X Over-voltage or Short-voltage Error O X O X Current Protection O O X X O O X O O O O X X X X X 46 Low-temperature Protection of Indoor Heat Exchanger (Freezing Prevention Protection) Communication Error between Outdoor Plate and Frequency Converter Plate Communication Error between Indoor Plate and Outdoor Plate High-temperature Protection of Outdoor Heat Exchanger

O O O O X X O O -O (On)/ -X(Off) / - (Flash) Protection for the Disconnection of Temperature Fuse Over-low or Over-high Outdoor Ambient Temperature (Cancelled) 47

Error Indication of Display Board for Indoor Unit Defrosting and Preheating Indicator Flash at 0.2Hz Timing Indicator and Defrosting Indicator Flash at 5Hz, Simultaneously Timing Indicator Flash at 5Hz Anti-cold fan Mode Conflict Room Temperature Sensor Error Automatic Indicator Flash at 5Hz Evaporator Error Sensor RUN Indicator Flash at 5 Hz Burnt out of 48

Temperature Fuse Defrosting Indicator Flash at 5Hz Communication Error of Indoor Units RUN Indicator LED1, Timing Indicator LED2, Automatic Indicator LED3 and Defrosting and Preheating Indicator LED4 Flash at 0.2 Hz, Outdoor Error Simultaneously 49

Error Indication of Indoor Unit with Variable-frequency One-Drivers-Two System LED Display Definition of Error or Protection RUN Indicator Flash, Slowly Initial Power On RUN Indicator On RUN Indicator of Principal Unit Flash, Slowly Preheating/Defrosting Indicator On Start up Single Unit Start up Double Units Period of Cold Air Prevention 50

Timing Indicator On Timing Indicator Flash Automatic Indicator Flash Timing Setting Room Temperature Sensor is Abnormal Evaporator Sensor is Abnormal Preheating/Defrosting Indicator Flash Communication Error Four Indicators Flash, Simultaneously Outdoor Unit Error 51

6. Variable- Frequency Water System Home Central Air Conditioner What displayed on the integrated controller (KJR-07B) of Midea variable frequency water chiller is only simple code, but not the real error code. The real error code is shown on the signaling transfer board of outdoor unit. Error Codes of Wire Controller LED Display Content E0 E1 E2 Parameter Error Communication Error of Outdoor Unit Outlet Water Temperature Sensor Error 52

E3 E4 E5 E6 E7 Outdoor Fixed-frequency System Heat Exchanger Sensor Error Refrigerant Inlet Sensor Error of Plate-type Heat Exchanger Side by Variable Frequency System Refrigerant Inlet Sensor Error of Plate-type Heat Exchanger Side by Fixed Frequency System Outdoor Heat Exchanger Sensor or Temperature Sensor (T4) Error of Variable Frequency System Communication Error of Wire Controller 53

P0 P1 P2 P3 P4 P5 P6 P7 Temperature Protection of Top Part of Compressor Pump Mode (Prevent pump being frozen) Hydraulic Pressure Protection of Inlet Water Module Protection Current Protection Voltage Protection Freezing Prevention Protection of Fixed-frequency System High-temperature Protection of Fixed-frequency Compressor and Condenser 54

P8 P9 PA PB Over-high Discharge Temperature Protection Freezing Prevention Protection of Variable-frequency System High-temperature Protection of Heat Exchanger (None) High-temperature Protection of Variable-frequency Compressor and Condenser As for the variable frequency water chiller being produced after 2005, signaling transfer board is cancelled in outdoor unit, while LED digital tube is added. Error Codes for Integrated Controller of Variable Frequency Water Chiller or Digital Tube of Outdoor Unit: 55

LED Display P0 P1 P2 P3 P4 P5 P6 Content Current Protection Temperature Protection of Top Part of Compressor Discharge Temperature Protection of Compressor Module Protection Voltage Protection High-temperature Protection of Frequency Converter Tube High-temperature Protection of Fixed Frequency Tube 56

Pb E0 E1 E2 Freezing Prevention Protection Detection Error of Water Flow EEPROM Error Communication Error between Integrated Controller and Outdoor Unit E3 E4 E5 E6 Communication Error of Outdoor Frequency Converter T4 or T3BP Error Temperature Sensor Error of Outlet Water T3DP Error 57

E7 E8 E9 H0 H1 H2 Temperature Sensor 1 Error of Plate Exchanger Temperature Sensor 2 Error of Plate Exchanger Error Codes of Integrated Controller EEPROM Error Error of Room Temperature T1 Communication Error between Integrated Controller and Outdoor Unit H3 Model Conflicts between Integrated Controller and Principal Unit 58

7. KFR-61T2W/BP or KFR-40 2W/BP-510T2 LED Display Timing Indicator and Defrosting Indicator Off, RUN Indicator Flash Timing Indicator and Defrosting Indicator Flash, RUN Indicator Flash, Alternate Flash Timing Indicator, RUN Indicator and Defrosting Indicator Flash Content Indoor Tube Temperature Error Communication Error between Indoor Units and Outdoor Unit Overloading Protection of Compressor (Temperature of top part 59

exceeds 120 ) Defrosting Indicator, RUN Indicator and Timing Indicator Flash Timing Indicator On, RUN Indicator and Defrosting Indicator Flash Defrosting Indicator On, RUN Indicator and Timing Indicator Flash Timing Indicator Off, Defrosting Indicator On, RUN Indicator Flash Module Protection High/Low Voltage Alarm Outdoor Temperature Sensor Error Defrosting 60

at 1.5Hz Timing Indicator On, Defrosting Indicator Unknown, RUN Indicator Plasma Dedusting Mark Flash at 1.5Hz 61

Direct-Current Variable-Frequency One-to-Any Air Conditioner with One Group of Tube Display Definition of Error or Protection Content E0 E2 EEPROM Error Communication Error between Indoor Chips and Outdoor Chip E3 E4 Communication Error between Outdoor Chip and DSP Ambient Temperature Sensor Error 62

E5 Voltage Protection of Compressor P0 P1 P2 P3 P4 P5 P6 Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High-temperature Protection of Outdoor Condenser Module Protection 63

DC Inverter "One-to-Two" or "One-to-Three" Air Conditioner with Several Groups of Tube Display Content E0 E1 E2 E3 E4 Definition of Error or Protection EEPROM Parameter Error Temperature Sensor Error of 1# Indoor Evaporator Outlet Temperature Sensor Error of 2# Indoor Evaporator Outlet Temperature Sensor Error of 3# Indoor Evaporator Outlet Ambient Temperature Sensor Error 64

E5 E6 E7 P0 P1 P2 P3 P4 Voltage Protection of Compressor Pre-reserved Communication Error of Outdoor Frequency Converter Temperature Protection of Top Part High-voltage Protection (Pre-reserved) Low-voltage Protection (Pre-reserved) Current Protection of Compressor Module Protection 65

P5 P6 P7 Ambient Low-Temperature Protection High-temperature Protection of Outdoor Condenser Pre-reserved 66

DC Variable-Frequency "One-to-Four" Air Conditioner with Several Groups of Tube Display Content E0 E1 E2 E3 Definition of Error or Protection EEPROM Parameter Error Temperature Sensor Error of 1# Indoor Evaporator Outlet Temperature Sensor Error of 2# Indoor Evaporator Outlet Temperature Sensor Error of 3# Indoor Evaporator Outlet 67

E4 E5 E6 Ambient Temperature and Tube Temperature Sensor Error Voltage Protection Temperature Sensor Error of 4# Indoor Evaporator Outlet E7 Communication Error between DSP and 780034 P0 P1 P2 Temperature Protection for Top of Inverter Compressor High-voltage Protection Low-voltage Protection 68

P3 P4 P5 P6 P7 P8 Current Protection of Frequency Converter Module Protection Ambient Low-Temperature Protection High-temperature Protection of Outdoor Condenser Pre-reserved Pre-reserved 69

V. Error Indication of Unitary Central Air Conditioner 1. Error Code List for Ordinary One-to-One Error Code Indication of Indoor Unit LED Flash All indicators flash at 5Hz Timing indicator flashes at 5Hz Definition of Error or Protection Neutral line has not been connected to the PRO port on indoor electric control panel, or optical coupler on circuit wafer has been damaged. Room Temperature Sensor Error 70

Run indicator flashes at 5Hz Temperature Sensor Error of Evaporator Defrosting indicator flashes Temperature Sensor Error of Condenser at 5Hz Warning indicator flashes at 5Hz Detection Error of Water Level Switch 71

LED Error Indication of Outdoor Main Control Board 1) LED Error List for 3HP Detection Panel of Outdoor Phase-sequence Symptom LED1 LED2 LED3 Definition of Error or Protection Off Off On Normal On Off On Phase-sequence is reversed. Off On On Over Current On On On Phase-loss On On On Pressure Protection 72

2) LED Error List for 5HP Outdoor Main Control Panel Symptom LED1 LED2 LED3 Definition of Error or Protection Flash Off Off Phase-loss, or Phase-sequence is reversed. Flash Flash Off High/Low Pressure Protection Off Off Flash Over Current Off Flash Flash T3 Open Circuit or Short circuit Error Off Flash Off T4 Open Circuit or Short circuit Error Flash Flash Flash High Temperature Protection of Condenser 73

2. Error Code List for Novel Four-way Cassette Symptom Definition of Operating Timing Defrosting Full-water Error Error or On On On On Code Protection Room X X X E2 Temperature Sensor Error X X X E3 Temperature Sensor Error of 74

Evaporator Temperature X X X E4 Sensor Error of Condenser Temperature X X E5 Sensor Error of Water Pump E6 75 Outdoor Error Unit

X X E7 EEPROM Error X X X E8 Full-water Error (X indicates that the indicator is Off, indicates that the indicator flashes at 5Hz.) (X indicates that the indicator is Off, 5Hz.) indicates that the indicator flashes at 76

3. Error Code List for 10HP Cabinet Unit Display Content Error Icon E1 On Error Icon E2 On Error Icon P1 On Error Icon P2 On Definition of Error or Protection T1 Open Circuit or Short Circuit Error T2 Open Circuit or Short Circuit Error T2 Low Temperature Protection under Cooling Model T2 High Temperature Protection under Heating Model 77

4. Error Indication of 20HP Medium Static-pressure (Outdoor Unit) Symptom LED1 LED2 LED3 Definition of Error or Protection Flash Off Off Communication Error Flash Flash Off Low-pressure Protection Off Off Flash Open Circuit or Short Circuit Error of Room Temperature Off Flash Flash High Temperature Protection of Condenser 78

Flash Flash Flash Phase-lacking or Phase-sequence is reversed. Off Flash Off T3 Open Circuit or Short Circuit Error Flash Off Flash None 79

53/71 DC Inverter "One-to One Air Conditioner Display Content E0 E2 E3 E4 Definition of Error or Protection EEPROM Error Communication Error between Indoor Chip and Outdoor Chip Communication Error between Outdoor Chip and DSP Ambient Temperature Sensor Error 80

E5 P0 P1 P2 P3 P4 P5 P6 Voltage Protection of Compressor Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High Temperature Protection for Outdoor Condenser Module Protection 81

90/105/140 Single-Phase Direct-Current Variable-Frequency "One-to One Air Conditioner Display Content E0 E2 E3 Definition of Error or Protection EEPROM Error Communication Error between Indoor Chip and Outdoor Chip Communication Error between Outdoor Chip and DSP 82

E4 E5 E6 P0 P1 P2 P3 P4 Ambient Temperature Sensor Error Voltage Protection of Compressor PFC Module Protection Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection 83

P5 P6 High Temperature Protection for Outdoor Condenser Module Protection 84

105/140/160 Three-Phase DC Inverter "One-to One Air Conditioner Display Content E0 E2 E3 E4 E5 Definition of Error or Protection EEPROM Error Communication Error between Indoor Chip and Outdoor Chip Communication Error between Outdoor Chip and DSP Ambient Temperature Sensor Error Voltage Protection of Compressor 85

P0 P1 P2 P3 P4 P5 P6 Temperature Protection of Top Part High-voltage Protection Low-voltage Protection Current Protection of Compressor Discharge Temperature Protection High Temperature Protection for Outdoor Condenser Module Protection 86

87

Indication List for LED Display No. LED1 LED2 LED3 Description 1 2 Heating Mode (after the Startup of Compressor) Cooling Mode (after the Startup of Compressor) 3 Defrosting 4 Heating Mode, Indoor T2 High-temperature Protection, Shut down Fan as Required. 88

5 Standby 6 Ambient Temperature Sensor Error 7 Outdoor Tube Temperature Sensor Error 8 Phase-sequence Protection 9 T3 High Temperature Protection 10 Low-voltage Protection 1 11 High-voltage Protection, Discharge Protection 1 89

12 Current Protection 1 13 Current Protection 2 14 Current Protection 3 15 Current Protection 4 16 Discharge Protection 2, 3 17 Discharge Protection 4 : On, : Off, : Flash Quickly, : Flash Slowly 90

DIP switch setting: J2: Double Fan / Single Fan (Connected / Unconnected) J1: Three-phase / Single-phase (Connected / Unconnected) ON 1: ON with self-check 2: ON with fast-check 1 2 91

VI. Error Indication of Digital Scroll Air Cooling Module 1. Error Protection Display for 60KW Modular Air-Cooling Heat-Pump Unit E0 E1 E2 E3 E4 E5 Detection Error of Water Flow (Third Time) Phase-sequence Error of Power Supply Communication Error Temperature Sensor Error of Master Outlet Water (Principal Unit is in Effect) Temperature Sensor Error of Outlet Water for Plate Exchanger Tube Temperature Sensor Error of Condenser A 92

E6 E7 E8 E9 Eb EF EA Tube Temperature Sensor Error of Condenser B Ambient Temperature Sensor Error Discharge Temperature Sensor Error of Digital Compressor for System A Detection Error of Water Flow (First and Second Time) Error of Plate Exchanger Low-temperature Freezing-prevention Protection Sensor T61 Error of Plate Exchanger Low-temperature Freezing-prevention Protection Sensor T62 Communication Protection of Subordinate Module (Display of Wire Controller) 93

P0 P1 P2 P3 P4 P5 P6 P7 High-voltage or Discharge Temperature Protection of System A Low-voltage Protection of System A High-voltage or Discharge Temperature Protection of System B Low-voltage Protection of System B Current Protection of System A Current Protection of System B High-temperature Protection of Condenser of System A High-temperature Protection of Condenser of System B 94

P8 Pb PE Discharge Temperature Protection of Digital Compressor for System A System Freezing-prevention Protection Low-temperature Protection of Plate Exchanger 95

2. Error Protection Display for 200KW Large Modular Air-Cooling Heat-Pump Unit E0 Detection Error of Water Flow (Third Time) E1 Phase-sequence Error of Power Supply E2 Communication Error E3 Temperature Sensor Error of Master Outlet Water E4 Temperature Sensor Error of System Inlet Water E5 Tube Temperature Sensor Error of Condenser E7 Ambient Temperature Sensor Error E9 Detection Error of Water Flow (First Time) EA Communication Protection of Subordinate Module Eb Error of Sensor T6 P0 High-voltage or Discharge Temperature Protection 96

P1 P4 P6 Pb Low-voltage Protection Current Protection of Compressor High-temperature Protection of Condenser of System System Freezing-prevention Protection 3. List of Display Code for Modular Wire Controller Error Protection E0 Detection Error of Water Flow (Third Time) E1 Phase-sequence Error of Power Supply E2 Communication Error E3 Temperature Sensor Error of Master Outlet Water (Principal Unit is in Effect) E4 Temperature Sensor Error of Outlet Water for Plate Exchanger 97

E5 E6 E7 E8 E9 EA Eb EC ED EE Tube Temperature Sensor Error of Condenser A Tube Temperature Sensor Error of Condenser B Ambient Temperature Sensor Error Discharge Temperature Sensor Error of Digital Compressor for System A Detection Error of Water Flow (First and Second Time) Reduction in the Number of Subordinate Unit Detected by Principal Unit Freezing-prevention Temperature Sensor Error of Plate Exchanger A Online module unit could not be found on Wire Controller. Communication Data Error for Wire Controller and Module Communication Error between Wire Controller and Computer 98

EF P0 P1 P2 P3 P4 P5 P6 P7 P8 Pb Freezing-prevention Temperature Sensor Error of Plate Exchanger High-voltage or Exhaust Temperature Protection of System A Low-voltage Protection of System A High-voltage or Exhaust Temperature Protection of System B Low-voltage Protection of System B Current Protection of System A Current Protection of System B High-temperature Protection of Condenser of System A High-temperature Protection of Condenser of System B Discharge Temperature Protection of Digital Compressor for System A System Freezing-prevention Protection 99

PC Protection for Digital Discharge Temperature above 125 PE Low-temperature Protection of Plate Exchanger VII. Error Indication of Water Cooled Cabinet Unit Error Display Content Error Icon E0 On Error Icon E1 On Error Icon E2 and No. 1 On Definition of Error or Protection T1 Open Circuit or Short Circuit Error Phase-sequence Error T2 Open Circuit or Short Circuit Error of System 1 (T2A) 100

Error Icon E2 and No. 2 On Error Icon E2 and No. 3 On Error Icon E5 and No. 1 On Error Icon E5 and No. 2 On Error Icon E5 and No. 3 T2 Open Circuit or Short Circuit Error of System 2 (T2B) T2 Open Circuit or Short Circuit Error of System 3 (T2C) Three errors in System 1 within 30 minutes Three errors in System 2 within 30 minutes Three errors in System 3 within 30 minutes 101

On Error Icon P0 and No. 1 On Error Icon P0 and No. 2 On Error Icon P0 and No. 3 On Error Icon P1 and No. 1 On T2 Low-temperature Protection of System 1 (T2A) T2 Low-temperature Protection of System 2 (T2B) T2 Low-temperature Protection of System 3 (T2C) Current Protection of Compressor 1 102

Error Icon P2 and No. 1 On Error Icon P3 and No. 2 On Error Icon P4 and No. 2 Current Protection of Compressor 2 Current Protection of Compressor 3 Current Protection of Compressor 4 On Error Icon P5 and No. 3 Current Protection of Compressor 5 On Error Icon P6 and No. 3 Current Protection of Compressor 6 103

On Error Icon P7 On Error Icon P9 and No. 1 On Error Icon P9 and No. 2 On Error Icon P9 and No. 3 On Protection of Indoor Blower Motor Discharge Temperature and High/Low Voltage Protection Discharget Temperature and High/Low Voltage Protection Discharge Temperature and High/Low Voltage Protection 104

VIII. Error Indication of Screw Unit Error Indication of Screw Unit with 100 (200) USRT LED1 LED2 LED3 Display Error Content On Off Off N/A Standby On On Off Operation Flash Off Off EP Voltage Protection and Phase-sequence Error Flash Flash On E1 Inlet Sensor Protection of Chilled Water 105

Flash Off On E2 Outlet Sensor Protection of Chilled Water On Flash On E3 Inlet Sensor Protection of Cooling Water Off Flash On E4 Outlet Sensor Protection of Cooling Water Flash On On E5 Protection of Discharge Temperature Sensor Flash Flash Off E6 Low-voltage Protection Flash Flash Flash E7 Communication Error 106

Flash Off Flash P0 Switch Protection of Chilled Water Flow On Flash Off P1 Switch Protection of Cooling Water Flow On Off Flash P2 High-voltage Protection Off Flash Flash P3 Internal Compressor Protection Off On Flash P4 Overload of Compressor Flash On Off P5 Protection of Oil Pressure Difference 107

Off Flash Off P6 Protection of Oil Level On On Flash P7 High Discharge Temperature Protection 108

Error Indication of Screw Unit with 400 USRT LED1 LED2 LED3 Display Error Content On Off Off N/A Standby On On Off Operation Flash Off Off EP Flash Flash On E1 Voltage Protection and Phase-sequence Error Inlet Sensor Protection of Chilled Water 109

Flash Off On E2 On Flash On E3 Off Flash On E4 Flash On On E5 Outlet Sensor Protection of Chilled Water Inlet Sensor Protection of Cooling Water Outlet Sensor Protection of Cooling Water Protection of Discharge Temperature Sensor 110

Flash Flash Off E6 Low-voltage Protection Flash Flash Flash E7 Communication Error Flash Off Flash P0 On Flash Off P1 On Off Flash P2 Off Flash Flash P3 Switch Protection of Chilled Water Flow Switch Protection of Cooling Water Flow High-voltage Protection Internal Compressor Protection 111

Off On Flash P4 Flash On Off P5 Overload of Compressor Protection of Oil Pressure Difference Off Flash Off P6 Protection of Oil Level On On Flash P7 Protection of Over-high Discharge Temperature 112

IX. Error Indication of Network Air Conditioner Error Code Error Content Protection Code Content of Protection Error and Protection of Air Conditioner EF Other Error PF Other Protection EE Error of Water Level Detection PE Reserved ED Protection of Outdoor Unit Error PD Reserved EC Fresh Error (Reserved) PC Reserved 113

Protection of Variable EB Frequency Module PB Reserved (Reserved) EA Over Current of Compressor (Four Times) PA Reserved Communication Error of E9 Main Board and Display P9 Reserved Board E8 Wind-speed detection is out of control (Reserved) P8 Over Current of Compressor 114

E7 E6 EEPROM Error (Reserved) Zero-crossing Detection Error (Reserved) P7 P6 Over/under Voltage Protection of Power Discharge Low-voltage Protection Sensor T3 or T4 Error or E5 Error of Discharge Temperature Sensor for Digital Compressor P5 Discharge High-voltage Protection (Reserved) 115

E4 Sensor T2B Error P4 E3 Sensor T2A Error P3 E2 Sensor T1 Error P2 Temperature Protection of Vent Tube Temperature Protection of Compressor High Temperature Protection of Condenser Communication Error E1 between Outdoor and Indoor Unit (Variable P1 Protection of Preventing Cold Air or Defrosting Frequency or Digital Unit) 116

(Reserved) E0 Phase-sequence Error or Phase-loss (Reserved) P0 Temperature Protection of Evaporator Network Error Communication Error Communication Error 03# between Centralized Monitor and Computer 01# between Centralized Monitor and Network (Gateway) Interface Module 117

Communication Error Communication Error 02# between Centralized Monitor and Function 00# between Network Interface Module and Module Main Control Board 118

Gongdong Midea Commercial Air-Conditioning Equipment Co., Ltd. Address: Midea Industrial City, Shunde, Foshan, Guangdong Postal Code: 528311 Tel: 0757-26338515 Service Hotline: 4008899315 or 0757-26338585 Fax: 0757-26338511 or 0757-26333541 Website: www.mdvchina.com 119

www.mdvchina.com 120