DM en. Service manual MIV V5 HEAT PUMP DC INVERTER R410A MVUH252B-VA3 MVUH280B-VA3 MVUH335B-VA3 MVUH400B-VA3 MVUH450B-VA3 MVUH500B-VA3

Size: px
Start display at page:

Download "DM13-01.01.01en. Service manual MIV V5 HEAT PUMP DC INVERTER R410A MVUH252B-VA3 MVUH280B-VA3 MVUH335B-VA3 MVUH400B-VA3 MVUH450B-VA3 MVUH500B-VA3"

Transcription

1 DM en Service manual MIV V5 HEAT PUMP DC INVERTER R410A MVUH252B-VA3 MVUH280B-VA3 MVUH335B-VA3 MVUH400B-VA3 MVUH450B-VA3 MVUH500B-VA3

2 Contents Part 1 General Information... 1 Part 2 Selection Procedure Part 3 Specification & Performance Part 4 Installation Part 5 Troubleshooting Part 6 Control System

3 DM en MIV V5 Heat Pump DC Inverter R410A Part 1 General Information 1. Midea Product Development History DC Inverter MIV V5 Introduction Model Line up Outdoor Unit Combinations Capacity Range of Indoor Units External Appearance and Model Names of Indoor Units Nomenclature General Information 1

4 MIV V5 Heat Pump DC Inverter R410A 1. Midea Product Development History In 1999, Midea cooperated with Toshiba, produced the No.1 AC Inverter VRF MDV. DM en In 2001, Midea produced the No1. MDV in Air-conditioning industry. In 2002, Midea developed the No.1 AC Inverter VRF MDV, and the No1. D series MDV in China. In 2003, Midea completed the 2nd D series and 2nd V series MDV. In 2005, Midea cooperated with Hitachi, produced the No.1 module s AC Inverter V3 and digital scroll D3. In 2008, Midea launched out the MDV4, which is the R410A DC Inverter VRF and Modular design also. In 2011, the new MIV V4+ was on sale, which owns the entirely DC Inverter technology and new low noise, technology (full systems line up: Heat Pump, mini, Heat Recovery, Individual). In 2013, Midea launched the DC Inverter MIV V5 Series outdoor unit. 2. DC Inverter MIV V5 Introduction 2.1. Free combination, the World s Largest Capacity 72HP MIV V5 Series achieves world s largest capacity of 72HP by combining maximum 4 outdoor units with 6 different capacities (8, 10, 12, 14, 16 and 18 HP), and 64 indoor units can be connected max. 2.2 High efficiency and Energy saving: MIV V5 Series achieves the industry's top class energy efficiency of cooling and heating by utilizing all DC inverter compressors, DC fan motors and high performance heat exchanger. All DC inverter compressors contribute to higher IPLV greatly. The highest IPLV is up to High efficiency DC inverter compressor, saving power 25% 8HP&10HP units adopt one DC inverter compressor only. 12, 14, 16, 18HP adopt two DC inverter compressors. With all DC inverter compressors, MIV V5 Series offers a wide operation range from 20Hz to 200Hz. The A/C load ratio of building is 30%-75%, the area use ratio is 55%, most of the A/C runs in the mid load, so the mid load operation ratio control the whole year AC running charge. Centralizing winding Distributing winding 2 General Information

5 DM en MIV V5 Heat Pump DC Inverter R410A All DC inverter compressors make the capacity output better distributed, and always work at 30-70Hz which is the most efficient range. It makes the efficiency more than 30% higher than the normal. Smooth Sine Wave DC Inverter Motor uses 180 sine wave vector drive technology to ensure transducer to output smooth curve, which shows motor rotor speed to run smooth. While, common frequency motor outputs sawtooth wave not precisely to show motor speed, so its efficiency is low. Common Sawtooth Wave Sine Wave DC Inverter High efficiency DC Fan motor, saving power 50% According to the running load and pressure, it controls the speed of DC fan to achieve the min. energy consumption, to reach the best effect. All DC fan motors saves much power consumption. Used across entire range of models (from 8 to 72 HP) Efficiency improved by up to 45% especially at low speed Pressure sensor DC Fan motor General Information 3

6 MIV V5 Heat Pump DC Inverter R410A DM en Motor rotor speed waves among ±5r, and can rapidly match DC Inverter Compressor to output, and enhance efficiency in part load Newly designed sub-cooling heat exchanger 12 C sub-cooling degree makes the cooling capacity increased efficiently. Thus, the total piping length becomes longer, reach up to 1000m. Meanwhile, the innovative designed high efficiency heat exchanger also simplified the pipeline of outdoor unit and realized compact design and low weight. By adoption of Pressure Sensor, EXV, all DC fan motors and all DC compressors, MIV V5 has an obvious improvement on efficiency than previous products. 2.3 More flexible design External static pressure enhanced up to 60Pa and air volume increases Applied high static pressure propeller fan and the optimum fan guard for high external static pressure, to respond to a range of various installation environments. Midea now offers up to 60Pa* (6.12 mm H 2 O) external static pressure for customized applications (60 Pa is available for the 12HP model; 40Pa is available for other models). A standard 0-20Pa function is equipped by default More options of indoor units and high capacity connection Lineup of heat pump types is 8 to 72 HP. Indoor units consist of 14 types with 115 models, capacity ranges from 1.8kW to 56kW. A maximum 130% indoor unit s connective ratio is allowed for all outdoor unit capacities. This wide selection of models makes it possible to build a system that suits the customer s requirements. 2.4 High Comfort Optional outdoor units Silent Mode control Night silent operation will be activated X (6, 8) hours after the peak temperature during daytime, and it will get back to normal operation after Y (8, 10, 12) hours. Super silent operation mode can reduce sound level further, minimum 45dB (A). This function can be activated by setting at site. Temperature (load) curve shown in the graph is just an example. 4 General Information

7 DM en MIV V5 Heat Pump DC Inverter R410A More options for outdoor units Night silent mode, silence mode, super silence mode Optimized fan design, strengthen heat exchanger By CFD software, the newly designed fan and grille enhance fan performance greatly and decrease the running noise as well. New designed fan outlet grille New designed fan impeller Conventional fan impeller 2.5 High Reliability Double Cycle Duty operation Cycle duty operation: both between the modules in one system and the compressors in one module, which extend the system lifespan significantly. The outdoor unit cycle duty operation happens once when running max. 125 minutes. General Information 5

8 MIV V5 Heat Pump DC Inverter R410A DM en Double Backup operation Outdoor unit adopts double backup function. If one module failed, other modules can be backup instead of the failed one, or if one of the compressors in one module failed, the other one can backup for continuing operation. Compressor backup in one module Compressor backup among modules Start backup operation Running state Stand by state Start backup operation Start backup operation Fault or stop state Dynamic gas balance technology Dynamic vector balance technology, no need to install gas balance pipe: High-precision pressure sensor monitors the system pressure on time and transfers the data to master unit Master unit sends the pressure data to every unit and make sure each outdoor unit in balance situation High efficiency oil balance technology Oil balance pipes set among the modules, and individual oil balance vector control ensures oil distribution among the modules to compressor smoothly and running reliably. When one compressor s oil is overfull, oil balance pipes and outlet pipes both send the oil to the system, and then the system distributes the oil to other compressors in average. Oil balance diagram: 6 General Information

9 DM en MIV V5 Heat Pump DC Inverter R410A Discharge pipe Refrigerant flow direction Oil separator Oil even pipe II Suction pipe Discharge pipe Oil even pipe Oil basin Enter condenser Oil balance pipe between modules Oil even pipe I Suction pipe From evaporator It adopts high efficient centrifugal type oil separator, which separates the oil from the discharged refrigerant with the efficiency up to 99% and makes all the lubricant discharged from the compressor can be returned in time. New designed low pressure liquid receiver with high efficiency of oil return effect. Oil balance ensures sufficient refrigerant lubricant supply. Elaborately designed oil return hole, which ensures reliable oil return for every compressor Oil return technology Centrifugal oil separator can be up to over 99% separating efficiency, which in time and efficiently send the oil to compressors to ensure compressor oil volume. System auto back oil design can complete through PC core to send oil back instruction by system running time and state. The accumulator is large volume design, which can save more refrigerant to avoid liquid strike. Multi back oil holes can ensure the oil back of the compressor smoothly Intelligent soft start technology, rapidly enhance refrigerant cycle volume Compressor soft start complete low frequency and low current start by DC Inverter compressor, and to reduce strike to electric network. When start DC Inverter Compressor, the system runs in large volume and offers more heating capacity. Compressor soft start Compressor soft start complete low frequency and low current start by DC Inverter compressor, and to induce strike to electric network. Lubrication system soft start 2.6 Convenient for installation and service Auto addressing General Information 7

10 MIV V5 Heat Pump DC Inverter R410A DM en Addressing outdoor units and indoor units are automatically done just by pressing the button of the controller. The outdoor unit can automatically distribute the address to indoor units without any manual settings. Wireless and wired controller can enquiry and modify every indoor units address. Up to 64 indoor units can be connected to one system and identified automatically Super Wiring It is possible to enable the shared use of the wiring between indoor & outdoor units, as well the centralized control. Hence make it easy for the user to retrofit the existing system with a centralized control, by simply connecting it to the outdoor units. PQE & XYE, just only one group of communication wire of PQE, achieved both of communication for indoor & outdoor unit and network. Reversible communication, central controller can connect from indoor side or outdoor side at will Convenient for maintenance Convenient electronic control check window. Can directly observe the operation status from the LED display, and directly press the FORCE COOLING / CHECK button. The high/low pressure valves adopt the Stop Valves, which have screwed thread nipple joint, can be connected to the meter connector directly in air tight test. And also make it more efficient and easy for installation. Self diagnosis function and four-digit Digital display, help service engineer to find out the fault fast and easily. 8 General Information

11 DM en 3. Model Line up Outdoor units (Combination Unit): 8, 10 HP 12,14,16 HP MIV V5 Heat Pump DC Inverter R410A 18 HP 18, 20, 22, 24, 26, 28, 30, 32 HP 34, 36, 38, 40, 42, 44, 46, 48 HP 50, 52, 54, 56, 58, 60, 62, 64 HP 66, 68, 70, 72 HP *The recommended combinations larger than 64HP adopt 5 basic models since 18HP model can be customized. General Information 9

12 MIV V5 Heat Pump DC Inverter R410A 4. Outdoor Unit Combinations Without 18HP model: DM en Capacity Recommend combination (HP) Model 8(HP) 10(HP) 12(HP) 14(HP) 16(HP) Max. indoor units nos. 8 MVUH252B-VA MVUH280B-VA MVUH335B-VA MVUH400B-VA MVUH450B-VA MVUH500B-VA MVUH560B-VA MVUH615B-VA MVUH680B-VA MVUH730B-VA MVUH780B-VA MVUH850B-VA MVUH900B-VA MVUH950B-VA MVUH1000B-VA MVUH1060B-VA MVUH1130B-VA MVUH1180B-VA MVUH1230B-VA MVUH1280B-VA MVUH1350B-VA MVUH1400B-VA MVUH1450B-VA MVUH1500B-VA MVUH1560B-VA MVUH1630B-VA MVUH1680B-VA MVUH1730B-VA MVUH1780B-VA General Information

13 DM en With 18HP model: MIV V5 Heat Pump DC Inverter R410A Recommend combination Max. Capacity (HP) Model 8(HP) 10(HP) 12(HP) 14(HP) 16(HP) 18(HP) indoor units nos. 8 MVUH252B-VA MVUH280B-VA MVUH335B-VA MVUH400B-VA MVUH450B-VA MVUH500B-VA MVUH560B-VA MVUH615B-VA MVUH680B-VA MVUH730B-VA MVUH780B-VA MVUH850B-VA MVUH900B-VA MVUH950B-VA MVUH1000B-VA MVUH1060B-VA MVUH1130B-VA MVUH1180B-VA MVUH1230B-VA MVUH1280B-VA MVUH1350B-VA MVUH1400B-VA MVUH1450B-VA MVUH1500B-VA MVUH1560B-VA MVUH1630B-VA MVUH1680B-VA MVUH1730B-VA MVUH1780B-VA MVUH1850B-VA3) MVUH1900B-VA MVUH1950B-VA MVUH2000B-VA3 64 General Information 11

14 MIV V5 Heat Pump DC Inverter R410A 5. Capacity Range of Indoor Units DM en Capacity (kw) HP INDEX One-way Cassette Two- way Cassette Compact Four- way Cassette Four-way Cassette Type Low Static Pressure Duct Middle Static Pressure Duct High Static Pressure Duct Ceiling & Floor Wall-mounted Type Console Exposed Floor-standing 12 General Information

15 DM en MIV V5 Heat Pump DC Inverter R410A 6. External Appearance and Model Names of Indoor Units External Appearance Model Name External Appearance Model Name One-way cassette MVN28A-VA1 MVN36A-VA1 MVN45A-VA1 MVN56A-VA1 MVN71A-VA1 Two-way cassette MVT22A-VA1 MVT28A-VA1 MVT36A-VA1 MVT45A-VA1 MVT56A-VA1 MVT71A-VA1 MVC28A-VA1 MVC36A-VA1 Compact four-way cassette MVS22A-VA1 MVS28A-VA1 MVS36A-VA1 MVS45A-VA1 MVS56A-VA1 Four-way Cassette Type MVC45A-VA1 MVC56A-VA1 MVC71A-VA1 MVC80A-VA1 MVC90A-VA1 MVC100A-VA1 MVC112A-VA1 MVC140A-VA1 MVM22A-VA1 MVM28A-VA1 Low Static Pressure Duct MVL18A-VA1 MVL22A-VA1 MVL28A-VA1 MVL36A-VA1 MVL45A-VA1 MVL56A-VA1 Middle Static Pressure Duct MVM36A-VA1 MVM45A-VA1 MVM56A-VA1 MVM71A-VA1 MVM80A-VA1 MVM90A-VA1 MVM112A-VA1 MVM140A-VA1 MVH71A-VA1 71~112 Model 140~160 Model MVH80A-VA1 MVH90A-VA1 MVH112A-VA1 MVH140A-VA1 MVH160A-VA1 High Static Pressure Duct MVH200A-VA1 MVH250A-VA1 MVH280A-VA1 High Static Pressure Duct MVX36A-VA1 MVX45A-VA1 High Static Pressure Duct MVH400A-VA1 MVH450A-VA1 MVH560A-VA1 Ceiling & Floor MVX56A-VA1 MVX71A-VA1 MVX80A-VA1 MVX90A-VA1 MVX112A-VA1 MVX140A-VA1 General Information 13

16 MIV V5 Heat Pump DC Inverter R410A DM en Wall-mounted S Type MVW22A-VA1 MVW28A-VA1 MVW36A-VA1 MVW45A-VA1 MVW56A-VA1 MVW71A-VA1 Exposed floor standing Type MVE22A-VA1 MVE28A-VA1 MVE36A-VA1 MVE45A-VA1 MVE56A-VA1 MVE71A-VA1 MVE80A-VA1 MVD22A-VA1 MVD28A-VA1 MVD36A-VA1 MVD45A-VA1 Console The specifications, designs, and information in this book are subject to change without notice for product improvement. 14 General Information

17 DM en 7. Nomenclature 7.1 Outdoor unit: MVUH252B - VA3 MIV V5 Heat Pump DC Inverter R410A Power 1-1 phase, 50 Hz 3-3 phases, 50 Hz Refrigerant A - R410A B - R22 Inverter (in)v(erter) - inverter S(tandard) on/off Model, Modification A Z, AA ZZ Capacity index kw*10 The main feature of the system air cooled: C(ooling) cooling only H(eat pump) cooling and heating R(ecovery) heat recovery, 3-pipe water cooled: Q(ooling) cooling only W(ater) cooling and heating (reco)v(ery) heat recovery, 3-pipe Identifier of the outdoor unit (o)u(tdoor) Manufacturer s brand and class of the system M(idea) V(RF) General Information 15

18 MIV V5 Heat Pump DC Inverter R410A 7.2 Indoor unit: MVC28A VA1 DM en Design features (may be absent) For example: G(rey), W (hite) - color Power 1-1 phase, 50 Hz 3-3 phases, 50 Hz Refrigerant A - R410A B - R22 Inverter (in)v(erter) - inverter S(tandard) - on/off Model, Modification A Z, AA ZZ Capacity index kw*10 Type of the indoor unit W(all) - wall (ca)s(sette) cassette 600x600 C(assette) - cassette (o)n(e way) 1-way cassette T(wo way) 2-way cassette L(ow) low static pressure duct M(edium) medium static pressure duct H(igh) - high static pressure duct (fle)x ceiling & floor F(loor standing) floor standing (колонный) E(floor-standing exposed) floor standing exposed D console Manufacturer s brand and class of the system M(idea) V(RF) 16 General Information

19 DM en MIV V4+ Heat Pump DC Inverter R410A Part 2 Selection Procedure 1 Introduction Unit selection (Based on cooling load) Selection Procedure 17

20 MIV V4+ Heat Pump DC Inverter R410A 1 Introduction 1.1 Model Selection Procedure DM en Select the model and calculate the capacity for each refrigerant system according to the procedure shown below. Calculation of the indoor air-conditioning load Calculate the maximum air-conditioning load for each room or zone. Selection of an air conditioning system Select the ideal air conditioning system for air conditioning of each room or zone Design of the control system Design a suitable control system for the selected air conditioning system Preliminary selection of indoor and outdoor units Make preliminary selections that are within the allowable range for the system Check of the tubing length and elevation difference Check that the length of refrigerant tubing and the elevation difference are within the allowable ranges Calculation of the corrected outdoor unit capacity Capacity correction coefficient for model, outdoor temperature conditions, tubing length and elevation difference Calculation of the actual capacity for each indoor unit Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit capacity and the total corrected capacity of all indoor units in the same system Recheck of the actual capacity for each indoor unit If the capacity is inadequate, reexamine the unit combinations. 1.2 Indoor Unit Selection Enter INDOOR UNIT CAPACITY TABLES at given indoor and outdoor temperature. Select the unit that the capacity is the nearest to and greater than given load. Note: Individual indoor unit capacity is subject to change by the combination. Actual capacity has to be calculated according to the combination by using outdoor unit capacity table Calculation of Actual Capacity of Indoor Unit Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference and other factors, select the correct model after taking into account the various correction values. When selecting the model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual final capacity of each indoor unit. Find the indoor unit capacity correction coefficient for the following items Capacity correction for the indoor unit temperature conditions From the graph of capacity characteristics, use the indoor temperature to find the capacity correction coefficient. Capacity distribution ratio based on the indoor unit tubing length and elevation difference. First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit to find the correction coefficient from the graph of capacity change characteristics Capacity distribution ratio for each indoor unit = Correction coefficient for that indoor unit / Correction coefficient for the outdoor unit 1.3 Outdoor Unit Selection Allowable combinations are indicated in INDOOR UNIT COMBINATION TOTAL CAPACITY INDEX TABLE. In general, outdoor unit can be selected as follows though the location of the unit, zoning and usage of the 18 Selection Procedure

21 DM en MIV V4+ Heat Pump DC Inverter R410A rooms may be considered. The indoor and outdoor unit combination is determined that the sum of indoor unit capacity index is nearest to and smaller than the capacity index at 100% combination ratio of each outdoor unit. Up to 8~16 indoor units can be connected to one outdoor unit. It is recommended to choose a larger outdoor unit if the installation space is large enough. If the combination ratio is greater than 100%, the indoor unit selection shall be reviewed by using actual capacity of each indoor unit. INDOOR UNIT COMBINATION TOTAL CAPACITY INDEX TABLE Outdoor Unit Indoor Unit Combination Ratio (kw) 130% 120% 110% 100% 90% 80% 70% 60% 50% 8HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP HP INDOOR UNIT CAPACITY INDEX Unit Size Model 18 Model 22 Model 28 Model 36 Model 45 Model 56 Model 71 Model 80 Model 90 Model 112 Model 140 Capacity Index (kw) Unit Size Model 160 Model 200 Model 250 Model 280 Capacity Index (kw) Selection Procedure 19

22 MIV V4+ Heat Pump DC Inverter R410A 1.3 Actual Performance Date DM en Use OUTDOOR UNIT CAPACITY TABLES. Determine correct table according to the outdoor unit model and combination ratio. Enter the table at given indoor and outdoor temperature and find the outdoor unit capacity and power input. The individual indoor unit capacity (power input) can by calculated as follows. IUC=OUC INX/TNX Where, IUC: Each indoor unit capacity OUC: Outdoors unit capacity INX: Each indoor unit capacity index TNX: Total capacity index Then, correct the indoor unit capacity according to the piping length. If the corrected capacity is smaller than the load, the size of indoor unit has to be increased and repeat the same selection procedure. 1.4 Variation in capacity in accordance with the length of refrigerant pipe Cooling capacity modification Modification coefficient of the length and high difference of refrigerant pipe: H (m) % L: Refrigerant pipe equivalent length H: Height difference between outdoor and indoor L (m) 20 Selection Procedure

23 DM en Heating capacity modification Modification coefficient of the length and high difference of refrigerant pipe: H (m) % L(m) L: Refrigerant pipe equivalent length H: Height difference between outdoor and indoor 96 MIV V4+ Heat Pump DC Inverter R410A Selection Procedure 21

24 MIV V4+ Heat Pump DC Inverter R410A 2 Unit selection (Based on cooling load) 2.1 Given condition DM en Design condition (Cooling: Indoor 20 C (WB), Outdoor 35 C (DB)) Cooling load Location Room A Room B Room C Room D Room E Room F Load (kw) Power supply unit: Outdoor 380~415V-3Ph-50Hz, Indoor 220~240V-1Ph-50Hz Pipe length: 50m Height difference: 30m 2.2 Indoor unit selection Select the suitable capacity for condition of Indoor 20 C (WB), Outdoor 35 C (DB) using indoor unit capacity table. The selected result is as follows. (Assuming the indoor unit type is duct) Location Room A Room B Room C Room D Room E Room F Load (kw) Unit size Capacity (kw) Outdoor unit selection Assume the indoor unit and outdoor unit combination as follows Calculate the total nominal capacity of indoor units in the combination according to the above table: = 25.8kW Select outdoor unit: MVUH280A-VA3 which has nominal cooling capacity: 28kW. Calculate the proportion between 1 and 2: 258/280= 92% Result: Because the proportion is within 50~130%, it is a «Right» selection Real function data with indoor unit combination For the 92% combination, calculate the cooling capacity of outdoor unit (MVUH280A-VA3) KW 90% (Indoor temperature: WB 20 C, Outdoor temperature: DB 35 C) 29.61KW 100% (Indoor temperature: WB 20 C, Outdoor temperature: DB 35 C) Then calculated the outdoor capacity in 92% combination index: Therefore: {( )/ 10} 2= 27.24; Outdoor unit (MVUH280A-VA3) cooling temperature: DB 35 C Capacity modification coefficient with pipe length (50m) and height difference (30m): Each indoor unit cooling capacity MVM22A-VA1: / = 2.22 (kw) MVM28A-VA1: / = 2.83 (kw) MVM36A-VA1: / = 3.64 (kw) MVM45A-VA1: / = 4.55 (kw) MVM56A-VA1: / = 5.66 (kw) MVM71A-VA1: / = 7.18 (kw) Location Room A Room B Room C Room D Room E Room F Load (kw) Unit size Capacity (kw) Selection Procedure

25 DM en MIV V4+ Heat Pump DC Inverter R410A 2.4 Conclusion Generally, we think this result is acceptable, so we can think we have accomplished the calculation. But if you think this result is not acceptable, you can repeat the above process. Remark: In this sample, we don t consider the other capacity modification index and assume them are 1.0. For more details about the effect factor such as outside ambient/inside ambient DB/WD, please refer to the performance table of indoor and outdoor units. Selection Procedure 23

26 MIV V5 Heat Pump DC Inverter R410A DM en Part 3 Specification & Performance 1. Specifications Dimensions Piping Diagrams Electric Characteristics Wiring Diagrams and Field Wiring Operation Limits Capacity Tables Sound Levels Outdoor Fan performance Accessories Functional parts and safety devices Specification & performance

27 DM en MIV V5 Heat Pump DC Inverter R410A 1. Specifications Model MVUH252B-VA3 MVUH280B-VA3 MVUH335B-VA3 Power supply V-Ph-Hz 380~415V 3Ph ~ 50Hz 380~415V 3Ph ~ 50Hz 380~415V 3Ph ~ 50Hz Capacity W Cooling (*1) Input W EER W/W Capacity W Heating (*2) Input W COP W/W Max. input consumption W Max. current A Model E655DHD-65D2YG E655DHD-65D2YG E655DHD-65D2YG+ E405DHD-36D2YG Quantities Type DC Inverter DC Inverter DC Inverter Brand Hitachi Hitachi Hitachi DC Inverter compressor Capacity W 31590(90Hz) 31590(90Hz) 31590(90Hz)+11800(60Hz) Input W 10340(90Hz) 10340(90Hz) 10340(90Hz)+3665(60Hz) Power supply V-Ph-Hz V~3Ph, 50Hz V~3Ph, 50Hz V~3Ph, 50Hz Operating frequency Hz 40~200 40~200 40~200 Crankcase W *2 Refrigerant oil ml FVC68D / 500 FVC68D / 500 FVC68D / 500+ FVC68D / 500 Model WZDK750-38G-4 WZDK750-38G-4 WZDK750-38G-4 Type DC Inverter DC Inverter DC Inverter Brand Panasonic&Nidec Panasonic&Nidec Panasonic&Nidec Quantities Outdoor fan motor Insulation class E E E Safe class IPX4 IPX4 IPX4 Input W 534(RATED) 534(RATED) 272 2(RATED) Output W Rated current A Speed r/min 850(RATED) 850(RATED) 930(RATED) Material Plastic Plastic Plastic Type Axial Axial Axial Outdoor fan Fan Quantities Dimension(Dia. H) mm Vane Quantities Number of rows Tube pitch(a)x row pitch(b) mm Fin spacing mm Outdoor coil Fin type (code) Hydrophilic aluminum Hydrophilic aluminum Hydrophilic aluminum Tube outside dia. mm Ф7.94 Ф7.94 Ф7.94 Tube type Inner-grooved Inner-grooved Inner-grooved Coil length x height mm Number of circuits Outdoor air flow m 3 /h External static pressure Pa 0~20 (default) 20~40 (optional) 0~20 (default) 20~40(optional) 0~20 (default) 20~60 (optional) Outdoor sound level(*3) db(a) Specification & performance 25

28 MIV V5 Heat Pump DC Inverter R410A DM en Dimension(W H D) mm Outdoor unit Packing (W H D) mm Net/Gross weight Kg 212/ / /300 Charged refrigerant type and volume kg R410A 10kg R410A 10kg R410A 12kg Throttle type EXV EXV EXV Excessive operating pressure MPa 4.4/ / /2.6 Liquid side/ Gas side(*4) mm Ф12.7/Ф25.4 Ф12.7/Ф25.4 Ф15.9/Ф31.8 Oil balance pipe mm Ф6.4 Ф6.4 Ф6.4 Total pipe length m Refrigerant piping Connection wiring The farthest pipe length(actual) The farthest pipe length (equivalent) The farthest equivalent pipe length from the first distributor (*5) Max. Vertical pipe length (When outdoor units is above) Max. Vertical pipe length (When outdoor units is below) Max. drop between indoor units Power wiring mm (L 20m); (L 50m) m m m 40(90) 40(90) 40(90) m m m core shielded wiring; Signal wiring mm wiring dia (L 20m); (L 50m) 3 core shielded wiring; wiring dia (L 20m); (L 50m) 3 core shielded wiring; wiring dia Ambient temp. range - Cooling Ambient temp. range - Heating Notes: 1. The cooling conditions: indoor temp.: 27 DB(80.6 ), 19 WB(60 ), outdoor temp.: 35 DB(95 ), equivalent pipe length: 5m, drop length: 0m. 2. The heating conditions: indoor temp.: 20 DB(68 ), 15 WB(44.6 ) outdoor temp.: 7 DB(42.8 ) equivalent pipe length: 5m drop length: 0m. 3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. It s the dimension of connecting pipes between outdoor and first branch joint when the Max. Equivalent length of tubing is less than 90m. 5. The farthest equivalent pipe length should be equal to or shorter than 40m, but it can be up to 90m if meet the required conditions following part 4 installation sections. 6. The above data may be changed without notice for future improvement on quality and performance. 26 Specification & performance

29 DM en MIV V5 Heat Pump DC Inverter R410A Model MVUH400B-VA3 MVUH450B-VA3 MVUH500B-VA3 Power supply V-Ph-Hz 380~415V 3Ph ~ 50Hz 380~415V 3Ph ~ 50Hz 380~415V 3Ph ~ 50Hz Capacity W Cooling Input W EER W/W Capacity W Heating Input W COP W/W Max. input consumption W Max. current A Model E655DHD-65D2YG+E405D HD-36D2YG E655DHD-65D2YG+E405D HD-36D2YG E655DHD-65D2YG Quantities Type DC Inverter DC Inverter DC Inverter DC Inverter compressor Brand Hitachi Hitachi Hitachi Capacity W 31590(90Hz) (60Hz) 31590(90Hz) (60Hz) Input W 10340(90Hz)+3665(60Hz) 10340(90Hz)+3665(60Hz) 31590(90Hz) (90Hz) 10340(90Hz) (90Hz) Power supply V-Ph-Hz V~3Ph, 50Hz V~3Ph, 50Hz V~3Ph, 50Hz Operating frequency Crankcase Refrigerant oil Hz 40~200/48~230 40~200/48~230 40~200 W ml FVC68D / 500+ FVC68D / 500 FVC68D / 500+ FVC68D / 500 FVC68D / 500+ FVC68D / 500 Model WZDK750-38G-4 WZDK750-38G-4 WZDK560-38G(A) Type DC MOTOR DC MOTOR DC MOTOR Brand Panasonic&Nidec Panasonic&Nidec Panasonic Quantities Outdoor fan motor Insulation class E E E Safe class IPX4 IPX4 IPX4 Input W 450 2(RATED) 450 2(RATED) Output W Rated current A Speed r/min material Plastic Plastic Plastic Type Axial Axial Axial Outdoor fan Fan Quantities Dimension(Dia. H) mm Vane Quantities Number of rows Tube pitch(a)x row pitch(b) mm Fin spacing mm Outdoor coil Fin type (code) Hydrophilic aluminum Hydrophilic aluminum Hydrophilic aluminum Tube outside dia. mm Ф7.94 Ф7.94 Ф7.94 Tube type Inner-grooved Inner-grooved Inner-grooved Coil length height mm Number of circuits Outdoor air flow m 3 /h External static pressure Pa 0~20 (default) 20~40 (optional) 0~20 (default) 20~40 (optional) 0~20 (default) 20~40 (optional) Outdoor sound level(*4) db(a) Outdoor unit Dimension(W H D) mm Specification & performance 27

30 MIV V5 Heat Pump DC Inverter R410A DM en Packing (W H D) mm Net/Gross weight Kg 288/ / /330 Charged refrigerant type kg R410A 15kg R410A 15kg R410A 16kg Throttle type EXV EXV EXV Excessive operating pressure MPa 4.4/ / /2.6 Refrigerant piping Connection wiring Liquid side/ Gas side mm Ф15.9/Ф31.8 Ф15.9/Ф31.8 Ф19.1/Ф31.8 Oil balance pipe mm Ф6.4 Ф6.4 Ф6.4 Total pipe length m The farthest pipe length(actual) The farthest pipe length (equivalent) The farthest equivalent pipe length from the 1st distributor tube(*5) Max. Vertical pipe length (When outdoor units is above) Max. Vertical pipe length (When outdoor units is below) Max. drop between indoor units m m m 40(90) 40(90) 40(90) m m m Power wiring mm (L 20m); (L 50m) 2 3 core shielded wiring; Signal wiring mm wiring dia (L 20m); (L 50m) 3 core shielded wiring; wiring dia (L 20m); (L 50m) 3 core shielded wiring; wiring dia Ambient temp. range - Cooling Ambient temp. range - Heating Notes: 1. The cooling conditions: indoor temp.: 27 DB(80.6 ), 19 WB(60 ), outdoor temp.: 35 DB(95 ), equivalent pipe length: 5m, drop length: 0m. 2. The heating conditions: indoor temp.: 20 DB(68 ), 15 WB(44.6 ), outdoor temp.: 7 DB(42.8 ), equivalent pipe length: 5m, drop length: 0m. 3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. It s the dimension of connecting pipes between outdoor and first branch joint when the Max. Equivalent length of tubing is less than 90m. 5. The farthest equivalent pipe length should be equal to or shorter than 40m, but it can be up to 90m if meet the required conditions following part 4 installation sections. 6. The above data may be changed without notice for future improvement on quality and performance. 28 Specification & performance

31 DM en 2. Dimensions 2.1 Units Dimension 8HP/10HP Dimensions (Combinable): MIV V5 Heat Pump DC Inverter R410A Specification & performance 29

32 MIV V5 Heat Pump DC Inverter R410A DM en Liquid side (The connected pipe diameter Φ12.7) Gauge point Detect the pressure/ Refrigerant replenishment Oil balancer For parallel connect the modular units Gas side (The connected pipe diameter Φ25.4) Position of Foot screw bolt (Unit: mm) B A Enlarged view for 8HP/10HP C D long u-shape hole For 8,10HP For 12,14,16,18HP A B C D Specification & performance

33 DM en 12HP/14HP/16HP/18HP (Combinable)Dimensions: MIV V5 Heat Pump DC Inverter R410A Specification & performance 31

34 MIV V5 Heat Pump DC Inverter R410A DM en Liquid side (The connected pipe diameter Φ15.9) Gauge point Detect the pressure/ Refrigerant replenishment Oil balancer For parallel connect the modular units Gas side (The connected pipe diameter Φ31.8) Enlarged view for 12HP/14/16HP 239 Gauge point (Cooling only type without) Detect the pressure/ Refrigerant replenishment Gas side (The connected pipe diameter Φ31.8) Oil balance pipe For parallel connect the modular units Liquid side (The connected pipe diameter Φ19.1) Enlarged view for 18HP 32 Specification & performance

35 DM en 2.2 Valve explanation MIV V5 Heat Pump DC Inverter R410A HP, 14HP, 16HP Connect the liquid pipe (accessory, field installation) Connect the gas pipe Low pressure float valve Oil balance pipe (only for combination) Gauge point(cooling only type without) HP Connect the liquid pipe (accessory, field installation) Connect the gas pipe Oil balance pipe (only for combination) Gauge point(cooling only type without) Stop valve Specification & performance 33

36 MIV V5 Heat Pump DC Inverter R410A 3. Piping Diagrams DC Fan SV6 DM en Heat Exchanger EXV A SV5 Stop Valve (High Pressure) ST 1 Stop Valve (Low Pressure) High PressureHPS Switch Compressor INVERTER High Pressure Sensor SENP Oil Separator SV 4 unloading valve Low Pressure Low Receiver Pressure Switch LPS SV 2 Oil Balance 8~10HP DC Fan SV6 EXV A Stop Valve (High Pressure) Heat Exchanger ST 1 SV5 Stop Valve (Low Pressure) Compressor INVERTER High Pressure HPS Switch High Pressure Sensor Compressor INVERTER SENP Oil Separator SV4 unloading valve Low Pressure Switch LPS Low Pressure Receiver SV2 Oil Balance 12HP DC Fan SV6 EXV A Stop Valve (High Pressure) Heat Exchanger ST 1 EXV B SV5 Stop Valve (Low Pressure) Compressor INVERTER High Pressure HPS Switch High Pressure Sensor Compressor INVERTER SENP Oil Separator SV4 unloading valve Low Pressure Switch LPS Low Pressure Receiver SV2 Oil Balance 14~16HP 34 Specification & performance

37 U Inverter U SV5 U Inverter U SV4 U Fix U DM en MIV V5 Heat Pump DC Inverter R410A SV6 SV1 ST1 EXVA EXVB SV5 Ф2.5x1.5x1500 SV4 SV2 Ф3.2x1.9x1000 Ф2.2x1.1x2500 Ф2.0 18HP Remark: 1.8~10 HP models only have one inverter compressor. 2.12~18HP have two DC inverter compressors. 3.14~18HP models have two EXV parts at the high-pressure pipe side, different with 12HP model. Key Components: Oil Separator: used to separate oil from high pressure & temperature gas refrigerant, which is pumped out from compressor. The separation efficiency is up to 99%, it makes the oil return back to each compressor very soon. Low pressure receiver: It is used to store the liquid refrigerant and oil, it can protect the compressor from liquid hammer. Four-way valve control (ST1): Closed in cooling mode and open in heating mode EXV (electromagnetic expansion valve) control: 1) Max. Open degree is 480 pulses. 2) Generally, when system is plug in the EXV closes 700pulse first, then opens to 350 pulse and stand by. When then the unit started, it opens to the right pulse. 3) When the running outdoor unit receives OFF signal, the EXV of slave unit will stop, while master unit is running and slave unit stopped at the same time. If all outdoor units stopped, the EXV will close first, and then open to the pulse of stand-by. 4) 8HP~12HP models have one EXV; 14~18HP models have double EXVs. SV2: spray a little liquid refrigerant to cooling compressor. Open when any compressor discharge temperature is higher than 100. SV4: oil returning valve. Opens after the DC inverter compressor has been run for 5 minutes and then closes 15 minutes later. (For the system has only one outdoor unit). Every 20 minutes, SV4 of each outdoor unit opens for 3 minutes. (For the system has more than one outdoor unit) SV5: for defrosting. In defrosting mode, the opening of SV5 can cut the refrigerant flowing circle, so the defrosting process will takes less time. In cooling mode, it is always off. SV6: for by-pass. Closed when the unit stands by and system is running at heating mode. Open when the discharge temperature is over-high in cooling mode, and close when the unit is standby or system is in heating mode. High pressure sensor: to supervisor the discharge pressure of the compressor and to control the DC fan speed. For example: Cooling mode launch sequence (The unit has accomplish commissioning): 60s later 60s later 40s later Plug in and unit start sv4, SV5 openu closed U closed U 50s later 20s later Inverter compressor start at 40 Hz U compressor start at 30hz U scroll 40s later compressor start (This step is omitted for 8HP&10HP models)u compressor running frequency will adjust according the capacity requirement. Specification & performance 35

38 MIV V5 Heat Pump DC Inverter R410A 4. Electric Characteristics Model DM en Outdoor Unit Power Supply Compressor OFM Hz Voltage Min. Max. MCA TOCA MFA MSC RLA KW FLA MVUH252B-VA ~ MVUH280B-VA ~ MVUH335B-VA ~ MVUH400B-VA ~ MVUH450B-VA ~ MVUH500B-VA ~ Remark: MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps. (A) MSC: Max. Starting Amps. (A) RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor. FLA: Full Load Amps. (A) KW: Rated Motor Output (KW) Notes: 1. RLA is based on the following conditions, Indoor temp. 27 DB/19 WB,Outdoor temp. 35 DB 2. TOCA means the total value of each OC set. 3. MSC means the Max. current during the starting of compressor. 4. Voltage range. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. 5. Maximum allowable voltage variation between phases is 2%. 6. Selection wire size based on the larger value of MCA or TOCA. 7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker). 36 Specification & performance

39 DM en 5. Wiring Diagrams and Field Wiring 5.1 Wiring Diagram For 8~10HP MIV V5 Heat Pump DC Inverter R410A Specification & performance 37

40 MIV V5 Heat Pump DC Inverter R410A Wiring Diagram For 12~18HP DM en 38 Specification & performance

41 DM en 5.2 Field Wiring Terminal of Outdoor unit MIV V5 Heat Pump DC Inverter R410A A B C N To V 3 N~ 5 0/60Hz Wiring between Indoor and Outdoor unit Power( V 3N ~ 50Hz/60Hz) L1L2 L3N Outdoor units centralized monitoring Network accounting Indoor units centralized controller Indoor units communication Outdoor units communication A B C N Branch Box Outdoor unit(master unit) Outdoor unit(slave unit) Outdoor unit(slave unit) A B C N H1 H2 E P Q E A B C N H1 H2 E P Q E A B C N H1 H2 E P Q E Signal wire between indoor/outdoor unith Indoor unit Indoor unit Indoor unit Signal wire between outdoor units L N P Q E A B C D E L N P Q E A B C D E L N P Q E A B C D E Branch Box Signal wire between indoor units Branch Box Branch Box Signal wire between indoor unit and wire controller A B C D E A B C D E A B C D E Wired controller Wired controller Wired controller Note: 1. The signal connecting line between outdoor units, indoor and outdoor units and indoor units has polarity. When connecting, be careful to prevent error connection. 2. Signal line shall adopt three-core shielded wire with an area above 0.75 mm Do not bind signal line and copper pipe together with belting. 4. Make sure that the shield metal layer should be grounded well indoor control box in order to prevent interference. 5. It s forbidden to connect 200V or above high-volt live wire to the communication terminal. Specification & performance 39

42 MIV V5 Heat Pump DC Inverter R410A 5.3 Outdoor unit power wiring Separate Power Supply (without power facility) Model Item Power supply Minimum Power wire diameter (mm 2 ) Wiring of mental and synthetic resin DM en manual switch(a) Creepage breaker Size Ground wire Capacity Fuse MVUH252B-VA mm 2 (<20 m) 4 16 mm 2 (<50 m) 1 10 mm MVUH280B-VA3 MVUH335B-VA3 MVUH400B-VA3 380V~415V, 3N, 50Hz 4 10 mm 2 (<20 m) 4 16 mm 2 (<50 m) 4 10 mm 2 (<20 m) 4 16 mm 2 (<50 m) 4 16 mm 2 (<20 m) 4 25 mm 2 (<50 m) 1 10 mm mm mm ma 0.1sec or less MVUH450B-VA mm 2 (<20 m) 1 16 mm MVUH500B-VA mm 2 (<50 m) 1 16 mm With power facilities: Out door u nit Leakage po w er supply pr o tec t or V3 N ~ 50/60 Hz Leaka ge pr otec tor M anual s wit ch M a nual swit ch Ou td o o r u nit GND Ou td o o r u nit GND ( a ) Ou td o o r u nit GND B ra n c h b o x Ou td o o r u nit GND Power facilities 1 (with leakage protector) Outdoor unit GND (a) Leakage protector Manual switch (b) Outdoor unit Outdoor unit GND GND Branch box Outdoor unit GND Power facilities 2 (with leakage protector) Outdoor unit Outdoor unit GND GND 40 Specification & performance

43 DM en Note: MIV V5 Heat Pump DC Inverter R410A 1. Select power cord for these five models separately according to relevant standard. 2. The wiring diameter and the length in the table indicate the condition that the voltage dropping range is within 2%. If the length exceeds the above figure, please select the wire diameter according to relevant standard. 3. Select the wire diameter Power wiring refer to the main wire (a) connecting to branch box and the wiring (b) between branch box and power facilities. Please select the wire diameter according to the following requirement. 4. Diameter of main wire (a) Depends on the total horsepower of outdoor unit and following table. E.g. In system:(8hp 1unit+8Hp 1unit+10Hp 1unit) Total Hp=26Hp (Table.6-4) size of wire=35mm2(within 50m) 5. Wiring(b):between branch box and power equipment. Depends on the number of combined outdoor unit. If fewer than 5, the diameter is the same as that of main wire (a); if more than 6, there will be 2 electric control boxes, and the diameter of wiring depends on the total horsepower of outdoor units connecting to each electric control box and following table. Specification & performance 41

44 MIV V5 Heat Pump DC Inverter R410A DM en Reference table of the cable size for each capacity Min. Diameter of wiring (mm 2 ) Total capacity (HP) from weather proof isolator to ODU Below 20 m 20 to 50 m Remark: The above selection is just for reference, it should be considered that the cable layout, space between cable and surroundings, etc. for an actual electrical project 42 Specification & performance

45 DM en 6. Operation Limits Outdoor temperature ( DB) Cooling Range for continuous operation Range for intermittent operation Outdoor temperature ( WB) Heating Range for intermittent operation MIV V5 Heat Pump DC Inverter R410A Range for continuous operation Indoor temperature ( WB) Indoor temperature ( DB) Outdoor temp. Indoor temp. Room relative humidity Cooling mode -5 C ~ 48 C 17 C ~ 32 C below 80% Heating mode -20 C ~ 27 C 15 C ~ 30 C Notes: 1. If the unit is running outside the above condition, protective device will start, and even then the units take place abnormality running. 2. These figures base on the operation conditions between indoor units and outdoor units: Equivalent pipe length is 5m, and height difference is 0m. Precaution: The indoor relative humidity should be lower than 80%. If the air conditioner works in an environment with a relative humidity higher than mentioned above, the surface of the air conditioner may condensate. In this case, it is recommended to set the air speed of the indoor unit to high. Specification & performance 43

46 MIV V5 Heat Pump DC Inverter R410A 7. Capacity Tables 8HP cooling mode Combination (%) (Capacity index) 130% 120% 110% Outdoor temperatur e ( C DB) Indoor temperature( C DB/WD) DM en DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18 DB:27,WB:19 DB:28.2,WB:20 DB:30.7,WB:22 DB:32,WB:24 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kw kw kw kw kw kw kw kw kw kw kw kw kw kw Specification & performance

FULL DC INVERTER SYSTEMS

FULL DC INVERTER SYSTEMS FULL DC INVERTER SYSTEMS INDIDUAL AND MODULAR DESIGN & FLEXIBLE COMBINATION commercial air conditioners SDV4 2011/2012 AIR CONDITIONING 1 WELCOME TO THE WORLD of SINCLAIR AIR CONDITIONERS Company operation

More information

Contents. Part 1 General Information... 1. Part 2 Outdoor Units... 9. Part 3 Installation... 50. Part 4 Troubleshooting 73

Contents. Part 1 General Information... 1. Part 2 Outdoor Units... 9. Part 3 Installation... 50. Part 4 Troubleshooting 73 MCAC-VTSM-2013-03 R410a Full DC Inverter Mini VRF Contents Part 1 General Information... 1 Part 2 Outdoor Units... 9 Part 3 Installation... 50 Part 4 Troubleshooting 73 Part 5 Control System... 100 Manufacture

More information

Appendix - Controllers 179

Appendix - Controllers 179 Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy

LG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy LG Air conditioning Company Multi V Water Ⅱ Air Conditioning Academy 1.1 What is Multi V Water II? High Performance Prospect rights Water pipe Refrigerant pipe Indoor unit Beautiful Exterior Convenience

More information

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE

Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE Hitachi Air Conditioning Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE Contents Page 04 Product Range 08-09 RAC Summit Wall Mounted 10 RAC Shirokuma Wall mounted 11 RAC S Series - Wall

More information

Super Modular Multi Design Manual HFC R-410A. Indoor unit. Outdoor unit

Super Modular Multi Design Manual HFC R-410A. Indoor unit. Outdoor unit Ref.-No. SMMS02-AE-10-05 Indoor unit 4-way ceiling cassette MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H 2-way ceiling cassette MMU-AP0071WH,

More information

PANASONIC TROUBLE SHOOTING GUIDE

PANASONIC TROUBLE SHOOTING GUIDE A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

GREE, MAKING BETTER AIR CONDITIONERS

GREE, MAKING BETTER AIR CONDITIONERS GREE ELECTRIC APPLIANCES,INC.OF ZHUHAI Add:Jinji RD.Qianshan Zhuhai 519070,Guangdong,China Tel: (+86-756)8614883 Fax: (+86-756)8627140 Email: gree@gree.com.cn http://www.gree.com.cn Heat Pump Water Heater

More information

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4. AquaFREE System Technical Catalogue Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.5/6)H(1/3) Specifications in this manual are subject to change without notice

More information

Midea Commercial Air Conditioner Malfunction Handbook

Midea Commercial Air Conditioner Malfunction Handbook Midea Commercial Air Conditioner Malfunction Handbook May 1, 2008 Customer Service Philosophy of Midea Air Conditioner Service Target: 100% Customer Satisfaction Service Standard: 100% Earnestness Service

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/

1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ 1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ ISO 9001 ISO 14001 Certified number : 01 100 89394 Certified number : 01 104 9245101 Fujitsu General (Thailand) Co.,

More information

Technical service manual

Technical service manual GD Midea Refrigeration Equipment Co.,Ltd ODMI-A-1202 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual R410A Multi DC inverter 220~240V-1Ph-50Hz Outdoor units Models M2OC-14HRDN1 M2OC-14HRDN1-Q

More information

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant

More information

Gree Solar Hybrid Hi Wall Inverter Air Conditioner

Gree Solar Hybrid Hi Wall Inverter Air Conditioner Gree Solar Hybrid Hi Wall Inverter Air Conditioner Utilize the natural power of the sun to heat or cool your home. Find out more at www.greeonline.com Why Choose a Solar Hybrid Inverter? The new Gree Solar

More information

NEW 3-PIPE ECOi MF2 SERIES

NEW 3-PIPE ECOi MF2 SERIES NEW 3-PIPE ECOi MF2 SERIES SIMULTANEOUS HEATING AND COOLING VRF SYSTEM Internet Control Ready INTERNET CONTROL NEW Energy Environmentally friendly refrigerant R410A Down to -20 ºC in heating mode OUTDOOR

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

Inverter Air Conditioning for Light Commercial Use

Inverter Air Conditioning for Light Commercial Use Inverter Air Conditioning for Light Commercial Use 02 Cost Saving Comfort An efficient use of time 03 SDISuper Digital Inverter Very efficient energy consumption Keeps down operating costs Heater operation

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

AquaFREE system. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE

AquaFREE system. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE AquaFREE system Technical Catalogue Outdoor units: RAS(3~5)HVRNE RAS(4/5)HRNE Indoor units: RWM(3~5)FSN1E RWM(3~5)FSN1E(4.5/6)H(1/3) RWM(3~5)FSN1ES1 RWM(3~5)FSN1E(4.5/6)SH(1/3) Specifications in this

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Hot Water. Heat pump water heaters. Residential and Commercial R410a

Hot Water. Heat pump water heaters. Residential and Commercial R410a Hot Water Heat pump water heaters Residential and Commercial R410a Heat pump technology Heat Pump Water Heating is a new idea using existing technology and is viewed as the latest generation of water heating

More information

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient

More information

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER

More information

HVAC SYSTEM (HEATER, VENTILATOR, AND A/C)

HVAC SYSTEM (HEATER, VENTILATOR, AND A/C) HVAC SYSTEM (HEATER, VENTILATOR, AND A/C) HEATER SYSTEM 1. Heater System A: GENERAL A semi-center type integrated air conditioning unit is used, where a high performance heater core and an evaporator core

More information

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................

More information

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC & hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS

More information

Earth can hardly wait for a change in the atmosphere. Nor can we. By making air conditioning supremely energy-efficient, quiet, easy to install, and

Earth can hardly wait for a change in the atmosphere. Nor can we. By making air conditioning supremely energy-efficient, quiet, easy to install, and 1 Earth can hardly wait for a change in the atmosphere. Nor can we. By making air conditioning supremely energy-efficient, quiet, easy to install, and cost-effective, Toshiba aims at the heart of growing

More information

Technical service manual 2009

Technical service manual 2009 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 CONTENT 1. Product features

More information

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH

More information

How To Make A High Efficiency Thermostat

How To Make A High Efficiency Thermostat Zoning with Variable Speed Mini-Split Systems Fujitsu Service Training Welcome - Thank you for attending Did you know? In 1940 only 42% of homes in the US had central heating In 1970 20% of homes had central

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH

More information

Development and testing of a multi-type air conditioner without using AC inverters

Development and testing of a multi-type air conditioner without using AC inverters Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department

More information

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0 Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view

More information

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED

More information

2 NOMENCLATURE 3 FUNCTION 4 PRODUCT DATA

2 NOMENCLATURE 3 FUNCTION 4 PRODUCT DATA CONTENTS PRODUCT... 2 1 MODELS LIST... 2 1.1 Outdoor Unit... 2 1.2 Indoor Unit... 3 2 NOMENCLATURE... 4 3 FUNCTION... 4 4 PRODUCT DATA... 5 4.1 Product Data at Rated Condition... 6 4.2 Operation Range...

More information

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with

More information

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

U-MATCH Air Conditioners. Service Manual. T1/R410a/50Hz

U-MATCH Air Conditioners. Service Manual. T1/R410a/50Hz U-MATCH Air Conditioners Service Manual T1/R410a/50Hz GREE ELECTRIC APPLIANCES INC. OF ZHUHAI 1 CONTENTS PRODUCT...2 1 MODELS LIST...2 1.1 Outdoor Unit...2 1.2 Indoor Unit...3 2 NOMENCLATURE...4 3 FUNCTION...5

More information

Versati Air to Water Heat Pump

Versati Air to Water Heat Pump Versati Air to Water Heat Pump VERSATI DC Inverter Multifunctional Air To Water Heat Pump Nowadays, people are increasingly focusing on heating costs as well as environmental issues. Traditional heating

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by

More information

Air Conditioning for Small and Medium-size Buildings

Air Conditioning for Small and Medium-size Buildings Air Conditioning for Small and Medium-size Buildings Defining a HIGHER standard The all-new MiNi-SMMS air conditioner lineup lets you cool or warm as many as 12 *1 rooms with a single system. Outdoor units

More information

SWIMMING POOL HEAT PUMP Owners Manual

SWIMMING POOL HEAT PUMP Owners Manual SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

Air Conditioning For Large Buildings

Air Conditioning For Large Buildings Air Conditioning For Large Buildings Index Introduction 3 Industry leading energy savings 6 New smart & sensitive VRF control 10 Industry leading layout flexibility 14 Other features 18 Outdoor units Outdoor

More information

D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43

D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43 D SERIES MODULAR AIR-COOLED SCROLL CHILLER TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43 CONTENTS 1.MODELS LIST... 3 2.NOMENCLATURE... 3 3.FEATURES... 3 4.PRODUCT

More information

ECO-AIR AIR CONDITIONING www.northamericanhvac.com

ECO-AIR AIR CONDITIONING www.northamericanhvac.com INDEX ACCESSORIES INSTALLATION... 3-7 LINE SETS... 3-7 GEOTHERMAL... 3-8 WIRING CABLE... 3-8 CIRCULATOR PUMPS (PRO-TECH MODEL)... 3-9 DC INVERTER SINGLE ZONE HEAT PUMP... 3-6 DC INVERTER TECHNOLOGY...

More information

HEATER, AIR CONDITIONING AND VENTILATION

HEATER, AIR CONDITIONING AND VENTILATION 55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2 SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW - AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402 TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE

More information

Introduction To VRF: System Overview, Applications, & Savings Opportunities

Introduction To VRF: System Overview, Applications, & Savings Opportunities Introduction To VRF: System Overview, Applications, & Savings Opportunities System Overview What is VRF? Zoning System Two-Pipe / Three Pipe System Packaged DDC Control Operates as a Heat Pump Simultaneous

More information

Heat Pump Product Brochure 2015/2016. Premier Series Hi-Wall Split Systems. Everyday Comfort

Heat Pump Product Brochure 2015/2016. Premier Series Hi-Wall Split Systems. Everyday Comfort Heat Pump Product Brochure 2015/2016 Premier Series Hi-Wall Split Systems Everyday Comfort Everyday Innovation We design with you in mind. You ll find that Haier Heat Pump units are quiet, efficient and

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

Multi Air Conditioner SVC MANUAL(Exploded View)

Multi Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Multi Air Conditioner SVC MANUAL(Exploded View) MDEL : A5UW306FA3 CAUTIN Before Servicing the unit, read the safety precautions in Standard SVC manual. nly for

More information

Engineering Specifications

Engineering Specifications Engineering Specifications NORDIC W-85-H-B-*S-PD Water to Water Heat Pump Single-Stage R134a Nominal 7.5 Ton With Double Wall Condenser for Domestic Hot Water Production Maritime Geothermal Ltd. P.O. Box

More information

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to: OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

Technical Service Manual. Version One

Technical Service Manual. Version One [Gree Central Air Conditioner] Technical Service Manual Ducted type unit 2.3KW-16KW Version One GREE ELECTRIC APPLIANCES.INC.OF ZHUHAI - 1 - FG Series wind pipe blowing air-conditioning unit Section One:

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008 Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

REGULINE 600VA / 1000VA REGULATOR USER MANUAL REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions

More information

Models Utopia ES Utopia IVX Utopia DC Inverter Utopia Fixed Speed Utopia Centrifugal

Models Utopia ES Utopia IVX Utopia DC Inverter Utopia Fixed Speed Utopia Centrifugal Utopia Split Systems Models Utopia ES (7.1-14 kw) Utopia IVX (7.1-30 kw) Utopia DC Inverter (5-14 kw) Utopia Fixed Speed (6.3-12.5 kw) Utopia Centrifugal (12.5-25 kw) Contents Company Profile 4 Utopia

More information

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual Instruction Manual OPC-LM1-IL Option Card for Encoder of Line Driver Output CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual

More information

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning

More information

CoolTeg Plus Chilled Water (CW) version: AC-TCW

CoolTeg Plus Chilled Water (CW) version: AC-TCW version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420

More information

DIGITAL SCROLL CENTRAL AIR CONDITIONER (OUTDOOR UNIT)

DIGITAL SCROLL CENTRAL AIR CONDITIONER (OUTDOOR UNIT) E-II-YDS-100-140-0907 ENGLISH INSTALLATION MANUAL DIGITAL SCROLL CENTRAL AIR CONDITIONER (OUTDOOR UNIT) YDS System, R410A, R407C & R22 / YDMH-C (B/A) 100&140 For correct installation, read this manual

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97

More information