D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43
|
|
|
- Letitia Horn
- 10 years ago
- Views:
Transcription
1 D SERIES MODULAR AIR-COOLED SCROLL CHILLER TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43
2 CONTENTS 1.MODELS LIST NOMENCLATURE FEATURES PRODUCT DATA PERFORMANCE CORRECTION FREEZE PROTECTION INSTALLATION ELECTRICAL DATA FIELD WIRING DIAGRAM MICROPROCESSOR CONTROLLER WIRED CONTROLLER ACCESSORIES APPLICATION DATA
3 D Seried Modular Air-cooled Scroll Chiller Technical Sales Guide 1 MODELS LIST Nominal Capacity Model Power Supply RT Refrigerant Model Name Ph, V, Hz 17.0 BLSQWRF65M/NaD-M 3, ,50 R410A 18.5 BLSQWRF130M/NaD-M 3, ,50 2 NOMENCLATURE B LS QW R F 130 M / NaD-M Model Model Description Options BLS Water Chiller - QW Scroll Compressor - R Heat Pump F Air Cooled - Default- Cooling only R-Heat pump 130 Nominal Cooling Capacity 65:60kW= 17.0RT 130:120kW=34.1RT M Module - Na Refrigerant Default R22 Na R410A D Development series number - M Voltage M: V 3Ph 50Hz 3 FEATURES 3.1 Brief Introduction D series modular air-cooled scroll chillers are well-developed products incorporated with multiple advanced technologies. It mainly features the low noise level, compact structure, easy and safe operation, and convenient maintenance and service etc., widely used at newly built or retrofitted industrial and civil buildings in various sizes, such as, hotels, apartments, restaurants, office buildings, shopping malls, theaters, gyms, workshops, hospitals and other places where there are high requirements on noise level and air but the cooling tower is going to be installed troublesomely. 3
4 D series modular air-cooled scroll chillers are constructed of one or up to 16 single units which may varies in structure and in capacity of either 65NaD(two independent refrigeration cycle) or 130NaD (four independent refrigeration cycle) so as to build up a array of products with the cooling capacity ranging from 60~960kW. 3.2 Major Features High energy efficiency It is initially certified as one of the energy-saving chiller products in China. Free master unit design Any single unit can operate as the master once connected with the wired controller. It overcomes the problem which would occur to the product of other manufacturer that the whole system would fail to work properly when the fixed master unit malfunctions. Excellent compatibility Each chiller is constructed of up to 16 single units of 65NaD or up to 8 single units of 130NaD Hermetic scroll compressor Compared with other type of compressor under the same cooling load, it has few movable components, smaller rotating torque, lower noise and vibration and higher reliability and efficiency. Super protection It is equipped with the top-end microcomputer control system which is capable of providing wellrounded protection and self-diagnosis. High reliability It is constructed of well-designed refrigeration parts for multiple refrigeration cycles, adequately guaranteeing the reliable operation. Compact structure The modular design enables the compact structure, reduced volume, light weight, easy handling and shipping and flexible installation. Low noise The unit runs with low noise and vibration, widely applicable for various projects. Quiet mode The unit is allowed to run in the quiet mode based on the user s requirement, which can not only save energy but also create a comfortable and pleasant living environment. Economy mode The unit can run in the economy mode without lessening the air conditioning effect so as to cut down the electricity consumption. 4
5 D Seried Modular Air-cooled Scroll Chiller Technical Sales Guide Equilibrium running It indicates each compressor will run alternately so as to extend their service life. Humanized alert When the unit runs out of the allowable temperature range, an alert will rise on the display. Powerful remote monitoring BGH centralized air conditioning system can be perfectly integrated to the BMS or BGH remote monitoring system through the BACnet interface and realize communication through the RS Standard Control & Safety Devices The chiller's Unit Control Module is an innovative, modular microprocessor control design. It coordinates the actions of the chiller in an efficient manner and provides stand-alone operation of the unit. A Human Interface Panel is a standard component of the Chiller. Access to all unit controls is via the Human Interface Panel. Compressor In-built protection device: Motor winding temperature, discharge gas temperature and phase reversal for direction of rotation. Crankcase heaters: Protects the unit against refrigerant migration, oil dilution and potential compressor failure. High pressure switch: Provides protection in case of excessive discharge press-ure. Low pressure switch: Provides protection in case of unsafe low suction pressure. 5
6 4 PRODUCT DATA 4.1 Ratings Model Name kw/tr EER BLSQWRF65M/NaD-M 60 / BLSQWRF130M/NaD-M 120 / EER=Energy Efficiency Ratio at full load-the cooling capacity in Btu's per hour(btu/h) divided by the power input in watts, expressed in Btu/h per watts((btu/h)/watt). 4.2 Unit Application Data Voltage Variation Min./Max. Ambient Air on Condenser coil Min./Max. ( / ) 4.3 Specification 342/456(50Hz) -15/43 ( 5/110) Models Heat Pump BLSQWRF M/D-M Capacity steps % Capacity Cooling Heating kw Ton kw Ton Power Input Cooling kw Heating kw EER W/W COP W/W Power Supply V 3Ph 50Hz Running Control Microcomputer Auto Control; Running Status Display; Abnormal Status Alarm Safeties High-low pressure protection, discharge temp. protection, motor overload protection, anti-freeze, water flow protection, phase-sequence protection, compressor overload protection Type Hermetic Scroll Compressors Compressor Starting mode Direct starting Quantity 2 4 Refrigerant Type R410A 6
7 D Seried Modular Air-cooled Scroll Chiller Technical Sales Guide Type Shell and Tube Evaporator Water side heat exchanger Water flow volume Pressure Drop Max. working Pressure water in/outlet pipe flange specification m 3 /h GPM kpa ft.wg MPa 1 mm DN65 DN80 Type Finned Coil Type Condenser Air side heat exchanger Fan type/ Number of fans Total fan air flow Total fan motor power Axial Fan/2 Axial Fan/4 m 3 /h L/s CFM kw Sound pressure level db(a) Width mm Outline Dimension Depth mm Height mm Net Weights kg Operating weight (Heat Pump) uxiliary electric heater-power (Ref.) kg kw Loading quantity 40'GP/40'HQ 10/10 6/6 7
8 5 PERFORMANCE CORRECTION Performance Correction Value Leaving Chilled Water ( / ) Ambient Temperature ( / ) 25(77) 30(86) 35(95) 40(104) 45(113) 5(41.0) (42.8) (44.6) (46.4) (48.2) (50.0) (51.8) (53.6) (55.4) (57.2) (59.0) Performance Correction Value Hot Water Outlet ( / ) Ambient Temperature ( / ) -10(14) -5(23) 0(32) 5(41) 10(50) 15(59) 30(86) (95) (104) (113) (122) Water side Item Outlet water temp. ( ) Difference of the in/outlet water temp. ( ) Air side Ambient temp. Db ( ) Cooling Heating
9 D Seried Modular Air-cooled Scroll Chiller Technical Sales Guide 6 FREEZE PROTECTION When the flow passage of the shell-and-tube heat exchanger is frozen up, it would cause serious damage to the heat exchanger, such as cracking and leakage which are out of warranty, therefore, the user should take measures stated below for freeze protection. 1. Under subzero conditions, it is necessary to shut down the chiller installed outdoor and then drain the evaporator completely. 2. Failure of the chilled water flow switch and the anti-freezing temperature sensor will cause the tube frozen up, so the flow switch shall be interlocked with the chiller. 3. When charging or recovering the refrigerant, the evaporator would crack because of frostbite provided the refrigerant pressure inside the evaporator is under 0.71Mpa. Therefore, be sure to keep the water flow continually inside the evaporator or drain it completely. 7 INSTALLATION 7.1 Dimensions Graph for the shape and dimensions for BLSQWRF65M/NaD-M Unit:mm 9
10 Graph for the shape and dimensions for BLSQWRF130M/NaD-M Unit:mm 7.2 Rigging Instruction Each unit will undergo a series of strict factory inspections and tests to guarantee the expected performance and quality. However, special attention should be paid during handling and shipping to prevent the control system and the piping system from being damaged. It is best to unpack the chiller at the installation location and keep the chiller upward. When the chiller is unpacked during handing, please follow the lifting instructions stated below. a. Move the chiller by placing three levers 1/5 wider than the width of the chiller under the base and meanwhile always keep the chiller in balance. b. See the figure below for more details Spreader bar, longer than the width ofthe chiller 10 Protective pad
11 D Seried Modular Air-cooled Scroll Chiller Technical Sales Guide 7.3 Mounting Location Unit:mm Model A B C D BLSQWRF130M/NaD-M BLSQWRF65M/NaD-M Load Distribution LOAD DISTRIBUTION (kg) Model R1 R2 R3 R4 BLSQWRF130M/NaD-M BLSQWRF65M/NaD-M
12 7.5 Installation Interspace A minimum spacing of 1m should be left between any two modules for unobstructed air intake and equipment service. Additionally, a minimum of 2m should be kept between the chiller and any barrier. If allowable, it would be better to set up a suncover 3m ahead of the chiller. Unit:mm 12
13 D Seried Modular Air-cooled Scroll Chiller Technical Sales Guide 8 ELECTRICAL DATA Model Power Supply Min. sectional area of the power cable (mm 2 ) Live Line Neutral Line Earth Line Capability of the Air Switch(A) BLSQWRF65M/NaD-M V 3Ph 50Hz BLSQWRF130M/NaD-M Notes: 1 The specifications of the breaker and power cable listed in the table above are determined based on the maximum power (maximum amps) of the unit. 2. The specifications of the power cable listed in the table above are applied to the conduit-guarded multi-wire copper cable (like, JYV copper cable, consisting of PV insulated wires and a PVC cable jacket) used at 40 and resistible to 90 (see GB/T ). If the working condition changes, they should be modified according to the related national standard. 3. The specifications of the breaker listed in the table above are applied to the breaker with the working temperature at 40. If the working condition changes, they should be modified according to the related national standard. FIELD WIRING DIAGRAM 9.1 Field Wiring Diagram 13
14 9.2 Wiring for Output Control Lines Note: The output control lines of the auxiliary electric heater 1, auxiliary electric heater 2 and the water pump AC contactor are allowed to the terminal boards 11/12/13/14/15/16 of any module Wiring between Chiller Modules 14
15 D Seried Modular Air-cooled Scroll Chiller Technical Sales Guide 10MICROPROCESSOR CONTROLLER 1. Automatic control of compressor start/stop, condenser fans, evaporator pump, evaporator heater, unit alarm contacts, and chiller operation from 5 to 110 (-15 to 43 ) ambient. Automatic reset to normal chiller operation after power failure. 2. Software stored in non-volatile memory. 3. Liquid Crystal Display, descriptions in English, numeric data in Metric unit. Sealed keypad with sections for On/Off Switch, Reset, Up, Down, Exit and Entry. 4. Programmable set-points (within Manufacturer limits):chilled liquid temperature set-point and range, evaporate heater on/off temperature set-point and range, daily schedule/holiday for start/stop. 5. Display Data: Return and leaving liquid temperatures, outdoor air temperature, discharge temperature, suction temperature, compressor run status, fan run status, day, date and time, compressor starts/operating hours. 6. System Safeties: Shall cause individual compressor systems to perform auto shut down. Manual reset required after the third trip of low pressure switch in 60 minutes. Manual reset required after every trip, including: high discharge temperature, high pressure switch. Compressor motor protector shall protect against damage due to high input current or thermal overload of windings. 7. Unit Safeties: Shall be automatic reset and cause compressors to shut down under low leaving chilled liquid temperature, and flow switch operation. Contractor shall provide flow switch and wiring per chiller manufacturer requirements. 8. Alarm Contacts: low leaving chilled liquid temperature, high discharge temperature, high pressure, low pressure. 15
16 11WIRED CONTROLLER 11.1 Operation View 1. Power indicator(red): the indicator is on when the Wired Controller is powered on, or otherwise it is off. 2. Run indicator(green): the indicator is on when the Wired Controller is started, or otherwise it is off. 3. Error indicator(red): The indicator is on when the unit is at fault, or otherwise it is off. 4. On/Off button: For controlling unit conversion between start and stop, press the button (for 3 seconds) in stop state to start the unit and press the button (for 3 seconds) in operation state to stop the unit. 5. Reset button: Press the button to clear fault and relieve the air discharge temperature sensor locking. 6. Up selection button: in menu selection, press the button to move the cursor upward or leftward; and in data modification mode, press the button to increase the value. 7. Down selection button: In menu selection, press the button to move the cursor downward or rightward; and in data modification mode, press the button to decrease the value. 8. Exit button: Press the button to go back to the previous menu. 9. Confirm button: In menu selection, press the button to confirm the selected item; and in data modification mode, press the button to confirm the parameter and move the cursor. 10. LCD: Information display zone. 16
17 D Seried Modular Air-cooled Scroll Chiller Technical Sales Guide 11.2 Menu Structure of Controller 17
18 12 ACCESSORIES S=Standard O= Prepared by users P=Optional Scope of supply Single chiller module Four-wire control line (8m) Chiller accessories CF 58 Electric control cabinet Auxiliary electric heater Power line Control line Flexible connector Thermometer Pressure gage Water tank Heat pump type S S S O O O O O O O O 13APPLICATION DATA Unit Location The chillers are designed for outdoor installation. When selecting a site for installation, be guided by the following conditions: 1. For outdoor locations of the unit, select a place having an adequate supply of fresh air for the condenser. 2. Avoid locations beneath windows or between structures where normal operating sounds may be objectionable. 3. Installation sites may be either on a roof, or on the ground. 4. The condenser fans are the propeller-type, and are not recommended for use with duct work in the condenser air stream. 5. When it is desirable to surround the unit(s), it is recommended that the screening be able to pass the required chiller CFM without exceeding 0.1" of water external static pressure. 6. Recommended clearances for units are given in DIMENSIONS. When the available space is less, the unit(s) must be equipped with the discharge pressure transducer option to permit high pressure unloading in the event that air recirculation were to occur. Foundation The unit should be mounted on a flat and level foundation, ground or roof, capable of supporting the entire operating weight of the unit. Operating weights are given in the Dimensions. 18
19 D Seried Modular Air-cooled Scroll Chiller Technical Sales Guide For ground level installations, precautions should be taken to protect the unit from being tampered by or injuring to unauthorized persons. Screws on access panels will prevent casual tampering; however, further safety precautions, such as unit enclosure options, a fenced in enclosure, or locking devices on the panels may be advisable. Check local authorities for safety regulations. Chilled Liquid Piping The chilled liquid piping system should be laid out so that the circulating pump discharges into the cooler. The inlet and outlet cooler liquid connections are given in Dimensions. Delivery and Handling A. Unit shall be delivered to job site fully assembled, and charged with refrigerant and oil by the Manufacturer. B. Unit shall be stored and handled according to the Manufacturer s instructions. Leveling Unit Unit must be leveled when installed to ensure proper oil return to the compressors. Fluid Temperature Maximum leaving chilled fluid temperature for unit is 59 (15 ). For continuous operation, it is recommended that inlet fluid temperature does not exceed 86 (30 ) ( If continuous operation is required for inlet water temperature above 86 (30 ), please refer to factory). Minimum leaving chilled fluid temperature for standard unit is 38 (3.3 ) (For lower leaving temperature contact BGH). Cooler Flow Range The cooler can operate with a leaving chilled fluid temperature from of 42 to 59 (5 ~15 ). Maximum Cooler Flow It Will be based on Minimum permissible AT across the cooler 5.4 (-15 ). Cooler protection A protection against low ambient freeze-up is required for ambient temperatures below 32 (0 ). Protection should be in the form of: Inhibited ethylene glycol or any other suitable glycol. Condenser Airflow Any restrictions on units fan airflow will affect unit capacity, condenser head pressure, and compressor power input. Such restrictions (i.e. not providing vertical clearance or lateral clearance, insufficient unitto-unit clearance) will cause warm air recirclation or coil starvation. Minimum required operational and maintenance clearances around the unit are shown in the figure below. 19
20 Garantiza: BGH S.A. Brasil 731 Ciudad Autónoma de Buenos Aires. Teléfono:
HP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -
AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75
Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling
Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle
Technical data. Danfoss DHP-A
Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Cool Design for Homes and Offices
AIR BLUE AIR BLUE air conditioning Homes Easy to install and use, quiet, attractive, and designed to fit any space: there are Cool Design for Homes and Offices a lot of reasons why Air Blue air conditioners
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
Condensing unit type EPSILON-ECHOS LE Technical information manual
Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps
YCAA-B AIR COOLED LIQUID CHILLER
YCAA-B AIR COOLED LIQUID CHILLER R407C REFRIGERANT COOLING CAPACITIES 46 kw to 152 kw York YCAA-B twin refrigerant circuit air cooled liquid chillers are a compact design suitable for chilled water or
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Air Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &
hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS
CRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
DATA CENTER SOLUTIONS. For More Information: (866) 787-3271 [email protected]. Technical Data
DATA CENTER SOLUTIONS For More Information: (866) 787-3271 [email protected] Technical Data Contents Overview................................................ 1 Scalable Solution for Critical Environments...................
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
Appendix - Controllers 179
Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
Hot Water. Heat pump water heaters. Residential and Commercial R410a
Hot Water Heat pump water heaters Residential and Commercial R410a Heat pump technology Heat Pump Water Heating is a new idea using existing technology and is viewed as the latest generation of water heating
CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability
PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
AFHX Guide Specifications
AFHX Guide Specifications Part 1: General 1.01 Work Included A. Provide a complete Air Cooled Packaged Chiller utilizing rotary screw compressors suitable for outdoor installation and be controlled by
TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402
TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE
INSTALLATION & OPERATION MANUAL MODULAR AIR COOLED CHILLER
INSTALLATION & OPERATION MANUAL MODULAR AIR COOLED CHILLER Model: MAC160/210A CONTENTS MAC00912-A4 Part No.: M08019301021 1. Features page2 2. Nomenclature page3 3. Specifications page5 4. Performance
SWIMMING POOL HEAT PUMP Owners Manual
SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor
REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: [email protected] Website: www.centrair.ca
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
III. Roof Mount AC Mobile Climate Control 19 MCC Reference Manual 2014
III. Roof Mount AC Mobile Climate Control 19 MCC Reference Manual 2014 III.1. Large Roof Mount PN: 89-3037 Roof Mount Unit Eco 136 Parallel roof mount Air-conditioning and ventilation systems The Eco 136
Chilled Water Precision Air Conditioner For Critical Application
AIRSYS-P-SC-OPTIMA-HD-E1304V01.2 HD Chilled Water Precision Air Conditioner For Critical Application Cooling capacity: 42.1kW~161.5kW OPTIMA product family is designed for medium to large data center.
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Cased/Uncased Coils For Gas And Oil Furnaces
Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFL- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,900 CFM [283-897 L/s] Rheem Indoor Coils are designed for use
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
Split System Heat Pump Product Data
Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]
www.inspection-for-industry.com
Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
Cold Room & Refrigeration System (Casserole Assembly) No of units: 1
Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency
ARMSTRONG AIR HEAT PUMPS www.armstrongair.com
INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
FULL DC INVERTER SYSTEMS
FULL DC INVERTER SYSTEMS INDIDUAL AND MODULAR DESIGN & FLEXIBLE COMBINATION commercial air conditioners SDV4 2011/2012 AIR CONDITIONING 1 WELCOME TO THE WORLD of SINCLAIR AIR CONDITIONERS Company operation
Gree Solar Hybrid Hi Wall Inverter Air Conditioner
Gree Solar Hybrid Hi Wall Inverter Air Conditioner Utilize the natural power of the sun to heat or cool your home. Find out more at www.greeonline.com Why Choose a Solar Hybrid Inverter? The new Gree Solar
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
UR...3 URX CF...7 URHE CF...11. Heat recovery unit. Heat recovery unit with refrigerant circuit(442-1947 cfm)
UR...3 Heat recovery unit URX CF...7 Heat recovery unit with refrigerant circuit(442-1947 cfm) URHE CF...11 High efficiency heat recovery unit with refrigeration circuit(588-1942 cfm) UR Heat recovery
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
INDOOR COILS. RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-211 REV. 3 Supersedes Form No. C11-211 Rev. 2 INDOOR COILS RCFA- featuring R-22 Refrigerant RCFL- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS
DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS AN EXCELLENT CHOICE IN COOLING, COMFORT AND CONVENIENCE Why choose a Mini-Split system? Installing
SMM. Installation Operation Maintenance
SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation Foreword These installation,
CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
SECTION 23 64 10 AIR COOLED WATER CHILLERS
PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2
INDOOR COILS. RCFM- featuring Earth-Friendly R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-212 REV. 1 Supersedes Form No. C11-212 INDOOR COILS RCFM- featuring Earth-Friendly R-410A Refrigerant earth friendly refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description
Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant
INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-211 REV. 7 Supersedes Form No. C11-211 Rev. 6 INDOOR COILS RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM
Split System Cooling Product Data
Split System Cooling Product Data 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-14 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, easy
U-MATCH Air Conditioners. Service Manual. T1/R410a/50Hz
U-MATCH Air Conditioners Service Manual T1/R410a/50Hz GREE ELECTRIC APPLIANCES INC. OF ZHUHAI 1 CONTENTS PRODUCT...2 1 MODELS LIST...2 1.1 Outdoor Unit...2 1.2 Indoor Unit...3 2 NOMENCLATURE...4 3 FUNCTION...5
INDOOR COILS. RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-213 REV. 4 Supersedes Form No. C11-213 Rev. 3 INDOOR COILS RCFN- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS
DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion
Water-Cooled Screw Chiller. Service Manual. (T1/R22, R134a)
Water-Cooled Screw Chiller Service Manual (T1/R22, R134a) GREE ELECTRIC APPLIANCES INC. OF ZHUHAI 1 CONTENTS PRODUCT INTRODUCTION......... 2 1 MODELS LIST...2 2 NOMENCLATURE...3 3 FEATUREAS...4 3.1 Brief
DUCTED AIR CONDITIONING SOLUTIONS
DUCTED AIR CONDITIONING SOLUTIONS H I G H E N E R G Y E F F I C I E N C Y B A C K E D B Y A 5 Y E A R F U L L P A R T S & L A B O U R W A R R A N T Y DUCTED RANGE WHY CHOOSE FUJITSU? AUSTRALIA S FAVOURITE
HEATER, AIR CONDITIONING AND VENTILATION
55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT
DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS
DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion
TWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
Inverter Air Conditioning for Light Commercial Use
Inverter Air Conditioning for Light Commercial Use 02 Cost Saving Comfort An efficient use of time 03 SDISuper Digital Inverter Very efficient energy consumption Keeps down operating costs Heater operation
Split System Cooling Product Data
Split System Cooling Product Data XR17 4TTR7 2, 3, 4 & 5 Tons PUB. NO. 22-1884-01 Features and Benefits CLIMATUFF 2-stage scroll compressor Efficiency up to 18.0 SEER All Aluminum SPINE FIN coil DURATUFF
SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:
OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Technical Service Manual. Version One
[Gree Central Air Conditioner] Technical Service Manual Ducted type unit 2.3KW-16KW Version One GREE ELECTRIC APPLIANCES.INC.OF ZHUHAI - 1 - FG Series wind pipe blowing air-conditioning unit Section One:
14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE
INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient
HVAC SYSTEM (HEATER, VENTILATOR, AND A/C)
HVAC SYSTEM (HEATER, VENTILATOR, AND A/C) HEATER SYSTEM 1. Heater System A: GENERAL A semi-center type integrated air conditioning unit is used, where a high performance heater core and an evaporator core
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Product Data. Features/Benefits. AquaForce 30XA080-501 Air-Cooled Liquid Chillers. 80 to 500 Nominal Tons (265 to 1740 Nominal kw)
Product Data AquaForce 080-501 Air-Cooled Liquid Chillers 80 to 500 Nominal Tons (265 to 1740 Nominal kw) a30-4024 Well exceeds ASHRAE 90.1 Standards. AquaForce chillers were designed from the ground up
Split units TH with hermetic compressors
Split units TH with compressors Refrigeration units in split variant. Available with screw or solder terminal. Condensing unit with sound insulated weatherproof housing for outdoor installation. Split
ice 3 FLUID TO FLUID HEAT PUMP
ice 3 FLUID TO FLUID HEAT PUMP SUBMITTAL DATA (888) 530-7713 P O Box 5, Wentworth, H 03282 Rev.3 (5-30-14) ice 3, IC-2040 Fluid-to-Fluid R-410a Heat Pump Engineering Guide Specifications General otes:
Split System Cooling Product Data
Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess
SiUS091133. Service Manual. Inverter Pair FTXS-L Series FDXS-L Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump
Service Manual Inverter Pair FTXS-L Series FDXS-L Series [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Inverter Pair FTXS-L Series FDXS-L Series Cooling Only Indoor Unit FTXS30LVJU
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
News in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
SERVICE MANUAL. Domestic Air Conditioner. Model. Feature HW-05LN03
Domestic Air Conditioner SERVICE MANUAL Model HW-05LN03 Feature Anti-mold filter Mechanical control Easy clean filters Slide chassis 4-way airflow direction 2 cool settings, 2 fan settings Serial Number:
SiBE12-625. D-Series / E-Series. [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump
SiBE12-625 D-Series / E-Series [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump SUPER MULTI NX D-Series / E-Series Cooling Only Indoor Unit FTKS20D3VMW FTKS20CAVMB FDKS25CAVMB
ALL IN ONE. Heat Pump Water Heater
ALL IN ONE Heat Pump Water Heater INSTALLATION AND OPERATION INSTRUCTIONS Please read this user s manual carefully before operate the unit. www.airtradecentre.com CONTENTS A. IMPORTANT REMARKS ------------------------------------------------------------------------------------------------
sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved
Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section
2 NOMENCLATURE 3 FUNCTION 4 PRODUCT DATA
CONTENTS PRODUCT... 2 1 MODELS LIST... 2 1.1 Outdoor Unit... 2 1.2 Indoor Unit... 3 2 NOMENCLATURE... 4 3 FUNCTION... 4 4 PRODUCT DATA... 5 4.1 Product Data at Rated Condition... 6 4.2 Operation Range...