UNINTERRUPTIBLE POWER SUPPLY SYSTEM MODEL 9900A SERIES (Incluive Parallel Operaion Syem Applicaion)
Preface Reviion 1.2 December 3, 08 ALN-H1844 MITSUBISHI CORPORATION
i TABLE OF CONTENTS LIST OF TABLES... LIST OF FIGURES... HOW TO USE THIS MANUAL... ii iii iv 1.0 INTRODUCTION... 1-1 1.1 SAFETY PRECAUTION... 1-2 1.2 GENERAL... 1-5 1.3 DEFINITIONS... 1-6 1.4 OPERATION OVERVIEW... 1-7 1.5 SPECIFICATIONS... 1-16 2.0 OPERATION CONTROLS AND INDICATORS... 2-1 2.1 LED DISPLAY... 2-2 2.2 EPO BUTTON... 2-2 2.3 LIQUID CRYSTAL DISPLAY... 2-3 2.4 EXTERNAL SIGNAL TERMINAL BLOCK... 2-10 2.5 EXTERNAL COMMUNICATION CONNECTOR... 2-15 3.0 INSTALLATION AND OPERATION... 3-1 3.1 TRANSPORTATION AND INSTALLATION... 3-1 3.2 INSTALLATION PROCEDURE... 3-1 3.3 PROCEDURE FOR CABLE CONNECTIONS... 3-2 3.4 OPERATING PROCEDURES... 3-11 4.0 RESPONSE TO UPS FAILURE... 4-1 5.0 PARTS REPLACEMENT... 5-1 6.0 FAULT CODES... 6-1 7.0 WARRANTY & OUT OF WARRANTY... 7-1 MITSUBISHI
ii LIST OF TABLES Table 1.1 UPS Inallaion Environmen... 1-3 Table 1.2 Raing of Bypa Inpu Circui Breaker... 1-4 Table 1.3 Power Specificaion... 1-16 Table 1.4 UPS Module Informaion... 1-16 Table 1.5 Deail of Specificaion... 1-17 Table 1.6 Raing of Conacor, Breaker and Fue... 1-18 Table 3.1 How o Tranpor and Inall he Syem... 3-1 Table 3.2 Li of UPS Weigh (lb.)... 3-1 Table 3.3 Maximum Permied Faul Curren... 3-2 Table 3.4 Recommended Cable Size... 3-5 Table 3.5 Crimp Type Compreion Lug... 3-6 Table 6.1 Faul Code... 6-2 MITSUBISHI
iii LIST OF FIGURES Figure 1.1 Single Line Diagram-Normal Operaion... 1-7 Figure 1.2 Single Line Diagram-Bypa Operaion... 1-8 Figure 1.3 Single Line Diagram-Baery Operaion... 1-9 Figure 1.4 UPS Par Locaion... 1-11 Figure 1.5 Diplay PCB DPAU-81... 1-12 Figure 1.6 Exernal I/F PCB IOAU-09... 1-12 Figure 1.7 Parallel I/F PCB IFAU-08... 1-13 Figure 1.8 MAIN PCB UPGR-M... 1-13 Figure 2.1 Operaion/Diplay Panel... 2-1 Figure 2.2 Main Screen... 2-3 Figure 2.3-a Sarup/Shudown guidance... 2-4 Figure 2.3-b Sarup guidance... 2-4 Figure 2.3-c Shudown guidance... 2-4 Figure 2.4-a Inpu value... 2-5 Figure 2.4-b Oupu value... 2-5 Figure 2.4-c Value baery operaion... 2-5 Figure 2.5-a Remoe/Local operaion elec... 2-6 Figure 2.5-b Dae & Time adjumen... 2-6 Figure 2.6-a Log menu... 2-7 Figure 2.6-b Even log... 2-7 Figure 2.6-c Baery log... 2-7 Figure 2.7-a Main Screen (Baery Operaion)... 2-8 Figure 2.7-b Meauremen Screen (Baery Operaion)... 2-8 Figure 2.8 Main Screen (Faul Indicaion)... 2-8 Figure 2.9 Meage Screen... 2-9 Figure 2.10-a Exernal Signal Terminal Block (TN2)... 2-10 Figure 2.10-b Exernal Signal Terminal Block (TN1)... 2-11 Figure 2.11 Conrol Wiring for Exernal Conac... 2-12 Figure 2.12 Remoe "Sar" Conac Connecion... 2-13 Figure 2.13 Exernal communicaion connecor... 2-15 Figure 3.1 UPS Terminal Deignaion... 3-6 Figure 3.2 Diagram of inpu/oupu bu bar and erminal block... 3-7 Figure 3.3 Diagram of Power wire & Conrol wire Iner-connec beween UPS and Baery... 3-8 Figure 3.4 Diagram of Power wire Connec (Parallel Connecion)... 3-9 Figure 3.5 Diagram of Power and Conrol wire Connec (Parallel Connecion)... 3-10 MITSUBISHI
iv HOW TO USE THIS MANUAL Thi manual i deigned for eae of ue, giving he uer eay and quick reference o informaion. Thi manual ue noice icon o draw aenion o he uer imporan informaion regarding he afe operaion and inallaion of he UPS. The noice icon ued in hi manual are explained below, and hould be aken ino accoun and adhered o whenever hey appear in he ex of hi manual. Warning: A warning noice icon convey informaion provided o proec he uer and ervice peronnel again hazard and/or poible equipmen damage. Cauion: A cauion noice icon convey informaion provided o proec he uer and ervice peronnel again poible equipmen damage. Noe: A Noe noice icon indicae when he uer hould make a reference of informaion regarding he UPS operaion, load au and diplay au. Such informaion i eenial if Miubihi field ervice group aiance and correpondence i required. Safey Recommendaion: If any problem are encounered while following hi manual, Miubihi field ervice group aiance and correpondence i recommended. MITSUBISHI
1-1 1.0 INTRODUCTION The Miubihi Uninerrupible Power Supply Syem (UPS) i deigned o provide many year of reliable proecion from power failure, brown-ou, line noie, and volage ranien. To enure opimum performance of he equipmen, follow he manufacurer' inrucion. Thi manual conain decripion required o operae he UPS. Pleae read hi manual carefully and reain i for fuure reference. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Thi manual conain imporan inrucion for he 9900A SERIES Uninerrupible Power Supply Syem ha hould be followed during inallaion and mainenance of he UPS and baerie. WARNING 1 Lehal volage exi wihin he equipmen during operaion. Oberve all warning and cauion in hi manual. Failure o comply may reul in eriou injury or deah. Obain qualified ervice for hi equipmen a inruced. MITSUBISHI
1-2 WARNING 2 In no even will MITSUBISHI be reponible or liable for eiher indirec or conequenial damage or injury ha may come from he ue of hi equipmen. Any modificaion wihou auhorizaion by MITSUBISHI could reul in peronal injurie, deah or derucion of he UPS. 1.1 SAFETY PRECAUTIONS APPLICATION Thi UPS hall NOT be applied o uppor equipmen (*) ha could affec he human live. * Medical operaion room equipmen Life uppor equipmen (arificial dialyi, incubaor, ec.) Toxic ga or moke eliminaor Equipmen ha mu be provided under fire law, conrucion andard or oher ordinance Equipmen equivalen o he above Special conideraion are required when applying hi UPS o he equipmen (**) ha affec human afey and/or mainain public ervice ** Equipmen o upervie or conrol airway, railway, road, ea-lane or oher ranporaion. Equipmen in nuclear power plan. Equipmen o conrol communicaion. Equipmen equivalen/imilar o he above menioned. MITSUBISHI
1-3 WARNING 3 The UPS i o be inalled in a conrolled environmen. Improper orage and inallaion environmen may deeriorae inulaion, horen componen life and caue malfuncion. Keep he inallaion environmen per andard decribed a follow: TABLE 1.1 UPS Inallaion Environmen No. Iem Environmen andard 1 Inallaion locaion 2 Ambien emperaure 3 Relaive humidiy Indoor Minimum emperaure: 32 F(0 C), Maximum emperaure: 104 F(40 C) The average emperaure over any 24-hour period mu be in he range 41 F (5 C) o 95 F(35 C). The relaive humidiy mu be held beween 5 and 95%. There mu be no condenaion due o emperaure change. 4 Aliude Thi equipmen mu no be applied a aliude ha exceed 2250m(7400f) above eal level. 5 Du Du in he room where he UPS i inalled mu no exceed normal amopheric du level. In paricular, ha du houd no include iron paricle, oil or fa, or organic maerial uch a ilicone. 6 Inflammable ga There hould be no inflammable/exploive ga. following IEC654-4 Par 4 Hydrogen ulfide (H 2 S) Sulfurou acid ga (SO 2 ) Chlorine ga (Cl 2 ) Ammonia ga (NH 3 ) Nirou oxide (NO x ) Ozone (O 3 ) No more han 0.003 PPM No more han 0.01 PPM No more han 0.002 PPM No more han 1 PPM No more han 0.05 PPM No more han 0.002 PPM MITSUBISHI
1-4 WARNING 4 Thi UPS doe no include a Bypa inpu circui breaker (MCCB) o proec bypa circui. The Bypa inpu circui breaker (MCCB) i o be field upplied and inalled. Recommended Breaker (MCCB)' Specificaion are a follow: TABLE 1.2 Raing of Bypa Inpu Circui Breaker Capaciy (kva) Bypa Volage (Vac) Bypa Raing (Aac) Breaker (A) 80 480 96 125 100 480 120 150 150 480 180 225 225 480 271 350 AC inpu and AC oupu overcurren proecion and diconnec device hall be field upplied and inalled. The DC circui breaker (MCCB) hall be field upplied and inalled. The overcurren proecion device hould be inalled in he Baery cabine and raed a indicaed in TABLE 1.6. Noe: The DC inpu overcurren proecion (Baery diconnec breaker) hereinafer will be referred a CB2. MITSUBISHI
1-5 1.2 GENERAL The Miubihi i deigned o provide coninuou and clean elecrical power o a criical load. Addiionally he UPS monior power condiion affecing he load. In he even of an inpu power failure, he UPS will upply power o he criical load for he pecified baery ime. If he inpu power i no reored promply, back up power from he UPS baery permi he orderly hudown of equipmen uppored by he UPS. The UPS i imple o ar-up, operae and mainain. The i available in Four kva ize - 80, 100, 150 and 225kVA. Specificaion for each kva model appear in Secion 1.5. The principle of operaion decribed herein are applicable o all model. Thi manual provide an overview of he 9900A SERIES componen and heir funcion. The appearance and purpoe of operaor conrol and indicaor i decribed wih procedure for operaion, ar-up, hudown and baic mainenance included. MITSUBISHI
1-6 1.3 DEFINITIONS UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All componen wihin he UPS Module Cabine and aociaed baerie ha funcion a a yem o provide coninuou, condiioned AC power o a load. Thi i omeime referred o a he "Syem". UPS MODULE CABINET - The meal encloure which conain he Converer / Charger, Inverer, Saic Tranfer Swich, Inernal Bypa line, operaor conrol, and inernal conrol yem required o provide pecified AC power o a load. UPS MODULE - The Converer / Charger and Inverer aemblie which, under he direcion of he inernal conrol yem and operaor conrol, provide pecified AC power o a load. INVERTER - The UPS componen which conain he equipmen and conrol neceary o conver DC power from he Converer / Charger, or he baery, o AC power required by he criical load. CONVERTER / CHARGER - The UPS componen which conain he equipmen and conrol neceary o conver inpu AC power o regulaed DC power required for baery charging and for upplying power o he Inverer. STATIC TRANSFER SWITCH - The device which connec he criical load o he bypa line when he Inverer canno upply coninuou power. BYPASS LINE - The line which conduc elecriciy direcly from he inpu power ource o he criical load during Mainenance or whenever he UPS i no compleely operaional. AC INPUT POWER - Power provided by he elecrical uiliy company, or auxiliary generaor, which i conneced o he UPS for upplying he criical load. BATTERY - The rechargeable baery ring which upply DC power o he inverer o mainain coninuou AC power o he load during AC inpu power failure condiion. MITSUBISHI
1-7 1.4 OPERATION OVERVIEW The UPS provide wo power pah beween he uiliy ource and he criical load. Figure 1.1 how he pah for normal operaion, wih he load powered from he inverer. Figure 1.2 how he pah for bypa operaion, wih he load upplied hrough he aic bypa line. A) Normal operaion: Load power upplied by each yem UPS inverer. Figure 1.1 Single Line Diagram - Normal Operaion: Load powered by UPS inverer Bypa inpu CB UPS Module 52S Uer upplied Saic Tranfer Swich CB3 CB CB1 CONVERTER / CHARGER INVERTER 52C AC inpu Oupu Uer upplied Power Flow No in Ue Baery Cabine CB2 Exernal BATTERY During normal operaion, he pah hrough he UPS inverer i ued o power he load. Referring o Figure 1.1: Inpu AC power i convered o DC by he Converer. DC power i uilized o charge he UPS baery and o provide power o he Inverer. The Inverer conver he DC power o clean AC power o upply he criical load. The converion - inverion proce eliminae any volage ranien or flucuaion exiing in he inpu power before i reache he criical load. The power drawn by he criical load i equally hared beween all UPS whenever he yem i in he Parallel Operaion. (Refer o Figure 3.4 ha how a ample of Parallel Operaion Syem Configuraion.) MITSUBISHI
1-8 In he even of a UPS module failure during Parallel Operaion, he criical load power will be coninually upplied and hared by all oher UPS. The Bypa Inpu circui breaker (MCCB) for proecion of he UPS and cable are field upplied and field inalled. (See WARNING 4 on page 1-4) B) Bypa Operaion: Load Power upplied hrough UPS inernal aic bypa line. FIGURE 1.2 Single Line Diagram - Bypa Operaion: Load fed hrough aic bypa line. Bypa inpu CB UPS Module 52S Uer upplied Saic Tranfer Swich CB3 CB CB1 CONVERTER / CHARGER INVERTER 52C AC inpu Oupu Uer upplied Power Flow No in Ue Baery Cabine CB2 Exernal BATTERY Referring o Figure 1.2: The Inernal Bypa line i a Hard-wired line hrough 52S which upplie he criical load wih uncondiioned bypa inpu power. Upon wiching o he Inernal Bypa line, he Saic Tranfer Swich line hrough CB3 (herein afer STS conacor CB3) upplie he power immediaely, and hen he Inernal Bypa line hrough 52S upplie he power. In he even of a wiching o he Bypa line, he power o he criical load will be uninerruped. The purpoe of hi Inernal Bypa line i o roue power o he criical load while he UPS module i de-energized (converer and inverer), and during Sar-up before he yem i fully operaional. Each UPS inernal aic bypa line will equally hare he power upplied o he criical load whenever he yem i in he Parallel Operaion. MITSUBISHI
1-9 In he even of a load overcurren, he UPS ranfer o bypa wihou inerrupion o he criical load. In he cae of he Parallel Operaion, all UPS will ranfer o bypa wihou inerrupion o he criical load. The inernal conrol yem deermine he operaion of he wo pah, wih he load powered from he inverer being he normal operaion. C) Baery operaion: Load Power upplied by UPS baery. FIGURE 1.3 Single Line Diagram - Baery Operaion Bypa inpu CB UPS Module 52S Uer upplied Saic Tranfer Swich CB3 CB CB1 CONVERTER / CHARGER INVERTER 52C AC inpu Oupu Uer upplied Power Flow No in Ue Baery Cabine CB2 Exernal BATTERY Referring o Figure 1.3: In he even of AC inpu ource failure or inerrupion, he UPS Converer()* will de-energize and he UPS baery()* will immediaely dicharge and upply DC power o he Inverer o mainain coninuou AC power o he load. Thi operaion will coninue unil: a) The baery capaciy expire and he inverer urn off, or b) Inpu power i reored afer which he converer will power he inverer and criical load and imulaneouly recharge he baerie. A fully charged baery will provide power for he pecified ime a he raed load, or longer, a a reduced load. ()* : In he cae of he Parallel Operaion MITSUBISHI
1-10 When power i reored afer a low baery hudown, he UPS converer()* auomaically rear operaion, he charger()* recharge he baerie and he Inverer()* i auomaically reared wihou operaor inervenion. Load i auomaically aumed by he inverer wihou operaor inervenion. ()* : In he cae of he Parallel Operaion The power drawn by he load i equally hared beween all UPS regardle of he preence or abence of he UPS ha i (are) in baery operaion or no whenever he yem i in he Parallel Operaion.. MITSUBISHI
1-11 FIGURE 1.4-a UPS Par Locaion (80/100kVA) UPS module Fron View 8. Parallel I/F PCB IFAU-08 CPMS CPMC EMB 88F 1. LCD ouch panel monior diplay 2. Diplay PCB DPAU-81 6. Exernal Communicaion Connecor 3. Exernal I/F PCB IOAU-09 Inverer, Converer, Charger Uni 5. Relay PCB RYAU-09 4. Main PCB UPGR-M 7. Parallel conrol PCB TLCR-C Ground Faul Senor FDAU-04 CB3 10. Grounding Bar (E) 52C 52S CB1 * Iem 9 (AC inpu, AC oupu, DC inpu erminal) i no hown in Figure 1.4-a. (Refer o Figure 3.2) 8. Parallel I/F PCB IFAU-08 FIGURE 1.4-b UPS Par Locaion (150, 225kVA) UPS module Fron View CPMS CPMC EMB 88F Inverer, Converer, Charger Uni 1. LCD ouch panel monior diplay 2. Diplay PCB DPAU-81 6. Exernal Communicaion Connecor 3. Exernal I/F PCB IOAU-09 5. Relay PCB RYAU-09 4. Main PCB UPGR-M 7. Parallel conrol PCB TLCR-C Ground Faul Senor FDAU-04 CB3 10. Grounding Bar (E) CB1 52S 52C * Iem 9 (AC inpu, AC oupu, DC inpu erminal) i no hown in Figure 1.4-b. (Refer o Figure 3.2) MITSUBISHI
1-12 FIGURE 1.5 Diplay PCB DPAU-81 CNV. SW. wich 11. SW1 RESET wich START buon STOP buon 12. SW5 TEST wich 13. SW6 MAINTENANCE buon FIGURE 1.6 Exernal I/F PCB IOAU-09 16. Exernal conac ignal erminal block TN1 TN2 IOAU-09 MITSUBISHI
1-13 FIGURE 1.7 Parallel I/F PCB IFAU-08 TLIN CN96 TLOUT CN95 IFAU-08 CBIN CBOUT CAIN CAOUT CN94 FIGURE 1.8 MAIN PCB UPGR-M 15. SW3 52L S/W wich UPGR-M 14. SW2 BOOT wich 11. SW1 RESET wich MITSUBISHI
1-14 Decripion of Figure 1.4 o 1.8: 1. LCD Touch Panel Monior Diplay The Liquid Cryal Diplay (LCD) Touch Panel Monior Diplay indicae power flow, meaured value and faul and error meage via uer elecable diplay creen. Refer o FIGURE 2.1 for deail. 2. Diplay PCB DPAU-81 (Figure 1.5): Swiche on DPAU-81 board : FOR PERSONNEL ONLY - (11) SW1 (RESET wich) - (12) SW5 (TEST wich) - (13) SW6 (MAINTENANCE wich) 3. Exernal I/F PCB IOAU-09 (Figure 1.6): Signal I/F on IOAU-09 board - (16) Exernal conac ignal erminal block Refer o FIGURE 2.10 for deail. 4. Main PCB UPGR-M (Figure 1.8): Swiche on UPGR-M board : FOR PERSONNEL ONLY - (11) SW1 (RESET wich) - (14) SW2 (BOOT wich) - (15) SW3 (52L S/W wich) 5. Relay PCB RYAU-09 6. Exernal Communicaion Connecor RS232C connecor on DPAU-81 board : FOR PERSONNEL ONLY Refer o FIGURE 2.13 for deail. 7. Parallel conrol PCB TLCR-C For ue in Parallel Operaion yem applicaion : Opion 8. Parallel I/F PCB IFAU-08 For ue in Parallel Operaion yem applicaion : Opion (Figure 1.7): Refer o FIGURE 3.5 for deail. 9. AC inpu, AC oupu, DC inpu erminal Refer o Figure 3.2 for deail 10. Grounding Bar (E) MITSUBISHI
1-15 11. "RESET" wich (FOR PERSONNEL ONLY) Thi wich ree error reuling from alarm condiion. 12. "TEST" wich (FOR PERSONNEL ONLY) Thi wich change yem operaion o he e-mode. 13. "MAINTENANCE" wich (FOR PERSONNEL ONLY) Thi wich e he UPS menu parameer. 14. "BOOT" wich (FOR PERSONNEL ONLY) Thi wich boo he proceor on he main conrol circui board following alarm condiion. 15. "52L S/W" wich (FOR PERSONNEL ONLY) Thi wich prohibi urning on he AC oupu conacor 52C during e/mainenance in Parallel Operaion yem applicaion. 16. Exernal conac ignal erminal block Terminal block o connec conac ignal inpu/oupu line o and from exernal dry conac. Refer o FIGURE 2.10 for deail. MITSUBISHI
1-16 1.5 SPECIFICATIONS The UPS nameplae diplay he raed kva a well a nominal volage and curren. The nameplae i locaed on he inide of he UPS fron door. TABLE 1.3 Power Specificaion Raed oupu Inpu volage Bypa inpu volage Oupu volage Power 3 phae / 3 wire 3 phae / 3 wire 3 phae / 3 wire 80kVA / 72kW 480V 480V 480V 100kVA / 90 kw 480V 480V 480V 150kVA / 135kW 480V 480V 480V 225kVA / 202.5kW 480V 480V 480V TABLE 1.4 UPS Module Informaion UPS [kva] Cable Enry Widh [in / mm] Deph [in / mm] Heigh [in / mm] Weigh [lb./ kg] Heaing [kbth / h] 80 BOTTOM 27.6 / 700 32.8 / 832 80.6 / 2047 855 / 388 11.3 100 BOTTOM 27.6 / 700 32.8 / 832 80.6 / 2047 855 / 388 14.1 150 BOTTOM 35.4 / 900 32.8 / 832 80.6 / 2047 1160 / 526 18.2 225 BOTTOM 35.4 / 900 32.8 / 832 80.6 / 2047 1230 / 558 27.3 MITSUBISHI
1-17 TABLE 1.5 Deail of Specificaion Raed Oupu kva 80 100 150 225 Raed Oupu kw 72 90 135 202.5 AC INPUT Configuraion 3 phae, 3 wire Volage 480 V +15% o -20% Frequency 60 Hz +/-10% Refleced Curren THD 3% a 100% load (no inpu filer required) STATIC BYPASS INPUT Configuraion 3 phae, 3 wire Volage 480 V +/-10% Frequency 60 Hz +/-5% BATTERY Type Lead Acid Ride Through Applicaion Specific Nominal Volage 480 Vdc Minimum Volage 400 Vdc Number of Cell 240 AC OUTPUT Configuraion 3 phae, 3 wire Volage 480 V Volage Regulaion +/-1% Frequency Frequency Regulaion Power Facor Power Facor Range Volage THD Tranien Repone 60 Hz +/-0.01 in free running mode 0.9 nominal 0.9 o 1.0 lagging (wihin oupu kw raing) 2% maximum THD a 100% Linear Load 5% maximum THD a 100% non-linear load +/-2% maximum a 100% load ep +/-1% maximum a lo/reurn of AC power +/-5% maximum a load ranfer o/from aic bypa Tranien Recovery Le han 20m Volage Unbalance 1% maximum a 100% unbalanced load Phae Diplacemen 1 deg. maximum a 100% load Inverer Overload 125% for 2 minue; 150% for 60 econd Bypa Overload 1000% for 1 cycle (wih bypa available) Wihand Raing 65kA* * : wih opional fue ENVIRONMENTAL Cooling Forced Air Operaing Temperaure 32 F o 104 F ( 0 C o 40 C). Recommended : 68 F o 86 F ( 20 C o 30 C) Relaive Humidiy 5% ~ 95% Non Condening Aliude 0 o 7400 fee No Deraing a 40 C Locaion Pain Color Indoor (free from corroive gae and du) Munell 5Y7/1 (Beige) MITSUBISHI
1-18 TABLE 1.6 Raing of Conacor, Breaker and Fue NUMBER APPLICATION OUTPUT CAPACITY OF EQUIPMENT 80kVA 100kVA 150kVA 225kVA 72kW 90kW 135kW 202.5kW CB1 AC inpu conacor 135A 135A 200A 285A Conacor Breaker Fue CB3 STS conacor 80A 80A 135A 150A 52C Inverer oupu conacor 135A 135A 200A 285A 52S Bypa conacor 135A 135A 200A 285A 88RC Conrol circui conacor 20A 20A 20A 20A CB2 Uer upply Uer upply FCU, FCV, FCW FCR, FCS, FCT FPU, FPV FNU, FNV Baery diconnec breaker (Recommended) AC inpu breaker (Recommended) AC oupu breaker (Recommended) 225A 300A 400A 600A 125A 150A 225A 350A 125A 150A 225A 350A DC fue 315A / 690V 315A / 690V 200A / 690V 200A / 690V DC fue 200A / 690V 200A / 690V 350A / 690V 350A / 690V FUA, FUB, FUC Conrol power fue 30A / 600V 30A / 600V 30A / 600V 30A / 600V (OPTION) FSU, FSV, FSW Bypa inpu fue 250A / 690V 250A / 690V 200A / 690V 250A / 690V FZS1, 2, 3 Bypa inpu ZNR fue 5A / 500V 5A / 500V 5A / 500V 5A / 500V FBS1, 2, 3 Conrol power fue 30A / 600V 30A / 600V 30A / 600V 30A / 600V FZR1, 2, 3 AC inpu ZNR fue 5A / 500V 5A / 500V 5A / 500V 5A / 500V Parallel conrol FEA, FEB, FEC circui fue *Raing would be changed. 3A / 600V 3A / 600V 3A / 600V 3A / 600V MITSUBISHI
2-1 2.0 OPERATOR CONTROLS AND INDICATORS The 9900A Serie operaor conrol and indicaor are locaed a follow (Door exerior) : FIGURE 2.1 Operaion/Diplay Panel (Fron panel) 8 3 2 1 4 5 6 7 MITSUBISHI
2-2 2.1 LED DISPLAY 1) Load on inverer [ LOAD ON INVERTER ](green) Illuminae when power i upplied from inverer o he criical load. (Indicae he ae of inverer ranfer wich "52C".) 2) Baery operaion [ BATTERY OP. ](orange) Illuminae when power i upplied from baerie following a power failure. 3) Load on bypa [ LOAD ON BYPASS ](orange) Illuminae when power i upplied o load device by aic bypa. (Indicae he ae of bypa ranfer wich "52S".) 4) Overload [ OVERLOAD ](orange) Illuminae in overload condiion. 5) LCD faul [ LCD FAULT ](red) Illuminae when an error occur. 6) UPS faul [ UPS FAULT ](red) [Annunciaor: inermien or conan one] Illuminae when an error occur in he yem. In hi cae, he deail of he error are indicaed on he diplay panel. 2.2 EPO BUTTON (Emergency Power Off buon) (7) When acivaed, he Emergency Power Off (EPO) funcion hu down he UPS module. The criical load will loe power and alo hudown. The EPO funcion can be performed boh locally or remoely. MITSUBISHI
2-3 2.3 LIQUID CRYSTAL DISPLAY (8) The Liquid Cryal Diplay (LCD) ouch panel indicae power flow, meaured value, operaional guidance, daa record and error meage. The LCD panel ha a back-ligh which faciliae viewing in differen ambien lighing condiion. The LCD will auomaically clear and urn off, if he creen i no acivaed wihin 3 minue period. The LCD i urned back on when i i ouched again. The ERROR indicaor i cleared afer 24 hour and can be reproduced by preing any key on he panel. 2.3.1 MENU A) MAIN MENU (FIGURE 2.2) The LCD panel indicae power flow and meaured value, while alo operaing he ar/op funcion. The LCD panel alo allow he uer o verify he au and operaion of he UPS Module. FIGURE 2.2 Main creen The following will be diplayed when he START/STOP key on he MAIN MENU i preed (Jump ino OPERATION MENU) : 1) Sarup/Shudown Guidance (FIGURE 2.3) The diplay indicae he Sarup and Shudown guidance for he UPS yem. If hi operaion i PIN proeced, he uer i required o ener he ecuriy PIN before he creen can be acceed. When in remoe mode, he meage REMOTE operaing model will appear on hi Screen. The uer canno operae he ar and op funcion wihou changing he eup from remoe mode o local mode. When bypa volage i abnormal, he meage Bypa volage abnormal will appear. MITSUBISHI
2-4 -Sar: When he bypa volage i abnormal, he LCD ak he operaor if an inerruped ranfer i accepable (Load may be lo). -Sop: When he bypa volage i abnormal, he uer canno ranfer from inverer o bypa line. FIGURE 2.3-a Sarup/Shudown guidance FIGURE 2.3-b Sarup guidance FIGURE 2.3-c Shudown guidance Follow Sarup/Shudown guidance accordingly. B) MEASUREMENT MENU (FIGURE 2.4) Thi creen how deail of meaured value. Inpu and Oupu value are diplayed. MITSUBISHI
2-5 During Baery operaion, Remaining baery power and Run ime are alo diplayed. FIGURE 2.4-a Inpu value FIGURE 2.4-b Oupu value FIGURE 2.4-c Value in Baery operaion MITSUBISHI
2-6 C) OPERATION MENU (FIGURE 2.5) Thi creen promp he uer o elec: (a) wheher he ar & op operaion will be performed by local or remoe operaion; (b) dae & ime adjumen; (c) baery equalizing charge. The baery equalizing charge operaion key will appear when baery equalizing charge i e up (Seup i baed on baery ype). FIGURE 2.5-a Remoe/Local operaion elec FIGURE 2.5-b Dae & Time adjumen MITSUBISHI
2-7 D) LOG MENU (FIGURE 2.6) Thi LOG MENU diplay wo Touch icon in EVENT LOG and BATTERY LOG. Preing he EVENT LOG icon, up o 50 condiion/operaion record will be diplayed. Pre or buon for page urning. Preing he BATTERY LOG icon, Number of baery operaion and Summed baery operaion ime are diplayed. FIGURE 2.6-a Log menu FIGURE 2.6-b Even log FIGURE 2.6-c Baery log MITSUBISHI
2-8 2.3.2 INPUT POWER FAILURE (FIGURE 2.7) During an Inpu Power Failure, he UPS inverer will be powered by he UPS baerie. The following will be diplayed on he main and meauremen creen (Indicaion of baery operaion and remaining baery life). FIGURE 2.7-a Main creen FIGURE 2.7-b Meauremen creen (Baery operaion) (Baery operaion) The LCD will diplay a baery low volage meage when he baery capaciy i near depleion. The End of Baery Dicharge announcemen i diplayed when he baery end volage i reached. A hi ime, he inverer will perform an elecronic hudown o preven baery lo of life ypical from exreme deep dicharge condiion. When he inpu power i reored, he inverer will auomaically rear o power he load, and he baerie will be imulaneouly recharged. The End of Baery announcemen i hown a he boom of he creen. 2.3.3 FAULT INDICATION (FIGURE 2.8) MESSAGE and SILENCE ALARM icon will appear on he main menu when UPS failure condiion ha occurred. FIGURE 2.8 Main creen (Faul indicaion) MITSUBISHI
2-9 The following will be diplayed when he MESSAGE icon on he main menu i preed. 1) MESSAGE (FIGURE 2.9) The diplay how a faul code, he decripion of he faul and a guidance of wha acion i o be aken by he uer. A maximum of 10 faul i diplayed a one ime. If an inpu power failure occur during a faul condiion, he faul indicaion and inpu power failure announcemen are alernaively diplayed a 5 econd inerval. FIGURE 2.9 Meage creen 2) SILENCE ALARM Thi icon will appear when a failure occur. The audible alarm (announcing he failure) can be ilenced by preing hi icon. MITSUBISHI
2-10 2.4 EXTERNAL SIGNAL TERMINAL BLOCK The UPS i equipped wih a erie of inpu/oupu erminal for exernal annunciaion of alarm and for remoe acce of cerain UPS funcion. The layou of erminal i hown in Figure 2.10 wih a funcional decripion of he inpu/oupu por preened. OUT1 o OUT8 are uer programmable, bu are facory defaul e being alo hown in Figure 2.10. Adding ame exernal I/F PCB IOAU-09, doubling ignal oupu i applicable for OUT1 o OUT8. FIGURE 2.10-a Exernal Signal Terminal Block (NEC Cla2) TN2 2 4 6 8 10 12 14 16 18 20 1 3 5 7 9 11 13 15 17 19 SUMMARY ALARM OUT1: LOAD ON BYPASS OUT2: LOAD ON INVERTER OUT3: BATTERY OPERATION OUT4: CONVERTEN OPERATION OUT5: BATTERY LOW VOLTAGE OUT6: OVERLOAD OUT7: SPARE OUT8: TOTAL ALARM UPS 52C CLOSE *1 *1 Relay conacor (52C cloe): Normal Cloed MITSUBISHI
2-11 FIGURE 2.10-b Exernal Signal Terminal Block (NEC Cla2) TN1 2 4 1 3 CB2 UVT CB2 AX Baery Breaker Panel 6 5 52L AX Load Circui Swich 8 10 7 9 IN1: REMOTE INVERTER START IN2: REMOTE INVERTER STOP (Uer upplied dry conac) 12 11 IN3: BATTERY TEMP. HIGH 14 13 IN4: POWER DEMAND 16 15 REMOTE EPO 18 17 20 19 UPS MITSUBISHI
2-12 A) Oupu Conac (for exernal alarm annunciaion) Oupu conac coni of form A dry ype conac. Raed capaciy of all oupu conac i NEC Cla2 (30Vdc/1Adc). All dry conac hould be operaed a heir raed value or lower. Figure 2.11 illurae a ypical inallaion. The exernal relay can alo be a lamp, LED, compuer, ec. UPS Cabine Relay Conac FIGURE 2.11 Conrol Wiring for Exernal Conac Terminal Terminal Exernal o UPS Cabine Relay Coil NEC Cla 2 Power Source Uer upplied Deail of oupu alarm conac : TN1 Terminal 1 o 2 "Summary Alarm" conac Acivaed when a major faul ha occurred wih he yem. Terminal 3 o 4 "Load on Bypa" conac (OUT1) Acivaed when he power i upplied from he aic bypa inpu. Terminal 5 o 6 "Load on Inverer" conac (OUT2) Acivaed when he power i upplied by he inverer. Terminal 7 o 8 "Baery Operaion" conac (OUT3) Acivaed when he baery i operaing following an AC power failure. Terminal 9 o 10 "Converer Operaion" conac (OUT4) Acivaed when he converer i operaing. Terminal 11 o 12 "Baery Low Volage" conac (OUT5) Acivaed when he baery volage drop below dicharge end volage level during inverer operaion (i.e. During AC fail condiion). Terminal 13 o 14 "Overload" conac (OUT6) Acivaed when an overload ha occurred o he yem. Terminal 15 o 16 "Toal Alarm" conac (OUT7) Acivaed during major faul, minor faul and alarm even. Terminal 17 o 18 "Spare" conac (OUT8) Terminal 19 o 20 "52C Cloe" conac (OUT9) Acivaed when he inverer oupu conacor 52C ha cloed. MITSUBISHI
2-13 NOTE: The UPS i equipped wih a elecable oupu conac feaure. The above alarm are he defaul eing. Conac MITSUBISHI POWER PRODUCTS, INC for eup informaion. B) Inpu Conac (for remoe acce of UPS) Exernal conac are provided by he uer of he UPS yem. Terminal volage a he UPS i 24Vdc. Provide exernal dry conac accordingly. CAUTION: Do no apply volage o remoe acce inpu erminal. Damage o UPS may reul. Refer o Figure 2.12 for a ypical wiring configuraion. Alhough hi figure applie o he remoe ar/op erminal, he ame wiring arrangemen i ued for emergency op; power demand; and baery emperaure high. FIGURE 2.12 Remoe "Sar" Conac Connecion UPS Cabine Relay Coil 24 VDC Sar Common Exernal o UPS Cabine Sar Swich 0.5S - 4S ON OFF Relay Coil curren : 8.3mA Ue Momenary Swiche Only Uer upplied MITSUBISHI
2-14 Deail of inpu conac for remoe acce : TN2 Terminal 7 o 8 Remoe "Inverer Sar" inpu erminal (IN1) Ued o ar inverer from a remoe locaion. UPS mu be programmed for remoe operaion. Refer o Operaion Menu for procedure. Terminal 9 o 10 Remoe "Inverer Sop" inpu erminal (IN2) Ued o op inverer from a remoe locaion. UPS mu be programmed for remoe operaion. Refer o Operaion Menu for procedure. Terminal 11 o 12 "Baery Temp. High" conac inpu (IN3) Inpu fed by a hermocouple ha monior baery emperaure. The converer floa volage level i reduced for baery over-emperaure condiion. Exernal hermocouple i uer upplied Terminal 13 o 14 "Power Demand Command conac inpu (IN4) Thi conac i ued o conrol he inpu power. Power demand i urned ON when he conac i cloed, and power demand i urned OFF when he conac i open. Terminal 15 o 16 "Remoe EPO" conac inpu Ued o perform a remoe UPS Emergency Power Off (EPO). The load will be dropped. NOTE: The UPS i equipped wih a elecable inpu conac iem. The above iem are he defaul eing. MITSUBISHI POWER PRODUCTS, INC for eup informaion. CAUTION : In all cae, a wich having a proecive cover i recommended in order o reduce he poibiliy of accidenal operaion. MITSUBISHI
2-15 2.5 EXTERNAL COMMUNICATION CONNECTOR Thi i an RS232C por for DiamondLink * monioring ofware. The layou of connecor i hown in Figure 2.13. FIGURE 2.13 Exernal communicaion connecor (NEC Cla2) 6 7 8 9 D-SUB 9Pin (male) 1 2 3 4 5 PCB DPAU-81 CN26 Pin 1. Pin 2. RXD Pin 3. TXD Pin 4. Pin 5. GND Pin 6. Pin 7. Pin 8. Pin 9. : No ued : Receive daa : Tranmi daa : No ued : Signal ground : No ued : No ued : No ued : No ued * Conul MITSUBISHI POWER PRODUCTS, INC for deail on DiamondLink monioring ofware and i capabiliie. MITSUBISHI
3-1 3.0 INSTALLATION AND OPERATION 3.1 TRANSPORTATION AND INSTALLATION TABLE 3.1 How o ranpor and inall he yem Tranporaion Tranpor uni wih forklif. Carry wih overhead crane uing 4xM12 crew-eyebol. (No provided) Inallaion Uing he pre-drilled four hole in he UPS channel bae, anchor he uni uing appropriae hardware. (No provided) CAUTION : Do no ranpor in a horizonal poiion. Cabine mu be mainained uprigh wihin +/- 15 of he verical during handling. 3.2 INSTALLATION PROCEDURE A) Noe he load olerance of he floor Refer o Table 3.2 for li of UPS weigh. TABLE 3.2 Li of UPS weigh UPS Capaciy (kva) 80 100 150 225 Weigh (lb.) 880 880 1160 1230 B) Minimum clearance required for venilaion Righ ide 25 mm (1 inch) (no required when idecar are ued) Lef ide 25 mm (1 inch) (no required when idecar are ued) Back ide 0.0 mm (0 inch) Top ide 500 mm (20 inche) (for air flow) C) Space requiremen for rouine mainenance Allow for he following pace a he ime of inallaion. Fron 1000 mm (40 inche) Side 0.0 mm (0 inch) Back ide 0.0 mm (0 inch) Top ide 500 mm (20 inche) MITSUBISHI
3-2 D) Exernal Baery Supply Pleae refer o he following when inalling and mainaining baerie: 1. The cuomer hall refer o he baery manufacurer' inallaion manual for baery inallaion and mainenance inrucion. 2. The maximum permied faul curren from he remoe baery upply, and he DC volage raing of he baery upply over-curren proecive device are hown in Table 3.3. TABLE 3.3 Maximum Permied Faul Curren UPS Capaciy (kva) DC Volage Raing (V) Maximum Faul Curren Permied (A) 80 480 25,000 100 480 25,000 150 480 25,000 225 480 25,000 3.3 PROCEDURE FOR CABLE CONNECTIONS * 1. Confirm he capaciy of he UPS being inalled. Idenify he inpu/oupu power erminal block a hown in he appropriae Figure 3.1 hrough 3.3. 2. Connec he inernal conrol wire and power wire. (1) Conrol wire Iner-connec 1. CB2 UVT o erminal TN1-1, 2 of exernal I/F PCB IOAU-09. 2. CB2 ON Auxiliary o erminal TN1-3, 4 of exernal I/F PCB IOAU-09. (2) Power wire (AC inpu, Bypa inpu, AC oupu) Iner-connec a.) From uer diribuion panel 1. X1 (A-phae) o A bu bar in UPS 2. X2 (B-phae) o B bu bar in UPS 3. X3 (C-phae) o C bu bar in UPS b.) DC Inpu o UPS 1. Poiive cable o BP bu bar in UPS 2. Negaive cable o BN bu bar in UPS MITSUBISHI
3-3 CAUTION : Afer he compleion of he inpu power cable connecion: Wih a phae roaion meer, check ha he phae roaion of he AC Inpu power erminal A, B and C a well a he Bypa Inpu power erminal A40, B40 and C40 are correc. The proper phae roaion i clockwie A B C. 3. Connec he grounding conducor from he inpu ervice enrance o he UPS Ground Bar (E). 4. Two (2) ource feeding he UPS: (1) Connec he AC inpu power cable from he inpu ervice enrance o he AC inpu power erminal, idenified a A, B, C in Figure 3.1 o 3.3. Inpu cable mu be ized for an ampere raing larger han he maximum inpu drawn by he converer. (Refer o equipmen nameplae for curren raing.) Confirm ha an exernal bypa inpu circui breaker (MCCB) i inalled (refer o WARNING 4, page 1-4). Connec he bypa inpu power cable from he inpu ervice enrance o he bypa inpu power erminal, idenified a A40, B40 and C40 in Figure 3.1 o 3.3. Bypa inpu cable mu be ized for an ampere raing larger han he maximum oupu curren capaciy of he UPS. Refer o Table 3.4 for recommended cable ize. (2) Connec he exernal ignal erminal block a deired. Refer o ecion 2.4 and Figure 2.10 for funcional decripion. 2mm 2, or le, hielded conducor i recommended. 5. One (1) ource feeding he UPS: (1) Confirm ha an exernal inpu circui breaker ized o proec boh he AC inpu and he bypa line i inalled. (Refer o equipmen nameplae for curren raing.) Connec he bypa inpu power cable from he inpu ervice enrance o he bypa inpu power erminal, idenified a A40, B40 and C40 in Figure 3.1 o 3.3. Inpu cable mu be ized for an ampere raing larger han he maximum curren capaciy of he UPS. Refer o Table 3.4 for recommended cable ize. (2) Uing adequaely ized conducor and referring o he appropriae figure idenified in Figure 3.1 o 3.3, connec jumper bypa erminal A40, B40, C40 o AC inpu power erminal A, B, C a idenified in Figure 3.1 o 3.3. MITSUBISHI
3-4 (3) Connec he exernal ignal erminal block a deired. Refer o ecion 2.4 and Figure 2.10 for funcional decripion. 2mm 2, or le, hielded conducor i recommended. CAUTION : 1. Confirm ha all UPS inernal conacor (breaker) "CB1", "CB2", and "CB3" are open before energizing UPS. 2. UPS power erminal are upplied wih ud ype fiing. I i recommended ha compreion lug be ued o faen all inpu/oupu power cable. 6. Procedure for Cable Connecion for Parallel Operaion Syem (1) Confirm he number of uni o be conneced in parallel. Idenify he inpu/oupu power erminal block and conrol wire connecion for parallel operaion yem a hown in he appropriae Figure 3.4 and 3.5. (2) Connec he exernal conrol wire and power wire. a.) Conrol wire connecion Parallel configuraion wiring (Refer o Figure 3.4 and 3.5.) - 52L conrol ignal from Criical Load Cabine (CLC) o UPS-n IOAU-09 (TN1 5, 6). - Parallel conrol ignal for CN94 a hown in Fig. 3.5. - Parallel conrol ignal for CN96 and CN95 a hown in Fig. 3.5. b.) Power wire connecion From UPS AC Oupu Terminal o Criical Load Cabine (CLC) (Refer o Figure 3.4 and 3.5.) MITSUBISHI
3-5 TABLE 3.4 kva Inpu Oupu Capaciy Volage Volage 80kVA 480V 480V 100kVA 480V 480V 150kVA 480V 480V 225kVA 480V 480V Recommended Cable Size Cable Size 1/0 AWG 2/0 AWG 1 AWG by 2 3/0 AWG by 2 Inpu Side Oupu Side Bypa Side DC Inpu Side Torque in. lb 100-135 in. lb 100-135 in. lb 100-135 in. lb 100-135 in. lb Cable Size 1/0 AWG 2/0 AWG 1 AWG by 2 3/0 AWG by 2 Torque in. lb 100-135 in. lb 100-135 in. lb 100-135 in. lb 100-135 in. lb Cable Size 1/0 AWG 2/0 AWG 1 AWG by 2 3/0 AWG by 2 Torque in. lb 100-135 in. lb 100-135 in. lb 100-135 in. lb 100-135 in. lb Cable Size 2/0 AWG 3/0 AWG 2/0 AWG by 2 250MCM by 2 Torque in. lb 100-135 in. lb 100-135 in. lb 100-135 in. lb 100-135 in. lb *1 - The cable mu be eleced o be equal o he ize lied in he able. *2 - Volage drop acro power cable no o exceed 2% of nominal ource volage. *3 - Allowable ampere-capaciie baed on 75 degree C. inulaion a ambien emperaure of 40 degree C. Noe: Copper conducor aumed. MITSUBISHI
3-6 TABLE 3.5 I 1/0 B Crimp Type Compreion Lug WIRE SIZE WIRE STRAND RECOMMENDATION CRIMP TOOL REQUIRED BURNDY TYPE Y35 OR Y46 (CODE) CLASS VENDOR CAT. NO. COLOR KEY DIE INDEX 1 B BURNDY YA1C GREEN 11 / 375 ILSCO CRA-1L GREEN 11 / 375 BURNDY YA25-LB --- 1019 I 2/0 B I 3/0 B I 4/0 B I 250 MCM B I 300 MCM B I 350 MCM B I 400 MCM B I 500 MCM B NOTE: I BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY YA25 CRA-1/OL YA25-LB YA26 CRA-2/OL YA27-LB YA27 CRB-3/OL YA28-LB YA28 CRB-4/OL YA29-LB YA29 CRA-250L YA30-LB YA30 CRA-300L YA32-LB YA31 CRA-350L YA34-LB YA32 CRA-400L YA36-LB YA34 CRA-500L YA38-LB PINK PINK --- BLACK BLACK --- ORANGE ORANGE --- PURPLE PURPLE --- YELLOW YELLOW --- WHITE WHITE --- RED RED --- BLUE BLUE --- BROWN BROWN --- 12 / 348 12 / 348 1020 13 13 1021 14 / 101 14 / 101 1022 15 15 1023 16 16 1024 17 / 298 17 / 298 1026 18 / 324 18 / 324 1027 19 / 470 19 / 470 1027 20 / 299 20 / 299 1029 When uing crimp ype lug, he lug hould be crimped o he pecificaion given in he manufacurer' inrucion for boh crimp ool and lug. FIGURE 3.1 UPS Terminal Deignaion Bypa inpu AC inpu Terminal A40 B40 C40 Terminal A B C CB1 52S Saic Tranfer Swich CB3 CONVERTER / CHARGER INVERTER 52C Oupu Terminal A50 B50 C50 Terminal BP BN CB2 Exernal BATTERY MITSUBISHI
3-7 FIGURE 3.2 Diagram of inpu/oupu bu bar and erminal block Locaion of bu bar and erminal block (Boom enry) H=80.6 (2047mm) D=32.8 (832mm) Deailed Power Terminal For power erminal, ue 1/2 (12mm) Diameer bol. 80kVA o 100kVA : 35.4 (900mm) 150kVA o 225kVA : 27.6 (700mm) UPS module Exernal Block IOAU-09 AC Inpu DC Inpu Bypa Inpu AC Oupu AC Inpu A,B,C AC Oupu A50,B50,C50 A C BN B40 B BP A40 C40 A50 B50 C50 Grounding Bar (E) UPS module Baery Inpu BN,BP Bypa Inpu A40,B40,C40 MITSUBISHI
3-8 FIGURE 3.3 Diagram of Power Wire & Conrol Wire Iner-Connec beween UPS and Baery 500kVA MITSUBISHI
3-9 FIGURE 3.4 Diagram of Power Wire Connec ( Parallel Operaion yem connecion ) CRITICAL LOAD CABINET SMB Bypa inpu UPS-1 Bypa 52S AC inpu CB1 Converer /Charger Inverer AC oupu 52L 52C Bypa inpu AC inpu UPS-2 Bypa CB1 CB2 Converer /Charger Baery Inverer 52S AC oupu 52L 2 52L 52C CB2 Baery Bypa inpu UPS-n*1 Bypa 52S AC inpu CB1 Converer /Charger Inverer AC oupu 52L n *1 52C CB2 Baery MITSUBISHI *1 n : Maximum = 4
3-10 FIGURE 3.5 Diagram of Power Wire & Conrol Wire Connec ( Parallel Operaion yem connecion ) 5 6 IOAU-09 TN1 UPS-1 5 6 IOAU-09 TN1 UPS-2 5 6 IOAU-09 TN1 *1 UPS-n Criical Load Cabine *3 *3 *3 IFAU-08 ON IFAU-08 OFF IFAU-08 ON TLIN TLOUT CBIN CAIN TLIN TLOUT CBIN CAIN TLIN TLOUT CBIN CAIN CN96 CN95 CBOUT CAOUT CN96 CN95 CBOUT CAOUT CN96 CN95 CBOUT CAOUT 1 8 1 8 CN94 CN94 CN94 UPS-3 CN96 (TLIN) 1 8 35 36 37 38... 49 50... 52L1-AX 52L2-AX *1 52Ln-AX UPS-3 CN94 (CAIN) *2 Ue Eherne STP (Shielded Twied Pair) Cable for all communicaion cabling. Ue of UTP (Unhielded Twied Pair) Cable may caue malfuncion. Toal cable lengh from UPS-1 o UPS-n hould be wihin 100m. UPS-3 CN94 (CBIN) UPS-(n-1) CN96 (TLOUT) UPS-(n-1) CN94 (CAOUT) UPS-(n-1) CN94 (CBOUT) *1 n : Maximum = 4 *2 Reurn from he la UPS module o he fir UPS module (coninuou loop). *3 DIP wich poiion UPS-1 and UPS-n : ON Oherwie : OFF AC OUTPUT UPS-1 A B C UPS-2 A B C AC OUTPUT A50 B50 C50 AC OUTPUT A50 B50 C50 AC OUTPUT A50 B50 C50 UPS-n*1 A B C MITSUBISHI
3-11 3.4 OPERATING PROCEDURES For Parallel Operaion yem, refer o ecion D) MMS Sar-up Procedure. (Parallel Operaion yem i herein afer MMS [Muli Module Syem]) A) Sar-up Procedure CAUTION : Before he UPS arup, he inernal Bypa line ar o upply he uncondiioned bypa inpu power o he criical load if he Exernal inpu (or Bypa) Circui Breaker i cloed. Be exremely careful wih cloing he Exernal inpu (or Bypa) Circui Breaker. a.) Verify ha he Exernal Bypa Inpu Circui Breaker for each uni i cloed. (uer upplied) b.) Verify ha Baery Diconnec Circui Breaker (CB2) i opened or in ripping poiion. c.) If a dual ource i feeding he UPS, cloe he Exernal AC Inpu Circui Breaker manually (uer upplied). d.) The LCD panel boo up auomaically, and he creen will how ha he Load i powered by bypa line. e.) On he LCD panel, elec OPERATION ab, and hen pre he STARTUP GUIDANCE buon o proceed wih UPS ar-up. (Refer o Figure 2.3) f.) Follow he STARTUP GUIDANCE accordingly unil he compleion of he inverer arup. Noe: When "REMOTE OPERATION MODE" i diplayed on he LCD panel, he inverer ar operaion can only be performed remoely. If local inverer ar operaion i required (a he UPS), elec "LOCAL ONLY" or REMOTE & LOCAL in he OPERATION MENU. MITSUBISHI
3-12 B) Shu-down Procedure If a oal UPS hudown i required, verify ha he criical load i OFF. a.) Pre he "START/STOP" icon from he Main Menu or he Operaion Menu on he LCD. b.) On he LCD panel, pre START/STOP icon, and hen elec SHUTDOWN GUIDANCE icon. (Refer o Figure 2.3) c.) Follow he SHUTDOWN GUIDANCE accordingly unil Inverer op. However UPS will imulaneouly ranfer he power feeding from he Inverer upply o he Bypa line upply. d.) In general, only he Inverer will be opped and he Converer will remain energized o charge he baerie. Noe: When "REMOTE OPERATION MODE" i diplayed on he LCD panel, he inverer ar operaion can only be performed remoely. If local inverer op operaion i required (a he UPS), elec "LOCAL ONLY" or REMOTE & LOCAL in he OPERATION MENU. e.) If opping boh he Inverer and Converer i required, open he Baery Diconnec circui breaker (CB2) manually in accordance wih guidance. WARNING : Verify he load i OFF if he nex ep i o be performed. NOTE : Power o he criical load i upplied hrough he bypa line. Power o he criical load will be lo afer execuion of he nex ep. The load will drop. f.) If a dual ource i feeding he UPS, open he Exernal AC Inpu Circui Breaker (uer upplied) manually. g.) If urning off all power o he criical load i deired, open he Exernal Bypa Inpu Circui Breaker (uer upplied) manually. CAUTION : In bypa mode, all UPS power erminal are ill live. Lehal volage are preen. De-energize all exernal ource of AC and DC power. Before removing he cover, wai 5 minue afer de-energizing. Check no-volage before handling UPS. Be careful for he device even when he UPS ha been de-energized, ill inernal device may be ho. MITSUBISHI
3-13 C) Bypa Operaion Procedure ** Tranfer from Inverer o Bypa 1. Check for SYNC on he LCD. 2. Pre he "START/STOP icon on he LCD. 3. Follow he SHUTDOWN GUIDANCE and Pre he "STOP" icon on he LCD. ** Tranfer from bypa o inverer. UPS 1. Pre he "START/STOP" icon on he LCD. 2. Follow he STARTUP GUIDANCE and Pre he "START" icon on he LCD.. Noe: When "REMOTE OPERATION MODE" i diplayed on he LCD panel, he inverer ar operaion can only be performed remoely. If local inverer ar or op operaion i required (a he UPS), elec "LOCAL ONLY" or REMOTE & LOCAL in he OPERATION MENU. MITSUBISHI
3-14 D) MMS Sar-up Procedure Exernal Circui Check 1. Verify ha Criical Load Cabine (CLC) Circui Breaker SMB i cloed. 2. Verify ha CLC Syem Oupu Circui Breaker 52L i open. 3. Verify ha CLC UPS Circui Breaker 52L1, 52L2 and 52Ln are cloed. Sar-up from UPS-1 o UPS-n 1. Sar-up each UPS in accordance wih A) Sar-up Procedure. Each UPS will ar Inverer Operaion in ynchronizaion wih he bypa inpu. Tranfer from Mainenance Bypa o MMS Bypa Operaion 1. Cloed he CLC Syem Oupu Circui Breaker 52L. 2. Open he CLC Circui Breaker SMB. Noe: When "REMOTE OPERATION MODE" i diplayed on he LCD panel, he inverer ar operaion can only be performed remoely. If local inverer ar operaion i required (a he UPS), elec "LOCAL ONLY" or REMOTE & LOCAL in he OPERATION MENU. Tranfer from UPS MMS Bypa Operaion To UPS MMS Inverer Operaion 1. Tranfer MMS Bypa Operaion o MMS Inverer Operaion from Operaion Menu on any UPS LCD a hown in Fig. 3.6. FIGURE 3.6 LCD Screen (MMS Operaion) Tranfer from UPS MMS Inverer Operaion To UPS MMS Bypa Operaion 1. Tranfer MMS Inverer Operaion o MMS Bypa Operaion from Operaion Menu on any UPS LCD a hown in Fig. 3.6. MITSUBISHI
4-1 4.0 RESPONSE TO UPS FAILURE UPS FAULT Annunciaor Silence Depre SILENCE ALARM icon on Main Menu. Recording of Faul Refer o he li of faul code in ecion 6.0 for error decripion. Primary Acion Take neceary acion according o diplay guidance. Informaion o Service Cener When faul happen, conac he Auhorized Miubihi Service Repreenaive or call Miubihi a 1-800-887-7830. Noe The error code indicaed on he LCD diplay panel when an UPS alarm i very imporan. In order o reduce repair ime, pleae include hi informaion, along wih he operaion and load au for all correpondence o Miubihi field ervice group. MITSUBISHI
5-1 5.0 PARTS REPLACEMENT Conac Miubihi Elecric Power Produc, Inc.or i auhorized ervice repreenaive on all iue regarding he replacemen of par. A) Baery Baery lifeime may vary according o he frequency of ue and he average ambien operaing emperaure. The end of baery life i defined a he ae of charge reuling in an ampere-hour capaciy le han, or equal o, 80% of nominal capaciy. Replace baery if i capaciy i wihin hi percenage. B) UPS Componen Par UPS componen have a defined life expecancy (Fan, Capacior, Filer, ec). Conac Miubihi Elecric Power Produc, Inc. or i auhorized ervice repreenaive for a complee par replacemen chedule. Recommended replacemen ime inerval varie wih operaing environmen. Conac Miubihi Elecric Power Produc, Inc. or i auhorized ervice repreenaive for applicaion pecific recommendaion. NOTE : Any par replacemen (including modificaion) wihou auhorized by Miubihi could reul in peronal injurie, deah or derucion of he UPS. MITSUBISHI
6-1 6.0 FAULT CODES Thi ecion cover faul code, heir decripion and required acion. A ime of error : A) Verify and record he occurrence of he alarm. Noe deail of alarm meage diplayed on he LCD diplay panel. Conac Miubihi Elecric Power Produc, Inc. a 1-800-887-7830. B) If a circui breaker (MCCB) ha ripped, depre he oggle o ree he breaker before cloing i again. MITSUBISHI
6-2 Failure Code Li Table 6.1 Faul Code Noe 3 Noe 1 Noe 2 Code indicaion Sau meage Meaning Guidance Buzzer Exernal relay conac Failure lamp UA801 AC INPUT VOLTAGE OUT OF RANGE Inpu line volage i ou of he pecified range. CHECK INPUT POWER SOURCE Alarm AC inpu abnormal - UA802 AC INPUT FREQUENCY OUT OF RANGE Inpu line frequency i ou of he pecified range. CHECK INPUT POWER SOURCE Alarm AC inpu abnormal - UA803 AC INPUT PHASE ROTATION ERROR Inpu line power conducor are no wired in a proper phae equence. CHECK INPUT POWER SOURCE Alarm AC inpu abnormal - UA804 UA805 UA806 UA807 UA808 UA810 CONVERTER OPE. PROHIBITION INVERTER OVERLOAD INVERTER OVERLOAD INVERTER OVERLOAD INVERTER OVERLOAD INVERTER OVERLOAD The converer inerlock i acive. The oupu load curren ha exceeded 105% of he raed curren. The oupu load curren ha exceeded 110% of he raed curren. The oupu load curren ha exceeded 125% of he raed curren. The oupu load curren ha exceeded 150% of he raed curren. Shor ime over-curren ha been deeced during he inverer operaion. - WARNING : DECREASE LOAD WARNING : DECREASE LOAD WARNING : DECREASE LOAD WARNING : DECREASE LOAD WARNING : DECREASE LOAD Alarm Alarm Overload Alarm Overload Alarm Overload Alarm Overload Alarm Overload - - - - - - UA812 BYPASS VOLTAGE OUT OF RANGE Bypa line volage i ou of he pecified range. CHECK BYPASS INPUT Alarm Bypa inpu abnormal - UA813 BYPASS PHASE ROTATION ERROR Bypa line power conducor are no wired in a proper phae equence. CHECK BYPASS INPUT Alarm Bypa inpu abnormal - UA814 BYPASS FREQUENCY OUT OF RANGE Bypa line frequency i ou of he pecified range. CHECK BYPASS INPUT Alarm Bypa inpu abnormal - UA815 UA817 TRANSFER PROHIBITION EMERGENCY STOP ACTIVATED Tranfer o he bypa i no available due o bypa abnormaliy. The emergency op wa acivaed by he EPO wich or an exernal conac. - Alarm - - Alarm - - MITSUBISHI
6-3 Noe 3 Noe 1 Noe 2 Exernal Code Sau Failure Meaning Guidance Buzzer relay indicaion meage lamp conac UA821 UA822 UA824 UA827 UA831 UA833 UA834 UA835 UA860 UA861 UA870 UA890 UF001 UF002 UF003 UF011 UF052 UF056 UF059 UF102 TRANSFER PROHIBITION TRANSFER PROHIBITION CB2 OPEN 52C OPE. PROHIBITION EMERGENCY BYPASS SWITCH ON 52L OPEN BATTERY DEPLETED/A C OUT STOPPED TRANSFER PROHIBITION REMOTE BUTTON ABNORMAL LOCAL BUTTON ABNORMAL BALANCER OVERLOAD EXTERNAL ALARM INPUT CIRCUIT ABNORMAL CONVERTER OVERCURRE NT CONVERTER ABNORMAL CB1 ABNORMAL CB1 ABNORMAL CONVERTER OVERCURRE NT INPUT CIRCUIT ABNORMAL DC OVERVOLTAG E The UPS could no ranfer o he bypa becaue he inverer oupu wa no ynchronized o he bypa. The UPS could no ranfer o he bypa becaue of backup generaor operaion. The baery circui breaker (CB2) i open. The inerlock for he inverer oupu conacor (52C) i acive. Emergency bypa wich ha been urned on. The load circui breaker(52l) i urned off. The baery volage ha reached he depleed level. The UPS could no ranfer o he bypa becaue he bypa ource ha an abnormaliy. Remoe ar or op ignal i being received coninuouly for a coniderable ime. Local ar or op ignal i being received coninuouly for a coniderable ime. The UPS deeced an neural poin volage unbalance. Exernal Alarm relay urned on. Deecion of a large variaion of he reference error ignal. Deecion of converer overcurren. Pre-charging circui i no working properly. dicrepancy beween reference ignal and acual ae of conacor CB1. Minor dicrepancy beween reference ignal and acual ae of conacor CB1. Deecion of converer overcurren. Deecion of a large variaion of he reference error ignal. DC volage urpae he overvolage level. - - Alarm - - - Alarm - TURN ON CB2 - - - - - Alarm Alarm Alarm Alarm End-of- Dicharge - - - - Li on - - Alarm - - - - - Coninuou Coninuou Coninuou Coninuou Coninuou Alarm Alarm Alarm Overload Alarm Minor Minor Minor - - - - Li on Li on Li on Li on Flicker Flicker Flicker Li on MITSUBISHI
6-4 UF103 UF108 DC UNDERVOLTA GE CHOPPER OVERCURRE NT DC volage dropped below he undervolage level. Deecion of DC overcurren. Coninuou Coninuou Li on Li on Noe 3 Noe 1 Noe 2 Exernal Code Sau Failure Meaning Guidance Buzzer relay indicaion meage lamp conac UF109 UF110 UF111 UF112 UF119 UF128 UF151 UF152 UF154 DC UNBALANCED ZERO PHASE OVERCURRE NT UPS CONTROL CIRCUIT ERROR DC CIRCUIT ABNORMAL DC GROUND FAULT CONTROL POWER SUPPLY ABNORMAL DC VOLTAGE ABNORMAL DC VOLTAGE ABNORMAL CB2 ABNORMAL unbalance of he neural poin volage. Deecion of converer zero-equence overcurren. Baery curren unbalance. Sudden change of he DC volage level. Deecion of DC ground faul. Power upply volage o IGBT driver PCB i below he pecified level. 24 hour afer inpu power reoraion, baerie doe no reach floa volage level. Unable o equalize he volage of variou baerie afer 24 hour. During UVT, au ignal from CB2 i ON. Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Minor Minor Minor Li on Li on Li on Li on Li on Li on Flicker Flicker Flicker UF156 CHG.STOPPE D(BATTERY OVERTEMP.) UF157 failure peried for over 2 hour. CHECK BATTERY Minor Baery abnormal Flicker UF157 BATTERY OVERTEMPE RATURE Deecion of overemperaure a he baerie. CHECK BATTERY Minor Baery abnormal Flicker UF158 BATTERY LIQUID LOW Low level of baery elecrolye oluion. CHECK BATTERY Minor Baery abnormal Flicker UF159 UF160 UF161 UF162 DC GROUND FAULT UPS CONTROL CIRCUIT ERROR CHG.STOPPE D(DC VOLT. ABNORMAL) BATTERY ABNORMAL Deecion of DC ground faul. Abnormal behavior of DC curren enor. UF151 failure i running for over 24 hour. Failure deecion baed on baery elf-check. Minor Minor Minor Minor Flicker Flicker Flicker Flicker MITSUBISHI
6-5 UF163 UF170 UF201 BATTERY VOLTAGE ABNORMAL VDB SENSOR ABNORMAL INVERTER OVERVOLTAG E Baery volage i abnormaliy. Deecion of a large variaion of he difference beween conrol-only and proecion-only baery volage. Deecion of oupu overvolage. Coninuou Minor Minor Flicker Flicker Li on Noe 3 Noe 1 Noe 2 Exernal Code Sau Failure Meaning Guidance Buzzer relay indicaion meage lamp conac UF202 UF203 UF204 UF206 UF207 UF208 UF209 UF210 UF211 UF213 UF214 UF217 UF230 UF253 UF256 UF257 INVERTER UNDERVOLTA GE INVERTER OVERCURRE NT OUTPUT CIRCUIT ABNORMAL UPS CONTROL CIRCUIT ERROR ZERO PHASE OVERCURRE NT UPS CONTROL CIRCUIT ERROR 52C ABNORMAL 52C ABNORMAL 52C ABNORMAL OVERTEMPE RATURE COOLING FAN ABNORMAL INVERTER OVERVOLTAG E ZERO PHASE OVERCURRE NT UPS CONTROL CIRCUIT ERROR OUTPUT VOLTAGE ABNORMAL 52C ABNORMAL Oupu volage dropped. Deecion of inverer overcurren. Deecion of a large variaion of he reference error ignal (curren reference and acual curren). Dicrepancy beween oupu volage and exernal volage (bypa, common ac bu) Inverer zero-equence overcurren. Cro curren i abnormaliy. Error o cloe he conacor 52C. Error o open he conacor 52C. No anwer from conacor 52C during inverer operaion. Heaink emperaure exceed hermal eing. Thermal relay acivaed proecion. Deecion of inverer oupu phae overvolage. Deecion of zero-equence overcurren. Dicrepancy beween oupu volage and inverer volage, or beween oupu volage and bypa volage. Oupu volage i ou of he pecified range. Conacor 52C failed o open during load ranfer from inverer o bypa. Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Minor Minor Minor Li on Li on Li on Li on Li on Li on Li on Li on Li on Li on Li on Li on Li on Flicker Flicker Flicker MITSUBISHI
6-6 UF258 UF259 UF301 UF302 LOAD ABNORMAL ANOTHER UPS ABNORMAL UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR Load ranfer due o overload for over 4 ime wihin 5 minue. No deecion of anoher UPS volage ignal. AD reference ha an abnormal value. Deecion of an exernal inerrupion during he ofware execuion. Coninuou Coninuou Minor Minor Flicker Flicker Li on Li on Noe 3 Noe 1 Noe 2 Exernal Code Sau Failure Meaning Guidance Buzzer relay indicaion meage lamp conac UF303 UF305 UF306 UF309 UF310 UF320 UF323 UF352 UF363 UF371 UF372 UF374 UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR INVERTER VOLTAGE ABNORMAL CONTROL POWER SUPPLY ABNORMAL UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR CONTROL POWER SUPPLY ABNORMAL UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT Timer doe no ree in he pecified period (WDT eing) Deecion of an abnormal clock peed in he DSP or FPGA. Conrol power upply volage are below he pecified level. Inverer volage i ou of he pecified range. Backup conrol power upplie exhibi abnormal condiion. Cable diconnecion in he parallel inerface board during load upply. communicaion error during parallel operaion. Backup conrol power upplie exhibi abnormal condiion. Synchronizaion au ignal i being received for a coniderable ime. Minor communicaion error during parallel operaion. Unable o ynchronize he inverer oupu and he bypa volage. Cable diconnecion in he parallel inerface board. Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Coninuou Minor Minor Minor Minor Minor Li on Li on Li on Li on Li on Li on Li on Flicker Flicker Flicker Flicker Flicker MITSUBISHI
6-7 ERROR UF375 UF376 UF377 UF378 UF379 UF401 UF402 UF420 UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR 52S ABNORMAL 52S ABNORMAL 52L OPERATION ERROR Unable o achieve ynchronizaion for parallel operaion. No conrol repone from anoher UPS alhough i deecion i poible. Overload deecion ignal i being received coninuouly for a coniderable ime. No anwer for ending ynchronizing ignal. Abnormal clock peed of he parallel conrol board proceor. Error o cloe he conacor 52S. Error o open he conacor 52S. Load circui breaker 52L opened during inverer operaion. CHECK 52L Coninuou Coninuou Coninuou Minor Minor Minor Minor Minor Flicker Flicker Flicker Flicker Flicker Li on Li on Li on Noe 3 Noe 1 Noe 2 Exernal Code Sau Failure Meaning Guidance Buzzer relay indicaion meage lamp conac UF451 UF452 52S ABNORMAL CB3 ABNORMAL Conacor 52S failed during load ranfer from inverer o bypa. Conacor CB3 i no working properly. Minor Minor Flicker Flicker MITSUBISHI
6-8 (Noe 1) 1) "" i defined a major failure. Inverer ranferred o he aic bypa line; 2) "Minor" i defined a a minor failure. UPS coninue o operae normally, bu caue of alarm mu be idenified; (Noe 2) Indicae one of wo poible LED illuminaion paern - coninuouly on (li on) or inermien (flicker). (Noe 3) Code indicaion mean: UA+++ --------------------- UF+++---------------------- U%0++--------------------- U%1++--------------------- U%2++--------------------- U%3++--------------------- U%4++--------------------- U%8++--------------------- U%+00 - U%+49 ------- U%+50 - U%+99 ------- Alarm Failure Recifier circui failure DC circui failure Inverer circui failure Conrol circui failure Bypa yem failure Alarm failure Minor failure *) + denoe any numeral from 0 o 9 *) % denoe eiher A or F MITSUBISHI
7-1 7.0 WARRANTY & OUT OF WARRANTY The Miubihi Elecric UPS Diviion Service Deparmen ha many Auhorized Service Cener place raegically hroughou he US, Canada and Lain America. For boh in warrany and ou of warrany ervice, pleae conac Miubihi Elecric Power Produc, Inc. a (724) 772-2555. To regier your UPS for warrany purpoe, pleae complee he warrany regiraion form and fax i o he Miubihi Elecric UPS Diviion Service Deparmen fax line hown on he regiraion form. (Nex page) For warrany purpoe, i i eenial ha any and all ervice work ha may be required on your Miubihi brand UPS equipmen i performed by a Miubihi Elecric Auhorized Service Cener. The ue of non-auhorized ervice provider may void your warrany. Miubihi Elecric Power Produc, Inc UPS Diviion Service Deparmen 530 Keyone Drive, Warrendale, PA 15086, USA Phone: (724) 772-2555 Fax: (724) 778-3146 MITSUBISHI
7-2 Miubihi Elecric Power Produc, Inc. UNINTERRUPTIBLE POWER SUPPLIES 530 Keyone Drive, Warrendale, PA 15086 Phone: (724) 772-2555, Fax: (724) 778-3146 UPS Warrany Regiraion Regier UPS for Warrany Addre Change To validae he Warrany on your UPS hi form mu be filled ou compleely by Cuomer and reurned. Your Name: CUSTOMER INFORMATION Job Tile: Company Name: Diviion / Deparmen: Addre: Ciy: Sae: Zip Code: Counry: Province: Buine Phone: Ex: Fax: E-Mail: Inerne Addre: @ UPS Model #: Capaciy (kva): UPS Serial #: Sar-Up Dae: Signaure: / / Auhorized Miubihi Service Company (if known): Dae: / / Which ONE of Thee Be Decribe Your Organizaion Primary Buine Claificaion? Number of Employee a Thi Locaion i: {Energy Producer} Educaion/Univ. Service 1 19 100-249 1000 or more Uiliy {Service} 20 49 250-499 Alernae Energy Conuling 50 99 500-999 {Manufacuring Co.} Engineering OEM Ouourcing Overall how wa Sar-Up performed: Proce Financial/Legal/Inurance Unaifacory Saifacory Exceeded {Expecaion} Conumer Good {Governmen} Elecronic Miliary Would you like o receive fuure produc updae and Power Qualiy Equipmen Municipal new? Commercial Buine Federal/Sae/Local Ye No Elecrical Conracor Healhcare Inerne Communicaion Diribuor/Rep Oher Afer Sar-Up ha been done Fax compleed Form o: (724) 778-3146 MITSUBISHI