9900B SERIES OWNER S / TECHNICAL MANUAL (Inclusive Parallel Operation System Application)
|
|
|
- Mitchell Carpenter
- 9 years ago
- Views:
Transcription
1 UNINTERRUPTIBLE POWER SUPPLY SYSTEM MODEL 9900B SERIES OWNER S / TECHNICAL MANUAL (Inclusive Parallel Operation System Application)
2 Preface Revision F 04/07/2014 4GBA0009
3 i TABLE OF CONTENTS LIST OF TABLES... ii LIST OF FIGURES... iii HOW TO USE THIS MANUAL... iv 1.0 INTRODUCTION SAFETY PRECAUTION GENERAL DEFINITIONS OPERATION OVERVIEW SPECIFICATIONS OPERATION CONTROLS AND INDICATORS LED DISPLAY EPO BUTTON LIQUID CRYSTAL DISPLAY EXTERNAL SIGNAL TERMINAL BLOCK EXTERNAL COMMUNICATION CONNECTOR INSTALLATION AND OPERATION TRANSPORTATION AND INSTALLATION INSTALLATION PROCEDURE PROCEDURE FOR CABLE CONNECTIONS OPERATING PROCEDURES RESPONSE TO UPS FAILURE PARTS REPLACEMENT FAULT CODES WARRANTY & OUT OF WARRANTY MITSUBISHI
4 ii LIST OF TABLES Table 1.1 UPS Installation Environment Table 1.2 Rating of Bypass Input Circuit Breaker Table 1.3 Power Specifications Table 1.4 UPS Module Information Table 1.5 Detail of Specifications Table 1.6 Rating of Contactors, Breakers and Fuses Table 3.1 How to Transport and Install the System Table 3.2 List of UPS Weights Table 3.3 Maximum Permitted Fault Current Table 3.4 Recommended Cable Sizes Table 3.5 Recommended Hardware Table 3.6 Crimp Type Compression Lug Table 6.1 Fault Code List MITSUBISHI
5 iii LIST OF FIGURES Figure 1.1 Single Line Diagram- Normal Operation: Load powered by UPS inverter Figure 1.2 Single Line Diagram- Bypass Operation: Load Fed through static bypass line Figure 1.3 Single Line Diagram-Battery Operation Figure 1.4 UPS Parts Location Figure 1.5 Display PCB DPAU Figure 1.6 External I/F PCB IOAU Figure 1.7 Parallel I/F PCB IFAU Figure 1.8 MAIN PCB UPGR-M Figure 2.1 Operation/Display Panel Figure 2.2 Main Screen Figure 2.3(a) Startup/Shutdown guidance Figure 2.3(b) Startup guidance Figure 2.3(c) Shutdown guidance Figure 2.4(a) Input values Figure 2.4(b) Output values Figure 2.4(c) Measurement during battery operation Figure 2.5(a) Remote/Local operation select Figure 2.5(b) Date & Time adjustment Figure 2.6(a) Log menu Figure 2.6(b) Event log Figure 2.6(c) Battery log Figure 2.7(a) Main Screen (Battery Operation) Figure 2.7(b) Measurement Screen (Battery Operation) Figure 2.8 Main Screen (Fault Indication) Figure 2.9 Message Screen Figure 2.10(a) External Signal Terminal Block (TN2) Figure 2.10(b) External Signal Terminal Block (TN1) Figure 2.11 Control Wiring for External Contacts Figure 2.12 Remote "Start" Contact Connections Figure 2.13 External communication connector Figure 3.1 UPS Terminal Designation Figure 3.2 Diagram of input/output bus bars and terminal blocks Figure 3.3 Diagram of power wire and control wire interconnection between UPS and battery Figure 3.4 Diagram of power wire connect (Parallel Connection) Figure 3.5 Diagram of power and control wire Connect (Parallel Connection) Figure 3.6 LCD screen (MMS operation) MITSUBISHI
6 iv HOW TO USE THIS MANUAL This manual is designed for ease of use, giving the user easy and quick reference to information. This manual uses notice icons to draw attention to the user important information regarding the safe operation and installation of the UPS. The notice icons used in this manual are explained below, and should be taken into account and adhered to whenever they appear in the text of this manual. Warning: A warning notice icon conveys information provided to protect the user and service personnel against hazards and/or possible equipment damage. Caution: A caution notice icon conveys information provided to protect the user and service personnel against possible equipment damage. Note: A Note notice icon indicates when the user should make a reference of information regarding the UPS operation, load status and display status. Such information is essential if Mitsubishi field service group assistance and correspondence is required. Safety Recommendations: If any problems are encountered while following this manual, Mitsubishi field service group assistance and correspondence is recommended. MITSUBISHI
7 INTRODUCTION The Mitsubishi Uninterruptible Power Supply System (UPS) is designed to provide many years of reliable protection from power failure, brown-outs, line noise, and voltage transients. To ensure optimum performance of the equipment, follow the manufacturer's instructions. This manual contains descriptions required to operate the UPS. Please read this manual carefully and retain it for future reference. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for the 9900B SERIES Uninterruptible Power Supply System that should be followed during installation and maintenance of the UPS and batteries. WARNING 1 Lethal voltages exist within the equipment during operation. Observe all warning and cautions in this manual. Failure to comply may result in serious injury or death. Obtain qualified service for this equipment as instructed. MITSUBISHI
8 1-2 WARNING 2 In no event will MITSUBISHI be responsible or liable for either indirect or consequential damage or injury that may come from the use of this equipment. Any modifications without authorization by MITSUBISHI could result in personal injuries, death or destruction of the UPS. 1.1 SAFETY PRECAUTIONS APPLICATION If the UPS System is to be applied to support equipment that could affect human safety, the following steps must be adhered to: 1. Consult with Mitsubishi Electric Power Products Inc. UPS Division. 2. Special consideration of the overall back up power system configuration is required so that the Mitsubishi UPS System is not the sole support required for operation, maintenance and management of power availability. Other available power sources; for example utility, emergency power generation or other systems shall also support power availability. Definition of equipment that could affect human safety: Life Support Systems (is a system whose failure to perform can be expected to result in bodily injury or death.) Essential Public Systems (is a system whose failure to perform can be expected to result in bodily injury or death and/or property damage.) MITSUBISHI
9 1-3 WARNING 3 The UPS is to be installed in a controlled environment. Improper storage and installation environment may deteriorate insulation, shorten component life and cause malfunctions. Keep the installation environment per standard described as follows: TABLE 1.1 UPS Installation Environment No. Item Environment standard 1 Installation Location Indoors 2 Ambient temperature 3 Relative humidity Minimum temperature: 32 F(0 C), Maximum temperature: 104 F(40 C) The average temperature over any 24-hour period must be in the range 41 F (5 C) to 95 F(35 C). The relative humidity must be held between 5 and 95%. There must be no condensation due to temperature changes. 4 Altitude This equipment must not be applied at altitude that exceeds 2250m(7400ft) above seal level. 5 Dust Dust in the room where the UPS is installed must not exceed normal atmospheric dust levels. In particular, that dust shoud not include iron particles, oils or fats, or organic materials such as silicone. 6 Inflammable gas following IEC654-4 Part 4 There should be no inflammable/explosive gas. Hydrogen sulfide (H 2 S) Sulfurous acid gas (SO 2 ) Chlorine gas (Cl 2 ) Ammonia gas (NH 3 ) Nitrous oxides (NO x ) Ozone (O 3 ) No more than PPM No more than 0.01 PPM No more than PPM No more than 1 PPM No more than 0.05 PPM No more than PPM MITSUBISHI
10 1-4 WARNING 4 This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass circuit. The Bypass input circuit breaker (MCCB) is to be field supplied and installed. Recommended Breaker (MCCB)'s Specifications are as follows: TABLE 1.2 Rating of Bypass Input Circuit Breaker Capacity (kva) Bypass Voltage (Vac) Bypass Rating (Aac) Breaker (A) AC input and AC output overcurrent protection and disconnect devices shall be field supplied and installed. The DC circuit breaker (MCCB) shall be field supplied and installed. The overcurrent protection device should be installed in the Battery cabinet and rated as indicated in TABLE 1.6. Note: The DC input overcurrent protection (Battery disconnect breaker) hereinafter will be referred as CB2. MITSUBISHI
11 GENERAL The Mitsubishi is designed to provide continuous and clean electrical power to a critical load. Additionally the UPS monitors power conditions affecting the load. In the event of an input power failure, the UPS will supply power to the critical load for the specified battery time. If the input power is not restored promptly, back up power from the UPS battery permits the orderly shutdown of equipment supported by the UPS. The UPS is simple to start-up, operate and maintain. The is available in 300, 500 and 750kVA. Specifications are shown in Section 1.5. The principles of operation described herein are applicable to all models. This manual provides an overview of the 9900B SERIES components and their functions. The appearance and purpose of operator controls and indicators is described with procedures for operation, start-up, shutdown and basic maintenance included. MITSUBISHI
12 DEFINITIONS UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All components within the UPS Module Cabinet and associated batteries that function as a system to provide continuous, conditioned AC power to a load. This is sometimes referred to as the "System". UPS MODULE CABINET - The metal enclosure which contains the Converter / Charger, Inverter, Static Transfer Switch, Internal Bypass line, operator controls, and internal control systems required to provide specified AC power to a load. UPS MODULE - The Converter / Charger and Inverter assemblies which, under the direction of the internal control system and operator controls, provide specified AC power to a load. INVERTER - The UPS components which contain the equipment and controls necessary to convert DC power from the Converter / Charger, or the battery, to AC power required by the critical load. CONVERTER / CHARGER - The UPS components which contain the equipment and controls necessary to convert input AC power to regulated DC power required for battery charging and for supplying power to the Inverter. STATIC TRANSFER SWITCH - The device which connects the critical load to the bypass line when the Inverter cannot supply continuous power. BYPASS LINE - The line which conducts electricity directly from the input power source to the critical load during Maintenance or whenever the UPS is not completely operational. AC INPUT POWER - Power provided by the electrical utility company, or auxiliary generator, which is connected to the UPS for supplying the critical load. BATTERY - The rechargeable battery strings which supply DC power to the inverter to maintain continuous AC power to the load during AC input power failure conditions. MITSUBISHI
13 OPERATION OVERVIEW The UPS provides two power paths between the utility source and the critical load. Figure 1.1 shows the path for normal operation, with the load powered from the inverter. Figure 1.2 shows the path for bypass operation, with the load supplied through the static bypass line. A) Normal operation: Load power supplied by each system UPS inverter. Figure 1.1 Single Line Diagram - Normal Operation: Load powered by UPS inverter During normal operation, the path through the UPS inverters is used to power the load. Referring to Figure 1.1: Input AC power is converted to DC by the Converter. DC power is utilized to charge the UPS battery and to provide power to the Inverter. The Inverter converts the DC power to clean AC power to supply the critical load. The conversion - inversion process eliminates any voltage transients or fluctuations existing in the input power before it reaches the critical load. The power drawn by the critical load is equally shared between all UPS whenever the system is in the Parallel Operation. (Refer to Figure 3.4 that shows a sample of Parallel Operation System Configuration.) MITSUBISHI
14 1-8 In the event of a UPS module failure during Parallel Operation, the critical load power will be continually supplied and shared by all other UPS. The Bypass Input circuit breaker (MCCB) for protection of the UPS and cables are field supplied and field installed. (See WARNING 4 on page 1-4). B) Bypass Operation: Load Power supplied through UPS internal static bypass line. FIGURE 1.2 Single Line Diagram - Bypass Operation: Load fed through static bypass line. Referring to Figure 1.2: The Internal Bypass line is a Hard-wired line through 52S which supplies the critical load with unconditioned bypass input power. Upon switching to the Internal Bypass line, the Static Transfer Switch line through CB3 (herein after STS contactor CB3) supplies the power immediately, and then the Internal Bypass line through 52S supplies the power. In the event of a switching to the Bypass line, the power to the critical load will be uninterrupted. The purpose of this Internal Bypass line is to route power to the critical load while the UPS module is de-energized (converter and inverter), and during Start-up before the system is fully operational. Each UPS internal static bypass line will equally share the power supplied to the critical load whenever the system is in the Parallel Operation. MITSUBISHI
15 1-9 In the event of a load overcurrent, the UPS transfers to bypass without interruption to the critical load. In the case of the Parallel Operation, all UPS will transfer to bypass without interruption to the critical load. The internal control system determines the operation of the two paths, with the load powered from the inverter being the normal operation. C) Battery operation: Load Power supplied by UPS battery. FIGURE 1.3 Single Line Diagram - Battery Operation Referring to Figure 1.3: In the event of AC input source failure or interruption, the UPS Converter(s)* will de-energize and the UPS battery(s)* will immediately discharge and supply DC power to the Inverter to maintain continuous AC power to the load. This operation will continue until: a) The battery capacity expires and the inverter turns off, or b) Input power is restored after which the converter will power the inverter and critical load and simultaneously recharge the batteries. A fully charged battery will provide power for the specified time at the rated load, or longer, at a reduced load. (s)* : In the case of the Parallel Operation When power is restored after a low battery shutdown, the UPS converter(s)* automatically MITSUBISHI
16 1-10 restarts operation, the charger(s)* recharges the batteries and the Inverter(s)* is automatically restarted without operator intervention. Load is automatically assumed by the inverter without operator intervention. (s)* : In the case of the Parallel Operation The power drawn by the load is equally shared between all UPS regardless of the presence or absence of the UPS that is (are) in battery operation or not whenever the system is in the Parallel Operation.. MITSUBISHI
17 1-11 FIGURE 1.4(a) UPS Parts Location (750kVA) 1) UPS cabinet Front View 1. LCD Touch Panel Monitor Display Left Door Right Door Cable Entry Section 2) Backside of left door MITSUBISHI
18 1-12 FIGURE 1.4(a) UPS Parts Location (750kVA) 3) UPS module Front View 52S CB3 5.Relay PCB (PSAU-73) CPMC CPMS EMB 52C 3.External I/F PCB (IOAU-09) CB1 AC Capacitors AC Capacitors Converter Unit Chopper Unit Inverter Unit * Items 9 and 10 (AC input, AC output, DC input terminal, and Grounding Bar) is not shown in Figure 1.4. (Refer to Figure 3.2) MITSUBISHI
19 1-13 FIGURE 1.4(b) UPS Parts Location (500kVA) 1) UPS cabinet Front View 2) Backside of right door 1. LCD Touch Panel Monitor Display Left Door Right Door 1. LCD Touch Panel Monitor Display 6. External Communication Connector Cable Entry Section 2. Display PCB DPAU Main PCB UPGR-M 3) UPS module Front View CB3 52S CPMC CPMS EMB 52C 3. External I/F PCB (IOAU-09) CB1 AC Capacitor AC Capacitor Converter Unit Chopper Unit Inverter Unit MITSUBISHI
20 1-14 FIGURE 1.4(c) UPS Parts Location (300kVA) 1) UPS cabinet Front View 2) Backside of right door 1. LCD Touch Panel Door Monitor Display 1. LCD Touch Panel Monitor Display Cable Entry Section 5. Relay PCB PSAU External Communication Connector 2. Display PCB DPAU Main PCB UPGR-M 3) UPS module Front View CB3 52S CPMC CPMS EMB 52C 3. External I/F PCB (IOAU-09) CB1 AC Capacitor Converter Unit Chopper Unit Inverter Unit MITSUBISHI
21 1-15 FIGURE 1.5 Display PCB DPAU SW6 MAINTENANCE switch 12. SW5 TEST switch 6. External Communication Connector 11. SW1 RESET switch FIGURE 1.6 External I/F PCB IOAU External contact signal terminal block FIGURE 1.7 Parallel I/F PCB IFAU Parallel I/F PCB IFAU-09 MITSUBISHI
22 1-16 FIGURE 1.8 MAIN PCB UPGR-M 15. SW3 52L S/W switch 14. SW2 BOOT switch 11. SW1 RESET switch MITSUBISHI
23 1-17 Description of Figures 1.4 to 1.8: 1. LCD Touch Panel Monitor Display The liquid crystal display (LCD) touch panel monitor display indicates power flow, measured values and fault and error messages via user selectable display screens. Refer to FIGURE 2.1 for details. 2. Display PCB DPAU-81 (Figure 1.5): Switches on DPAU-81 board : FOR PERSONNEL ONLY - (11) SW1 (RESET switch) - (12) SW5 (TEST switch) - (13) SW6 (MAINTENANCE switch) 3. External I/F PCB IOAU-09 (Figure 1.6): Signal I/F on IOAU-09 board - (17) External contact signal terminal block Refer to FIGURE 2.10 for details. 4. Main PCB UPGR-M (Figure 1.8): Switches on UPGR-M board : FOR PERSONNEL ONLY - (11) SW1 (RESET switch) - (14) SW2 (BOOT switch) - (15) SW3 (52L S/W switch) 5. Relay PCB PSAU External Communication Connector RS232C connector on DPAU-81 board : FOR PERSONNEL ONLY Refer to FIGURE 2.13 for details. 7. Parallel control PCB TLCR-E (not shown) For use in Parallel Operation system application : Option 8. Parallel I/F PCB IFAU-09 For use in Parallel Operation system application : Option (Figure 1.7): Refer to FIGURE 3.5 for details. 9. AC input, AC output, DC input terminal Refer to Figure 3.2 for details 10. Grounding Bar (E) MITSUBISHI
24 "RESET" switch (FOR PERSONNEL ONLY) This switch resets errors resulting from alarm conditions. 12. "TEST" switch (FOR PERSONNEL ONLY) This switch changes system operation to the test-mode. 13. "MAINTENANCE" switch (FOR PERSONNEL ONLY) This switch sets the UPS menu parameters. 14. "BOOT" switch (FOR PERSONNEL ONLY) This switch boots the processor on the main control circuit board following alarm conditions. 15. "52L S/W" switch (FOR PERSONNEL ONLY) This switch prohibits turning on the AC output contactor 52C during test/maintenance in Parallel Operation system application. 16. External contact signal terminal block Terminal block to connect contact signal input/output lines to and from external dry contacts. Refer to FIGURE 2.10 for details. MITSUBISHI
25 SPECIFICATIONS The UPS nameplate displays the rated kva as well as nominal voltages and currents. The nameplate is located on the backside of the UPS front left door. TABLE 1.3 Power Specifications Rated output Input voltage Bypass input voltage Output voltage Power 3 phase / 3 wire 3 phase / 3 wire 3 phase / 3 wire 300kVA / 300kW 480V 480V 480V 500kVA / 500kW 480V 480V 480V 750kVA / 750kW 480V 480V 480V TABLE 1.4 UPS Module Information UPS [kva] Cable Entry BOTTOM / TOP / LEFT SIDE BOTTOM / TOP / LEFT SIDE BOTTOM / TOP / LEFT SIDE Width [in / mm] Depth [in / mm] Height [in / mm] Weight [lb./ kg] Heating [kbth / h] 55.1 / / / / / / / / / / / / MITSUBISHI
26 1-20 TABLE 1.5 Detail of Specifications Rated Output kva Rated Output kw AC INPUT Configuration 3 phase, 3 wire Voltage 480 V +15% to -20% Frequency 60 Hz +/-10% Reflected Current THD 3% max. at 100% load STATIC BYPASS INPUT Configuration 3 phase, 3 wire Voltage 480 V +/-10% Frequency 60 Hz +/-5% BATTERY Type Lead Acid Ride Through Application Specific Nominal Voltage 480 Vdc Minimum Voltage 400 Vdc Number of Cells 240 AC OUTPUT Configuration 3 phase, 3 wire Voltage 480 V Voltage Stability +/-1% Frequency 60 Hz Frequency Stability +/-0.01% in free running mode Power Factor Unity (nominal) Power Factor Range 0.7 lagging to 0.8 leading Voltage THD 2% maximum THD at 100% Linear Load 5% maximum THD at 100% non-linear load Transient Response +/-2% maximum at 100% load step +/-1% maximum at loss/return of AC power +/-5% maximum at load transfer to/from static bypass Transient Recovery Less than 20ms Voltage Unbalance 2% maximum at 100% unbalanced load Phase Displacement Inverter Overload System Overload (with bypass available) 1deg. maximum at 100% load 125% for 10 minutes 150% for 60 seconds 1000% for 1 cycle 500% for 1 cycle ENVIRONMENTAL Cooling Forced Air Operating Temperature 32 F to 104 F ( 0 C to 40 C). Recommended : 68 F to 86 F ( 20 C to 30 C) Relative Humidity 5% ~ 95% Non Condensing Altitude 0 to 7400 feet No Derating at 40 C Location Indoor (free from corrosive gases and dust) Paint Color Munsell 5Y7/1 (Beige) MITSUBISHI
27 1-21 TABLE 1.6 Rating of Contactors, Breaker and Fuses IDENTIFI- CATION APPLICATION OUTPUT CAPACITY OF EQUIPMENT 300kVA 500kVA 750kVA 300kW 500kW 750kW CB1 AC input contactor 452A 680A 1005A Contactors CB3 STS contactor 260A 350A 52C Inverter output contactor 452A 680A 1005A 52S Bypass contactor 452A 680A 1005A 88RC Control circuit contactor 20A CB2 User supply Battery disconnect breaker (Recommended) AC input breaker (Recommended) 800A 1400A 2000A 500A 800A 1200A Breakers User supply FPR, FPS, FPT, FPU, FPV, FPW, FCR, FCS, FCT, FCU, FCV, FCW, FNR, FNS, FNT, FNU, FNV, FNW, FBPR, FBPS, FBPT, FBNR, FBNS, FBNT Bypass input breaker (Recommended) 500A 800A 1200A DC fuse 450A / 690V 630A / 690V 800A / 690V FUA, FUB, FUC Control power fuse 30A / 600V FBS1, FBS2, FBS3 Control power fuse 30A / 600V FOA, FOB, FOC Control power fuse 30A / 600V (OPTION) FSU, FSV, FSW (OPTION) FEA, FEB, FEC * Rating would be changed. Bypass input fuse 250A / 690V 315A / 690V Parallel control circuit fuse (optional) 3A / 600V MITSUBISHI
28 OPERATOR CONTROLS AND INDICATORS The 9900B Series operator controls and indicators are located as follows (Door exterior) : FIGURE 2.1 Operation/Display Panel (Front panel) MITSUBISHI
29 LED DISPLAY 1) Load on inverter [ LOAD ON INVERTER ](green) Illuminates when power is supplied from inverter to the critical load. (Indicates the state of inverter transfer switch "52C".) 2) Battery operation [ BATTERY OP. ](orange) Illuminates when power is supplied from batteries following a power failure. 3) Load on bypass [ LOAD ON BYPASS ](orange) Illuminates when power is supplied to load devices by static bypass. (Indicates the state of bypass transfer switch "52S".) 4) Overload [ OVERLOAD ](orange) Illuminates in overload condition. 5) LCD fault [ LCD FAULT ](red) Illuminates when an error occurs. 6) UPS fault [ UPS FAULT ](red) [Annunciator: intermittent or constant tones] Illuminates when an error occurs in the system. In this case, the details of the error are indicated on the display panel. 2.2 EPO BUTTON (Emergency Power Off button) (7) When activated, the Emergency Power Off (EPO) function shuts down the UPS module. The critical load will lose power and also shutdown. The EPO function can be performed both locally or remotely. MITSUBISHI
30 LIQUID CRYSTAL DISPLAY (8) The Liquid Crystal Display (LCD) touch panel indicates power flow, measured values, operational guidance, data records and error messages. The LCD panel has a back-light which facilitates viewing in different ambient lighting conditions. The LCD will automatically clear and turn off, if the screen is not activated within 3 minute period. The LCD is turned back on when it is touched again. The ERROR indicator is cleared after 24 hours and can be reproduced by pressing any key on the panel MENU A) MAIN MENU (FIGURE 2.2) The LCD panel indicates power flow and measured values, while also operating the start/stop function. The LCD panel also allows the user to verify the status and operation of the UPS Module. FIGURE 2.2 Main screen The following will be displayed when the START/STOP key on the MAIN MENU is pressed (Jump into OPERATION MENU) : 1) Startup/Shutdown Guidance (FIGURE 2.3) The display indicates the Startup and Shutdown guidance for the UPS system. If this operation is PIN protected, the user is required to enter the security PIN before the screen can be accessed. When in remote mode, the message REMOTE operating model will appear on this Screen. The user cannot operate the start and stop functions without changing the setup from remote mode to local mode. When bypass voltage is abnormal, the message Bypass voltage abnormal will appear. - Start: When the bypass voltage is abnormal, the LCD asks the operator if an interrupted transfer is acceptable (Load may be lost). - Stop: When the bypass voltage is abnormal, the user cannot transfer from inverter to bypass line. MITSUBISHI
31 2-4 FIGURE 2.3(a) Startup/Shutdown guidance FIGURE 2.3(b) Startup guidance FIGURE 2.3(c) Shutdown guidance Follow Startup/Shutdown guidance accordingly. B) MEASUREMENT MENU (FIGURE 2.4) This screen shows details of measured values. Input and Output values are displayed. During Battery operation, Remaining battery power and Run time are also displayed. FIGURE 2.4(a) Input values MITSUBISHI
32 2-5 FIGURE 2.4(b) Output values FIGURE 2.4(c) Measurement during Battery operation C) OPERATION MENU (FIGURE 2.5) This screen prompts the user to select: (a) whether the start & stop operation will be performed by local or remote operation; (b) date & time adjustment; (c) battery equalizing charge. The battery equalizing charge operation key will appear when battery equalizing charge is set up (Setup is based on battery type). FIGURE 2.5(a) Remote/Local operation select FIGURE 2.5(b) Date & Time adjustment MITSUBISHI
33 2-6 D) LOG MENU (FIGURE 2.6) This LOG MENU displays two Touch icons in EVENT LOG and BATTERY LOG. Pressing the EVENT LOG icon, up to 50 condition/operation records will be displayed. Press or button for page turning. Pressing the BATTERY LOG icon, Number of battery operations and Summed battery operation time are displayed. FIGURE 2.6(a) Log menu FIGURE 2.6(b) Event log FIGURE 2.6(c) Battery log MITSUBISHI
34 INPUT POWER FAILURE (FIGURE 2.7) During an Input Power Failure, the UPS inverter will be powered by the UPS batteries. The following will be displayed on the main and measurement screen (Indication of battery operation and remaining battery life). FIGURE 2.7(a) Main screen (Battery operation) FIGURE 2.7(b) Measurement screen (Battery operation) The LCD will display a battery low voltage message when the battery capacity is near depletion. The End of Battery Discharge announcement is displayed when the battery end voltage is reached. At this time, the inverter will perform an electronic shutdown to prevent battery loss of life typical from extreme deep discharge conditions. When the input power is restored, the inverter will automatically restart to power the load, and the batteries will be simultaneously recharged. The End of Battery announcement is shown at the bottom of the screen FAULT INDICATION (FIGURE 2.8) MESSAGE and SILENCE ALARM icons will appear on the main menu when UPS failure condition has occurred. FIGURE 2.8 Main screen (Fault indication) The following will be displayed when the MESSAGE icon on the main menu is pressed. 1) MESSAGE (FIGURE 2.9) MITSUBISHI
35 2-8 The display shows a fault code, the description of the fault and a guidance of what action is to be taken by the user. A maximum of 10 faults is displayed at one time. If an input power failure occurs during a fault condition, the fault indication and input power failure announcement are alternatively displayed at 5 second intervals. FIGURE 2.9 Message screen 2) SILENCE ALARM This icon will appear when a failure occurs. The audible alarm (announcing the failure) can be silenced by pressing this icon. MITSUBISHI
36 EXTERNAL SIGNAL TERMINAL BLOCK The UPS is equipped with a series of input/output terminals for external annunciation of alarms and for remote access of certain UPS functions. The layout of terminals is shown in Figure 2.10 with a functional description of the input/output port presented. OUT1 to OUT8 are user programmable, but are factory default set being also shown in Figure Adding same external I/F PCB IOAU-09, doubling signal outputs is applicable for OUT1 to OUT8. FIGURE 2.10(a) External Signal Terminal Block (NEC Class2) TN2 2 1 SUMMARY ALARM 4 3 OUT1: LOAD ON BYPASS 6 5 OUT2: LOAD ON INVERTER 8 7 OUT3: BATTERY OPERATION 10 9 OUT4: CONVERTER OPERATION OUT5: BATTERY LOW VOLTAGE *1 OUT6: OVERLOAD OUT7: TOTAL ALARM OUT8: SPARE 52C CLOSE UPS *1 Relay contactor (52C close): Normal Closed MITSUBISHI
37 2-10 FIGURE 2.10(b) External Signal Terminal Block (NEC Class2) TN CB2 UVT CB2 AX Battery Breaker Panel L AX Load Circuit Switch IN1: REMOTE INVERTER START IN2: REMOTE INVERTER STOP (User supplied dry contact) IN3: BATTERY TEMP. HIGH IN4: POWER DEMAND REMOTE EPO UPS MITSUBISHI
38 2-11 A) Output Contacts (for external alarm annunciation) Output contacts consist of form A dry type contacts. Rated capacity of all output contacts is NEC Class2 (30Vdc/1Adc). All dry contacts should be operated at their rated values or lower. Figure 2.11 illustrates a typical installation. The external relay can also be a lamp, LED, computer, etc. FIGURE 2.11 Control Wiring for External Contacts UPS Cabinet Relay Contact Terminal Terminal External to UPS Cabinet Relay Coil NEC Class 2 Power Source User supplied Details of output alarm contacts : TN2 Terminals 1 to 2 "Summary Alarm" contact Activated when a major fault has occurred with the system. Terminals 3 to 4 "Load on Bypass" contact (OUT1) Activated when the power is supplied from the static bypass input. Terminals 5 to 6 "Load on Inverter" contact (OUT2) Activated when the power is supplied by the inverter. Terminals 7 to 8 "Battery Operation" contact (OUT3) Activated when the battery is operating following an AC power failure. Terminals 9 to 10 "Converter Operation" contact (OUT4) Activated when the converter is operating. Terminals 11 to 12 "Battery Low Voltage" contact (OUT5) Activated when the battery voltage drops below discharge end voltage level during inverter operation (i.e. During AC fail condition). Terminals 13 to 14 "Overload" contact (OUT6) Activated when an overload has occurred to the system. Terminals 15 to 16 "Total Alarm" contact (OUT7) Activated during major fault, minor fault and alarm events. Terminals 17 to 18 "Spare" contact (OUT8) Terminals 19 to 20 "52C Close" contact (OUT9) MITSUBISHI
39 2-12 Activated when the inverter output contactor 52C has closed. NOTE: The UPS is equipped with a selectable output contact feature. The above alarms are the default settings. Contact MITSUBISHI POWER PRODUCTS, INC for setup information. B) Input Contacts (for remote access of UPS) External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is 24Vdc. Provide external dry contact accordingly. CAUTION: Do not apply voltages to remote access input terminals. Damage to UPS may result. Refer to Figure 2.12 for a typical wiring configuration. Although this figure applies to the remote start/stop terminals, the same wiring arrangement is used for emergency stop; power demand; and battery temperature high. FIGURE 2.12 Remote "Start" Contact Connections MITSUBISHI
40 2-13 Details of input contacts for remote access : TN1 Terminals 7 to 8 Remote "Inverter Start" input terminal (IN1) Used to start inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure. Terminals 9 to 10 Remote "Inverter Stop" input terminal (IN2) Used to stop inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure. Terminals 11 to 12 "Battery Temp. High" contact input (IN3) Input fed by a thermocouple that monitors battery temperature. The converter float voltage level is reduced for battery over-temperature conditions. External thermocouple is user supplied Terminals 13 to 14 "Power Demand Command contact input (IN4) This contact is used to control the input power. Power demand is turned ON when the contact is closed, and power demand is turned OFF when the contact is open. Terminals 15 to 16 "Remote EPO" contact input Used to perform a remote UPS Emergency Power Off (EPO). The load will be dropped. NOTE: The UPS is equipped with a selectable input contact item. The above items are the default settings. MITSUBISHI POWER PRODUCTS, INC for setup information. CAUTION : In all cases, a switch having a protective cover is recommended in order to reduce the possibility of accidental operation. MITSUBISHI
41 EXTERNAL COMMUNICATION CONNECTOR This is an RS232C port for DiamondLink * monitoring software. The layout of connector is shown in Figure FIGURE 2.13 External communication connector (NEC Class2) D-SUB 9Pin (male) PCB DPAU-81 CN26 Pin 1. Pin 2. RXD Pin 3. TXD Pin 4. Pin 5. GND Pin 6. Pin 7. Pin 8. Pin 9. : Not used : Receive data : Transmit data : Not used : Signal ground : Not used : Not used : Not used : Not used * Consult MITSUBISHI POWER PRODUCTS, INC for details on DiamondLink monitoring software and its capabilities. MITSUBISHI
42 INSTALLATION AND OPERATION 3.1 TRANSPORTATION AND INSTALLATION TABLE 3.1 How to transport and install the system Transportation Transport unit with forklift. Carry with overhead crane using provided screw-eyebolts. Installation Using the pre-drilled four holes in the UPS channel base, anchor the unit using appropriate hardware. (Not provided) CAUTION : Do not transport in a horizontal position. Cabinets must be maintained upright within +/- 15 of the vertical during handling. 3.2 INSTALLATION PROCEDURE A) Note the load tolerance of the floor Refer to Table 3.2 for list of UPS weights. TABLE 3.2 List of UPS weights UPS Capacity (kva) Weight (lb.) 2,250 3,330 4,250 B) Minimum clearance required for ventilation Right side 25 mm (1 inch) (not required when sidecars are used) Left side 25 mm (1 inch) (not required when sidecars are used) Back side 0.0 mm (0 inch) Top side 600 mm (24 inches) (for air flow) C) Space requirement for routine maintenance Allow for the following space at the time of installation. Front 1075 mm (43 inches) Sides 0.0 mm (0 inch) Back side 0.0 mm (0 inch) Top side 500 mm (20 inches) MITSUBISHI
43 3-2 D) External Battery Supply Please refer to the following when installing and maintaining batteries: 1. The customer shall refer to the battery manufacturer's installation manual for battery installation and maintenance instructions. 2. The maximum permitted fault current from the remote battery supply, and the DC voltage rating of the battery supply over-current protective device are shown in Table 3.3. TABLE 3.3 Maximum Permitted Fault Current UPS Capacity (kva) DC Voltage Rating (V) Maximum Fault Current Permitted (A) , , , PROCEDURE FOR CABLE CONNECTIONS * 1. Confirm the capacity of the UPS being installed. Identify the input/output power terminal blocks as shown in the appropriate Figures 3.1 through Connect the internal control wire and power wire. (1) Control wire interconnections 1. CB2 UVT to terminal TN1-1, 2 of external I/F PCB IOAU CB2 ON Auxiliary to terminal TN1-3, 4 of external I/F PCB IOAU-09. (2) Power wire (AC input, Bypass input, AC output) interconnections a.) From user s distribution panel 1. X1 (A-phase) to A bus bar in UPS 2. X2 (B-phase) to B bus bar in UPS 3. X3 (C-phase) to C bus bar in UPS b.) DC Input to UPS 1. Positive cable to BP bus bar in UPS 2. Negative cable to BN bus bar in UPS CAUTION : After the completion of the input power cables connection: With a phase rotation meter, check that the phase rotation of the AC Input power terminals A, B and C as well as the Bypass Input power terminals A40, B40 and C40 are correct. The proper phase rotation is clockwise A B C. MITSUBISHI
44 Connect the grounding conductor from the input service entrance to the UPS Ground Bar (E). 4. Two (2) sources feeding the UPS: (1) Connect the AC input power cables from the input service entrance to the AC input power terminals, identified as A, B, C in Figures 3.1 to 3.3. Input cables must be sized for an ampere rating larger than the maximum input drawn by the converter. (Refer to equipment nameplate for current ratings.) Confirm that an external bypass input circuit breaker (MCCB) is installed (refer to WARNING 4, page 1-4). Connect the bypass input power cables from the input service entrance to the bypass input power terminals, identified as A40, B40 and C40 in Figures 3.1 to 3.2. Bypass input cables must be sized for an ampere rating larger than the maximum output current capacity of the UPS. Refer to Table 3.4 for recommended cable sizes. (2) Connect the external signal terminal block as desired. Refer to section 2.4 and Figure 2.10 for functional description. 2mm 2, or less, shielded conductor is recommended. 5. One (1) source feeding the UPS: (1) Confirm that an external input circuit breaker sized to protect both the AC input and the bypass line is installed. (Refer to equipment nameplate for current ratings.) Connect the bypass input power cables from the input service entrance to the bypass input power terminals, identified as A40, B40 and C40 in Figures 3.1 to 3.3. Input cables must be sized for an ampere rating larger than the maximum current capacity of the UPS. Refer to Table 3.4 for recommended cable sizes. (2) Using adequately sized conductors and referring to the appropriate figure identified in Figures 3.1 to 3.2, connect jumper bypass terminals A40, B40, C40 to AC input power terminals A, B, C as identified in Figures 3.1 to 3.2. (3) Connect the external signal terminal block as desired. Refer to section 2.4 and Figure 2.10 for functional description. 2mm 2, or less, shielded conductor is recommended. MITSUBISHI
45 3-4 CAUTION : UPS power terminals are supplied with stud type fittings. It is recommended that compression lugs be used to fasten all input/output power cables. 6. Procedure for Cable Connections for Parallel Operation System (1) Confirm the number of units to be connected in parallel. Identify the input/output power terminal blocks and control wire connections for parallel operation systems as shown in the appropriate Figures 3.4 and 3.5. (2) Connect the external control wire and power wire. a.) Control wire connections Parallel configuration wiring (Refer to Figure 3.5.) - 52L control signal from Critical Load Cabinet (CLC) to UPS-n IOAU-09 (TN1 5, 6). - Parallel control signal for TLIN, TLOUT, CIN,COUT as shown in Fig b.) Power wire connections From UPS AC Output Terminals to Critical Load Cabinet (CLC) (Refer to Figure 3.4 and 3.5.) MITSUBISHI
46 3-5 TABLE 3.4 Recommended Cable Sizes Input Side Output Side Bypass Side DC Input Side kva Input Output Cable Torque Cable Torque Cable Torque Cable Torque Capacity Voltage Voltage Size in. lbs Size in. lbs Size in. lbs Size in. lbs 300kVA 480V 480V 3 x 1/0 or larger in. lbs 3 x 1/0 or larger in. lbs 3 x 1/0 or larger in. lbs 3 x 300MCM in. lbs 500kVA 480V 480V 3 x 250MCM or larger in. lbs 3 x 250MCM or larger in. lbs 3 x 250MCM or larger in. lbs 4 x 400MCM in. lbs 750kVA 480V 480V 3 x 600MCM or larger in. lbs 3 x 600MCM or larger in. lbs 3 x 600MCM or larger in. lbs 5 x 700MCM in. lbs *1 Use 75 degree C copper wire. *2 - The cables must be selected to be equal or larger to the sizes listed in the table. *3 - Voltage drop across power cables not to exceed 2% of nominal source voltage. *4 - Allowable ampere-capacities based on copper conductors with 75 degree C. insulation at ambient temperature of 40 degree C. TABLE 3.5 Recommended Hardware UPS Capacity Bolt size Flat washer size Split lockwasher size Nut size 300kVA M12 x 40mm M12 M12 M12 500kVA M12 x 40mm M12 M12 M12 750kVA M12 x 40mm M12 M12 M12 MITSUBISHI
47 3-6 TABLE 3.6 Crimp Type Compression Lug WIRE SIZE WIRE STRAND RECOMMENDATION CRIMP TOOL REQUIRED BURNDY TYPE Y35 OR Y46 (CODE) CLASS VENDOR CAT. NO. COLOR KEY DIE INDEX 1 B BURNDY YA1C GREEN 11 / 375 ILSCO CRA-1L GREEN 11 / 375 BURNDY YA25-LB I 1/0 B I 2/0 B I 3/0 B I 4/0 B I 250 MCM B I 300 MCM B I 350 MCM B I 400 MCM B I 500 MCM B I 600 MCM B BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO BURNDY BURNDY ILSCO I BURNDY 750 MCM B BURNDY ILSCO YA25 CRA-1/OL YA25-LB YA26 CRA-2/OL YA27-LB YA27 CRB-3/OL YA28-LB YA28 CRB-4/OL YA29-LB YA29 CRA-250L YA30-LB YA30 CRA-300L YA32-LB YA31 CRA-350L YA34-LB YA32 CRA-400L YA36-LB YA34 CRA-500L YA38-LB YA36 CRA-600L YA39-LB YA39 CRA-750L PINK PINK --- BLACK BLACK --- ORANGE ORANGE --- PURPLE PURPLE --- YELLOW YELLOW --- WHITE WHITE --- RED RED --- BLUE BLUE --- BROWN BROWN --- GREEN GREEN --- BLACK BLACK 12 / / / / / / / / / / / / / / NOTE: When using crimp type lugs, the lugs should be crimped to the specifications given in the manufacturer's instructions for both crimp tool and lug. MITSUBISHI
48 3-7 FIGURE 3.1 UPS Terminal Designation MITSUBISHI
49 3-8 FIGURE 3.2(a) Diagram of input/output bus bars and terminal blocks Location of bus bars and terminal blocks (Bottom/Top/Left Side entry) D=32.7 (831.6mm) 90.6" (2300) Detailed Power Terminals For power terminals, use 1/2 (12mm) diameter bolts. AC Input A, B, C Bypass Input A40, B40, C40 DC Input BP, BN AC Output A50, B50, C (2000) Grounding Bar (not shown ) 19. 7" (500) UPS module (750kVA) MITSUBISHI
50 3-9 FIGURE 3.2(b) Diagram of input/output bus bars and terminal blocks Location of bus bars and terminal blocks (Bottom/Top/Left Side entry) D=32.7 (831.6mm) 72.0 (1830) Detailed Power Terminals For power terminals, use 1/2 (12mm) diameter bolts. AC Input A, B, C Bypass Input A40, B40, C40 DC Input BP, BN AC Output A50, B50, C (2000) Grounding Bar (not shown ) 19.7 (500) UPS module (500kVA) MITSUBISHI
51 3-10 FIGURE 3.2(c) Diagram of input/output bus bars and terminal blocks Location of bus bars and terminal blocks (Bottom/Top/Left Side entry) D=32.7 (831.6mm) 55.1 (1400) Detailed Power Terminals For power terminals, use 1/2 (12mm) diameter bolts. AC Input A, B, C Bypass Input A40, B40, C40 DC Input BP, BN AC Output A50, B50, C (2000) Grounding Bar ( not shown) 19.7 (500) UPS module (300kVA) MITSUBISHI
52 3-11 FIGURE 3.3 Diagram of Power Wire & Control Wire Interconnections between UPS and Battery User supplied CB2 (DC circuit breaker) External signal terminal IOAU-09 - [TN1] Power terminal BN BP UVT Auxiliary - Negative + Positive User supplied UPS module Wall mounted DC breaker for Battery MITSUBISHI
53 3-12 FIGURE 3.4 Diagram of power wire connections (Parallel Operation system connection ) CRITICAL LOAD CABINET SMB Bypass input UPS-1 Bypass 52S AC input CB1 Converter /Charger Inverter AC output 52L 1 52C UPS-2 CB2 Battery Bypass input AC input Bypass CB1 Converter /Charger Inverter 52S AC output 52L 2 52L 52C CB2 Battery UPS-n *1 Bypass input Bypass 52S AC input CB1 Converter /Charger Inverter AC output *1 52L n 52C CB2 Battery *1 n : Maximum = 8 MITSUBISHI
54 3-13 FIGURE 3.5(a) Diagram of Power Wire & Control Wire Connect ( Parallel Operation system connection 2x to 4x)... ON ON ON ON ON ON CN99 CN98 TLIN TLBIN TLAIN DAS-8S CN97 CN96 TLOUT TLBOUT TLAOUT OFF CN954 CN953 CIN CN952 CN951 CB2IN CB1IN CA2IN CA1IN DAS-8S OFF CN944 CN943 COUT CN942 CB2OUT CB1OUT CA2OUT CN941 CA1OUT CN99 CN98 TLIN TLBIN TLAIN DAS-8S CN97 CN96 TLOUT TLBOUT TLAOUT OFF CN954 CN953 CIN CN952 CN951 CB2IN CB1IN CA2IN CA1IN DAS-8S OFF CN944 CN943 COUT CN942 CB2OUT CB1OUT CA2OUT CN941 CA1OUT CN99 CN98 TLIN TLBIN TLAIN DAS-8S CN97 CN96 TLOUT TLBOUT TLAOUT OFF CN954 CN953 CIN CN952 CN951 CB2IN CB1IN CA2IN CA1IN DAS-8S OFF CN944 CN943 COUT CN942 CB2OUT CB1OUT CA2OUT CN941 CA1OUT MITSUBISHI
55 3-14 FIGURE 3.5(b) Diagram of Power Wire & Control Wire Connect ( Parallel Operation system connection 5x to 8x)... ON ON ON ON ON ON CN99 CN98 TLIN TLBIN TLAIN DAS-8S CN97 CN96 TLOUT TLBOUT TLAOUT OFF CN954 CN953 CIN CN952 CN951 CB2IN CB1IN CA2IN CA1IN DAS-8S OFF CN944 CN943 COUT CN942 CB2OUT CB1OUT CA2OUT CN941 CA1OUT CN99 CN98 TLIN TLBIN TLAIN DAS-8S CN97 CN96 TLOUT TLBOUT TLAOUT OFF CN954 CN953 CIN CN952 CN951 CB2IN CB1IN CA2IN CA1IN DAS-8S OFF CN944 CN943 COUT CN942 CB2OUT CB1OUT CA2OUT CN941 CA1OUT CN99 CN98 TLIN TLBIN TLAIN DAS-8S CN97 CN96 TLOUT TLBOUT TLAOUT OFF CN954 CN953 CIN CN952 CN951 CB2IN CB1IN CA2IN CA1IN DAS-8S OFF CN944 CN943 COUT CN942 CB2OUT CB1OUT CA2OUT CN941 CA1OUT MITSUBISHI
56 OPERATING PROCEDURES For Parallel Operation system, refer to section D) MMS Start-up Procedure. (Parallel Operation system is herein after MMS [Multi Module System]) A) Start-up Procedure CAUTION : Before the UPS startup, the internal Bypass line starts to supply the unconditioned bypass input power to the critical load if the External input (or Bypass) Circuit Breaker is closed. Be extremely careful with closing the External input (or Bypass) Circuit Breaker. a) Verify that the External Bypass Input Circuit Breaker for each unit is closed (user supplied). b) Verify that Battery Disconnect Circuit Breaker (CB2) is opened or in tripping position. c) If a dual source is feeding the UPS, close the External AC Input Circuit Breaker manually (user supplied). d) The LCD panel boots up automatically, and the screen will show that the Load is powered by bypass line. e) On the LCD panel, select OPERATION tab, and then press the STARTUP GUIDANCE button to proceed UPS start-up. (Refer to Figure 2.3). f) Follow the STARTUP GUIDANCE accordingly until the completion of the inverter startup. NOTE : When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start operation can only be performed remotely. If local inverter start operation is required (at the UPS), select "LOCAL ONLY" or REMOTE & LOCAL in the OPERATION MENU. MITSUBISHI
57 3-16 B) Shutdown Procedure If a total UPS shutdown is required, verify that the critical load is OFF. a.) On the LCD panel, select OPERATION tab, and then press the SHUTDOWN GUIDANCE icon to proceed UPS shutdown. (Refer to Figure 2.3) b.) Follow the SHUTDOWN GUIDANCE accordingly. During the procedure, UPS will transfer the power feeding from the Inverter supply to the Bypass line supply. c.) Both Converter and Inverter will remain energized until complete disconnection from all power sources. NOTE : When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start operation can only be performed remotely. If local inverter stop operation is required (at the UPS), select "LOCAL ONLY" or REMOTE & LOCAL in the OPERATION MENU. d.) If stopping both the Inverter and Converter is required, open the Battery Disconnect circuit breaker (CB2) manually in accordance with guidance. WARNING : Verify the load is OFF if the next step is to be performed. NOTE : Power to the critical load is supplied through the bypass line. Power to the critical load will be lost after execution of the next step. The load will drop. e.) If a dual source is feeding the UPS, open the External AC Input Circuit Breaker (user supplied) manually. f.) If turning off all power to the critical load is desired, open the External Bypass Input Circuit Breaker (user supplied) manually. CAUTION : In bypass mode, all UPS power terminals are still live. Lethal voltages are present. De-energize all external sources of AC and DC power. Before removing the covers, wait 5 minutes after de-energizing. Check no-voltage before handling UPS. Be careful for the devices even when the UPS has been de-energized, still internal devices may be hot. MITSUBISHI
58 3-17 C) Bypass Operation Procedure ** Transfer from Inverter to Bypass 1. Check for SYNC on the LCD. 2. Press the "START/STOP icon on the LCD. 3. Follow the SHUTDOWN GUIDANCE and Press the "STOP" icon on the LCD. ** Transfer from bypass to inverter. UPS 1. Press the "START/STOP" icon on the LCD. 2. Follow the STARTUP GUIDANCE and Press the "START" icon on the LCD.. NOTE : When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start operation can only be performed remotely. If local inverter start or stop operation is required (at the UPS), select "LOCAL ONLY" or REMOTE & LOCAL in the OPERATION MENU. D) MMS Start-up Procedure External Circuit Check 1. Verify that Critical Load Cabinet (CLC) Circuit Breaker SMB is closed. 2. Verify that CLC System Output Circuit Breaker 52L is open. 3. Verify that CLC UPS Circuit Breakers 52L1, 52L2 and 52Ln are closed. Start-up from UPS-1 to UPS-n 1. Start-up each UPS in accordance with A) Start-up Procedure. Each UPS will start Inverter Operation in synchronization with the bypass input. Transfer from Maintenance Bypass to MMS Bypass Operation 1. Closed the CLC System Output Circuit Breaker 52L. 2. Open the CLC Circuit Breaker SMB. NOTE : When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start operation can only be performed remotely. If local inverter start operation is required (at the UPS), select "LOCAL ONLY" or REMOTE & LOCAL in the OPERATION MENU. MITSUBISHI
59 500kVA MITSUBISHI 3-18 Transfer from UPS MMS Bypass Operation To UPS MMS Inverter Operation 1. Transfer MMS Bypass Operation to MMS Inverter Operation from Operation Menu on any UPS LCD as shown in Fig FIGURE 3.6 LCD Screen (MMS Operation) Transfer from UPS MMS Inverter Operation To UPS MMS Bypass Operation 1. Transfer MMS Inverter Operation to MMS Bypass Operation from Operation Menu on any UPS LCD as shown in Fig MITSUBISHI
60 RESPONSE TO UPS FAILURE UPS FAULT Annunciator Silence Depress SILENCE ALARM icon on Main Menu. Recording of Fault Refer to the list of fault codes in Section 6.0 for error description. Primary Action Take necessary action according to display guidance. Information to Service Center When faults happen, contact the Authorized Mitsubishi Electric Service Representatives or call Mitsubishi Electric at NOTE: The error code indicated on the LCD display panel when an UPS alarms is very important. In order to reduce repair time, please include this information, along with the operation and load status for all correspondence to Mitsubishi Electric field service group. MITSUBISHI
61 PARTS REPLACEMENT Contact Mitsubishi Electric Power Products, Inc.or its authorized service representatives on all issues regarding the replacement of parts. A) Battery Battery lifetime may vary according to the frequency of use and the average ambient operating temperature. The end of battery life is defined as the state of charge resulting in an ampere-hour capacity less than, or equal to, 80% of nominal capacity. Replace battery if its capacity is within this percentage. B) UPS Component Parts UPS components have a defined life expectancy (Fan, Capacitors, Filters, etc). Contact Mitsubishi Electric Power Products, Inc. or its authorized service representatives for a complete parts replacement schedule. Recommended replacement time interval varies with operating environment. Contact Mitsubishi Electric Power Products, Inc. or its authorized service representatives for application specific recommendations. NOTE : Any parts replacements (including modification) without authorized by Mitsubishi Electric could result in personal injuries, death or destruction of the UPS. MITSUBISHI
62 FAULT CODES This section covers fault codes, their description and required action. In the event of a fault occurring: A) Verify and record the occurrence of the alarm. Note details of alarm message displayed on the LCD display panel. Contact Mitsubishi Electric Power Products, Inc. at B) If a circuit breaker (MCCB) has tripped, depress the toggle to reset the breaker before closing it again. MITSUBISHI
63 6-2 Table 6.1 Fault Code List Code indication (Note 3) UA801 UA802 UA803 UA804 UA805 UA806 UA807 UA808 UA810 UA812 UA813 UA814 UA815 UA817 UA821 Status message AC INPUT VOLTAGE OUT OF RANGE AC INPUT FREQUENCY OUT OF RANGE AC INPUT PHASE ROTATION ERROR CONVERTER OPE. PROHIBITION INVERTER OVERLOAD INVERTER OVERLOAD INVERTER OVERLOAD INVERTER OVERLOAD INVERTER OVERLOAD BYPASS VOLTAGE OUT OF RANGE BYPASS PHASE ROTATION ERROR BYPASS FREQUENCY OUT OF RANGE TRANSFER PROHIBITION EMERGENCY STOP ACTIVATED TRANSFER PROHIBITION Meaning Guidance Buzzer Input line voltage is out of the specific range. Input line frequency is out of the specified range. Input line power conductors are not wired in a proper phase sequence. The converter interlock is active. The output load current has exceeded 105% of the rated current. The output load current has exceeded 110% of the rated current. The output load current has exceeded 125% of the rated current. The output load current has exceeded 150% of the rated current. Short time over-current has exceeded 150% of the rated current Bypass line voltage is out of the specific range. Bypass line power conductors are not wired in a proper phase sequence. Bypass line frequency is out of the specific range. Transfer to bypass is not available due to bypass abnormality. The emergency stop was activated by the EPO switch or an external contact. The UPS cannot transfer to the bypass because the inverter output is not synchronized to the bypass. CHECK INPUT POWER SOURCE CHECK INPUT POWER SOURCE CHECK INPUT POWER SOURCE - WARNING: DECREASE LOAD WARNING: DECREASE LOAD WARNING: DECREASE LOAD WARNING: DECREASE LOAD WARNING: DECREASE LOAD CHECK BYPASS INPUT CHECK BYPASS INPUT CHECK BYPASS INPUT - External relay contact (Note 1) Alarm AC input abnormal Alarm AC input abnormal Alarm AC input abnormal Failure lamp (Note 2) Alarm - Alarm Overload Alarm Overload Alarm Overload Alarm Overload Alarm Overload Alarm Bypass Input Abnormal Alarm Bypass Input Abnormal Alarm Bypass Input Abnormal Alarm Alarm Alarm MITSUBISHI
64 6-3 Table 6.1 (continuation) Code indication (Note 3) UA822 UA824 UA827 UA831 UA833 UA834 UA835 UA860 UA861 UA870 UA890 UF001 UF002 UF003 UF011 UF052 UF056 UF059 UF102 Status message TRANSFER PROHIBITION CB2 OPEN 52C OPE. PROHIBITION EMERGENCY BYPASS SWITCH ON 52L OPEN BATTERY DEPLETED/AC OUT STOPPED TRANSFER PROHIBITION REMOTE BUTTON ABNORMAL LOCAL BUTTON ABNORMAL BALANCER OVERLOAD EXTERNAL ALARM INPUT CIRCUIT ABNORMAL CONVERTER OVERCURRENT CONVERTER ABNORMAL CB1 ABNORMAL CB1 ABNORMAL CONVERTER OVERCURRENT INPUT CIRCUIT ABNORMAL DC OVERVOLTAGE Meaning Guidance Buzzer The UPS cannot transfer to the bypass because of backup generator operation. The battery circuit breaker (CB2) is open. The interlock for the inverter output contactor (52C) is active. Emergency bypass switch has been turned on. The load circuit breaker(52l) is turned off. The battery voltage has reached the depleted level. The UPS could not transfer to the bypass because the bypass source has an abnormality. Remote start or stop signal is being received continuously for a considerable time. Local start or stop signal is being received continuously for a considerable time. The UPS detected an neutral point voltage unbalance. External Alarm relay turned on. Detection of a large variation of the reference error signal. Detection of converter overcurrent. Pre-charging circuit is not working properly. discrepancy between reference signal and actual state of contactor CB1. Minor discrepancy between reference signal and actual state of contactor CB1. Detection of converter overcurrent. Detection of a large variation of the reference error signal. DC voltage surpasses the overvoltage level. TURN ON CB2 External relay contact (Note 1) Failure lamp (Note 2) - - Alarm Alarm - Alarm - Alarm - Alarm - End-of- Discharge - - Alarm Alarm - Alarm - Alarm Overload Alarm - Minor Minor Minor - Flicker Flicker Flicker MITSUBISHI
65 6-4 Table 6.1 (continuation) Code indication (Note 3) UF103 UF108 UF109 UF110 UF111 UF112 UF119 UF128 UF151 UF152 UF154 UF156 UF157 UF158 UF159 UF160 UF161 UF162 Status message DC UNDERVOLTAGE CHOPPER OVERCURRENT DC UNBALANCED ZERO PHASE OVERCURRENT UPS CONTROL CIRCUIT ERROR DC CIRCUIT ABNORMAL DC GROUND FAULT CONTROL POWER SUPPLY ABNORMAL DC VOLTAGE ABNORMAL DC VOLTAGE ABNORMAL CB2 ABNORMAL CHG.STOPPED (BATTERY OVERTEMP.) BATTERY OVERTEMPERA TURE BATTERY LIQUID LOW DC GROUND FAULT UPS CONTROL CIRCUIT ERROR CHG.STOPPED (DC VOLT. ABNORMAL) BATTERY ABNORMAL Meaning Guidance Buzzer DC voltage dropped below the undervoltage level. Detection of DC overcurrent. unbalance of the neutral point voltage. Detection of converter zero-sequence overcurrent. Battery current unbalance. Sudden change of the DC voltage level. Detection of DC ground fault. Power supply voltage to IGBT driver PCB is below the specified level. 24 hours after input power restoration, batteries does not reach float voltage level. Unable to equalize the voltage of various batteries after 24 hours. During UVT, status signal from CB2 is ON. UF157 failure persisted for over 2 hours. Detection of overtemperature at the batteries. Low level of battery electrolyte solution. Detection of DC ground fault. Abnormal behavior of DC current sensor. UF151 failure is running for over 24 hours. Failure detection based on battery self-check. CHECK BATTERY CHECK BATTERY CHECK BATTERY s ound External relay contact (Note 1) Minor Minor Minor Minor Battery abnormal Minor Battery abnormal Minor Battery abnormal Minor Minor Minor Minor Failure lamp (Note 2) Flicker Flicker Flicker Flicker Flicker Flicker Flicker Flicker Flicker Flicker MITSUBISHI
66 6-5 Table 6.1 (continuation) Code indication (Note 3) UF163 UF170 UF171 UF201 UF202 UF203 UF204 UF206 UF207 UF208 UF209 UF210 UF211 UF213 UF214 UF217 UF230 Status message BATTERY VOLTAGE ABNORMAL VDB SENSOR ABNORMAL UPS CONTROL CIRCUIT ERROR INVERTER OVERVOLTAGE INVERTER UNDERVOLTAGE INVERTER OVERCURRENT OUTPUT CIRCUIT ABNORMAL UPS CONTROL CIRCUIT ERROR ZERO PHASE OVERCURRENT UPS CONTROL CIRCUIT ERROR 52C ABNORMAL 52C ABNORMAL 52C ABNORMAL OVERTEMPERAT URE COOLING FAN ABNORMAL INVERTER OVERVOLTAGE ZERO PHASE OVERCURRENT Battery voltage is abnormality. Meaning Guidance Buzzer Detection of a large variation of the difference between control-only and protection-only battery voltage. Battery current unbalance. Detection of output overvoltage. Output voltage dropped. Detection of inverter overcurrent. Detection of a large variation of the reference error signal (current reference and actual current). Discrepancy between output voltage and external voltage (bypass, common ac bus) Inverter zero-sequence overcurrent. Cross current is abnormality. Error to close the contactor 52C. Error to open the contactor 52C. No answer from contactor 52C during inverter operation. Heatsinks temperature exceeds thermal settings. Thermal relay activated protection. Detection of inverter output phase overvoltage. Detection of zero-sequence overcurrent. External relay contact (Note 1) Minor Minor Minor Failure lamp (Note 2) Flicker Flicker Flicker MITSUBISHI
67 6-6 Table 6.1 (continuation) Code indication (Note 3) UF253 UF256 UF257 UF258 UF259 UF301 UF302 UF303 UF305 UF306 UF309 UF310 UF320 UF323 UF331 UF332 UF333 UF334 Status message UPS CONTROL CIRCUIT ERROR OUTPUT VOLTAGE ABNORMAL 52C ABNORMAL LOAD ABNORMAL ANOTHER UPS ABNORMAL UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR INVERTER VOLTAGE ABNORMAL CONTROL POWER SUPPLY ABNORMAL UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR CONTROL POWER SUPPLY ABNORMAL UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR Meaning Guidance Buzzer Discrepancy between output voltage and inverter voltage, or between output voltage and bypass voltage. Output voltage is out of the specified range. Contactor 52C failed to open during load transfer from inverter to bypass. Load transfer due to overload for over 4 times within 5 minutes. No detection of another UPS voltage signal. AD reference has an abnormal value. Detection of an external interruption during the software execution. Timer does not reset in the specified period (WDT settings) Detection of an abnormal clock speed in the DSP or FPGA. Control power supply voltage are below the specified level. Inverter voltage is out of the specified range. Backup control power supplies exhibit abnormal condition. Cable disconnection in the parallel interface board during load supply. communication error during parallel operation. Cable disconnection in the main driver PCB (Phase A) Cable disconnection in the main driver PCB (Phase B) Cable disconnection in the main driver PCB (Phase C) Cable disconnection in the main driver PCB (Chopper)) External relay contact (Note 1) Minor Minor Minor Minor Minor Failure lamp (Note 2) Flicker Flicker Flicker Flicker Flicker MITSUBISHI
68 6-7 Table 6.1 (continuation) Code indication (Note 3) UF352 UF363 UF371 UF372 UF374 UF375 UF376 UF377 UF378 UF379 UF401 UF402 UF420 UF451 UF452 Status message CONTROL POWER SUPPLY ABNORMAL UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR UPS CONTROL CIRCUIT ERROR 52S ABNORMAL 52S ABNORMAL 52L OPERATION ERROR 52S ABNORMAL CB3 ABNORMAL Meaning Guidance Buzzer Backup control power supplies exhibit abnormal condition. Synchronization status signal is being received for a considerable time. Minor communication error during parallel operation. Unable to synchronize the inverter output and the bypass voltage. Cable disconnection in the parallel interface board. Unable to achieve synchronization for parallel operation. No control response from another UPS although its detection is possible. Overload detection signal is being received continuously for a considerable time. No answer for sending synchronizing signal. Abnormal clock speed of the parallel control board processor. Error to close the contactor 52S. Error to open the contactor 52S. Load circuit breaker 52L opened during inverter operation. Contactor 52S failed during load transfer from inverter to bypass. Contactor CB3 is not working properly. CHECK 52L s ound External relay contact (Note 1) Minor Minor Minor Minor Minor Minor Minor Minor Minor Minor Minor Minor Failure lamp (Note 2) Flicker Flicker Flicker Flicker Flicker Flicker Flicker Flicker Flicker Flicker Flicker Flicker (Note 1) 1) "" is defined as a major failure. Load transferred from the inverter circuit to the static bypass line; 2) "Minor" is defined as a minor failure. UPS continues to operate normally, but cause of alarm must be identified; (Note 2) Indicates one of two possible LED illumination patterns - continuously on (lit on) or intermittent (flicker). MITSUBISHI
69 6-8 (Note 3) Code indication means: UA Alarm UF Failure U% Rectifier circuit failure U% DC circuit failure U% Inverter circuit failure U% Control circuit failure U% Bypass system failure U% Alarm U%+00 - U% failure U%+50 - U% Minor failure *) + denotes any numeral from 0 to 9 *) % denotes either A or F MITSUBISHI
70 WARRANTY & OUT OF WARRANTY The Mitsubishi Electric UPS Division Service Department has many Authorized Service Centers place strategically throughout the US, Canada and Latin America. For both in warranty and out of warranty service, please contact Mitsubishi Electric Power Products, Inc. at (724) To register your UPS for warranty purposes, please complete the warranty registration form and fax it to the Mitsubishi Electric UPS Division Service Department fax line shown on the registration form. (Next page) For warranty purposes, it is essential that any and all service work that may be required on your Mitsubishi brand UPS equipment is performed by a Mitsubishi Electric Authorized Service Center. The use of non-authorized service providers may void your warranty. Mitsubishi Electric Power Products, Inc UPS Division Service Department 530 Keystone Drive, Warrendale, PA 15086, USA Phone: (724) Fax: (724) MITSUBISHI
71 7-2 Mitsubishi Electric Power Products, Inc. UNINTERRUPTIBLE POWER SUPPLIES 530 Keystone Drive, Warrendale, PA Phone: (724) , Fax: (724) UPS Warranty Registration Register UPS for Warranty Address Change To validate the Warranty on your UPS this form must be filled out completely by Customer and returned. Your Name: CUSTOMER INFORMATION Job Title: Company Name: Division / Department: Address: City: State: Zip Code: Country: Province: Business Phone: Ext: Fax: Internet UPS Model #: Capacity (kva): UPS Serial #: Start-Up Date: Signature: / / Authorized Mitsubishi Service Company (if known): Date: / / Which ONE of These Best Describes Your Organization s Primary Business Classification? {Energy Producer} Education/Univ. Service Utility {Service} Alternate Energy Consulting {Manufacturing Co.} Engineering OEM Outsourcing Process Financial/Legal/Insurance Consumer Goods {Government} Electronics Military Power Quality Municipals Equipment Federal/State/Local Commercial Business Communications Electrical Contractor Distributors/Reps Healthcare Other Internet Number of Employees at This Location is: Overall how was Start-Up performed: Unsatisfactory Satisfactory Exceeded Expectations 1000 or more Would you like to receive future product updates and news? Yes No After Start-Up has been done Fax completed Form to: (724) MITSUBISHI
72
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
MITSUBISHI UNINTERRUPTIBLE POWER SUPPLY 7011A SERIES UPS SINGLE PHASE PRODUCT OWNERS / TECHNICAL MANUAL. 6kVA 8kVA 10kVA 12kVA
UNINTERRUPTIBLE POWER SUPPLY SINGLE PHASE PRODUCT 6kVA 8kVA 10kVA 12kVA Revision 6.5: Jan. 24, 2003 ALN-H0379 i Preface MITSUBISHI ii TABLE OF CONTENTS LIST OF TABLES... iii LIST OF FIGURES... iv HOW TO
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
TOSHIBA G9000 80/100/160/225 kva
CORPORATE OFFICE 13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041 PHONE: (713) 466-0277 (800) 231-1412 FACSIMILE: (713) 896-5226 TOSHIBA G9000 80/100/160/225 kva GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
DC UPS. RTB.e 50-1000 A. IMB.e/ITB.e 5-200 kva. E2001.e/E3001.e 5-200 kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.
Oil & Gas Energy Catalogue DC UPS RTB.e 50-1000 A 3 phase rectifier battery chargers voltage: 400 Vac, 3-phase, 50/60 Hz voltage: 24/48/110/220 Vdc RMB.e/RCB.e 50-100-150 A 1 and 3 phase compact rectifier
Online UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL [email protected] / www.tuncmatik.com Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3.
OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE
OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &
AC Power For Business-Critical Continuity. Liebert NX UPS. Operation and Maintenance Manual 10-30kVA, 208V, 60Hz
AC Power For Business-Critical Continuity Liebert NX UPS Operation and Maintenance Manual 10-30kVA, 208V, 60Hz TABLE OF CONTENTS 1.0 GENERAL DESCRIPTION...................................................1
10000HXL31/15000HXL31/20000HXL31
Table of Contents www.eaton.com/dxups USER MANUAL ON LINE UPS 10000HXL31/15000HXL31/20000HXL31 Uninterruptible Power Supply Table of Contents 1. Brief introduction 1.1 System and model description---------------------------------------------------------------------1
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.
Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com
Applied Electronics. Commercial Dimming System UPDATE NOTICE
REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with
Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6. User s manual
Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6 User s manual Index Safety Warnings... 2 1 Introduction... 3 2 General Characteristics... 4 3 Receipt and site selection... 4 4 EXTERNAL
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content
Liebert NX UPS. User Manual 40-200kVA, 480V, 60Hz
Liebert NX UPS User Manual 40-200kVA, 480V, 60Hz TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................................1 GLOSSARY OF SYMBOLS........................................................5
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence
SECTION 16260 STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM
1 0 1 0 1 SECTION 0 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Uninterruptible power supply (UPS) system. B. Related Sections include but are not necessarily limited to: 1. Owner s - Bidding
DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0
Form No. 74-00-4001 S168-195-001 Revision E DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0 INTRODUCTION Allied Healthcare Products, Inc. s Digital Alarm
EATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved.
ENGLISH EATS6 EATS6N Installation and user manual Copyright 05 EATON All rights reserved. Service and suppt: Call your local service representative SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
INSTALLATION & SERVICE MANUAL. Display Panel
INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed
Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives
DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)
User Manual. Hybrid 1KW-5KW INVERTER / CHARGER. Version: 1.1
User Manual Hybrid 1KW-5KW INVERTER / CHARGER Version: 1.1 Table of Contents ABOUT THIS MANUAL... 1 Purpose... 1 Scope... 1 SAFETY INSTRUCTIONS... 1 INTRODUCTION... 2 Product Overview... 3 INSTALLATION...
Parallel Redundant Uninterruptible Power Supply
9 315 Parallel Redundant Uninterruptible Power Supply Installation/Operation Manual 164202013 Rev. D ------------------------------------------------------------------------ ------------------------------------------------------------------------
Liebert NXL Power-Tie Controls
AC Power For Business-Critical Continuity Liebert NXL Power-Tie Controls Operation and Maintenance Manual CONTACTING EMERSON NETWORK POWER FOR SUPPORT Contact Emerson Network Power Liebert Services for
User Manual 1K/2K/3K Online UPS
User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...
Contractors Guide Central Inverter System Installation
Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V
Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
Specification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
OWNER'S MANUAL. Model 20-1050CUL AC Power Inverter/Charger System OM/A96283 REV. A
OWNER'S MANUAL Model 20-1050CUL AC Power Inverter/Charger System OM/A96283 REV. A Table of Contents Section 1 Introduction... 1 Section 2 Installing the 20-1050CUL... 4 Section 3 Installing the IFM1 Interface
When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only
Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811
Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The
Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers
Technical Note Freedom/Fleet Power 512-0084-01-01 Rev 1 Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers Overview This document is a guide for troubleshooting inverters, battery chargers,
USER MANUAL Online UPS 1K/2K/3K
USER MANUAL EN Online UPS 1K/2K/3K Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1.1. Transportation 2 1.2. Preparation 2 1.3. Installation 2 1.4. Operation 2 1.5.
3000W Power Inverter
3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Manual Ranging MultiMeter
Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!
VLT Series 300 Watt True Sine Wave Inverter
VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS
Galleon 6-10K Online UPS. Voltronic Power Technology Corporation
Galleon 6-10K Online UPS Voltronic Power Technology Corporation Features Galleon online UPS series delivers optimal power quality, provides superior power management, resolves utility power protection
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass APC AIS 3000, 12 kw / 15 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9 RS-232,
HP R12000 and R18000 DirectFlow UPS User Guide
HP R12000 and R18000 DirectFlow UPS User Guide Abstract This document includes installation, configuration, and operation information for the HP R12000 and R18000 DirectFlow UPS. This document is for the
PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS
PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000
TSn SERIES Surge Protective Device
Page: 1 of 8 TSn SERIES Surge Protective Installation & Operation Manual 3621 Saunders Avenue www.systems.us Ph 804.355.1100 Richmond, VA 23227 4354 [email protected] Fax 804.355.8900 Page: 2 of 8 Quick
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar
UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES
UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)
Technical data UNIBLOCK UBSF 180 625
Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual
PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code
Installation Instructions
H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
User Manual. Modular Online UPS
User Manual Modular Online UPS Uninterruptible Power Supply System Version: 1.5 Table Of Contents 1. Safety... 1 1.1 Important Safety Instructions... 1 1.2 EMC... 1 1.3 Installation information... 1 1.4
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
User Manual for CH-PFC76810
AA Portable Power Corp www.batteryspace.com, Email: [email protected] User Manual for CH-PFC76810 1. Overview The CH-PFC76810 charger is suitable for charging lithium ion battery packs such as those
TIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
Battery Power Inverters
Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.1 Important Safety Instructions Please save these instructions.
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Digi-Motor Installation Guide
Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
Power Management Module 2. Installation
Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...
ST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
Always On UPS Systems Inc., #100-150 Campion Road, Kelowna, BC Canada V1X 7S8
Door Mount UPS (Patent Pending) Shelf Mount UPS (Patent Pending) DESCRIPTION: The Always On NDM (door mount) and NSM (shelf mount) Series UPS s are dual conversion online UPS systems provided in slim,
Operation and Installation Manual
Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Product description Wide rated operational voltage 208 600 V AC Wide rated control supply voltage 100 250 V, 50/60 Hz Rated operational current 18 to 370 A Wide ambient temperature range, -25 to +60 ºC
HotSwap MBP Maintenance Bypass
ENGLISH HotSwap MBP Maintenance Bypass MBP6Ki MBP11Ki MBP11Ki1 Installation and user manual Copyright 201 EATON All rights reserved. Service and support: Call your local service representative SAFETY INSTRUCTIONS
/ Instruction Manual. Analog Input/Output Interface Card "OPC-G1-AIO"
/ Instruction Manual Analog Input/Output Interface Card "OPC-G1-AIO" Fuji Electric Co., Ltd. INR-SI47-1288b-JE English Version Preface Thank you for purchasing our analog input/output interface card.
Operation Manual. Smart-UPS C. Uninterruptible Power Supply. Tower 1000/1500 VA. 120/230 Vac. su0813a
Operation Manual Smart-UPS C Uninterruptible Power Supply Tower 1000/1500 VA 120/230 Vac su0813a Product Description The APC by Schneider Electric Smart-UPS is a high performance uninterruptible power
