L5354 ControlNet Communications Interface



Similar documents
8903/CN ControlNet Communications Interface

User Manual. DeviceNet Network Configuration

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

Install the DeviceNet Module using the following procedure:

DeviceNet Bus Software Help for Programming an Allen Bradley Control System

Logix5000 Controllers Nonvolatile Memory Card

Module 1 Overview ControlLogix5000

Installation Instructions

ControlNet PLC-5 Hot Backup System

EtherNet/IP Adapter. 22-COMM-E FRN 1.xxx. User Manual

DeviceNet Motor Control

CMC-DN01 DeviceNet Slave Communication Card Operation Manual

Bluetooth to Serial Adapter

Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP. 1 Application Description Objective Goals...

Wireless Router Setup Manual

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

ControlLogix Remote I/O Communication Module

ENET-710. ENET Ethernet Module ENET-710 JAN / 06 FOUNDATION

Modbus Communications for PanelView Terminals

Accessing EtherNet/IP Network Variables in a WAGO with a ControlLogix PLC Application note

AC-115 Compact Networked Single Door Controller. Installation and User Manual

ZC-24DO CANopen I/O Module: 24 Digital Outputs

Series Six Plus Programmable Controller

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

BroadBand PowerShield. User Manual

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

DeviceNet Communication Manual

About This Guide SolarEdge Configuration Tool Software Guide. About This Guide

Application/Connection Examples

Modular I/O System Analog and Digital Interface Modules

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

Medical Vacuum Systems-PXMI

DeviceNet Scanner Module

SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2

Termination Resistors:

4469 en / c. Ready. Run Start. Stop LCL RMT. Reset USB MODULE. Communications module. User Guide

Universal Serial Bus (USB) to DH-485 Interface Converter

M-series Virtual I/O Module 2

Backup Scanner Module

Technical Note. Monitoring Ethernet Traffic with Tolomatic ACS & Managed Switch. Contents

PLCM-T1 / PLCM-T2 Torch height controller

Inwall 4 Input / 4 Output Module

In this section we tell you how to set the fault mode selection plug, key your I/O chassis, install your module and make your wiring connections.

User Manual. ControlNet Network Configuration

Non-Isolated Analog Voltage/Current Output module IC695ALG704 provides four configurable voltage or current output channels. Isolated +24 VDC Power

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

CMC-PD01 PROFIBUS DP Slave Communication Card Operation Manual

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

Current Monitoring Kit

1 Serial RS232 to Ethernet Adapter Installation Guide

Computer Gateway Specification and Technical Data

Allen-Bradley/Rockwell

ADM1TE 5/30A DIN rail single phase two wire energy meter

SIS-PM / SiS-PM-841 / SIS-PMS User Manual. Table of contents

Different Ways of Connecting to. 3DLevelScanner II. A.P.M Automation Solutions LTD. Version 3.0

3500/22M Transient Data Interface

Building a groov HMI for Allen-Bradley Logix Systems. About groov. Building a groov HMI for Allen-Bradley Logix. A-B Systems and groov

Crow Limited Warranty. Print Version 017

ETS4 Diagnostics. KNX Association

Logix5000 Controllers Import/Export Project Components

User s Manual. Management Software for ATS

Smart DeviceNet Remote I/O Terminals

BIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter

Product Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB

How to read this guide

SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.

SIP Proxy Server. Administrator Installation and Configuration Guide. V2.31b. 09SIPXM.SY2.31b.EN3

Introduction: Implementation of the MVI56-MCM module for modbus communications:

PLC Master / Slave Example

AIS750 Series Alarm Annunciator

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

BECKHOFF. Application Notes. BC9000: Getting Started Guide. For additional documentation, please visit.

Current Monitoring Kit QUICK START GUIDE

Modbus and ION Technology

USB-to-Data Highway Plus Cable

StarPort iscsi and ATA-over-Ethernet Initiator: Using Mirror (RAID1) disk device

Wireless Link. Introduction. Setup, Configuration and Connection ENGLISH

PU-USBX. USB over Ethernet Extender OPERATION MANUAL

PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN. User Manual. Document version ( )

ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1

EZ-ZONE RMA & EtherNet/IP Configuration & Startup Using an Allen-Bradley CompactLogix PLC EtherNet/IP Fundamentals

PN L, Revision B, October Epic 950 TM. Master Programmer User s Guide

Using Ladder Logic Instructions to Communicate with an Ethernet IP Nexus Unit

Setting Up and Testing the MAX Hardware

AKD EtherNet/IP Communication

Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: Data sheet GIOD.1 V_3.0

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

Using Logix5000 Controllers as Masters or Slaves on Modbus

Part Number Revision A, January Monitoring System Rack Configuration and Utilities Guide

Switch Actuator, 8-fold, 10 A, MDRC AT/S , GH Q R0111

Application about Communication

IO-DIM6 6-Channel, Digital to Analogue Converters

PCI/PXI ETHERNET ADAPTERS

MADRIX NEO Quick Start Guide & User Manual

Product Data. Thermal Comfort Data Logger Type Including Application Software Type 7301

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Centran Version 4 Getting Started Guide KABA MAS. Table Of Contents

Using the WAGO PROFINET Coupler as Remote I/O with a Siemens S7 PLC

MiniPlex-41USB NMEA-0183 multiplexer Manual

Transcription:

L5354 ControlNet Communications Interface Technical Manual HA470733 Issue 2 Copyright SSD Drives Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any form or by any means to persons not employed by a SSD group company without written permission from SSD Drives Inc. Although every effort has been taken to ensure the accuracy of this document it may be necessary, without notice, to make amendments or correct omissions. SSD Drives cannot accept responsibility for damage, injury, or expenses resulting therefrom.

Safety Information! Please read this information BEFORE installing the equipment. Intended Users This manual is to be made available to all persons who are required to install, configure or service equipment described herein, or any other associated operation. The information given is intended to highlight safety issues, and to enable the user to obtain maximum benefit from the equipment. Application Area The equipment described is intended for industrial motor speed control using DC or AC motor controllers, with DC motors AC induction or AC synchronous machines. Personnel Qualified personnel should carry out installation, operation and maintenance of the equipment. A qualified person is someone who is technically competent and familiar with all safety information and established safety practices; with the installation process, operation and maintenance of this equipment; and with all the hazards involved. REFER TO YOUR MAIN PRODUCT MANUAL FOR SPECIFIC SAFETY INFORMATION ABOUT THE DEVICE YOU ARE CONTROLLING IMPORTANT It is required that the users have DSD, RSLogix 5000 and RS Networx for ControlNet installed on a computer and have a working knowledge of these software packages. ACKNOWLEDGEMENTS Drive System Designer, DSD is a registered trademark of SSD Drives Inc. RSLogix 5000, ControlLogix500, and RSNetworx for ControlNet are registered trademarks of Allen-Bradley Inc.

Table of Contents Chapter 1 System Overview... 1 Product Features... 1 Product Code... 1 DSD Requirements... 1 Wiring the System... 1 Chapter 2 Hardware Installation... 2 Installing and Connecting the ControlNet LinkCard... 2 Installing the ControlNet LinkCard... 2 Initial Power on Checks... 3 Understanding the LED Indications... 3 Network and Module LED Indications... 3 Chapter 3 Configuring the LinkRack... 4 Chapter 4 Configuring the PLC/SCADA Supervisor... 6 Chapter 5 Configuring RSNetworx for ControlNet... 10 Appendix A Configuration Tips... 12 Appendix B Troubleshooting... 13 L5354 Module Status LED... 13 Technical Specifications... 14 Environmental... 14 Supply Voltage... 14 Physical... 14

1 Chapter 1 System Overview Product Features Suitable for use with Link modules: L5392 LinkStation L5300 LinkRack Connection using RG 59 (75Ω) double shielded coaxial cable LED s to indicate board and communications status Configured using Function Block inputs and outputs Diagnostics using Function Block outputs Automatic Baud Rate selection Software-selectable Slave Address The ControlNet LinkCard is provided as a plug-in LinkCard. ControlNet.eds file is provided with the LinkCard. 224 words in and out. Product Code Part Number: L5354 ControlNet LinkCard DSD Requirements Software version: 1.13 or higher. Database level: 1037 or higher. Wiring the System WARNING! Before installing, ensure that the LinkRack wiring is electrically isolated and cannot be made live unintentionally by other personnel. Wait 5 minutes after disconnecting power before working on any part of the system or removing the covers from the drives.

NETWORK STATUS MODULE STATUS Chapter 2 Hardware Installation 2 Installing and Connecting the ControlNet LinkCard -L5354- -L5354- NETWORK STATUS ControlNet MODULE STATUS ControlNet Figure 1. L5392 LinkStation with L5354 ControlNet LinkCard WARNING! Prior to starting work on the LinkRack or LinkStation ensure all sources of power are isolated. Installing the ControlNet LinkCard The ControlNet LinkCard plugs into a LinkRack or a LinkStation. The ControlNet LinkCard can be installed into any site (J1, J2, J3, and J4) of the LinkRack. Remove the back cover of the LinkRack Insert the ControlNet card into the recess on the back of the LinkRack. Re-fit the back cover to the LinkRack Make all user-wiring connections. Refer to Wiring Diagram, Figure 3.

3 Initial Power on Checks With the correct connections to the active PLC/SCADA supervisor, the MODULE LED will be ON continuously and the NETWORK LED will flash to indicate the No Connection State. Understanding the LED Indications ON FLASH MODULE LED NETWORK LED LED Indication Network and Module LED Indications Network LED Indicates the state of the connected network. Module LED Indicates the set-up state of the LinkCard. The states indicated are those produced by the FAULT parameter of the LinkCard function block. Description FAULT Parameter Description OFF Disabled HARDWARE Hardware Fault - external FLASH No Connection CONFIGURING Card is initializing ON Data exchange NONE Valid set-up, ready for external communications Figure 2. LED Status Indication Note: The NETWORK LED is always in the OFF State when the MODULE LED is not ON continuously, indicating that the LinkCard is not receiving external communications or the PLC is off. -L5354- NETWORK STATUS ControlNet MODULE STATUS Figure 3. ControlNet connections to the L5354

Chapter 3 Configuring the LinkRack 4 1. Create the LINK configuration with all the reader and writer blocks that are required for the project. Placing other function blocks into the LINK module will decrease performance. Insert the writer blocks before inserting the reader blocks into the handler. The LinkCard transmits and receives the data in the order in which the blocks are inserted into the handler. 2. The LINK ControlNet handler block identifies the slot location in the LinkRack/LinkStation and the ControlNet node address on your ControlNet network. The node address is not hardware selected; the two rotary switches on the L5354 are set to 00. Figure 4. ControlNet Handler Block with one writer and one reader block installed 3. Load the LINK configuration first. The PLC will connect once its configuration is installed. The connection to the LINK module will equal the PLC configuration size. If the PLC configuration is smaller than the LINK configuration, there will be no I/O error and only the PLC configured data will be transmitted. Figure 5. Basic LINK Setup Note: The above LINK configuration is sending a value signal (16 bit) to the PLC. 1% = 328-1% = 65209 10% = 3277-10% = 62259 100% = 32767-100% = 32769

5 Figure 6. Logical to Ordinal and Value LINK Setup Figure 7. Ordinal to Logical and Value LINK Setup Note: The above configurations are sending seven values and 16 Boolean signals from within the LINK network to the ControlNet network and from the ControlNet network to the Link network. The Logics to Ordinal and the Ordinal to Logics function blocks multiplexes and demultilpexes the 16 Boolean signals into one word.

Chapter 4 Configuring the PLC/SCADA Supervisor 6 Our example will use the RSLogix 5000 software and ControlLogix PLC. 1. Start a new program and select the PLC processor and chassis type that will be used in your project. Our example will use a 1756-L55 processor and 1756-A7 chassis. Remain Offline until you are ready to download the program. 2. In the I/O configuration, select the ControlNet scanner. Right click on the I/O Configuration folder to select a New Module. Select the type of scanner module that will be used in the PLC. Figure 8. Selecting New Module Figure 9. Select Scanner

7 3. Under the scanner card, add a new module. Right click on the scanner module and select New Module. Select Generic ControlNet module. Figure 10. Select New Remote Module Figure 11. Select Remote Module Type 4. This window allows you to name the module and to set network address, set data type (dataint), and set data size. The input assembly instance is 100 and the size is the configured number of words plus 2. The output assembly instance is 150 and the size is the number of words you are sending to LINK. The configuration assembly instance is 1 and the size is 0. The Comms Format is set for DATA-INT to allow transferring 16 bit words. Refer to Figure 12. 5. Click the NEXT button to the set the Requested Packet Interval time. The default setting should be sufficent for most applications. When finished with the Requested Packet Interval screen, click the FINISH button to exit. Refer to Figure 13.

8 Figure 12. Defining the Module Name and Data Size Figure 13. Packet Rate Selection

9 6. The RSLogix 5000 program will configures your data types and I/O data points automatically. 7. Once the PLC is configured for the LinkCard, the program can be downloaded to the PLC. The program needs to be loaded before RSNetWorx can create the proper configuration for the ControlNet network. 8. The PLC automatically creates a configuration data block. The block is always ends a C. This block is part of every configuration. L5354_LinkCardC: 0 was created for this module. The type and size of the data is fixed, (Type: SINT, Size: 400 bytes). This configuration data block is created regardless of the configuration size. Figure 14 ControlNet Data allocations for the PLC

Chapter 5 Configuring RSNetworx for ControlNet 10 The fastest way to configure the ControlNet scanner is online with RSNetworx and all the nodes connected to the network. 1. Load the EDS file for the LinkCard first. A diskette is included with the L5354 LinkCard that contains the ControlNet.eds file. Using the Tools menu, select EDS Wizard. The EDS wizard will guide you through the process. Figure 15 RSNetworx configuration screen 2. Set the scanner network address using the two rotary switches located on the top of the scanner card. If different hardware is being used, refer to instruction manual for the hardware. This example uses an Allen-Bradley model 1756-CNB/D. 3. The RSNetworx software queries the network and reads the PLC configuration to generate the proper network configuration. 4. RSNetworx should see the nodes on the network. The scanner card is the only image you see for the PLC. Enable the edits enabled checkbox to configure the rack and the PLC processor. Right click on the scanner card and choose the edit chassis option. Select the rack, processor and any other cards that are in the PLC. 5. RSNetworx is used to configure the network update time. Right click in the area outside of the modules, select Properties. Enter the update time and other network parameters as needed. The only requirement is that the network update time is shorter than the PLC Requested Packet Interval. After configuring the rack and setting the network update time, you should have updates pending to the network. 6. A File-Save saves the configuration to your file and to the network at the same time. After the network changes have been saved, the network and the I/O should become healthy. The network and LinkCard LEDs should be solid green.

11 7. The ControlNet tags can be monitored online using PLC software. Select Controller tags to change the view to display the tags. The tag names match the module name that is being monitored. Figure 16 PLC monitor screen

Appendix A 12 Configuration Tips 1. Define the total amount of data you wish to send to and from the ControlNet scanner. The limit for the card is 224 words each way. You can have less and the number of inputs and outputs do not have to match. The LINK blocks are 8 words each. Your total words should be a multiple of 8. 2. Inputs are words transmitted from the LINK module to the PLC. These will be LINK writer blocks. Outputs are words transmitted from the PLC to the LINK module. These are LINK reader blocks. 3. The LinkCard transmits two status words so the total number of input words will be your data size plus two. 4. The ControlNet Node Address for the LinkCard is assigned using the DSD software. The rotary switches on the LinkCard are set to 00. 5. The bottom coaxial connector is for the primary ControlNet network. 6. The minimum Network Update Time for the card is 5ms.

13 Appendix B Troubleshooting L5354 Module Status LED Table 1 This bi-color (green - red) LED provides device status. It indicates whether or not the device is powered and operating properly. Table 1 defines the different states of the Module Status LED. Status LED State Reason Power off Off No power applied to the device Host LINK2 module is not running its configuration Device in standby Flashing Green Device needs commissioning because of missing, incomplete or incorrect configuration PLC is off Device operational Green The device is operating in a normal condition Configuration fault Red LINK2 configuration fault. Device Self-test failure Flashing Red Device self test failure may need replacing, try power down/up sequence L5354 Network Status LED Table 2 This bi-color (green - red) LED indicates the status of the communications link. Table 2 defines the different states of the Network Status LED. Status LED State Reason Bus Controller Self Test On-Line No Connection Off The device may not have power applied to it. Look at Module Status LED PLC power off Flashing Green Device is active on the network, but is not owned by a PLC On-line Green ControlNet Master cycling through its configuration steps Communicating with, correct configuration between L5354 and the PLC Network Error Flashing Red Cable improperly terminated or connected No Network Red LinkCard is powered on but in state of waiting for network messages Network not communicating with the LinkCard Listen Only Orange Module forced into listen only mode

Technical Specifications 14 Environmental Operating temperature 0º C to 50º C (32º to 122º F) Storage temperature -10º C to +70º C (14º to 158º F) Humidity Enclosure Rating 85% RAH. in a dry, non-condensing environment Touchsafe IP20. To be mounted inside a SSD L5300, or L5392 series enclosure Supply Voltage Supply Voltage Current Consumption Power Dissipation 5VDC, supplied by backplane 275 ma @ 5VDC 1.375 W ControlNet Connection Types Baud Rate Data Types Indicators supported Transfer delay Configurability Connector type Process Data parameters selected by ControlNet Demand Data protocol to provide random access to any network parameter. 5 Mbaud Unsigned Integers (LINK Ordinals) Network status bi-color LED, Module status bi-color LED Typically < 1 0ms LINK input to ControlNet output and vice-versa LinkCard configuration performed using DSD. ControlNet network and PLC programmed independently Coaxial. Physical Height Width Depth Weight 120mm (4.72 in) 32mm (1.25 in) 90mm (3.54in) 0.16 kg (0.35 lbs)