Safe Isolation of low voltage installations. by Jon Elliott. 12 Safe Isolation of low voltage installations



Similar documents
Circuit Electrical Testing

Are you aware. Outline

Electrical safety and you

Roadmap to Compliance with NFPA 70E Arc Flash Requirements

Electrical test equipment for use on low voltage electrical systems

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

SELECTION OF FINAL CIRCUIT PROTECTION

GUIDANCE ON ELECTRICAL INSPECTIONS

High Voltage. Hazards

ELECTRICAL SAFETY Make It Your Priority!

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

Types of electrical injuries

St Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.

Electrical safety for entertainers

Electrical Safety Policy

RCD Health and Safety Guide for Ropes Course Owners and Operators

Guide to the Selection & Use of Residual Current Devices

Use of Residual Current Devices in Departmental Infrastructure

Electricity at work Safe working practices

Safety in electrical testing at work

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

Dielectric Withstand Testing in a Production Environment

1 Introduction. 2 Hazards From Electricity

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Mark Coles BEng (Hons) MIEE

The Electrical Safety Regulation (pre and post 1 January 2014)

Model 1756 Test Lead Kit

Best Methods for Safe Hipot Testing

Level 3 Certificate in the Certification of Electrical Installations (Design, Erection and Verification of Electrical Installations) ( )

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance

What s up with Arc Flash?

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Residual Current Circuit Breaker

INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES

ADM1TE 5/30A DIN rail single phase two wire energy meter

This Guidance Notes is prepared by the Occupational Safety and Health Branch, Labour Department. This edition July 2004

Electrical Resistance Resistance (R)

Electrical Contractors Association

chapter8 Testing and commissioning Unit 2 outcome 2

LOS ANGELES UNIFIED SCHOOL DISTRICT DIVISION OF ADULT AND CAREER EDUCATION SAFETY TEST FOR ELECTRICIAN PROGRAM

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

Section B: Electricity

Pontyclun Electrotechnical Training Ltd. (P.E.T. Ltd.)

Electrical Safety Training for the Manufacturing Industry

Customer Installation Safety Plan. March 2015

Work in Substations - General

LOCKOUT GUIDELINE. To ensure that a piece of equipment cannot be turned on, pressurized or switched on accidently while an employee is working on it.

Lockout Tagout Presentation For GOSH Group Aberdeen UK

BWC Division of Safety and Hygiene

Electrical installation condition reporting:

Briefing 43. The Corporate Manslaughter and Corporate Homicide Act NHS Employers. Background. Key points

The Electrical Contractor Safety Program Guide

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS

MODULE 1 INTRODUCTION TO ELECTRICAL SAFETY

By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E

Maintaining portable electric equipment in low-risk environments

Does this topic relate to the work the crew is doing? If not, choose another topic.

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV

6.0 Electrical Installations

Procedure. Work Health and Safety Incident Notification. Document number: PRO Description Process Owner Approved for issue. Rev no.

Electrical Method Statement. Guidance Note 8

Intertek Cleeve Road, Leatherhead, Surrey KT22 7SB UK

Connecting a microgeneration system to a domestic or similar electrical installation

Electrical safety code of practice Managing electrical risks in the workplace

employed to ensure the continuing reliability of critical systems.

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

What Are Arrhythmias?

Model UT33A: OPERATING MANUAL Table of Contents (1)

Electrical Safety Tips. Help us keep you safe

Power presses: A summary of guidance on maintenance and thorough examination

Keeping electrical switchgear safe

Model UT201/202: OPERATING MANUAL. Table of Contents

Electrical Practices for Construction Work

DIOCESE OF LINCOLN GUIDELINES

Unit 4: Electricity (Part 2)

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

3088 Lockout-Tagout Training Program Course Outline

Unified requirements for systems with voltages above 1 kv up to 15 kv

Safety guidance. Buying electrical goods online? The safe shopper s guide. electricalsafetyfirst.org.uk

Understanding Emergency Power Off (EPO)

PRODUCT STANDARDS. Electrical Equipment - Requirements for Plugs & Sockets etc

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

November Stray Voltage Test Procedure for Electrical Contractors

THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE

Why Construction Workers are Getting Electrocuted

Common Sense and Knowledge Approach to Electrical Safety

NZECP 14: 1995 ISSN COVER PAGE

Transcription:

12 Safe Isolation of low voltage installations Safe Isolation of low voltage installations by Jon Elliott The HSE and other major stakeholders in the electrical installation industry have, for some time been concerned about the number of serious electric shock and burn accidents which have been occurring to experienced electricians and others carrying out electrical work. Many of these incidents can be attributed to a failure to perform safe electrical isolation procedures prior to work on or near conductors or equipment intended to dead. This article seeks to summarise the statutory and non-statutory requirements for isolation; to raise awareness of the many and various devices now produced to enable virtually all switching devices to be safely isolated and to describe the requirements for voltage indicating devices and the need to confirm their continued suitability for use. The basic procedure for safe isolation is described, followed by an overview of the health implications and legal consequences that may arise as a result of not carrying out safe isolation where required. Mostly this article seeks to point out that there is no excuse for not being able to safely isolate an installation, circuit or item of equipment. Statutory requirements The most important statutory requirement concerning work carried out on or near electrical installations is the Electricity at Work Regulations (EWR) 1989. Those regulations within EWR of particular relevance to safe isolation are numbers 12 (Means for cutting off the supply and for isolation) and 13 (Precautions for work on equipment made dead). Regulation 12 (1) (b) states that where necessary to prevent danger, suitable means shall be available for the isolation of any electrical equipment, where isolation means the disconnection and separation of the electrical equipment from every source in such a way that the disconnection and separation is secure (para (2) refers). The Memorandum of Guidance on the Electricity at Work Regulations 1989 (HS(R) 25) published by the Health and Safety Executive advises with reference to Regulation 12 (1) (b) above that isolation is the process of ensuring that the supply to all or a particular part of an installation remains switched off and that inadvertent reconnection is prevented. The issue of preventing inadvertent reconnection is covered in Regulation 13 (of EWR 1989) which requires that Adequate precautions shall be taken to prevent electrical equipment, which has been made dead in order to prevent danger while work is being carried out on or near that equipment, from becoming electrically charged during that work if danger may thereby arise. The coverage of Regulation 13 in HS(R) 25 highlights the need to lock off any switching device being used to provide isolation, or where isolation has been achieved by a fuse, by their removal and retention in a safe place during the isolation period. Non-statutory Requirements Within BS 7671:2008, the following are of particular relevance in terms of safe isolation: Regulation 132.15.1 contains the following fundamental principle: Effective means, suitably placed for ready operation, shall be provided so that all

Safe Isolation of low voltage installations 13 voltage may be cut off from every installation, from every part thereof and from all equipment, as may be necessary to prevent or remove danger. Regulation group 537.2 contains the requirements relating to isolation Regulation group 537.3 contains the requirements for switching off for mechanical maintenance. Table 53.2 summarises the suitability of particular protective, isolation and switching devices to be used as an isolator, an emergency switch, or a functional switch and is reproduced overleaf. Electrical installation work trainees and apprentices that have attended college for appropriate initial training should have been taught how to carry out safe isolation, including securing the device in the OFF position. However, adoption of incorrect isolation procedures in the field still appears to be far too frequent. Clearly, the commonly occurring practices of simply switching circuitbreakers off, and placing insulation tape over them, when a circuit needs to be isolated, or merely removing a fuse and leaving it on top of the distribution board are not acceptable and do not give compliance with Regulation 13 as stated above. Moreover, to leave a circuit which is intended to be safely isolated unsecured is totally unnecessary and potentially dangerous. It should be noted at this point that it is not necessary to lock off a means of isolation which remains, at all times, under the control of the person who is dependent upon the continued isolation of the circuit or item of equipment in question, although doing so may still be wise where this is possible. HSE and SELECT (the Electrical Contractors Association of Scotland) have produced a guide on safe isolation procedures. This may be accessed and downloaded at the following internet address: http://www.select.org.uk/ downloads/publications/ Select%20-%20Safe%20 Isolation%20Procedures.pdf The HSE / SELECT guide was used as the basis of a similar, later guide produced by the Electrical Safety Council in association with a number of organisations having an interest in electrical safety, including the IET. This guide may be accessed at the following internet address: http://www.esc.org.uk/pdfs/ business-and-community/ electrical-industry/bpg2_08.pdf Locking devices Employers should ensure that appropriate locking devices are made available to their employees (as defined in the Health and Safety at Work etc Act 1974) and to ensure that they are used when it is necessary to isolate circuits or items of equipment fed from live distribution boards. Most switchgear manufacturers now produce Specialist Electrical Training & Consultancy High voltage accredited courses & competence HV safety training: land based & marine/offshore assessment, including: power systems HV authorised person training courses HV safety training: land based & marine/offshore LV authorised person training power systems Electrical protection & switchgear maintenance HV authorised person training courses 17th Edition Wiring Regulations Electrical protection & switchgear maintenance HV 17 th safety rules auditing and developing HV sanction Edition Wiring for test Regulations ROV HV safety HV safety rules operation auditing and developing Electrical Electrical equipment Testing in hazardous area Electrical Basic Electrical for non-electrical Safety personnel Live Electrical testingequipment on AC & DC in Hazardous systems Area Industrial Electrical electrical for Non-electrical plant maintenance Personnel Basic electrical safety training Training centres in the UK & Cyprus Training centres in the UK & Cyprus The Faraday Centre Tel: 01642 467236 www.faradaycentre.co.uk Tel: 01642 467236 www.faradaycentre.co.uk MoD ELCAS Approved Training Provider Qualifications with appeal We ve got it covered EAL - leading the field in engineering vocational qualifications Tel: +44 (0) 870 240 6889 Fax: +44 (0) 870 240 6890 Email: customercare@eal.org.uk www.eal.org.uk

14 Safety Isolation of low voltage installations Examples of readily available lock-out devices for use with circuit-breakers Devices Standard Isolation (5) Emergency Functional switching (2) switching Switching device BS 3676: Pt 1 1989 Yes (4) Yes Yes BS EN60669-1 No Yes Yes BS EN60669-2-1 No No Yes BS EN60669-2-2 No Yes Yes BS EN60669-2-3 No Yes Yes BS EN60669-2-4 Yes Yes Yes BS EN60947-3 Yes (1) Yes Yes BS EN 60947-5-1 No Yes Yes Contactor BS EN 60947-4-1 Yes (1) Yes Yes BS EN 61095 No No Yes Circuit-breaker BS EN 60898 Yes Yes Yes BS EN 60947-2 Yes (1) Yes Yes BS EN 61009-1 Yes Yes Yes RCD BS EN 60947-2 Yes (1) Yes Yes BS EN 61008-1 Yes Yes Yes BS EN 61009-1 Yes Yes Yes Isolation Switch BS EN 60669-2-4 Yes Yes Yes BS EN 60947-3 Yes Yes Yes Plug and socket-outlet ( 32 A) BS EN 60309 Yes No Yes IEC 60884 Yes No Yes IEC 60906 Yes Yes Yes Plug and socket-outlet (>32 A) BS EN 60309 Yes No No Device for the connection BS IEC 61995-1 Yes (3) No No of luminaire Control and protective switching BS EN 60947-6-1 Yes Yes Yes device for equipment (CPS) BS EN 60947-6-2 Yes (1) Yes Yes Fuse BS88 Yes No No Device with semiconductors BS EN 60669-2-1 No No Yes Luminaire Supporting Coupler BS 6972 Yes (3) No No Plug and unswitched socket-outlet BS 1363-1 Yes (3) No Yes BS 1363-2 Yes (3) No Yes Plug and switched socket-outlet BS 1363-1 Yes (3) No Yes BS 1363-2 Yes (3) No Yes Plug and socket-outlet BS 5733 Yes (3) No Yes Switched fused connection unit BS 1363-4 Yes (3) Yes Yes Unswitched fused connection unit BS 1363-4 Yes (3) No No (removal of fuse link) Fuse BS1362 Yes No No Cooker Control Unit switch BS4177 Yes Yes Yes Yes - Function provided No - Function not provided (1) Function provided if the device is suitable and marked with the symbol for isolation ( see BS EN 60617 identity number S00288). (2) See Regulation 537.4.2.5 (3) Device is suitable for on-load isolation, i.e. disconnection whilst carrying load current. (4) Function provided if the device is suitable and marked with (5) In an installation forming part of a TT or IT system, isolation requires disconnection of all the live conductors. See Regulation 537.2.2.1. Examples of lock-out devices which may be obtained from switchgear manufacturers free of charge Table 53.2: Guidance on the selection of protective, isolation and switching devices locking devices that allow a range of moulded case circuit breakers (MCCBs), circuitbreakers (formerly known as MCBs) and RCBOs to be padlocked in the OFF position. A number of manufacturers will now provide lock-out kits designed for use with their Universal lock-out device shown separately and securing a consumer unit main switch in the OFF position

16 Safe Isolation of low voltage installations Examples of lock-out devices permitting more than one person to apply a lock for reasons of safety Fused connection unit isolated by means of a small padlock products free of charge upon request. There are also a number of manufacturers of safety equipment that produce a range of universal circuitbreaker locking kits and other products allowing the secure isolation of virtually any type of switching device or even domestic and industrial type plugs and socket-outlets. In situations where a number of persons are reliant upon a single isolation device remaining in the OFF position, a number of devices which permit the use of multiple locks are also available as can be seen above. In many cases fused Use of proving unit to verify functionality of voltage indicator connection units (commonly, but incorrectly referred to as fused spurs) can have the fuse carrier secured in the OPEN position as shown using a padlock thus providing an effective means of isolating equipment being supplied by the connection unit. Whenever an electrical installation, circuit or item of equipment is secured in the OFF position by use of a lock, the key to the lock should be taken away and kept under the control of the person relying upon the safe isolation remaining effective. Similarly where a fuse has been removed to effect isolation, the fuse and any spare fuses in close proximity to the distribution board or consumer unit should be retained under the control of the person relying upon the isolation remaining effective. Voltage indicating devices and proving units In order to carry out the safe isolation of an installation or part thereof it will be necessary to use a voltage indicating device. HSE state clearly in guidance note GS 38 - Electrical test equipment for use by electricians that contact type voltage detectors and test lamps specifically designed to identify whether or not a voltage is present should be used for this purpose. The use of multirange instruments is not recommended as it is possible to select an inappropriate range setting; the leads may not be sufficiently robust; and the probes may have excessive bare metal exposed; all of which may possibly put the user in danger. Reliance on non-contact type voltage indicators is also not recommended for use as the sole means of confirming that a circuit or piece of equipment has been made dead. A wide range of contact type voltage indicating device are available as can be seen from the images included in this article. The general condition of a voltage indicator should be checked prior to each use and especially if the instrument has not been used for some time. Particular attention should be paid to the outer casing, leads, and probes. Only the minimum amount of probe should be exposed to allow the instrument to be used correctly. If a voltage indicator shows significant damage or deterioration, the voltage indicating device, or where appropriate, the component parts in question, such as tips and lamps, should be replaced before further use. The functionality of a voltage indicating device must be confirmed prior to each use. This can be achieved by checking on a known supply or perhaps more conveniently by using a proving unit such as the one shown. Basic Safe isolation procedure The following steps are the minimum that would be expected in terms of confirming safe isolation of a circuit or item of equipment. Locate / positively identify correct isolation point or device Check condition of voltage indicating device Confirm that voltage indication device is functioning correctly Switch off installation / circuit to be isolated Verify with voltage indicating device that no voltage is present Re-confirm that voltage indicating device functions correctly on known supply / proving unit Lock-off or otherwise secure device used to isolate installation / circuit Post warning notice(s) Any warning notice posted should convey in simple terms that the installation, circuit or item of equipment has been

Safe Isolation of low voltage installations 17 deliberately disconnected from the supply. It should inform the reader that care must be taken to ensure the safety of persons who are reliant upon the continued effectiveness of the isolation and should state that the installation, circuit or equipment should not be reenergised until it has been confirmed that it is safe to do so. The health implications The health implications which may be experienced as a result of a failure to correctly isolate before working on or near conductors or equipment intended to be dead are Physiological shock in the short term this might be manifested as nausea and disorientation and in the longer term, a loss of confidence Involuntary muscular action resulting in injury in such cases, injury may occur directly as a result of a muscular reaction sufficiently violent to tear muscle, break bones or dislocate joints, or indirectly as a result for example of falling from a ladder or from impact with objects in close proximity to the person receiving the shock Burns and tissue damage depending upon the amount of energy expended at the points of contact (an electric shock characteristically leaves both an entry and an exit wound), burns may range from relatively superficial levels of tissue damage causing discomfort but no long term damage, through to deep seated burns causing a medical condition known as compartment syndrome the effects of which can be necrosis (tissue death). This may necessitate amputation of fingers or limbs to prevent the onset of complications such as gangrene. Any current will travel along the path to earth offering the least resistance. In the case of human tissue, nerves and blood vessels offer the least resistance whilst bones offer the highest resistance. As a result, damage to the circulatory and nervous system occur frequently Renal (kidney) damage, which may range from being minor to long term and severely debilitating Atrial fibrillation - an irregularity in the rhythm of the heartbeat somewhat less severe than ventricular fibrillation. In most cases, a condition that can be reversed with typically few or no long term complications Myocardial infarction - heart attack caused by the presence of a blood clot within the coronary artery Ventricular fibrillation the most common cause of death from electrocution, which generally occurs immediately In the case of an alternating current and assuming a hand contact, the average person will be aware of a current passing through their body at around 0.5 ma. Such a current level will not have a detrimental effect. A person generally loses the ability to break contact with the live part at around 10 ma and beyond this level, ventricular fibrillation (an erratic heart beat characterised by an inability to circulate sufficiently oxygenated blood around the body) may occur and may result in death. Currents above 2 A will result in the heart stopping. The likelihood of ventricular fibrillation occurring is dependent upon a number of factors: Skin resistance sweat dramatically lowers resistance of skin whilst hardness (typical of manual labour activities), dryness and presence of dirt typically raise skin resistance The path of the current through the body by way of example, the risk factor is 2 ½ times higher for a hand to foot contact than for a hand to hand contact. It is worth mentioning at this point that hand to hand contact electric shocks are thought to account for approximately 60% of fatalities The magnitude and type of current human tissue is most sensitive to currents at frequencies between 40 Hz and 150 Hz The duration of the current the more prolonged the contact time, the greater the damage caused by the shock The magnitude of the voltage in general, the higher the voltage the higher the risk of shock When, during the heart s cycle, the shock occurs The legal consequences Employers or employees who commit an offence as a result of a failure to comply with the requirements of the Electricity at Work Regulations 1989 can be prosecuted under the Health and Safety at Work etc. Act 1974. On 16th January 2009 the Health and Safety (Offences) Act 2008 came into force. This Act has the effect of increasing penalties and providing courts with greater sentencing powers for those who break health and safety legislation. To summarise, the Health and Safety (Offences) Act 2008 introduces a new schedule 3A to the Health and Safety at Work etc. Act 1974 and to the Health and Safety at Work (Northern Ireland) Order 1978. This new schedule: Raises the maximum fine which may be imposed in the lower courts to 20,000 for most health and safety offences Allows certain offences, which were previously only pursuable in the lower courts, to be triable in either the lower or higher courts Makes the imposition of a prison sentence an option for more health and safety offences in both the lower and higher courts Prosecutions are likely to be made against employers and employees considered to have breached health and safety legislation. References (and useful sources for further reading) BS 7671: 2008 - IET DD IEC/TS 60479-1: 2005 Effects of current on human beings and livestock. Part 1 General characteristics Electrical injuries and lightning strikes www.patient.co.uk Electrical test equipment for use by electricians (GS 38) HSE Electricity at Work Regulations (EWR) 1989 The Stationery Office Ltd Health and Safety (Offences) Act 2008 The Stationery Office Ltd Memorandum of Guidance on the Electricity at Work Regulations 1989 (HSR 25) HSE Acknowledgements Images of Martindale voltage indicator, Martindale proving unit and Drummond test lamp were reproduced with the kind permission of Martindale Electric Company Ltd Thanks are also extended to Schneider Electric Limited and Hager Engineering Ltd for providing samples of lock-out devices and circuit-breakers for use in some of the images contained in this article.