Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling



Similar documents
MAC-120HE-01 Air-Cooled Chiller

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Calculating System Flow Requirements

Cooling kw Heating kw

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Solar Thermal TECHNOLOGY. Eric Buchanan Renewable Energy Scientist West Central Research and Outreach Center Wcroc.cfans.umn.edu

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

GLOBACON 05 HVAC Systems for Cogen

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Nirvana. Cycling Refrigerated Dryers

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

2A.1 Features of Chiller Control Components A.3 Chilled-Water Supply Temperature Control A.4 Cooling-Water Supply Control...

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

DATA CENTER SOLUTIONS. For More Information: (866) Technical Data

Defining Quality. Building Comfort. Heating and Cooling Coils

Product Data. Features/Benefits

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, Instruction No.

An Overview of Solar Assisted Air-Conditioning System Application in Small Office Buildings in Malaysia

How To Understand Evaporator

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

HVAC Simplified Approach Option

2015 HVAC Excellence Educator Conference Variable Refrigerant Flow & Variable Refrigerant Temperature

Chilled Water HVAC Systems

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Building Energy Systems. - HVAC: Heating, Distribution -

Product Data. 16DNH 20% Energy Saving Model, Direct-Fired, Double Effect, Hermetic Absorption Liquid Chiller/Heater

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

UNIT 2 REFRIGERATION CYCLE

MUELLER FALLING FILM CHILLERS

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

White Paper #10. Energy Efficiency in Computer Data Centers

Two-Phase Evaporative Precision Cooling Systems

D SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43

USER S MANUAL HSC-24A

Absorption. LG HVAC Solution.

Oil and Coolant Circulating Heating System. Model - OCSM

Commercial Gas Water Heater

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

Maxi Pressurisation Units (Maxi, Maxi Plus & HP)

SWIMMING POOL HEAT PUMP

NSN

TANKLESS DURABILITY Tankless Product Guide

Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX

Chapter 3.4: HVAC & Refrigeration System

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

SOLI TANKLESS PRODUCT GUIDE

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.

Ceiling Mount Air Handler Manual

Innovent LASER Packaged Fresh Air Conditioning Units

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Lesson 36 Selection Of Air Conditioning Systems

Nordic Heat Pump Product Guide

CGC s Hybrid System Loop Control

SWIMMING POOL HEAT PUMP Owners Manual

REFRIGERATED COMPRESSED AIR DRYERS

Technical data. Danfoss DHP-A

SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: Fax:

Air Conditioning Clinic

GEOTHERMAL HEATING AND COOLING INTRODUCTION

HVAC Systems: Overview

How To Clean Water From An Ammonia Refrigeration System

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

INSTALLATION MANUAL. Address card EKAC10B

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

CA SERIES. Available in sizes from 3/4 through 1-1/4 tons the CA Series offers a wide range of features such as:

Refrigeration Basics 101. By: Eric Nelson

ECOCIAT. Domestic hot water heat recovery unit

State of the Art Energy Efficient Data Centre Air Conditioning

presents Hydraulic Separation Beyond Primary / Secondary Piping

Small-Scale Solar Heating and Cooling Systems

AIR-COOLED CONDENSERS Technical Guide

Commercial Semi-Instantaneous Water Heaters

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

Tempra / DHC-E. Simply the Best The Finest Tankless Electric Water Heater Available! Featuring Advanced Microprocessor Control

HVAC Processes. Lecture 7

How To Use A Water Source Heat Pump

SONNENKLIMA package solution description

HOT WATER SYSTEMS CONTENTS

CRAC Precision climate control units for data centres

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: Uptime Racks:

Contents. Introduction

HP switch LP switch Discharge thermo Comp. Surface thermo

SECTION AIR COOLED WATER CHILLERS

Condensing unit type EPSILON-ECHOS LE Technical information manual

CoolTeg Plus Chilled Water (CW) version: AC-TCW

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

AFHX Guide Specifications

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Liebert DS Thermal Management Unit

Air Conditioners Technical Data

Transcription:

Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H

Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle Yazaki water fired SINGLE-EFFECT chillers or chiller-heaters have cooling capacities of 1, 2 and 3 tons of refrigeration and produce chilled water for cooling or hot water for heating in comfort air conditioning applications. The absorption cycle is energized by a heat medium (hot water) at 158 o F to 23 o F from an industrial process, cogeneration system, solar energy or other heat source and the condenser is water cooled through a cooling tower. The Yazaki absorption chiller or chiller-heater uses a solution of lithium bromide and water, under a vacuum, as the working fluid. Water is the refrigerant and lithium bromide, a nontoxic salt, is the absorbent. Refrigerant, liberated by heat from the solution, produces a refrigerating effect in the evaporator when cooling water is circulated through the condenser and absorber. GENERATOR CONDENSER COOLING/ HEATING CHANGE- OVER VALVE ORIFICE ABSORBER Dilute Solution Concentrated Solution Refrigerant Vapor Refrigerant Liquid Cooling Water Chilled Water Chilled Water Cooling Water SOLUTION PUMP EVAPORATOR HEAT EXCHANGER Generator When the heat medium inlet temperature exceeds 154.4 o F, the solution pump forces dilute lithium bromide solution into the generator. The solution boils vigorously under a vacuum and droplets of concentrated solution are carried with refrigerant vapor to the primary separator. After separation, refrigerant vapor flows to the condenser and concentrated solution is precooled in the heat exchanger before flowing to the absorber. Condenser In the condenser, refrigerant vapor is condensed on the surface of the cooling coil and latent heat, removed by the cooling water, is rejected to a cooling tower. Refrigerant liquid accumulates in the condenser and then passes through an orifice into the evaporator. 2

Evaporator In the evaporator, the refrigerant liquid is exposed to a substantially deeper vacuum than in the condenser due to the influence of the absorber. As refrigerant liquid flows over the surface of the evaporator coil it boils and removes heat, equivalent to the latent heat of the refrigerant, from the chilled water circuit. The recirculating chilled water is cooled to 44.6 o F and the refrigerant vapor is attracted to the absorber. Absorber A deep vacuum in the absorber is maintained by the affinity of the concentrated solution from the generator with the refrigerant vapor formed in the evaporator. The refrigerant vapor is absorbed by the concentrated lithium bromide solution flowing across the surface of the absorber coil. Heat of condensation and dilution are removed by the cooling water and rejected to a cooling tower. The resulting dilute solution is preheated in a heat exchanger before returning to the generator where the cycle is repeated. Heating Cycle GENERATOR CONDENSER Dilute Solution Concentrated Solution COOLING/ HEATING CHANGE- OVER VALVE ORIFICE ABSORBER Refrigerant Vapor Refrigerant Liquid Hot Water Hot Water SOLUTION PUMP EVAPORATOR HEAT EXCHANGER Generator When the heat medium inlet temperature exceeds 154.4 o F, the solution pump forces dilute lithium bromide solution into the generator. The solution boils vigorously under a vacuum to generate refrigerant vapor and droplets of concentrated solution. Since the changeover valve is open during heating operation, the mixture of refrigerant vapor and concentrated solution flows directly into the evaporator. Some refrigerant vapor flows through the condenser before reaching the evaporator. Evaporator Hot refrigerant vapor condenses on the surface of the evaporator coil and heat, equivalent to the latent heat of the refrigerant, is transferred to the hot water circuit. The recirculating water is heated to 131 o F. Refrigerant liquid mixes with concentrated lithium bromide solution and the resulting dilute solution returns to the generator where the cycle is repeated. 3

Features Control Characteristics Absorption cycle energized by hot water at 158 o F to 23 o F from process, cogeneration, solar or other waste heat sources. Safe, odorless, non-toxic working fluids of lithium bromide and water operate under a vacuum at all times. Supplied as a chiller only or a chillerheater for applications that require separation of heating water and heat medium circuits due to glycol, operating pressure, flow or piping limitations. Crystallization prevented in the generator by utilizing a solution pump and gravity drain-back system. Single hermetic pump controls solution flow. Faster cold start-up time than similar chillers with flooded generators. Chilled water and hot water outlet temperatures controlled by a built-in microprocessor with outputs to control a 3-way valve and/or heat medium pump (supplied by others). 1 COOLING All chillers and chiller-heaters supplied with a standard weatherproof cabinet suitable for outdoor installation. Built-in shutdown controls for high heat medium temperature and abnormal cooling water conditions. Cooling capacities increased at 85 o F cooling water and when energized by 23 o F heat medium. Ideal for a two pipe hydronic system in which chilled or hot water is circulated to a central airhandling unit or multiple fan-coil units. Cooling or heating operation on chiller-heaters can be selected from a remote or built-in switch. Only 3 minute delay required for operation changeover. Transportation and lifting are simplified because of modular construction. Factory charged and performance tested. UL Listed for USA and Canada. Capacity (%) 75 5 25 Minimum Limit 4.1 43.7 47.3 5.9 54.5 58.1 61.7 65.3 41.9 45.5 49.1 52.7 56.3 59.9 63.5 67.1 Chilled Water Outlet Temperature ( o F) Maximum Limit 1 HEATING 4 Capacity (%) 75 5 25 Minimum Limit 113.9 117.5 121.1 124.7 128.3 131.9 135.5 139.1 115.7 119.3 122.9 126.5 13.1 133.7 137.3 14.9 Standard Rating Point Hot Water Outlet Temperature ( o F) Maximum Limit Standard Control Settings

Application (Water Fired Cooling & Heating System - Cooling Operation) * Dilute Solution FAN COIL UNIT Cooling Water COOLING TOWER Concentrated Solution Refrigerant Vapor Chilled Water * Cooling/Heating Changeover Valve supplied on Chiller-Heaters only Refrigerant Liquid Specifications WATER FIRED CHILLER-HEATER Model WFC SC1 SH1 SC2 SH2 SC3 SH3 Cooling Capacity (Btu/hr x 1) 12. 24. 36. Chilled Water Temp. ( o F) 44.6 Outlet, 54.5 Inlet Heating Capacity (Btu/hr x 1) 166.3 332.6 498.9 Hot Water Temp. ( o F) 13 Outlet, 117.3 Inlet Rated Water Flow (gpm) 24.2 48.4 72.6 Chilled/Hot Water Evap. Press Drop (psi) 8.1 9.6 1.1 Water Retention Volume (gal) 4.5 12.4 19.3 Heat Rejection (Btu/hr x 1) 29 582.8 874.2 Inlet Temperature ( o F) 87.8 (Standard) Cooling Water *Rated Water Flow (gpm) 8 161.7 242.5 Cond./Abs. Press. Drop (psi) 12.3 6.6 6.7 Water Retention Volume (gal) 17.4 33. 51.3 Input (Btu/hr x 1) 17 342.8 514.2 19 (Standard) Inlet Temperature ( o F) Heat Temperature Range 158 (min.) - 23 (max.) Medium Rated Water Flow (gpm) 38. 76.1 114.1 Generator Press. Drop (psi) 13.1 6.7 8.8 Water Retention Volume (gal) 5.5 14.3 22.2 Electrical Power Supply 28V, 6Hz, 3 ph Consumption (W) 21 26 31 Capacity Control On - Off Noise Level Sound Pressure db(a) 49 49 46 Chilled/Hot Water (in) 1-1/2 NPT 2 NPT 2 NPT Piping Cooling Water (in) 2 NPT 2 NPT 2-1/2 NPT (in) 1-1/2 NPT 2 NPT 2-1/2 NPT Weight Dry (lb) 1,1 2,5 3,2 Operating (lb) 1,329 2,548 3,975 * Minimum cooling water flow NOTES: 1. Specifications are based on water in all circuits and fouling factor of.5 ft 2 hr o F/Btu. 2. Do not exceed 85.3 psi operating pressure in any water circuit. 3. If heat medium inlet temperature exceeds 23 o F the chiller/chiller-heater will shutdown and require manual reset. 4. Optional cooling water crossover piping with 3 in. type L copper connections available for WFC-SC2/SH2 and WFC-SC3/SH3. 5. Sound pressure noise level measured in a free field at a point 79 in. behind the chiller/chiller-heater and 59 in. above the ground. 5

Performance Characteristics 1.6 WFC-SC1/SH1 (44.6 o F CHILLED WATER) WFC-SC2/SH2 (44.6 o F CHILLED WATER) Cooling Capacity Factor Cooling Water Inlet Temp. 8 o F 85 o F 87.8 o F Cooling Capacity Factor Cooling Water Inlet Temp. 8 o F 85 o F 87.8 o F 1.6 Cooling Water Inlet Temp. 8 o F 85 o F 1.6 Cooling Water Inlet Temp. 8 o F 85 o F Heat Input Factor 87.8 o F Heat Input Factor 87.8 o F Hot Water Outlet Temp. 131 o F Hot Water Outlet Temp. 131 o F Heating Capacity Factor 158 o F (MIN) 23 o F (MAX) Heating Capacity Factor 158 o F (MIN) 23 o F (MAX) 6 15 16 17 18 19 2 21 Inlet Temperature ( o F) 15 16 17 18 19 2 21 Inlet Temperature ( o F)

WFC-SC3/SH3 (44.6 o F CHILLED WATER) Cooling Water Inlet Temp. 8 o F HM FLOW CORRECTION (44.6 o F CHILLED WATER) Cooling Capacity Factor 85 o F 87.8 o F Flow Correction 3% (MIN) 1.6 2 4 6 8 1 12 Flow (%) Heat Input Factor Cooling Water Inlet Temp. 8 o F 85 o F 87.8 o F NOTES: 1. designates Standard Rating Point. 2. Capacity and Heat Input curves based on standard water flow rates in all circuits. 3. Flow Correction curve only applicable for heat medium inlet temperatures of 176 o F to 23 o F. Hot Water Outlet Temp. 131 o F 4. Heating Efficiency = 97%. 5. Performance based on standard fouling factor of.5 ft 2 hr o F/Btu in all circuits. Heating Capacity Factor 158 o F (MIN) 23 o F (MAX) 6. Performance data may be interpolated but must not be extrapolated. 7. Expanded performance curves are provided for reference only. Contact Yazaki Energy Systems, Inc. to obtain certified performance ratings from the factory or to determine performance at other conditions outside the scope of this publication. 15 16 17 18 19 2 21 Inlet Temperature ( o F) 7

ABSORPTION CHILLER HEAT BALANCE HEAT IN = HEAT OUT Where, Qg + Qe = Qc Qg = Heat input to generator Qe = Cooling capacity Qc = Heat rejected to cooling tower COOLING CAPACITY CLG. CAP. HM FLOW STD. CLG. Qe = x x FACTOR CORRECTION CAPACITY HEAT INPUT (COOLING) HEAT INPUT HM FLOW STD. HEAT Qg = x x FACTOR CORRECTION INPUT HEATING CAPACITY HTG. CAP. HM FLOW STD. HTG. Qh = x x FACTOR CORRECTION CAPACITY Where, Qh = Heating Capacity HEAT INPUT (HEATING) HEATING CAPACITY Qg = = Qh EFFICIENCY.97 TEMPERATURE DIFFERENCE ( o F) ADJUSTED CAPACITY OR HEAT INPUT (MBH) T=.5 x FLOW (gpm) PRESS. DROP FOR NONSTANDARD FLOW (psi) STANDARD P= x NONSTANDARD FLOW 2 PRESS. DROP STANDARD FLOW EXAMPLE 1. Given design conditions: Heat medium inlet temperature...195 o F Heat medium flow...114.1 gpm Cooling water inlet temperature...85 o F Cooling water flow...242.5 gpm Chilled water outlet temperature...44.6 o F Hot water outlet temperature...131 o F Chilled/hot water flow...72.6 gpm Absorption chiller-heater model...wfc-sh3 Refer to Capacity Factor curves and Specifications for model WFC-SC3/SH3. Since 114.1 gpm is standard, the (HM) Flow Correction is. 1. AVAILABLE COOLING CAPACITY: ( Cooling Capacity Factor = 1.12 Flow Correction = Standard Cooling Capacity = 36. MBH Qe = 1.12 x x 36. = 43.2 MBH (33.6 tons) 43.2 Chilled Water T = = 11.1 o F.5 x 72.6 Chilled Water P = 1.1 psi (Standard) ( 2. HEAT INPUT (COOLING): Heat Input Factor = 1.17 Flow Correction = Standard Heat Input = 514.2 MBH Qg = 1.17 x x 514.2 = 61.6 MBH 61.6 T = = 1.5 o F.5 x 114.1 P = 8.8 psi (Standard) 3. HEAT REJECTED TO COOLING TOWER: Qc = Qg + Qe = 61.6 + 43.2 = 14.8 MBH 14.8 Cooling Water T = = 8.3 o F.5 x 242.5 Cooling Water P = 6.7 psi (Standard) 4. AVAILABLE HEATING CAPACITY: Heating Capacity Factor = 1.12 Flow Correction = Standard Heating Capacity = 498.9 MBH Qh = 1.12 x x 498.9 = 558.8 MBH 558.8 Hot Water T = = 15.4 o F.5 x 72.6 Hot Water P = 1.1 psi (Standard) 5. HEAT INPUT (HEATING): Qg = EXAMPLE 2. Qh 558.8 =.97.97 = 576.1 MBH 576.1 T = = 1.1 o F.5 x 114.1 P = 8.8 psi (Standard) Given design conditions: Heat medium inlet temperature...23 o F Heat medium flow...57. gpm Cooling water inlet temperature...85 o F Cooling water flow...242.5 gpm Chilled water outlet temperature...44.6 o F Hot water outlet temperature...131 o F Chilled/hot water flow...72.6 gpm Absorption chiller-heater model...wfc-sh3 Refer to Capacity Factor curves and Specifications for model WFC-SC3/SH3. Since 57. gpm is 5% of standard, the Heat Medium (HM) Flow Correction is 6. 1. AVAILABLE COOLING CAPACITY: Cooling Capacity Factor = 2 Flow Correction = 6 Standard Cooling Capacity = 36. MBH Qe = 2 x 6 x 36. = 377.7 MBH (31.5 tons) 377.7 Chilled Water T = = 1 o F.5 x 72.6 Chilled Water P = 1.1 psi (Standard) 8

2. HEAT INPUT (COOLING): Heat Input Factor = 1.35 Flow Correction = 6 Standard Heat Input = 514.2 MBH Qg = 1.35 x 6 x 514.2 = 597. MBH 597. T = = 2.9 o F.5 x 57. 2 57. P = 8.8 x ( = 2.2 psi 114.1 3. HEAT REJECTED TO COOLING TOWER: Qc = Qg + Qe = 597. + 377.7 = 974.7 MBH 974.7 Cooling Water T = = 8. o F.5 x 242.5 Cooling Water P = 6.7 psi (Standard) ( 4. AVAILABLE HEATING CAPACITY: Heat Capacity Factor = 1.33 Flow Correction = 6 Standard Heating Capacity = 498.9 MBH Qh = 1.33 x 6 x 498.9 = 57 MBH 57 Hot Water T = = 15.7 o F.5 x 72.6 Hot Water P = 1.1 psi (Standard) 5. HEAT INPUT (HEATING): Qg = Qh = 57 = 588.2 MBH.97.97 588.2 T = = 2 o F.5 x 57. 57. 2 P = 8.8 x ( = 2.2 psi 114.1 ( Cooling Water Crossover Piping (Optional) The condenser and absorber of chiller/chiller-heater models WFC-SC2/SH2 and WFC-SC3/SH3 are connected in parallel by cooling water crossover piping installed at the jobsite. If this piping is fabricated at the jobsite by others it must be designed in accordance with the following recommendations to ensure balanced flow through the condenser and absorber: 1. Branch piping is 2 in. (WFC-SC2/SH2) or 2-1/2 in. (WFC-SC3/SH3). 2. Common inlet and outlet piping is 3 in. NOTES: 1. All pipe (or tube) sizing is nominal. 2. Install a manual balancing valve in the branch cooling water circuits to the condenser and absorber if flow is unbalanced due to changes in the piping configuration or pipe sizes. COOLING WATER OUTLET 3 PIPE UNION 2 NPT (WFC-SC2/SH2) 2-1/2 NPT (WFC-SC3/SH3) CONDENSER BRANCH CROSSOVER 2 PIPE (WFC-SC2/SH2) 2-1/2 PIPE (WFC-SC3/SH3) ABSORBER BRANCH CROSSOVER 2 PIPE (WFC-SC2/SH2) 2-1/2 PIPE (WFC-SC3/SH3) COOLING WATER INLET 3 PIPE 9

Typical Piping COOLING TOWER CW CONTROL VALVE M Cooling Water Outlet Condenser Water Inlet T Outlet Inlet T Air Vent HM BYPASS VALVE CT SWITCH P P CW TEMP. SWITCH Flush Valve T CHILLER/ CHILLER- HEATER T FREEZE SWITCH T T Air Vent P M HM PUMP LIMIT SWITCH P P P Drain Water Supply CW PUMP Flush Valve/ Drain Absorber Water Outlet ----------- Crossover piping for WFC-SC2/ SH2 and WFC-SC3/SH3 only. Cooling Water Inlet Chilled/ Hot Water Outlet Chilled/Hot Water Inlet FREEZE SWITCH Drain CHILLED/HOT WATER PUMP Typical Field Wiring CT (COOLING TOWER) SWITCH T CW (COOLING WATER) TEMP. SWITCH T OPTIONAL JUNCTION BOX CONNECTIONS OPTIONAL CONTROL BOX CONNECTIONS CW (COOLING WATER) CONTROL VALVE M COOLING WATER PUMP CHILLED/HOT WATER PUMP POWER BOX (Supplied by others) CHILLER/ CHILLER- HEATER COOLING TOWER LIMIT SWITCH M HM PUMP Wiring (Number of conductors) OPTIONAL JUNCTION BOX CONNECTIONS Remote cooling/heating mode selection (Model SH only) Remote start/stop selection (All models) Cooling tower fan control output (Alternative to CT Switch) Heating/cooling mode status Microturbine or engine override control output General shutdown alarm output HM BYPASS VALVE Optional methods of controlling (HM) input to chiller/chiller-heater. FUSED DISCONNECTS Power Supply (28V, 6Hz, 3 ph) OPTIONAL CONTROL BOX CONNECTIONS Heat medium supply shutdown control output Auxiliary boiler control output Heat available input (Temp. switch supplied by others) Cooling water flow input (Flow switch supplied by others) OPTIONAL I/O BOARD CONNECTIONS OPTIONAL I/O BOARD CONNECTIONS Shutdown interlock (Additional interlock) Freeze protection switch inputs for chilled/hot water and heat medium circuits (Temp. switches supplied by others) Chiller-heater standby status Operating status General fault alarm output 1

Dimensions WFC-SC1/SH1 LEFT SIDE FRONT REAR WFC-SC2/SH2 LEFT SIDE FRONT REAR WFC-SC3/SH3 LEFT SIDE FRONT REAR All Dimensions In Inches 11

YAZAKI SALES REPRESENTATIVE/DISTRIBUTOR For information concerning sales, operation, application or technical assistance, please contact your Yazaki Sales Representative/Distributor or the following: YAZAKI ENERGY SYSTEMS, INC. 1374 OMEGA RD., DALLAS, TEXAS 75244-4516 Phone: 972-385-8725 Fax: 972-385-1324 Email: yazaki@yazakienergy.com Web: www.yazakienergy.com Yazaki reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. SB-WFCS-93