OPTIMAL DG PLACEMENT BASED ON STATIC SECURITY ASSESSMENT



Similar documents
Application of GA for Optimal Location of FACTS Devices for Steady State Voltage Stability Enhancement of Power System

Optimal Branch Exchange for Feeder Reconfiguration in Distribution Networks

A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

A Method for Assessing Relative Value of Central Generation and Distributed Energy Resources (DERs) in Distribution Feeders

Distributed Generation and Power Quality Case Study

OPTIMAL DISPATCH OF POWER GENERATION SOFTWARE PACKAGE USING MATLAB

Power System Security in Market Clearing and Dispatch Mechanisms

Phase Balancing of Distribution Systems Using a Heuristic Search Approach

SOFTWARE FOR THE OPTIMAL ALLOCATION OF EV CHARGERS INTO THE POWER DISTRIBUTION GRID

Chapter 5. System security and ancillary services

Linear AC Power Flow for Disaster Management

A Reactive Tabu Search for Service Restoration in Electric Power Distribution Systems

Dynamic Security Assessment in the Future Grid. Vijay Vittal Ira A. Fulton Chair Professor Arizona State University

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

Steady-State Power System Security Analysis with PowerWorld Simulator

IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS

Analysis of the Effect of Tap Changing Transformer on Performance of SVC

2Azerbaijan Shahid Madani University. This paper is extracted from the M.Sc. Thesis

SPEED CONTROL OF INDUCTION MACHINE WITH REDUCTION IN TORQUE RIPPLE USING ROBUST SPACE-VECTOR MODULATION DTC SCHEME

ENHANCEMENT OF POWER SYSTEM SECURITY USING PSO-NR OPTIMIZATION TECHNIQUE

EVALUATION OF VOLTAGE STABILITY INDICES BY USING MONTE CARLO SIMULATION

Phase Balancing of Unbalanced Distribution Network through Hybrid Greedy-Fuzzy Algorithm

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

Service restoration in naval shipboard power systems

Voltage Stability Improvement using Static Var Compensator in Power Systems

Radial Distribution Network Reconfiguration for Loss Reduction and Load Balancing using Plant Growth Simulation Algorithm

GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)

SIMULATION AND ASSESSMENT OF SINGLE PHASE SEMI-Z-SOURCE INVERTER (S-ZSI)

Hybrid processing of SCADA and synchronized phasor measurements for tracking network state

Optimal Power Flow Analysis of Energy Storage for Congestion Relief, Emissions Reduction, and Cost Savings

16 West Coast Regional Plan

OPTIMAL DISTRIBUTION PLANNING INCREASING CAPACITY AND IMPROVING EFFICIENCY AND RELIABILITY WITH MINIMAL-COST ROBUST INVESTMENT

USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SUPPLY TO A THREE-PHASE AC FOR CONTROLLING THE SPEED OF A THREE-PHASE INDUCTION MOTOR BY USING A THREE-PHASE TO THREE-PHASE CYCLOCONVERTER

Line Security Evaluation of WANS Considering Protectability of Relays and Vulnerability of Lines

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid

Modeling Simulation Technology Research for Distribution Network Planning *

Context: significant penetration of DG = increased risks for system security

Droop Control Forhybrid Micro grids With Wind Energy Source

Re-Dispatch Approach for Congestion Relief in Deregulated Power Systems

De Jaeger, Emmanuel ; Du Bois, Arnaud ; Martin, Benoît. Document type : Communication à un colloque (Conference Paper)

IESO Supply Deliverability Guidelines

Voltage regulation in distribution systems - Tap changer and Wind Power

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Optimal Feeder Reconfiguration with Distributed Generation in Three-Phase Distribution System by Fuzzy Multiobjective and Tabu Search

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System

LV4MV: A CONCEPT FOR OPTIMAL POWER FLOW MANAGEMENT IN DISTRIBUTION GRIDS, USING DER FLEXIBILITY

Neutral to Earth Voltage Reduction Methods in Three-Phase Four Wire Distribution Systems

AMSC s Superconductor Cable Technologies for Electric Utilities

A New Method for Estimating Maximum Power Transfer and Voltage Stability Margins to Mitigate the Risk of Voltage Collapse

Impact of electric vehicles on the IEEE 34 node distribution infrastructure

Modern Power Systems for Smart Energy Society

RENEWABLE ENERGY INFEED R Herman, M Malengret and CT Gaunt University of Cape Town, South Africa

Introduction to PowerWorld Simulator: Interface and Common Tools

A Direct Numerical Method for Observability Analysis

A Tariff for Reactive Power Christopher Tufon, Alan Isemonger, Brendan Kirby, Senior Member, John Kueck, Senior Member, and Fangxing Li, Senior Member

FLUID FLOW ANALYSIS OF CENTRIFUGAL FAN BY USING FEM

Weighted-Least-Square(WLS) State Estimation

A Design of DC/DC Converter of Photovoltaic Generation System for Streetcars

Power System Simulation for Engineers (PSS/E version 33)

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

International journal of Engineering Research-Online A Peer Reviewed International Journal Articles available online

Network Reconfiguration for Service Restoration in Shipboard Power Distribution Systems

A Flexible Machine Learning Environment for Steady State Security Assessment of Power Systems

ONE OF THE anticipated main benefits of a distribution

J. Electrical Systems 9-4 (2013): Regular paper

VOLATILITY AND DEVIATION OF DISTRIBUTED SOLAR

Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems

School of Electrical Engineering and Computer Science

Efficient Energy Management In India

IMPACT OF DISTRIBUTED SYSTEMS IN MANAGING CLOUD APPLICATION

Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing Switches

Review on Existing Load Balancing Techniques of Cloud Computing

A Novel Multi Ring Forwarding Protocol for Avoiding the Void Nodes for Balanced Energy Consumption

Reduction of Power Losses Using Phase Load Balancing Method in Power Networks

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report

DECENTRALIZED LOAD BALANCING IN HETEROGENEOUS SYSTEMS USING DIFFUSION APPROACH

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: [633] [Choudhary, 3(12): December, 2014] ISSN:

DYNAMIC ANALYSIS ON STEEL FIBRE

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

Risk of Large Cascading Blackouts

Power System Simulation for Engineers (PSS/E): Fault Analysis

Fleet Management and Grid Integration of PV Generating Stations

The design and performance of Static Var Compensators for particle accelerators

Distributed Flexible AC Transmission System (D FACTS) Jamie Weber ext. 13

LOW-COST ACTIVE SHIELD FOR MV/LV SUBSTATIONS

Renewable Energy Grid Integration

Software Implementation of Online Risk-Based Security Assessment

Advanced Network Management Systems: A Risk-Based AC OPF Approach

Iman Ziari. M.Sc, B.Eng (Electrical Engineering) A Thesis submitted in Partial Fulfillment of the Requirement for the Degree of. Doctor of Philosophy

CHAPTER 3 SECURITY CONSTRAINED OPTIMAL SHORT-TERM HYDROTHERMAL SCHEDULING

Online Risk-Based Security Assessment

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

IMPROVEMENT OF POWER QUALITY (PQ) BY UPQC (UNIFIED POWER QUALITY CONDITIONER) IN POWER SYSTEM USING ADAPTIVE NEURO FUZZY (ANFIS) TECHNIQUE

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

Risk Management for IT Security: When Theory Meets Practice

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

Transcription:

International Journal of Electrical Engineering & Technology (IJEET) Volume 7, Issue 2, March-April, 2016, pp.37 49, Article ID: IJEET_07_02_005 Available online at http:// http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=7&itype=2 ISSN Print: 0976-6545 and ISSN Online: 0976-6553 Journal Impact Factor (2016): 8.1891 (Calculated by GISI) www.jifactor.com IAEME Publication OPTIMAL DG PLACEMENT BASED ON STATIC SECURITY ASSESSMENT Gopala Reddy K Associate Professor, Department of E&EE, VVCE, Mysuru Dr. T. Ananthapadmanabha Professor, Department of E&EE, NIE, Mysuru Mohan N Assistant Professor, Department of E&EE, NIE IT, Mysuru Likith Kumar M V Assistant Professor, Department of E&EE, ATME CE, Mysuru ABSTRACT: The integration of distributed generation (DG) in distribution network may significantly affect its performance. Transmission networks are no longer accountable solely for voltage security issues in distribution networks with penetration of DGs. The reactive power support from the DG sources greatly varies with the type of DG units and may potentially distress the larger portion of the network from the voltage stability aspects. This paper presents the analysis for the selection of the best type of DG unit among different categories and its optimal location that can enhance the static security of distribution network with simultaneous improvement in voltage profile. Key words: Static Security Analysis (SSA), Static Security Index (SSI), DG, PF, Fast Approach, Line over Load Index (LOI) & Real Power Loss Reduction. Cite this Article: Gopala Reddy K., Dr. T. Ananthapadmanabha, Mohan N. and Likith Kumar M. V., Optimal DG Placement Based on Static Security Assessment. International Journal of Electrical Engineering & Technology, 7(2), 2016, pp. 37 49. http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=7&itype=2 http://www.iaeme.com/ijeet/index.asp 37 editor@iaeme.com

Gopala Reddy K., Dr.T. Ananthapadmanabha, Mohan N. and Likith Kumar M. V. 1. INTRODUCTION The integration of DG is expected to play an increasingly important role in the electric power system infrastructure planning and market operations. The integration of DG at the distribution network results in operating situations that do not occur in a conventional system without generation directly connected at the distribution level. Attention must be paid to effectively eliminate the potentially adverse impacts that DG penetration could impress on the electric delivery system. Inappropriate DG placement and sizing may increase system losses and network capital and operating costs. Hence, systematic studies and planning are required to locate and operate the DGs at the distribution level in order to improve voltage profile, to reduce system losses, and to enhance the stability. Power systems are expected to become more heavily loaded in the forthcoming years as the demand for electric power rises sharply. The economic and environmental concerns limit the construction of new transmission and generation capacity. This may result in deficit of local reactive power support in heavily loaded system which in turn causes the progressive voltage decline. The decline in voltage level is one of important factors which restrict the increase of load served by distribution companies. Therefore, it is necessary to consider Static Security constraints for planning and operation of distribution systems. As the main form of decentralized power supply, the proportion of the Distributed generation (DG) in the distribution network will be increasingly larger. The access of the DG will change the original flow distribution, the transmission line power, etc, which will be a great impact to the static stability of distribution network. Therefore, the static stability indicators and stability analysis are the premise and basis of measures to improve stability. DG has many advantages over centralized power generation, including reduction of power system losses and improved voltage profile. The optimum DG placement and sizing at planning stage of distribution system is necessary to achieve the maximum benefits. The non-optimum DG placement and sizing could results in increase power losses and affect the system voltage profile. However the optimum A method for DG placement in radial distribution network based on Voltage security margin (VSM) enhancement and loss reduction is presented in [15], which use CPF to identify the most sensitive bus to voltage collapse. The work in [16] is suggested that voltage magnitude is not a suitable indicator for the proximity to voltage collapse. A method is presented for locating and sizing of DGs to enhance voltage stability and to reduce network losses simultaneously in [18], where Modal analysis and continuous power flow are used for DG placement in the event of reactive power deficit. The enhancement of voltage profile, load ability with simultaneous reduction distribution losses considering voltage related constraint is discussed in [19]. Based on the literature review discussed above, it has been observed that the different issues in the field of distributed generation are covered which are based on optimal location and sizing of DG, loss minimization, voltage stability enhancement and reconfiguration of distribution network after the integration of DG resources. This paper is mainly focused on static security analysis which has been rarely addressed earlier in the literature. Section 1 gives the Introduction about the work and rest of the paper is organized as follows: Section 2 presents SSA. Proposed analytical expressions for finding optimal sizes of various DG types are introduced in Section 3 & 4. Optimal placement and operating power factor of DG is also addressed in the section. Section 5 presents numerical results of application of http://www.iaeme.com/ijeet/index.asp 38 editor@iaeme.com

Optimal DG Placement Based on Static Security Assessment developed analytical expression in two different test systems, interesting observations along with discussions. Finally, the major contributions and conclusions are summarized in Section 6. 2. STATIC SECURITY ANALYSIS (SSA) A given system operating condition is said to be static secure, if the bus voltage magnitudes and real power generation of generator buses are well within their limits, without any occurrence of line overloads. In this paper, we define a term called Static Security Index (SSI) for evaluating static security level for a given system operating condition and a specified contingency. The SSI is defined by calculating the Line Overload Index (LOI) and Voltage Deviation Index (VDI) as given by (1) and (2) respectively. where S km and MVA km represents the Mega Volt-Ampere(MVA) flow and MVA limit of branch k-m, V kmin, V kmax and V k the minimum voltage limit, maximum voltage limit and bus voltage magnitude of k th bus respectively, N L and N B being number of lines and buses respectively. Evaluating the Static Security Index (SSI) as given by (3), each pattern is labeled as belonging to one of the four classes as shown in Table I. In calculation of SSI, weighting factors for LOI and VDI are taken as W1=3 and W2=2 respectively. These weighting factors are fixed based on the order of priority in requirement of system security. SSI is a percentage measure, taking value in the range of 0 to 100. Here in this paper, SSA is done by varying the system load 100% to 200% of their base case values and SSI is found. The work can also be extended by considering the outages of lines in the network. Hence, this work gives an overview of effect of DG on improvement of Static Security of the system by considering only the variation of the load in the system. Also, this work can be extended for SSA of a system by considering line outages and generator outages. http://www.iaeme.com/ijeet/index.asp 39 editor@iaeme.com

Gopala Reddy K., Dr.T. Ananthapadmanabha, Mohan N. and Likith Kumar M. V. Table I Security Levels Static Security Index Security Status SSI=0 0<SSI 5 5<SSI 15 SSI>15 Secure Critically Secure Insecure Highly Secure 3. POWER LOSS CALCULATION The real power loss in a system is given by (1). This is popularly referred to as exact loss formula [11]. The losses can also be calculated by using any conventional load flow techniques. Moreover, in this paper, the backward/forward sweep method is utilized to perform the power flow in the distribution network. Where N N P [ ( PP QQ ) ( Q P PQ )] L ij i j i j ij i j i j i1 j1 (1) rij ij cos( i j ) VV i j rij ij sin( i j) VV i j P i and Q i are active and reactive power at bus i. The above equation is used in power loss calculation in the proposed work which is also the exact loss formula. 4. PROPOSED ALGORITHM The purpose of this paper is to find the best location and size of a DG unit in order to decrease the power losses of the system and improve the voltage profile through static security analysis. The proposed algorithm of this paper gives the most optimum location and size of a DG unit in a distribution system based on a Static Security Index (SSI) which considers the voltage deviation at nodes and Line overloads. 4.1. To find Location of DG Placement The location of DG is chosen as the one that improves the SSI. This could be done by injecting the DG at each node calculating the SSI by using equation. (2). The best location is selected as the node with least SSI. http://www.iaeme.com/ijeet/index.asp 40 editor@iaeme.com

Optimal DG Placement Based on Static Security Assessment 4.2. To find Optimal Power Factor [14] Figure 1. Two bus distribution system Consider a simple distribution system with two buses, a source, a load and DG connected through a transmission line as shown in Fig. 1. The power factor of the single load (PF D2 ) is given by (4) PF D 2 P P D2 Q 2 2 D2 D2 It can be proved that at the minimum loss occur when power factor of DG is equal to the power factor of load as given by (5). PF PF D 2 DG2 P P DG 2 Q 2 2 DG2 DG2 In practice, a complex distribution system includes a few sources, many buses, many lines and loads. The power factors of loads are different. If each load is supplied by each local DG, at which the power factor of each DG is equal to that of each load, there is no current in the lines. The total line power loss is zero. The transmission lines are also unnecessary. However, that is unrealistic since the capital investment cost for DG is too high. Therefore, the number of installed DGs should be limited. To find the optimal power factor of DG for a radial complex distribution system, fast and repeated methods are proposed. It is interesting to note that in all the three test systems the optimal power factor of DG (Type 3) placed for loss reduction found to be closer to the power factor of combined load of respective system. 1) Fast Approach: Power factor of combined total load of the system (PFD) can be expressed by (5). In this condition, the total active and reactive power of the load demand are expressed as The possible minimum total loss can be achieved if the power factor of DG (PFDG) is quickly selected to be equal to that of the total load (PFD ). That can be expressed by (6) PF DG = PF D (6) 2) Repeated Approach: In this method, the optimal power factor is found by calculating power factors of DG (change in a small step of 0.01) near to the power factor of combined load. The sizes and locations of DG at various power factors with respect to losses are identified from (5). The losses are compared together. The optimal power factor of DG for which the total loss is at minimum is determined. The present work uses the Fast Approach to find the optimal value of Power Factor of DG. (4) (5) http://www.iaeme.com/ijeet/index.asp 41 editor@iaeme.com

Gopala Reddy K., Dr.T. Ananthapadmanabha, Mohan N. and Likith Kumar M. V. 4.3. Computational Procedure for DG Placement and Sizing Read system data. Run the base case load flow. Compute SSI for base case. Calculate the optimal power factor of DG by using Fast Approach. Compute the SSI at each node using equation (3) by penetrating the DG at respective node Select the bus with least value of index and that is the optimal location of DG. Repeat the above steps for another penetration level of DG (if required). 5. RESULTS AND ANALYSIS A) Case Study 1 The developed methodology is applied to 25kV, IEEE six bus system [12] shown in Figure 2 without any capacity and location constraint. Figure. 2 Standard IEEE 6 bus test system Table I shows the summary of the results of the proposed algorithm for IEEE 6 bus test system. The optimal location of DG has been found by SSI shown in Table II. The least value of the index is at bus no 3 for both 10% and 50% DG penetration levels and hence it is chosen as the best location and optimal size of DG is chosen by finding the optimal power factor of the DG using the proposed two approaches. From Figure 3 and Figure 4 it is evident that the DG placement through the proposed method improves the voltage profile and percentage power loss reduction at two different DG penetration levels. http://www.iaeme.com/ijeet/index.asp 42 editor@iaeme.com

Optimal DG Placement Based on Static Security Assessment Table I Summary of Results 6 Bus Test System 6 BUS TEST SYSTEM DG PENETRATION LEVEL 10% 50% OPTIMAL LOCATION (BUS NO) 3 3 OPTIMAL POWER FACTOR 0.96 0.96 OPTIMAL DG SIZE PDG IN MW 2.25 11.35 QDG IN MVAR 0.605 3.025 REAL LOSS BEFORE DG PLACEMENT in MW 0.7033 0.7033 REAL LOSS AFTER DG PLACEMENT in MW 0.4879 0.184 SSI before DG placement 11.348 11.348 SSI After DG placement 0.988 0.046 % REAL LOSS REDUCTION 30.627 73.837 Table II. SSI of Standard 6 Bus Test System for various locations of DG DG Location 10% DG penetration 50% DG penetration SSI Status SSI Status 1 2 3.78 Critically Secure 3.345 Critically Secure 3 0.0988 Secure 0.046 Secure 4 5.578 Insecure 4.787 Critically Secure 5 6.123 Insecure 5.879 Insecure 6 8.456 Insecure 7.456 Insecure http://www.iaeme.com/ijeet/index.asp 43 editor@iaeme.com

Gopala Reddy K., Dr.T. Ananthapadmanabha, Mohan N. and Likith Kumar M. V. 1.01 Voltage Profile in p.u 1 0.99 0.98 0.97 0.96 0.95 0.94 Base Case At 10% DG penetration At 50% DG penetration 0.93 0.92 0.91 1 2 3 4 5 6 Figure 3 Voltage profile of Standard 6 bus Test System 0.8 Real Power Loss in MW 0.7 0.6 0.5 0.4 0.3 0.2 Before DG placement After DG placement @ 10% Penetration Level After DG placement @ 50% Penetration Level 0.1 0 Figure 4 Real Power Loss profile of Standard 6 bus Test System B) Case Study 2: The algorithm has been applied to a radial system of sixteen buses with three feeders and three tie switches as shown in Figure 5. The line data is taken from [13] without any DG injection. The branches S15, S21and S26 are the tie branches. http://www.iaeme.com/ijeet/index.asp 44 editor@iaeme.com

Optimal DG Placement Based on Static Security Assessment Figure 5 Standard Civanlar 16 bus test system Table III Summary of Results 16 Bus Test System 16 BUS TEST SYSTEM DG PENETRATION LEVEL 10% 50% OPTIMAL LOCATION (BUS NO) 12 8 OPTIMAL POWER FACTOR 0.856 0.856 OPTIMAL DG SIZE PDG IN MW 2.87 14.35 QDG IN MVAR 1.73 8.65 REAL LOSS BEFORE DG PLACEMENT in MW 0.5036 0.5036 REAL LOSS AFTER DG PLACEMENT in MW 0.336 0.209 SSI before DG placement 13.676 13.676 SSI after DG placement 0.098 0.0348 % REAL LOSS REDUCTION 33.280 58.498 http://www.iaeme.com/ijeet/index.asp 45 editor@iaeme.com

Gopala Reddy K., Dr.T. Ananthapadmanabha, Mohan N. and Likith Kumar M. V. Table IV SSI of Standard 16 Bus Test System for various locations of DG DG Location 10% DG penetration 50% DG penetration SSI Status SSI Status 1 2 3 4 9.4678 Insecure 8.1211 Insecure 5 9.23 Insecure 7.8833 Insecure 6 9.76 Insecure 8.4133 Insecure 7 4.37 Critically Secure 3.0233 Critically Secure 8 5.123 Insecure 0.0348 Secure 9 5.578 Insecure 4.2313 Critically Secure 10 8.123 Insecure 6.7763 Insecure 11 9.456 Insecure 8.1093 Insecure 12 0.0984 Secure 3.7763 Critically Secure 13 6.345 Insecure 4.9983 Critically Secure 14 6.456 Insecure 5.1093 Insecure 15 16 5.6578 Insecure 4.3111 Critically Secure 4.3789 Critically Secure 3.0322 Critically Secure Table III shows the summary of the results of the proposed algorithm for standard 16 bus test system. The optimal location of DG has been found by voltage indices shown in Table IV. The least value of the index is at bus no 12 and bus 2 respectively for 10% and 50% DG penetration levels and hence they are chosen as the best location and optimal size of DG is chosen by finding the optimal power factor of the DG using the proposed two approaches. From Figure 6 and Figure 7 it is evident that the DG placement through the proposed method improves the voltage profile and percentage power loss reduction at two different DG penetration levels. http://www.iaeme.com/ijeet/index.asp 46 editor@iaeme.com

Optimal DG Placement Based on Static Security Assessment Voltage Profile in p.u 1.03 1.02 1.01 1 0.99 0.98 0.97 0.96 0.95 0.94 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Base Case At 10% DG penetration At 50% DG penetration Figure 3 Voltage profile of 5 Standard Civanlar 16 bus Test system 0.6 Real Power Loss in MW 0.5 0.4 0.3 0.2 Before DG Placement After DG Placement @ 10% Penetration Level After DG Placement @ 50% Penetration Level 0.1 0 Figure 7 Real Power Loss profile of Standard 16 Bus Test System 6. CONCLUSION Size and location of DG are crucial factors in the application of DG for loss minimization. This paper presents an algorithm to calculate the optimum size of DG at various buses and proposes a fast methodology to identify the best location corresponding to the optimum size for reducing total power losses in primary distribution network. The proposed methodology for location selection correctly identifies the best location for single DG placement in order to minimize the total power losses and improve the voltage profile through Static Security Analysis. In practice, the choice of the best site may not be always possible due to many constraints. However, the analysis here suggests that the losses arising from different placement varies greatly and hence this factor must be taken into consideration while determining appropriate location. The optimal size and location of DG are two http://www.iaeme.com/ijeet/index.asp 47 editor@iaeme.com

Gopala Reddy K., Dr.T. Ananthapadmanabha, Mohan N. and Likith Kumar M. V. important factors for the planning and operation of modern electric power distribution systems. This paper presents a simplified index based approach for optimum location and allocation of DG in distribution system in which the optimal siting of DG is determined by Static Security Index for improving the voltage profiles and power loss reduction. The proposed method is tested on IEEE 6 bus and standard Civanlar 16 bus system and results were tabulated. The obtained location and size is the most optimum location and size in all of the possible optimum solutions because of analyzing all of the locations and sizes for each bus. REFERENCES [1] A. Ipakchi and F. Albuyeh. Grid of the future. IEEE Power and Energy Magazine. 2009, 7 (2): 52-62. [2] T. Ackermann, G. Andersson and L. Soder. Distributed generation: a definition, Electrical Power System Research. 2001, 57 (3): 195-204. [3] P. Chiradeja and R. Ramkumar. An approach to quantify the technical benefits of distributed generation. IEEE Transaction on Energy Conversion. 2004, 19 (4): 764-773. [4] H. Khan and M.A. Choudhry. Implementation of distributed generation algorithm for performance enhancement of distribution feeder under extreme load growth. International Journal of Electrical Power and Energy Systems. 2010, 32 (9): 985-997. [5] D.Q. Hung, N. Mithulanathan and R.C. Bansal. Multiple distributed generators placement in primary distribution networks for loss reduction. IEEE Transactions on Industrial Electronics. (In Press). [6] N. Mithulanathan, T. Oo and L. V. Phu. Distributed generator placement in power distribution system using Genetic Algorithm to reduce losses. Thammasat International Journal on Science and Technology. 2004, 9 (3): 55-62. [7] S. Ghosh, S.P. Ghoshal and S. Ghosh. Optimal sizing and placement of DG in network system. International Journal of Electrical Power and Energy Systems. 2010, 32 (8): 849-856. [8] I. Ziari, G. Ledwich, A. Ghosh, D. Cornforth and M. Wishart. Optimal allocation and sizing of DGs in distribution networks. Proc of IEEE Power and energy society general meeting. 2010:1-8. [9] R.M. Kamel and B. Karmanshahi. Optimal size and location of DGs for minimizing power losses in a primary distribution network. Transaction on Computer Science and Electrical and Electronics Engineering. 2009, 16 (2):137-144. [10] D. Singh, D. Singh and K.S. Verma. Multi-objective optimization for DG planning with load models. IEEE Transactions on Power Systems. 2009, 24 (1): 427-436. [11] Ljubomir Kojovic, " Impact of DG on voltage regulation ", IEEE conference 2002 [12] J.O. Kim, S. W. Nam, S.K. Park, C. Songh, Dispersed generation planning using improved Hereford ranch algorithm, International Journal: Electric Power Systems Research 47 (1998), pp 47-55. [13] S. Civanlar, J.J. Grainger, H. Yin and S.S.H. Lee, Distribution Feeder Reconfiguration for Loss Reduction, IEEE Transactions on Power Delivery, Volume 3, No. 3, July 1988, pp1217-1223. http://www.iaeme.com/ijeet/index.asp 48 editor@iaeme.com

Optimal DG Placement Based on Static Security Assessment [14] Duong Quoc Hung et. al, Analytical Expressions for Dg allocation in primary Distribution Networks, IEEE Transactions on Energy Conversions, Volume 25, No. 3, September 2010, pp814-820. [15] Hedayati H, Nabaviniaki SA, Akbarimajd A. A method for placement of DG units in distribution networks. IEEE Trans Power Del 2008; 23 (3):1620 8 [July]. [16] Hill DJ, Hiskens IA. Load recovery in voltage stability analysis and control, presented at the National Science Foundation/ECC Workshop Bulk Power System. Davos, Switzerland: Voltage Phenomena III; 1994 [August]. [17] Arya LD, Koshti Atul, Choube SC. Distributed generation planning using differential evolution accounting voltage stability consideration. Int J Electr Power Energy Syst 2012; 42:196 207. [18] Ettehadi M, Ghasemi H, Vaez-Zadeh S. Voltage stability-based DG placement in distribution networks. IEEE Trans Power Del January 2013;28(1). [19] Esmaili Masoud, Firozjaee Esmail Chaktan, Shayanfar Heidar Ali. Optimal placement of distributed generations considering voltage stability and power losses with observing voltage-related constraints. Int J Appl Energy 2014;113:1252 60 http://www.iaeme.com/ijeet/index.asp 49 editor@iaeme.com