Three-phase analysis of unbalanced systems



Similar documents
Chapter 12: Three Phase Circuits

Introduction to PowerWorld Simulator: Interface and Common Tools

How To Balance Three Phase Power In A Balanced System

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

Genetic Algorithm approach to find excitation capacitances for 3- phase smseig operating single phase loads

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

Chapter 12 Three-Phase Circuit

Chapter 9 Balanced Faults

BALANCED THREE-PHASE CIRCUITS

Static Analysis of Power Systems. Lennart Söder and Mehrdad Ghandhari

Open Phase Conditions in Transformers Analysis and Protection Algorithm

De Jaeger, Emmanuel ; Du Bois, Arnaud ; Martin, Benoît. Document type : Communication à un colloque (Conference Paper)

A Direct Numerical Method for Observability Analysis

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Performance of 3-Phase 4-Wire Solid State Transformer under Imbalanced Loads

Three phase circuits

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Chapter 11 Balanced Three-Phase Circuits

Radial Distribution Test Feeders

Fault Analysis I PowerWorld Corporation

Steady-State Power System Security Analysis with PowerWorld Simulator

ACCURACY OF POTENTIALTRANSFORMERS

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Neutral to Earth Voltage Reduction Methods in Three-Phase Four Wire Distribution Systems

Weighted-Least-Square(WLS) State Estimation

Chapter 24. Three-Phase Voltage Generation

Electrical network protection. Protection guide. Guide G 51G 51G 51G 51G. network protection solutions

BALANCED THREE-PHASE AC CIRCUIT

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Simulation of Ungrounded Shipboard Power Systems in PSpice

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

How To Limit Voltage Unbalance

FUNDAMENTALS OF ENGINEERING (FE) EXAMINATION REVIEW

Lecture 20: Transmission (ABCD) Matrix.

WHITE PAPER GROUND FAULT. Lowering the Limits for Ground Fault Detection

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

Calculating voltage dips in power systems using probability distributions of dip durations and implementation of the Moving Fault Node method

4.5 Transformer Connections

TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering

How To Understand And Understand The Theory Of Electricity

Modeling of Transmission Lines

Transformers. Special transformers Reactors products

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS

Effect of Unbalance Voltage on the Operation and Performance of a Three Phase Distribution Transformers

THREE PHASE CIRCUITS

Power System Harmonics

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

Basic Laws Circuit Theorems Methods of Network Analysis Non-Linear Devices and Simulation Models

Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer

Electrical network protection. Protection guide. Guide

Network Theory Question Bank

1 Introduction. 2 Power Flow. J.L. Kirtley Jr.

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Symmetrical Components in the Time Domain and Their Application to Power Network Calculations

GE Multilin technical note

Ground Fault Protection on Ungrounded and High Resistance Grounded Systems

Voltage regulation in distribution systems - Tap changer and Wind Power

A student friendly toolbox for power system analysis using MATLAB

Protection of Phase Angle Regulating Transformers

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Chapter 10. RC Circuits ISU EE. C.Y. Lee

3 Calculation of Short-Circuit Currents in Three-Phase Systems

Lecture 7 Circuit analysis via Laplace transform

OPTIMAL DISPATCH OF POWER GENERATION SOFTWARE PACKAGE USING MATLAB

Neutral Currents in Three Phase Wye Systems

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

NETWORK RECONFIGURATION FOR LOSS REDUCTION IN THREE-PHASE POWER DISTRIBUTION SYSTEMS

GE Protection and Control Business Department. Page 1 Date 5/11/99

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

ACADEMIC INTERGRITY POLICY

1 Introduction. 2 Two Phases. J.L. Kirtley Jr.

FOUR LEGGED ACTIVE POWER FILTER COMPENSATION FOR A UTILITY DISTRIBUTION SYSTEM

Short Circuit Current Calculations

Electrical Fault Level Calculations Using the MVA Method

UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE. Department of Electrical and Computer Engineering

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

THREE-PHASE POWER SYSTEMS ECE 454/554: Power Systems Laboratory

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

The following table shows approximate percentage wise the

Line Current Characteristics of Three-Phase Uncontrolled Rectifiers Under Line Voltage Unbalance Condition

Students Manual for the Exam. General Engineering and Electrical Civil Engineering Discipline

AC Generators. Basic Generator

IEEE TUTORIAL ON VOLTAGE SAG ANALYSIS

IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS

How To Improve Power Quality

13 ELECTRIC MOTORS Basic Relations

Transformer Short Circuit Current Calculation and Solutions

How To Improve Power Quality

zcable Model for Frequency Dependent Modelling of Cable Transmission Systems

Medium-voltage Transformers

TRANSFORMER: THREE PHASE

High Voltage Transient Analysis

Lecture Notes ELE A6

Topic Suggested Teaching Suggested Resources

Transcription:

Exercises of course ELEC0029 - Electric power systems analysis and operation Three-phase analysis of unbalanced systems Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct March 205 / 26

Objectives Three-phase analysis of unbalanced systems It is common practice to have the lines, cables, transformers and generators modelled by their positive, negative and zero sequence equivalent circuits (the latter are assumed decoupled) for each of those components, we consider how to pass from the symmetric-component model (+,, o) to the three-phase model (a, b, c) for other components, we derive the (a, b, c) model directly all these individual models are assembled to build the three-phase bus admittance matrix Y and the vector of three-phase injected currents Ī of the linear model: Ī = Y V which is solved to obtain the vector V of three-phase bus voltages for each component, a MATLAB script is available and its use is described. 2 / 26

Remarks Three-phase analysis of unbalanced systems All voltages refer to their local grounds as in the Theory, the neutrals are eliminated thus, for an N-bus system, Y is a 3N 3N matrix Y and Ī are built for the balanced system; imbalances resulting from faults, loads, lines, etc. will be added by modifying Y and Ī some models require values from an initial power flow computation of the balanced system the per unit system uses the single-phase base power (see Chapter 5) however, the base impedances are the same as with a three-phase base power: three-phase base power S B3 = 3V B I B3 = 3U B I B3 single-phase base power S B = V B I B I B3 = S B3 = S B3 3V B 3UB Z B3 = V B I B3 = 3V 2 B S B3 = U2 B S B3 I B = S B V B Z B = V B I B = V 2 B S B 3 / 26

Load Three-phase analysis of unbalanced systems Load Star-connected load Input data: complex power consumed in one phase: P + jq (in pu) magnitude of the phase-to-neutral voltage under which this power is consumed: V (in pu) impedance between neutral and ground: z n (in pu) y = P jq V 2 y n = z n 4 / 26

Load Ī a = y( V a V n ) () Ī b = y( V b V n ) (2) Ī c = y( V c V n ) (3) Ī a + Īb + Īc = y n Vn (4) Adding (, 2 and 3) and introducing the result in (4) yields: V n = y V a + y V b + y V c y tot with y tot = 3y + y n (5) Introducing (5) into (,2,3) and arranging the results in matrix form: Ī ā y y 2 y tot y 2 y tot y 2 y tot V a I = y 2 y tot y y 2 y tot y 2 y tot V b bīc y 2 y tot y2 y tot y y 2 V c y tot } {{ } contribution to matrix Y Question. Determine the admittance matrix when z n = 0 ( solid grounding)? 5 / 26

Load Delta-connected load Input data: complex power consumed in each branch: P + jq (in pu) magnitude of the phase-to-phase voltage under which those powers are consumed: U (in pu) y = P jq U 2 6 / 26

Load Ī a = y( V a V b ) + y( V a V c ) Ī b = y( V b V a ) + y( V b V c ) Ī c = y( V c V a ) + y( V c V b ) which can be rewritten in matrix form as: Ī ā 2y y y I = y 2y y bīc y y 2y } {{ } contribution to matrix Y V a V b V c Remarks this admittance matrix is singular because the voltage reference node is not located in the circuit ( indefinite admittance matrix ) this is not a problem since it will be combined with other admittance matrices to form Y. 7 / 26

Load Matlab script Yload.m 8 / 26

Balanced Norton equivalent Balanced Norton equivalent Input data: complex power produced by one of the three phases: P + jq (in pu) Thévenin impedance: z th (in pu) complex (phase-to-neutral) voltage of phase a: Va (in pu) Ē a = V a + z th P jq V a Ē b = a 2 Ē a Ē c = aēa 9 / 26

Balanced Norton equivalent Ī a = ( V a Ē a )/z th Ī b = ( V b Ē b )/z th Ī c = ( V c Ē c )/z th which can be rewritten in matrix form as: Ī ā /z th 0 0 I = 0 /z th 0 bīc 0 0 /z th } {{ } contribution to matrix Y V a V b V c Ē a /z th Ē b /z th } Ē c /z th {{ } contrib. to vector Ī 0 / 26

Balanced Norton equivalent Matlab script Norton equ.m / 26

Generator Three-phase analysis of unbalanced systems Generator Input data: positive, negative and zero-sequence impedances: z +, z and z o (in pu) impedance between neutral and ground: z n (in pu) complex power produced by one of the three phases: P + jq (in pu) complex (phase-to-neutral) voltage of phase a: V a (in pu) 2 / 26

Generator To identify Īnor,a, Īnor,b and Īnor,c we assume initial balanced operating conditions: Hence: V = V o = 0 V+ = V a Ī = Īo = 0 Ī + = Īa = P jq V a Ē + = V + z + Ī + = V a + z + P jq V a Contribution to vector Ī : Ī nor,a Ī nor,b Ī nor,c = Ē + /z + a 2 Ē + /z + a Ē + /z + Contribution to admittance matrix Y : with: YF = YT = TYF T /z + 0 0 0 /z 0 0 0 /(z o + 3z n ) and T = a 2 a a a 2 3 / 26

Generator Matlab script Norton gen.m 4 / 26

Line or cable Three-phase analysis of unbalanced systems Line or cable Full three-phase symmetry is assumed. Input data: positive-sequence series impedance: z + = r + + jx + (in pu) zero-sequence series s: z o = r o + jx o (in pu) positive-sequence half shunt susceptance: b + (in pu) zero-sequence half shunt susceptance: b o (in pu) 5 / 26

Line or cable It has been shown (see theory): z + = z s z m z o = z s + 2z m from which one obtains: z s = 2z + + z o z m = z o z + 3 3 z s z m z m and the impedance matrix: Z = z m z s z m z m z m z s The voltage-current relations of the series part are: V A V g I A V B V g V C V g = Z I B I C + and I A I B I C I A I B I C = = Z I A I B I C V A V g V B V g V C V g = Z V A V g V B V g V C V g Z V A V g V B V g V C V g V A V g V B V g V C V g Z V A V g V B V g V C V g (6) (7) 6 / 26

Line or cable It has been shown (see theory): b + = b s b m b o = b s + bz m from which one obtains: and the admittance matrix: b s = 2b + + b o b m = b o b + 3 3 b s b m b m j B = j b m b s b m b m b m b s For the shunt part on the left, the voltage-current relations are: I a V a V g I A I b I c = j B V b V g V c V g + I B I C (8) Similarly, for the shunt part on the right: I a V a V g I b I c = j B V b V g V c V g + I A I B I C (9) 7 / 26

Line or cable Taking into account that: V a = V A V b = V B V c = V C V a = V A V b = V B V c = V C Eqs. (6, 7, 8, 9) can be combined into: I a I b I j B + Z Z c = I a I b Z j B + Z I c } {{ } 6 6 admittance matrix Y V a V g V b V g V c V g V a V g V b V g V c V g 8 / 26

Line or cable Matlab script Yline.m 9 / 26

Transformer Three-phase analysis of unbalanced systems Transformer Input data: positive-sequence series impedance: R + jx (in pu) positive-sequence magnetizing reactance: X m (in pu) zero-sequence series impedance: R o + jx o (in pu) zero-sequence magnetizing reactance: X mo (in pu) impedance neutral - ground on primary and secondary sides: z n, z n2 (in pu) complex transformer ratio n not used in some transformers 20 / 26

Transformer Admittance matrix of the direct-sequence equivalent two-port (Ī + ) abc = ( V + ) abc + jx m (Ī+) a b c = n R + jx [( V + ) abc n ] R + jx ( V + ) a b c ] [ n ( V + ) a b c ( V + ) abc or in matrix form: [ (Ī+ ) abc (Ī+) a b c ] = [ jx m + R+jX n R+jX n R+jX n 2 R+jX } {{ } posit.-sequ. admittance matrix ] [ ( V + ) abc ( V + ) a b c ] 2 / 26

Transformer Admittance matrix of the negative-sequence equivalent two-port Replacing n by n in the direct-sequence admittance matrix: [ ] [ ( Ī ) abc jx m + R+jX n ] [ = R+jX ( V ) abc (Ī ) a b c n ( V ) a R+jX n 2 R+jX b c } {{ } negative-sequ. admittance matrix ] Admittance matrix of the zero-sequence equivalent two-port. Transformer of type Ynd* [ (Īo ) abc (Īo) a b c ] [ = jx mo + R o+jx o+3z n 0 0 0 } {{ } zero-sequ. admit. matrix ] [ ( V o ) abc ( V o ) a b c ] 22 / 26

2. Transformer of type Ynyn0 Transformer [ ( Ī o ) abc (Ī o ) a b c ] = [ jx mo + R o+jx o+3z n+3z n2/n 2 n R o+jx o+3z n+3z n2/n 2 n R o+jx o+3z n+3z n2/n 2 n 2 R o+jx o+3z n+3z n2/n 2 } {{ } zero-sequ. admittance matrix ] [ ( Vo ) abc ( V o ) a b c ] 3. Transformer of any other type [ ( Ī o ) abc (Ī o ) a b c ] = [ jx mo 0 ] 0 0 } {{ } zero-sequ. admit. matrix [ ( Vo ) abc ( V o ) a b c ] 23 / 26

Transformer Assembling the admittance matrices of all three sequences (Ī + ) abc ( V + ) abc (Ī ) abc ( V ) abc (Ī o ) abc (Ī+) a = ( V o ) abc YF b c ( V + ) a b c (Ī ) a b c ( V ) a b c (Ī o ) a b c ( V o ) a b c with where YF = jx m + R+jX 0 0 n R+jX 0 0 0 jx m + R+jX 0 0 n R+jX 0 0 0 y 0 0 y 2 n R+jX 0 0 0 n n 2 R+jX 0 0 R+jX 0 0 n 2 R+jX 0 0 0 y 2 0 0 y 22 [ ] y y 2 is the zero-sequence admittance matrix previously derived. y 2 y 22 24 / 26

Getting back to the a, b, c, a, b, c phases Transformer Using the inverse Fortescue transformation: or Ī ā I bīc Ī a Ī b Ī c = T T Ī ā I bīc Ī a Ī b Ī c T 0 0 T = YF YF T T V a V b V c V a V b V c T 0 0 T } {{ } the sought admittance matrix. Yeah! V a V b V c V a V b V c 25 / 26

Transformer Matlab script Ytrfo.m 26 / 26