3M Scotchcast Mine and Portable Cable Splice Kit 8096-4



Similar documents
Instruction Manual. Cable Splicing. Models , HDF1, HDF SS1

3M Quick Connect System (QCS) 2810 Models 2810A and 2810B

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS

Expanding a 40-Type Cabinet

Scotchlok Connectors and Tools

Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement

2178-S Fiber Optic Splice Case

GENERAL RUBBER LINING PRINCIPLES

Document Library TS Data Sheet

Cables and Accessories Selection Guide

Document Library TS Data Sheet M Windo-Weld Super Fast Urethane. Data Sheet. Public

3M Fiber Optic Splice Closure 2178-LS Series with Gasket

3M Electrically Conductive Adhesive Transfer Tape 9703

3M High Flex Life Cable.050" 28 AWG Stranded, PVC 3319 Series

SC, FC and ST * Hot Melt Fiber Optic Connectors

Juice Box Stages 1&2 135&335 Installation Guide 5/10/08

Application Tooling Specification Sheet

AMPSEAL* Automotive Plug Connector and Header Assembly

EMI Shielding Tapes Product Selection Guide. Trusted. Performance. from the. Tape Experts

4 Installation Requirements

3M Quick Connect System (QCS) 2814

Cable Preparation Best Practices for Fiber Optic Indoor/Outdoor Stranded Loose Tube Cable

UNIVERSAL LUMBAR INSTALLATION INSTRUCTIONS

Weatherproofing Coaxial Cable Connections

BILLET HEADLAMP WITH SHORT/TALL MOUNTS

Contact Information: Electrical Connection Kit for CL Series Constant Wattage Temptrace for Low Temperature Maintenance.

Application Instructions for Avery Dennison Films SF S LTR EZ RS, Conform Chrome

HGS620 Shielded Outlet Termination Instructions

Andersen Electric Window Opener for Andersen Awning and Roof Windows

Scotchgard Multi-Layer Protective Film 1004

3M Twisted Pair Flat Cable.050" 28 AWG Stranded, Mass Terminatable Pair, PVC 1700 Series

4 Small Cables Sealing Kit: Wrap Style

COYOTE PUP CLOSURE FOR UNDERGROUND, AERIAL, AND BURIED SPLICES 6.0" x 17" (152.4 mm x mm)

Cable Preparation and Pulling Procedure Best Practices for Fiber Optic Indoor Tight-Buffered Cable

Weatherproofing Kit for Connectors and Antennas

Physical. Electrical. Environmental. Insulation: Contact: Plating: Temperature Rating: -55 C to +85 C

TBM5, TBM5-S and TBM5-SV

Instructions Fiber Optic Splice Case

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES

3M Wire Connectors. Reliable, high performing solutions for every wire connecting application. 3Innovation

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

Fabric Replacement Top Installation Instructions

Reasons for reissue are in Section 6, REVISION SUMMARY.

Industrial Attachment Tapes X-Series. Value, Performance. & Quality. Simply X.

Section kv Power Cables

3M Scotchcast Electrical Resin 251 Two-Part, Oven-Curing, Class F, Rigid, Filled, Epoxy Liquid Resin

User s Manual. BNC Mini-High Res, 75 Ohm Termination Kit Connector Installation Guide ( )

LED Wiring and Connections

Computer Lane Monitor HOW TO MAKE A TAPE AND HOW TO READ A TAPE

Standard Operating Procedures 4ft Muscle Wall

HAND CRIMP TOOL Specification Sheet Order No

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint


5800 Temperature Sensor Cable Assembly

TABLE OF CONTENTS. I. TROUBLESHOOTING Section 1.01: Common Problems/Solutions... 2

Double Coated Urethane Foam Tapes

CamSplice Assembly Manual

MESSENGERS FOR AERIAL CABLE

TEXAS A&M CENTRAL ACADEMIC BUILDIING & PATRIOT S CASA SUBMITTAL Pre-Insulated Piping

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Speed-Mat Rectangle Cutter

3M Thermally Conductive Adhesive Transfer Tapes

TERMINATION EQUIPMENT INSTRUCTION MANUAL TELE-PIERCE P/N

Crystal Clear Sealant

MIRAGE. Set-Up Instructions.

Build Your Own Solar Car Teach build learn renewable Energy! Page 1 of 1

Active and Passive Sash Replacement

Position Cat5e (EMT) Modular Plug Connectors. Application Specification

Scotch-Weld TM. Epoxy Adhesive 1838 B/A Green 1838 B/A Tan 1838-L B/A Translucent. Technical Data February, Product Description

BASIC PLUMBING. 2 - Preparation. The simple skills required for basic plumbing are explained in this project.

DIY Advanced Dry Bags

3M Pin Strip Header Single and Dual Row.100,.235 /.318 Mating Length, Straight & Right Angle, Solder Tails 929 Series

Operating Instructions

INSTALLATION INSTRUCTIONS

Draka Industrial Cable GmbH

3M Wrist Strap and Footwear Tester 740. User s Guide

Operator s Manual. Pressure Injection Cell Model PC8500. Congratulations! Contents

3M Thermal Bonding Film AF42

Anderson Powerpoles. Powerpole Assembly Instructions for SCOUT, NAVIGATOR AND RANGER ROV s

EH-20 20m antenna. By VE3RGW

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions

Instructions for assembly of your Pop-Up Display

Power Cable Splicing & Terminating. edited by Robert Goodman and William Osborn

Advantium 2 Plus Alarm

MGB Chrome Bumper Conversion

COMPACT ELITE MAT CUTTER

*PATENT PENDING. NS1100 / NS2200 Installation Manual & Owner s Guide

3 740 Wrist strap + shoe tester

Black Wolf POCKET BILLIARD TABLE INSTALLATION MANUAL. SERVICE DEPARTMENT P.O. BOX 68 BRISTOL, WI 53104

3M xdsl Line Conditioners 3620

3M Dynatel Triple Play Customer Service Test Set INS970

Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

Maintenance & repair Solutions

staple gun with 5/16 Long staples

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

General Information and Selection

Step 1. Item 6. Item 1

Transcription:

3M Scotchcast Mine and Portable Cable Splice Kit 8096-4 Installation Instructions 1.0 Kit Contents: 2 Funnels 3 EPDM Rubber Cold Shrink Cold Shrink Insulator 1 Wrap-around Mold Assemblies 2 Rubber Mold Straps 1 Roll Scotch Super 33+ Vinyl Electrical Tape 2 Funnel Supports 2 Rolls Scotch Electrical Shielding Tape 24 3 Spacer Webs 1 3M Cable Cleaning Preparation Kit CC-2 1 Strip 3M Three-M-Ite Elek-Tro-Cut Abrasive Cloth, 80J Grit 1 Roll Scotch Electrical Semi-conducting Tape 13 6 Size C Bags, 3M Scotchcast Flame-Retardant Compound 2131 1 Roll Scotch Linerless Rubber Splicing Tape 130C Ground Wire Cable Insulation Color-Coding Fabric and/or Semi-Conducting Cloth Ground Check Wire Cable Shielding Cable Jacket Scotch Electrical Semi-conducting Tape 13 Scotch Linerless Rubber Splicing Tape 130C Scotch Electrical Shielding Tape 24 EPDM Rubber Cold Shrink Insulator Assembly Scotch Linerless Rubber Splicing Tape 130C Scotch Super 33+ Vinyl Electrical Tape Scuff Taper Scotch Super 33+ Vinyl Electrical Tape Spacer Web Collar 3M Scotchcast Flame- Retardant Compound 2131 NOTE: On large 15kV cables, additional Scotch Tape 130C, Scotch Tape13 and Scotch Tape 24 may be required. DANGER: BEFORE ATTEMPTING ANY CABLE REPAIRS, MAKE SURE THAT THE PROPER CABLE IS DISCONNECTED, LOCKED OUT AND SUITABLY TAGGED. Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product. Technical Information: For use on three-conductor mine and portable cables: 5 & 8kV Type SHD-GC: #4 AWG to 4/0 AWG Type MPF-GC & MPF: 1/0 AWG to 300 kcmil 15 kv Type SHD-GC: #2 AWG to #1 AWG Type MPF-GC & MPF #2 AWG to 3/0 AWG 3M Scotchcast Mine and Portable Cable Splice Kit 8096-4 Mine Safety and Health Administration Acceptance: 78-8126-9793-2 07-KA060007-MSHA June, 2011 1 of 8

2.0 Prepare Cables 2.1. Position cables and cut so conductor ends butt squarely. 2.2 Remove cable jackets for 10 (250 mm). (Figure 1) 2.3 FULLY taper jacket ends: 1 (25 mm) for jackets less than 3/16 (5 mm) thick 2 (50 mm) for jackets of 3/16 (5 mm) and thicker 2.4 Scuff jacket ends for 6 (150 mm) with coarse #80 abrasive strip provided. Clean dust from scuffed area. (Figure 1) 2.5 Remove cable fillers back to jackets. 2.6 Apply 2 wraps of tightly stretched Scotch Super 33+ Vinyl Electrical Tape around each conductor, 4 (100 mm) from end. (Figure 1) 2.7 Bend shielding back over the Scotch Super 33+ Tape. USE CARE TO EVENLY DISTRIBUTE WIRES. (Figure 1) NOTE: FOR RIBBON (TAPE) SHIELDING, CUT SHIELDING OFF AT Scotch Super 33+ TAPE AND PROCEED TO STEP 2.9. 2.8 Trim shielding to 3/4 (20 mm) and overwrap with a layer of Scotch Super 33+ Tape. (Figure 1) 2.9 Remove cable color-coding fabric and /or semi-conducting cloth, leaving 1/4 (6 mm) exposed beyond shielding. (Figure 1) 2.10 Remove insulation from ends of conductors for 1/2 connector length plus 1/4 (6 mm). CONNECTOR LENGTH SHOULD NOT EXCEED 2 1/2 (60 mm). 2.11 Clean and smooth exposed insulations using 3M Cable Cleaning Preparation Kit CC-2 provided. (Figure 1) 2.12 Pencil insulations for 3/4 (20 mm); buff SMOOTH AND EVEN with fine #120 abrasive from CC-2 Kit. (Figure 1) 3.0 Connect Power Conductors Cold Shrink Insulator Assembly 3.1 Select one cable end and slide a cold shrink insulator assembly onto each power conductor, putting the loose core ends on first. (Figure 2) 3.2 Phase match conductors to appropriate color codes. 3.3 Join power conductors with proper connectors and appropriate crimping tool and die. MAKE CERTAIN CONDUCTORS BUTT INDENTS IN CENTER OF CONNECTORS. NOTE: GROUND WIRES AND GROUND CHECK WILL BE JOINED LATER. 2 of 8

Scotch Electrical Semi-Conducting Tape 13 3.4 Fill connector indents with Scotch Electrical Semi-Conducting Tape 13; smoothly apply 2 half-lapped layers, highly elongated over exposed conductor and connector area, OVERLAPPIING 1/16 (2 mm) ONTO INSULATION PENCILS. (Figure 3) 4.0 Apply Primary Insulation NOTE: On large 15 kv cables, additional Scotch Linerless Rubber Splicing Tape 130C, Scotch Tape 13 and Scotch Electrical Shielding Tapes 24 may be needed. Overlap 1/16 Scuff Cable Insulation Scotch Linerless Rubber Splicing Tape 130C Equal Diameter 4.1 Smoothly fill in connector area with half-lapped, highly elongated Scotch Tape 130C; BUILD UP TO DIAMETER OF CABLE INSULATION, overlapping 1/16 (2 mm) beyond pencils. (Figure 4) 4.2 Slide cold shrink insulator assembly over taped connection. As the core is removed, the rubber tube will elongate approximately 1/4. Position insulator so tube is centered over connection when core is removed. 4.3 Remove cores by UNWINDING COUNTERCLOCKWISE. (Figure 5) NOTE: An occasional tug of the strand while unwinding will aid in removal of core. 3 of 8

4.4 Apply highly elongated Scotch Linerless Rubber Splicing Tape 130C to cable insulation at ends of cold shrink insulators, forming tapers to insulators Extend tapers from cable color-coding fabric and/or semi-conducting cloth to 1/16 (2 mm) onto insulators. (Figure 6) FOR 15kV ONLY: Extend tapers from cable color-coding fabric and/or semi-conducting cloth to insulators. Wrap an additional 2 half-lapped layers of Scotch Tape 130C over cold shrink insulators. 4.5 Wrap 1 half-wrapped layer of Scotch Electrical Semi-Conducting Tape 13 over previously applied Scotch Tape 130C and cold shrink insulators extending 1/2 (12 mm) onto exposed cable metallic shielding. (Main illustration front page) 4.6 Wrap 1 half-lapped layer of Scotch Electrical Shielding Tape 24 over the semi-conducting tape, extending 1/2 (12 mm) onto exposed cable metallic shielding. Secure ends with 2 wraps of tightly applied Scotch Super 33+ Vinyl Electrical Tape. (Main illustration front page) 5.0 Connect Ground Wires 5.1 Join ground wires with proper connectors and appropriate crimping tool and die. Half-lap or overwrap entire length of ground wires with Scotch Super 33+ Tape. 5.2 GROUND CHECK (if present): remove conductor insulation for 1/2 connector length. Join wires with proper connector. Insulate connection with 2 half-lapped layers of Scotch Super 33+ Tape, extending 1 (25 mm) onto conductor insulations. Half-lap or overwrap remaining exposed ground check insulation with Scotch Super 33+ Tape. 5.3 Bundle all conductors, grounds, and ground check (if present) by overwrapping entire length with 2 half-lapped layers of Scotch Super 33+ Tape, extending ¼ (6 mm) onto jacket taper at each end. 6.0 Install Spacer Web 6.1 Wrap INVERTED Scotch Super 33+ Tape (adhesive side out) around bundled conductors at 5½ (140 mm) spacing, as shown in Figure 7. 6.2 Wrap on spacer web over inverted Scotch Super 33+ Tape to form collars; build EQUAL diameters to 1 layer greater than repair or cable diameter, whichever is larger. (Figure 7) 4 of 8

6.3 Split ends of spacer web and press into sides of collars. (Figure 8) 7.0 Install Mold 7.1 Inspect Mold: On previously used mold, make certain vent slits are clear of resin. 7.2 With cable straight, center mold over repair area with vent slits on top (printing on mold should be readable). Wrap snuggly around, tucking one edge under. (Figure 9) NOTE: TUCKED EDGE MUST BE STRAIGHT TO FORM A SEAL. 7.3 On small cables, where mold overlaps mold fill-holes, reduce mold width by folding, then cutting on appropriate score marks. (Figure 10) 7.4 Reposition mold according to Step 7.2. NOTE: IF NECESSARY, SLIGHTLY ADJUST MOLD POSITION SO SPACER WEB COLLARS ARE NOT BLOCKING MOLD FILL- HOLES. Caution: Mold must not overlap fill-holes. 7.5 Position Funnel Supports over mold holes and secure tightly with Mold Straps. (Figure 11) NOTE: MOLD, FUNNEL SUPPORTS AND MOLD STRAPS MAY BE MOVED AROUND AT THIS TIME, TO ADJUST FOR FINAL POSITION. 5 of 8

Scotch Super 33+ Vinyl Electrical Tape (Low Tension) 7.6 Bundle mold s notched ends evenly around cable, maintaining cable centering. Starting 1/2 (12 mm) on cable jacket, apply 1 half-lapped layer of Scotch Super 33+ Vinyl Electrical Tape over notches. (Figure 12) NOTE: TENSION Scotch Super 33+ TAPE ONLY ENOUGH TO CONFORM TO MOLD. 7.7 Install funnels into Funnel Support holes. (Figure 11) 8.0 Pour Compound 8.1 Premix BLACK side of 3M Scotchcast Flame Retardant-Compound 2131 pouch by squeezing to a smooth consistency and uniform color. 3M Scotchcast Flame-Retardant Compound 2131 8.2 Firmly grasp each flat side of the closed mixing pouch near the center barrier; at the same time, pull sides of barrier apart and roll sides of thumbs through barrier. Break the barrier all the way across to the side seals. (Figure 13) 8.3 Alternately squeeze ends of pouch forcing compound rapidly back and forth, strip compound from corners of pouch between fingers. Mix until color is completely uniform 30 to 40 VIGOROUS SQUEEZES. DO NOT EXCEED 1 MINUTE. (Figure 14) 8.4 Clip off a corner of pouch and immediately pour into funnels, alternating back and forth between them. 8.5 Fill mold until compound fills funnels to 1/2 full. 8.6 Allow compound to cure. 8.7 Check compound in Funnels for curing. NOTE: REPAIR MAY BE DE-MOLDED WHEN COMPOUND IS NO LONGER TACKY. 6 of 8

Typical Cure Time: Typical De-mold Time: 16 24 hrs. @ 70ºF (21ºC) 24 30 hrs. @ 50ºF (10ºC) 36 hrs. @ 32ºF (0ºC) 1.5 hrs. @ 70ºF (21ºC) 4 hrs. @ 50ºF (10ºC) 6 8 hrs. @ 32ºF (0ºC) NOTE: Values are typical, not to be considered minimum or maximum. Always confirm based on tack and hardness of compound. 9.0 De-mold 9.1 Remove funnels by twisting and lifting, breaking off from compound. (Figure 15) 9.2 Remove Mold Straps and Funnel Supports. (Figure 15) 9.3 Carefully cut off spout compound protrusions from repair, using a knife. (Figure 15) 9.4 Remove Scotch Super 33+ Vinyl Electrical Tape from mold ends. 9.5 Remove mold from cable repair, working from ends toward center. 78-8126-9693-2 A 7 of 8

3M, Scotch, Scotchcast, Super 33+, Three-M-Ite and Elek-Tro-Cut are trademarks of 3M Company. Important Notice: All statements, technical information, and recommendations related to 3M s products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product, which are not contained in 3M s current publications, or any contrary statements contained on your purchase order, shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M. Warranty; Limited Remedy; Limited Liability: This product will be free from defects in material and manufacture at the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted. 3 Electrical Markets Division 6801 River Place Blvd. Austin, TX 78726-9000 800.245.3573 Please Recycle. Printed in USA. Fax 800.245.0329 3M 2011 All Rights Reserved. www.3m.com/electrical 8 of 8