Thermal and air quality effects on the performance of schoolwork by children. Field intervention experiments



Similar documents
DK2 IEA. Replacing mechanical ventilation with natural ventilation at Enghøjskolen school in Denmark

HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help?

Information paper 20. Prepared by: David Clark. book:

ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

A Breath of Poor Air: Inspecting Indoor Air Quality in the Classroom Ashley Schopieray

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

Energy savings in the residential area are essential in

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Air Conditioning, Comfort and Energy in India s Commercial Building Sector

INDOOR AIR QUALITY ASSESSMENT

INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT. Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA

Indoor Environmental Quality Management Plan

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation The Building Regulations 2010

CHAPTER 3. The sun and the seasons. Locating the position of the sun

Federation of European Heating, Ventilation and Air-conditioning Associations

Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside.

Indoor Air Quality Issues for Hotels

The efficient heat pump

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. READ ONLY

Lesson 36 Selection Of Air Conditioning Systems

Resources for School Energy Managers

IEQ-15 Air Distribution System

Whole House Dehumidification for Occupant Comfort and Energy Savings

Energy Saving Fact Sheet Air Conditioning

Adapting to Change: New Thinking on Comfort Natural ventilation in UK schools: design options for passive cooling Steven Firth* and Malcolm Cook

forair optimal air environments ResidentialPresentation

Priority School Building Programme

Molds and mildew are fungi that grow

VENTILATIVE COOLING EBC ANNEX 62 PER HEISELBERG DEPARTMENT OF CIVIL ENGINEERING

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

Displacement Ventilation in Schools

Indoor Air Quality- What You Need to Know

Crawl space heat and moisture behaviour

Investigation of sound insulation for a Supply Air Window field measurements and occupant response

Mechanical and Natural Ventilation

Indoor environment and productivity in office environment

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Dehumidification Frequently Asked Questions

Breathing The Air In Your Home Is Like Living In A Closed Jar. It s Enough To Make You Sick.

INDOOR AIR QUALITY REASSESSMENT. Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts

Comfosystems Systems with heat recovery for a comfortable indoor climate

Cool Spaces. earth-wise guide to. green strategies: light strategies: Keep Austin Cool

EXTREME HEAT/HUMIDEX ADVISORY FACT SHEET

Residential HVAC Load Sizing Training October 14, David Kaiser Green Code Plan Reviewer

RosevilleProject. LoE _ 2 Glass Products. You can reduce your cooling energy usage by 25% or more. Here is the proof.

The Only GUY To Call. Why are my utility bills so high? What can I do to lower my energy expenses?

Key energy-efficient features of your new home

YORK CATHOLIC DISTRICT SCHOOL BOARD

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST

Energy Efficiency, Let s Save Energy!

The Finnish Classification of Indoor Environment and Material Emissions

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE

ENERGY SAVING WINDOW FILMS S LAR CONTROL

Optimum Solar Orientation: Miami, Florida

warm air for the healthiest, most comfortable home environment possible. This occurs with a system efficiency of up to 90%.

Heating and Ventilation

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: Uptime Racks:

Why is it renewable? Well, the sun will always be there for us, and we can use as much of the sun s energy as we want and it will never run out.

School Performance Specifications. SPACES Engineering Technical Meeting 22 September 2015

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

CEN/TC 156. pren Date: CEN/TC 156. Secretariat: BSI ICS: Descriptors:

Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro

Which filter class for supply air is required in a typical HVAC system?

Heat Wave Preparedness Checklists for Vulnerable Populations Service Providers

Wildfire Smoke and Your Health

MOLD ASSESSMENT. Charles A. Bernazzani Elementary School 701 Furnace Brook Parkway Quincy, Massachusetts

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

INDOOR AIR QUALITY INTRODUCTION WHAT ARE THE SYMPTOMS OF SICK BUILDING SYNDROME? WHEN DID POOR INDOOR AIR QUALITY BECOME A PROBLEM?

Heating and cooling. Insulation. Quick facts on insulation:

Humidity Control in School Facilities

Air Handlers HIGHER PERFORMANCE FOR A HIGHER STANDARD OF COMFORT AND EFFICIENCY. Read Only

There are several types of air cleaning devices available, each designed to remove certain types of pollutants.

INVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE

IAQ - indoor ventilation Air contaminants Molds Requirements for growth Health effects Mold prevention - moisture EH&S mold checks & removal

Make plans for outreach during heat emergencies, prioritizing those at highest risk. Document these plans and communicate them to staff.

Technical Cleaning Ó

air conditioners how to choose a cooling system

First Time Home Buyers Energy Efficiency Workshop Guide

Adaptive strategies for office spaces in the UK climate

Transcription:

Thermal and air quality effects on the performance of schoolwork by children David P. Wyon Technical University of Denmark Swegon Air Academy Leiden, NDL 07.04.2010 Field intervention experiments This lecture reports the findings of a recent series of field intervention experiments that was carried out in schools in Denmark and Sweden on behalf of ASHRAE DTU was awarded the research contract in open competition with bidders from USA, Europe, Australia and the Far East The Final Report was accepted in 2009

Final Report of ASHRAE 1257 The effects of temperature, outdoor air supply rate and airborne particles on children in school classrooms David P. Wyon and Pawel Wargocki Technical University of Denmark www.ie.dtu.dk Main RP-1257 Objective To determine whether improving classroom air quality and ensuring classrooms do not become warm can improve the performance of schoolwork by children Window opening behavior was passively recorded during the experiments

Methods Indoor air quality was modified by increasing the outdoor air supply rate from a mechanical ventilation system Air temperature was reduced in hot weather by operating split cooling units Windows could be opened as usual Window opening behavior was recorded as all windows closed or 11 or more open Door opening was also recorded Selected school in Denmark School at Rungsted DTU

Schools Elementary school with no IEQ problems South-facing facades Mechanically ventilated Energy conservation measures in place Plan of the selected classrooms Selected classrooms

Selected classrooms View of classroom

Ventilation system Split cooling Electrostatic air cleaners Split cooling was installed and either operated or idled in summer

Silent electrostatic air cleaners were installed and operated or idled 4th to 6th grade 10-12 12-year old ~300 pupils Pupils

Physical measurements Continuous measurements (with pupils): CO 2, Air T, RH, window opening state recorders Effective outdoor air supply rate in L/sp was estimated from CO 2 rate of increase each time children entered the classroom. Note that this includes air entering through windows as well as supply air Measurements of perceptions and symptoms The children marked Visual-Analogue scales at the end of the week Intensity of symptoms and their perceptions of the classroom environment was indicated How is the classroom right now? Too cold The air is It is draughty humid The air is poor Too dark Too noisy How do I feel right now? Nose is blocked Throat is dry Lips are dry Skin is dry I am very hungry I slept badly last I feel very night tired I slept too little last I do not feel night like I working have a headache Too warm The air is still It is dry The air is fresh Too much light Too dark I can breathe freely Throat is not dry Lips are not dry Skin is not dry I am full I slept well last night I am not at all tired I slept long last night I feel like working today I do not have a headache

Measurements of performance Tasks appropriate to children children s age, developed in consultation with class teachers 4 languagelanguage-based: Acoustic proofproof-reading Reading and comprehension Logical reasoning ProofProof-reading 4 numerical: Subtraction Multiplication Number comparison Addition Tasks performed during mathematics and language lessons Sensory assessments of air quality by visiting adult panel ACCEPTABILITY SCALE Clearly acceptable Just acceptable Just not acceptable Clearly not acceptable After classes ended

Permission was obtained from: Parents School Headmaster School Board Teachers Local Authority Danish Ethics Review Board Swedish Ethics Review Board Design of experiments Interventions always improved conditions Interventions were for 1 week at a time in balanced order of presentation Cross-over design (one classroom with existing conditions and one with improved conditions) The ventilation system was modified to provide more air to one classroom at a time Split cooling installed and run in one classroom at a time

2x2 design Temperature Current Cool Ventilation rate current high Estimated effective L/s p 10 8 L/s per person 6 4 2 AC No AC 0 Low L/s High L/s

Mean classroom CO2 ppm 1200 1000 Mean CO2 ppm 800 600 400 200 AC No AC 0 Low L/s High L/s Peak classroom CO2 ppm Peak CO2 ppm 1400 1200 1000 800 600 400 200 0 Low L/s High L/s AC No AC

Teaching environment and routines No restrictions on normal daily activities No changes in class schedules Doors and windows could be opened No contact between researchers and children Reduced classroom temperature 2 independent experiments in August/September 2004 and 2005: 1st experiment: temperature reduced from 23.5 to 20 o C at two ventilation rates 2nd experiment: temperature reduced from 25 to 21 o C with no mechanical ventilation Other parameters of classroom IEQ were unchanged

Typical time-course of classroom temperature in the two classrooms 30 28 26 T [ C ] 24 22 20 18 07:30 09:00 10:30 12:00 13:30 15:00 16:30 Time Children s s perception of temperature Too warm (P<0.001) Too cold Estimated PMV Low temp PMV=0 High temp PMV=0.7

Performance of schoolwork as a function of classroom temperature 1,4 Performance 1,2 1 0,8 R 2 = 0.68 0,6 18 20 22 24 26 Temperature 1 o C lower temperature ~3.5% higher performance Earlier experiments by DP Wyon in Sweden in 1967 Raising classroom temperature from 20 C to 30 C C reduced most types of schoolwork performance by up to 30% For 40 years this was widely believed to be an overestimate The present results confirm the size of the thermal effect first reported in 1967: +10 C would lead to 35% less schoolwork

Increased outdoor air supply rate Three independent field intervention experiments with 100% outdoor air supplied through new filters: 1. 3.4 was increased to 9.5 L/sp 2. 3.0 was increased to 6.5 L/sp 3. 5.0 was increased to 9.5 L/sp (with and without cooling 2200 2000 1800 Time-course of classroom CO 2 concentration, example ppm 1600 1400 1200 1000 800 600 400 15:59 15:30 15:02 14:33 14:04 13:35 13:06 12:38 12:09 11:40 11:11 10:42 10:14 09:45 09:16 08:47 08:18 07:50

Children s s perception of IAQ Fresh air (P<0.001) Poor air Low vent High vent Sensory assessments of air quality made by an untrained panel after children had left the classroom % (P<0.001) 40 Dissatisfied 30 20 10 0 Low vent High vent

Effect of increasing ventilation rate on performance: increase in speed % 45 35 25 15 5 Experiment 1 Experiment 2 Experiment 3 * * * * * * * * * -5 Subtraction Multiplication Number comparison Addition Logical reasoning Reading and comprehension Performance of schoolwork as a function of classroom ventilation 1,4 Performance 1,2 1 0,8 0,6 R 2 = 0.59 0 2 4 6 8 10 12 Ventilation (L/sp) Doubling ventilation rate ~14.5% higher performance

Classroom air quality matters Windows are often not opened Outdoor air supply rates are often low CO2 levels are often above 1000 ppm Increasing the air supply rate from 2.5 to 5 to 10 L/sp would improve the performance of schoolwork by 29% Poor air quality is a major disadvantage for children, and especially for slow workers CO2 in 1663 Scandinavian classrooms October 2009

Overall result from 1663 Scandinavian clasrooms CO2 in Danish classrooms Random selection of 100 classrooms Structured representative sample CO2 recorded throughout school hours 2 weeks in November 2009 Outdoor temperature was 0-150 C Proportion with mean CO2 > 1000 ppm : 66%

Results Condition of supply air filter Two studies in January 2005 No consistent effects on perceptions, symptoms or perceived air quality when a used filter was replaced with a new one Installing a new filter had no effect on children s s performance % 120 110 Speed (P<0.92) % 120 110 % errors (P<0.37) Performance 100 90 100 90 80 80 70 Used filter New filter 70 Used filter New filter

Interpretation Results differ from office findings because: Very little dust was retained in the used supply air filter Supply air was 100% outdoor air, so all the dust originated outdoors Operation of electrostatic air cleaners 2 independent experiments in January and March/April 2005 in 1 Danish and 4 Swedish schools Concentration of particles in classrooms was considerably reduced when electrostatic air cleaners were in operation

Number of particles per cm3 6000 5000 4000 Placebo units Air cleaners 3000 2000 1000 0 >0.75 >1.0 >2.0 >3.5 >5.0 >7.5 >10 >15 Concentration of particles per cm3 (with/without electrostatic deposition) Reduction greater in the 2 poorly ventilated classrooms 6000 5000 4000 3000 2000 1000 0

Operating electrostatic air cleaners had no effects on performance Performance % 120 110 100 90 80 Speed (P<0.59) % 120 110 100 90 80 % errors (P<0.36) 70 Placebo units Air cleaners 70 Placebo units Air cleaners Conclusions on filters and airborne particles Electrostatic air cleaners reduced the concentration of airborne particles but had no effects on schoolwork Installing a new filter in the outdoor air supply flow had no effects on schoolwork However, reducing airborne particle concentration may reduce the long-term effects of IAQ on health

Main 1257-RP conclusions Reducing even slightly warm classroom temperatures eliminated thermal discomfort and improved children s performance Increasing outdoor air supply rate improved classroom air quality and children s performance Schoolwork was performed faster, with no increase in errors, in both cases Implications Removing airborne particles had no effect, so the IAQ effects were due to gas-phase pollutants in classroom air Replacing supply air filters had no effect but increasing the outdoor air supply rate did, so pollutants must originate indoors The active pollutants could be bioeffluents or emissions from materials, or both

IAQ effects on adults Emissions: : performance of office work was reduced when office materials were present behind a screen in a clean room Bioeffluents: : performance of office work was reduced when the outdoor air supply was reduced in a clean room Conclusion: both classroom emissions and bioeffluents are likely to affect the performance of schoolwork by children Window opening Throughout the DK experiments, state loggers fitted to windows and doors recorded when they were open Teachers and children were able to open windows and doors as usual This is the first intervention experiment on window-opening opening behaviour in response to raised temperature or decreased outdoor air supply rate in school classrooms

Summertime classroom T in C (NB: Different classes with natural/mechanical ventilation) 30 25 20 No AC AC 15 Off Low High Mechanical ventilation Observations Split cooling reduced air T by only 1.7 C C at the highest ventilation rate (T was reduced by 5.4 C C at the lower rate) With natural ventilation, cooling was not very effective, reducing T by only 3.3 C (NB: this could be due to poor mixing, as T was recorded at 2.2m height)

Outdoor air supply rate (L/sp) (NB: Different classes with natural/mechanical ventilation) 10 5 No AC AC 0 Off Low High Mechanical ventilation Hours/week with windows open (NB: Different classes with natural/mechanical ventilation) 15 10 5 No AC AC 0 Off Low High Mechanical ventilation

Observations Windows were opened ed much more when it was warm in the classroom Even at 10 L/sp, a 1.7 C C increase in T increased window opening by 75% With no cooling, opening windows provided only 3.7 L/sp Split cooling reduced window opening by 65%, reducing the outdoor air supply rate to only 2.7 L/sp Classroom T 25 (NB: different classes in winter & summer) C 20 Summer Winter 15 Low High Ventilation (with no AC)

Outdoor air supply rate (L/sp) 10 (NB: different classes in winter & summer) 8 6 4 Summer Winter 2 0 Low High Ventilation (with no cooling) Hours/week with windows open 10 (NB: different classes in winter & summer) 8 6 4 Summer Winter 2 0 Low High Ventilation (with no cooling)

Hours/week with windows open and with cross ventilation 10 (2 classes in winter, 2 other classes in summer) 8 6 4 Windows open Cross ventilation 2 0 Winter Summer (With mechanical ventilation set to low in both seasons) 15 Hours per week with windows open and with cross ventilation (Summer, same 2 classes in all 4 conditions) 10 5 Windows open Cross ventilation 0 T low (A/C) T high (No A/C) (With mechanical ventilation set to low throughout)

Observations Windows were open 4x as long in summer (when classroom T was 5 C 5 C warmer) This raised the total outdoor air supply rate from 6.5 to 9.5 L/sp Both windows and doors were used adaptively to achieve cross-ventilation Window opening was triggered by warmth but not by poor air quality Conclusions on window opening Windows were opened to reduce classroom temperatures, not to improve IAQ Natural ventilation did not ensure adequate ventilation,, even with cross-ventilation Split cooling, by eliminating the perceived need to open windows, decreased the air quality still further In this study, both slightly raised T and poor IAQ decreased children s s performance

Our thanks t are due to ASHRAE, STVF, Asthma and Allergifond and Formas for funding Sophie Irgens (mid-term project student) Bartlomiej Matysiak, Line Jark, Maria Schaub- Hansen, Kasper Lynge Jensen, Mateusz Komenda (M.Sc. students) Cristina Pirvu, Henry Willem (Ph.D. students) Pupils, teachers, schools, municipalities School Technical Services in Rungsted & Lund Further reading ASHRAE Journal, October 2006 (Summary of T, IAQ effects) ASHRAE HVAC&R Research J, March 2007 (2 papers: T, IAQ effects) ASHRAE HVAC&R Research J, May 2008 (e-filters) Indoor Air 2008, September 2008 (Observations of window opening)