Which filter class for supply air is required in a typical HVAC system?
|
|
|
- Rosamund Kelley
- 9 years ago
- Views:
Transcription
1 Which filter class for supply air is required in a typical HVAC system? Thomas Carlsson, Technical Director, Magnus Johnsson, Vokes Air Table of Contents: Background 2 Energy Demand 2 Air Quality and PM Measurements in Europe 3 Energy Demand caused by Filter Pressure Drop 3 Air Quality Improvement with Different Filter Classes 4 Calculation of Energy Demand for Different Filter Classes 6 Conclusion 7
2 Background Air Quality In 1555, the Danish bishop Olaus Magnus said that the farmers should not thresh hay against the wind because the dust is so fine that one cannot notice its inhalation and accumulation in the back of the throat. The effect of particles on human health had been recognised as early as the sixteenth century. The present levels of airborne particles are causing severe damage to human health in Europe. The World Health Organisation (WHO) has estimated that 100,000 premature deaths in Europe every year can be attributed to exposure to particulate matter (PM) [1]. Furthermore, it is believed that the incidence and severity of respiratory diseases such as asthma and bronchitis are aggravated by exposure to PM. Levels of PM must be reduced if we are to reach the objective of avoiding significant negative impact on human health. The distribution of costs on the different categories depends on which filter class is used, fan efficiency and service time. The dominating part is the energy cost (for a filter with filter class F7 the energy cost is 80 % of the total cost [1] ). Using a filter with lower pressure drop (more filter bags) will reduce the cost for energy use, but the filter cost will increase. To get a cost-effective installation, the ventilation system has to be optimised regarding the number of pockets on the filter. Energy Demand The Energy Performance of Buildings Directive (EPBD) [2] came into force at the beginning of 2003, and the EU member states were obliged to incorporate the directive into national law by The EPBD will be an important tool in helping the EU members to fulfil their commitments according to the Kyoto protocol. A major part of EU energy demand originates from the building sector. The EU has estimated that it will be able to reduce its total energy demand by 11% by targeting measures in the building sector. The directive allows member states considerable freedom in implementation, but one area that will receive a great deal of attention are measures to reduce the power demand in HVAC installations. Fans in office buildings are one of the largest consumers of power in buildings (15-20% in Sweden) [3]. A very cost efficient way to reduce the power demand of this type of application is to use filters that have the correct design and dimensions in an air conditioning system. The EPBD also states that the requirements on the energy demand of a building must be strongly correlated to the requirements on the indoor climate. This means that we must consider both the energy demand of the filter and the minimum filter class required in order to maintain a good indoor air climate. The correct design of filter class for supply air ensures that the installation will fulfil the threshold values for PM concentration in the indoor air. Such a design will also ensure that the requirement for low energy demand imposed by the EPBD will be fulfilled. 2
3 Air Quality and PM Measurements in Europe Air quality measurements are becoming more common in Europe. Many European municipalities have continuous measurements of sulphur dioxide (SO 2 ), nitrogen dioxide (NO 2 ), particulate matter 10 (PM 10 ), particulate matter 2.5 (PM 2.5 ), lead (Pb), carbon monoxide (CO), benzene (C 6 H 6 ) and ozone (O 3 ). Twenty-six EU member states submit their results from air quality measurements to the EIONET network [5]. The measurement stations are located both in city centres and in rural areas, and the purpose of the measurements is to check whether the air quality requirements defined by the European Commission are achieved. Results from air quality measurements can be found on the internet [5]. The following threshold values have been laid down for particles [6] : Table 1: Threshold values for PM, according to EU directive 1999/30 [6] Pollutant Concentration Averaging period Legal nature Percentile PM µg/m 3 24 hours PM µg/m 3 24 hours Threshold value enters into force Threshold value enters into force The threshold values from the EU are intended to be applied to outdoor air. There are, however, no recommendations for indoor air quality, and thus these threshold values can be considered to be maximum values for indoor air [7]. Energy Demand caused by Filter Pressure Drop The pressure drop across a full size filter (592*592 mm) at a nominal air flow rate of 1 m 3 /s (which is a typical air flow for a full size filter) can lie between 60 and 350 Pa. The value depends on the filter class, the filter design and how much dust the filter contains. The energy demand that the pressure drop creates can be calculated by the following equation: Q = Δp x q v x h 1000 x η where: Q = energy demand (kwh) Δp = average pressure drop across the filter during the service time (Pa) h = service time (hours) q v = flow rate (m 3 /s) η = total fan efficiency (%) 3
4 Example: [4] Air flow rate = 1 m 3 /s Average pressure drop = 200 Pa (typical for a filter of class F7/MERV 13) Service time = 8760 h Total fan efficiency = 50% Q = 1 x 200 x x kWh/year The annual energy demand for the filtration of a 1 m3/s air flow per year is thus 3500 kwh when a filter of filter class F7/MERV 13 is used. The annual energy demand for a filter of filter class F5/MERV 10 is approximately 1100 kwh/year. This value is lower since the pressure drop is lower. The energy bill for air filtration is huge. There is a great potential for energy saving by decreasing pressure drops! Air Quality Improvement with Different Filter Classes The first question facing a designer of filter classes is the quality of air desired. The air quality of supply air must comply with the European Directive 1999/30 [6], namely 50 µg/m 3, 98 percentile values for PM 10 (by 2010). The concentration of PM 10 in the air entering a building (supply air) can be found using data from existing measurement stations in Europe. The filter data (particle removal efficiency) can be found from a test report of the filter [9]. The distribution for the particle sizes can be estimated using a Junge distribution. This information enables us to calculate the PM 10 value of supply air for different filter classes. PM 10 concentrations in Stockholm in 2006 were 98 percentile, 109 µg/m 3. Calculating the PM 10 removal for different filter classes gives the following results. 109 µg/m³ F5=71 µg/m³ F6=48 µg/m³ F7=22 µg/m³ PM10 Gauge PM10 Gauge Figure 2. The particle removal efficiency differs for different filters in the same filter class. The calculation gives results for a typical filter from each filter class. 4
5 F5/MERV10 F6/MERV12 F7/MERV13 Filter Class Filter class F6/MERV 12 is sufficient to meet the required threshold value of 50 µg/m 3. The calculation gives the particle concentration in the duct downstream of the filter. Previous work [8], however, has shown that the air quality in the building will not be the same as in the duct. Not all supply air to a building will pass the supply air filter. Figure 3: Not all supply air will pass the filter before entering the building. It has been shown that 20-30% of the supply air does not pass the filter (in the case in which the air exchange rate is one exchange per hour)the infiltration is caused by extra exhaust air which is needed to create an under pressure in the building. Moreover, wind and the temperature differences also contribute to the infiltration. Exfiltration can occur in special cases. Infiltration and exfiltration must be included in the calculation of indoor air quality. This gives the following values for Stockholm. 109 µg/m³ F5=81 µg/m³ F6=67 µg/m³ F7=48 µg/m³ Air Leakage Figure 4: The particle removal efficiency differs for different filters in the same filter class. The calculation gives results for a typical filter from each filter class. Including infiltration and exfiltration leads us to conclude that a filter of filter class F7/MERV 13 is needed to meet the requirement for indoor air quality. The F6/MERV 12 is not sufficient. 5
6 Calculation of Energy Demand for Different Filter Classes The pressure drop across a filter will depend on the filter design and the filter class. The equation that gives the energy demand for a filter is Q = Δp x q v x h 1000 x η If we take the following typical values: Air flow rate = 1 m 3 /s Service time = 8760 h Fan efficiency = 50% and use the following values of average pressure drop for filters of different classes: F5/MERV 10=65 Pa, F6/MERV 12=100 Pa, F7/MERV 13=200 Pa, we can predict the energy demands: 3500 Energy Consumption For Different Filter Classes at a air flow rate of 1m 3 /s F5/MERV10 F6/MERV12 F7/MERV13 Filter Class 6
7 Conclusions This article has described a design tool for determining the filter class required to achieve a given air quality with the lowest possible energy demand. The EU s EPBD [2] has set a target for electricity demand reduction in buildings of 11%. Statistics of filter sales and energy demand for fans in Sweden allow us to calculate that it is possible to save 2-3% of the electricity demand in office buildings by using the correct design of the filter class. This saving can be achieved simply by changing the filter; there is no need to rebuild the system. For calculation of heating and cooling systems climate data is used, today it is possible to use particle data for designing filter classes. References [1] World Health Report 2002, WHO [2] Energy Performance of Building Directives 2002/91/EC [3] Förbättrad energistatistik för lokaler Stegvis STIL Rapport för år 1, Energimyndigheten, 2006 (in Swedish) [4] Recommendation Concerning Calculating of Life Cycle Cost for Air Filters, Eurovent [5] 6] EU Directive 1999/30/EC [7] The Swedish Building Code, 2006:12 [8] Healthy Buildings 1997, System Effects on Filtration Efficiency, Thomas Carlsson [9] EN779:EN 2002, Particulate Filters for General Ventilation Determination of the Filter Performance 7
Calculating the cost of HVAC air filters
Thomas Carlsson R&D Director Table of Contents: Abstract 2 Background 3 Project Aim 3 Results 4 Conclusions 6 Abstract A computer program for calculating and optimising the filter cost in a ventilation
2) Relevance for environmental policy... 2. 4) Data sources and reporting... 5 5) References at the international level... 6
A- 2: Ambient air quality in urban areas 1) General description... 2 1.1) Brief definition... 2 1.2) Units of measurement... 2 1.3) Context...2 2) Relevance for environmental policy... 2 2.1) Purpose...
IEQ-15 Air Distribution System
AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA
3M Personal Safety Division 3M Center, Building 0235-02-W-75 St. Paul, MN, USA 55144-1000 651 733 1110
3M Personal Safety Division 3M Center, Building 0235-02-W-75 St. Paul, MN, USA 55144-1000 651 733 1110 3 24 March 2014 Respiratory Protection for Exposures to Particulate Air Pollution Air pollution is
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of
Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice
Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice A truly international certification The Eurovent Certification Programmes are managed by an autonomous
i n d o o r a i r q u a l i t y I AQ EN 13779:2007 European standard Camfil Farr clean air solutions
i n d o o r a i r q u a l i t y I AQ Camfil Farr Segment brochure EN 13779:2007 European standard Camfil Farr clean air solutions en 13779 environment, air quality and health The industrialised world is
Air Quality: Public Health Impacts and Local Actions
Air Quality: Public Health Impacts and Local Actions This briefing is to inform public health professionals of the public health impacts of air pollution, the sources of air pollution and measures available
National Environment Protection (Ambient Air Quality) Measure. Appendix 6
SOCO National Environment Protection (Ambient Air Quality) Measure Report of the Risk Assessment Taskforce 2 Appendix 6 Pb NO 2 Possible use of Health Risk Assessment in the Review of NEPM Pollutants Specified
HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.
HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains
DATA CENTRES. Camfil Farr Segment Brochure Data Centres Camfil Farr - Clean Air solutions
DATA CENTRES Camfil Farr Segment Brochure Data Centres Camfil Farr - Clean Air solutions Camfil Farr Leading the way in clean air Technology About Camfil Farr Camfil Farr is a world Leader in clean air
Health effects of particulate matter and implications for policy in Europe
Health effects of particulate matter and implications for policy in Europe Marie-Eve Héroux Technical Officer, Air Quality and Noise WHO European Centre for Environment and Health Bonn, Germany Presentation
Quick wins for energy savings in buildings
Quick wins for energy savings in buildings Choosing low energy air filters for both optimized energy performance and indoor air quality Executive Summary HVAC systems heat, cool and clean the air within
Wildfire Smoke and Your Health
PUBLIC HEALTH DIVISION http://public.health.oregon.gov Wildfire Smoke and Your Health When smoke levels are high, even healthy people may have symptoms or health problems. The best thing to do is to limit
How To Get A Passive House
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product
COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI
Proceedings of Healthy Buildings 2000, Vol. 2 675 COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI Mikko Saari 1, Juhani Laine 1, Sami Karjalainen 1 and Klaus Hamström
Robert McCabe Director, Health Care Solutions HTS Chicago. Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade
Robert McCabe Director, Health Care Solutions HTS Chicago Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade Biography Robert McCabe has been involved in commercial
Jorine Campopiano US Environmental Protection Agency Region 9 Schools Environmental Health Coordinator. May 27, 2014
Jorine Campopiano US Environmental Protection Agency Region 9 Schools Environmental Health Coordinator May 27, 2014 Today we ll talk about The Flag Program The purpose of the program Background information
FACT SHEET PROPOSED REVISIONS TO THE NATIONAL AMBIENT AIR QUALITY STANDARDS FOR SULFUR DIOXIDE
FACT SHEET PROPOSED REVISIONS TO THE NATIONAL AMBIENT AIR QUALITY STANDARDS FOR SULFUR DIOXIDE SUMMARY OF ACTION o On November 16, 2009, EPA proposed to strengthen the National Ambient Air Quality Standard
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
Impact Assessment of Dust, NOx and SO 2
Impact Assessment of Dust, NOx and SO 2 By Pat Swords Content of the Presentation Historical Basis for Air Pollution Control Impacts of air pollutants on human health, etc. Impact Pathway Approach to assessing
WHY IS BREATHING SO IMPORTANT?
You need to breathe to stay alive. But how clean is the air you breathe? If you breathe dirty air, you are more likely to develop health problems and become ill. Plants and animals need clean air too.
2014 Aamjiwnaang Air Monitoring Station Results. Ministry of the Environment and Climate Change April 19, 2016
2014 Aamjiwnaang Air Monitoring Station Results Ministry of the Environment and Climate Change April 19, 2016 Outline Key Results Parameters Measured Benchmarks 2014 Report Results Mobile Monitoring Results
What are the causes of air Pollution
What are the causes of air Pollution Pollutant Particulate Matter (PM-PM 10 and PM 2.5 ) Description and main UK sources Particulate Matter is generally categorised on the basis of the size of the particles
An overview of Euro VI for trucks over 3.5t. Brought to you by Mercedes-Benz
An overview of Euro VI for trucks over 3.5t Brought to you by Mercedes-Benz Contents What is Euro VI? What is Euro VI? 01 What s different about Euro VI? 02 When do you need to think about it? 03 How is
UK Air Quality Monitoring Networks
UK Air Quality Monitoring Networks Steve Telling 28 August 2012 Introduction History of air quality monitoring Legislative drivers The monitoring networks Data quality considerations Access to data Concern
NSW Air Quality Monitoring Network: Quality Assurance Procedures
NSW Air Quality Monitoring Network: Quality Assurance Procedures Copyright State of NSW and Office of Environment and Heritage With the exception of photographs, the State of NSW and Office of Environment
INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT. Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA
INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health
The Challenges In Monitoring And Control Of Indoor Air Pollution Due To Combustion In Kitchens In Urban And Rural Areas
The Challenges In Monitoring And Control Of Indoor Air Pollution Due To Combustion In Kitchens In Urban And Rural Areas Rural Urban Rashmi S. Patil Professor Centre for Environmental Science and Engineering,
INDOOR AIR QUALITY REASSESSMENT. Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts
INDOOR AIR QUALITY REASSESSMENT Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor
Energy Efficient HVAC-system and Building Design
Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: [email protected] SUMMARY This paper
Adverse Health Effects of Air Pollution in India
Health Impacts of Air in India in India in India JN Pande Sitaram Bhartia Institute of Science and Research, New Delhi Well documented in developed countries using several epidemiological study designs.
Offshore Substation. HVAC System. ETS-09 Rev. 2. technical standards. Dok. 44969-09 Sag 09/1437
technical standards Offshore Substation HVAC System ETS-09 Rev. 2 Dok. 44969-09 Sag 09/1437 Revision survey Document title HVAC System Document no. 44972-09 Target group Fabrications Contractors and Designer
THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM
1 Application Note AT-102 THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM Lawrence B. Kilham 1 and Randall M. Dodd 2 1 Eco Sensors, Inc. Santa Fe, New Mexico, USA [email protected]
Hackney Biomass Boiler Information Request Form
Hackney Biomass Boiler Information Request Form In common with other types of combustion appliances, biomass boilers are potentially a source of air pollution. Pollutants associated with biomass combustion
Testing and Assessment Protocol Release 2.0. Programme Manager Dipl.-Ing. (FH) Sonja Schmidt ADAC Technik Zentrum
Testing and Assessment Protocol Release 2.0 Programme Manager Dipl.-Ing. (FH) Sonja Schmidt ADAC Technik Zentrum Contents 1 Introduction... 3 2 Testing Protocol... 3 2.1 New European Driving Cycle (NEDC)...
WATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts
WATER DAMAGE INVESTIGATION Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor
Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program
Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality
INDOOR AIR QUALITY INTRODUCTION WHAT ARE THE SYMPTOMS OF SICK BUILDING SYNDROME? WHEN DID POOR INDOOR AIR QUALITY BECOME A PROBLEM?
INDOOR AIR QUALITY Public Employees Occupational Safety and Health Program Richard J. Codey Acting Governor November, 2004 INTRODUCTION The average person sends approximately 90% of their time indoors.
ECHO System for Basements
ECHO System for Basements Homeowners looking for more space are all too familiar with the cold, damp and dingy basement. Now, the Enclosure Conditioned Housing (ECHO) System TM, winner of the Ottawa-Carleton
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
Costs of air pollution from European industrial facilities 2008 2012 an updated assessment
Costs of air pollution from European industrial facilities 2008 2012 an updated assessment Summary In 2012, air pollution from European industrial facilities cost at least EUR 59 billion (and up to EUR
Educational Performance, Environmental Management, and Cleaning Effectiveness in School Environments
Educational Performance, Environmental Management, and Cleaning Effectiveness in School Environments By Michael A. Berry, Ph.D. 16 Charrington Place Chapel Hill, NC 27514 Phone: (919) 493-7409 E-mail:
The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity
Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings
Phoenix Process Engineering, Inc. Project Experience Helping Clients Achieve MACT Compliance
Phoenix Process Engineering, Inc. Project Experience Helping Clients Achieve MACT Compliance The Boiler MACT, 40 CFR 63, Subpart DDDDD, was vacated in 2007 by the U.S Court of Appeals and the 2004 rule
about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house
about your house CE 64 How to Get the Ventilation That You Need in Your House Canadian houses are relatively airtight, and have been for years. The old farmhouses where people lived several generations
Clean Up Your Fleet. Introducing a practical approach to cleaner, more efficient fleet operation
Clean Up Your Fleet Introducing a practical approach to cleaner, more efficient fleet operation The value of clean fleet management Reduce air pollution from your fleet Reduce greenhouse gas emissions
warm air for the healthiest, most comfortable home environment possible. This occurs with a system efficiency of up to 90%.
Lifebreath delivers a complete indoor climate control package Indoor comfort in a small package The patented Lifebreath Clean Air Furnace combines the fresh air benefits of the Heat Recovery Ventilator
Information paper 20. Prepared by: David Clark. book:
Information paper 20 Ventilation rates in offices and natural mechanical Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information
Continuous flow direct water heating for potable hot water
Continuous flow direct water heating for potable hot water An independently produced White Paper for Rinnai UK 2013 www.rinnaiuk.com In the 35 years since direct hot water systems entered the UK commercial
There are several types of air cleaning devices available, each designed to remove certain types of pollutants.
Please Note: EPA neither certifies nor recommends particular brands of home air cleaning devices. While some home air cleaning devices may be useful in some circumstances, EPA makes no broad endorsement
AMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL
AMCA International Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on Air
The Ambient Air Monitoring System
The Ambient Air Monitoring System 1.0 Introduction: The Ambient Air Monitoring System (AAMS) can measure a range of toxic and flammable gases, particulate matter, meteorological and environmental parameters
The design of the Romanian national air quality monitoring network
The design of the Romanian national air quality monitoring network Ecaterina SZABO NRC Air Quality Romania Senior Councilor Pollution Control and Air Quality Department Ministry of Environment and Forestry
Monitoring of air pollution spread on the car-free day in the city of Veszprém
INTERNATIONAL JOURNAL OF ENERGY AND ENVIRONMENT Volume 5, Issue 6, 2014 pp.679-684 Journal homepage: www.ijee.ieefoundation.org Monitoring of air pollution spread on the car-free day in the city of Veszprém
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction
your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction What is DNSS EcoSave? The Daikin Network Service System (DNSS EcoSave) is a Daikin developed internet based remote
Innovation #9/12. of all Formaldehyde for up to
Innovation #9/12 of all Formaldehyde for up to Gyproc Activ Air Benefits of Activ Air Improves the indoor air quality, providing healthier interior environments Permanently reduces Formaldehyde and other
Air quality and biomass installations. A briefing for local authorities
Air quality and biomass installations A briefing for local authorities March 2011 Published by BioRegional Development Group BedZED Centre, 24 Helios Road, Wallington, Surrey SM6 7BZ. www.bioregional.com
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
AIR QUALITY IN PARIS REGION 2014
AIR QUALITY IN PARIS REGION 214 Summary May 215 AIR QUALITY IN THE PARIS REGION 214 Summary May 215 This report is an English summary of the annual report on ambient air quality in the Paris region. It
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Combi Unit Genius. The energy efficient Building Service Centre
Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Combi Unit Genius The energy efficient Building Service Centre systemair Central Building Services
Technology: Heating, Ventilation and Air Condition (HVAC) Zone Controls
Accelerated Capital Allowances Eligibility Criteria Ref No.: HZC C2.1 Category: Process and Heating, Ventilation and Air conditioning (HVAC) Control Systems Technology: Heating, Ventilation and Air Condition
136 deaths in 2007 (Latest figures available) UK (129 in England) 2,458 serious injuries in 2007 in the UK source- National Office of Statistics
Cycle facts to arm and protect DEATHS AND INJURIES Time: 136 deaths in 2007 (Latest figures available) UK (129 in England) 2,458 serious injuries in 2007 in the UK source- National Office of Statistics
Guide to UK Air Pollution Information Resources June 2014
www.gov.uk/defra Guide to UK Air Pollution Information Resources June 2014 Contents Introduction... 1 What public information is available?... 2 UK-AIR online... 2 Air Quality Websites for Scotland, Wales
GAS HEATING IN COMMERCIAL PREMISES
ENERGY EFFICIENCY OFFICES GAS HEATING IN COMMERCIAL PREMISES www.energia.ie www.energia.ie Typically, energy reductions of 10% or more can be made easily through maintenance and low cost improvements.
Testing of particulate emissions from positive ignition vehicles with direct fuel injection system. Technical Report 2013-09-26
Testing of particulate emissions from positive ignition vehicles with direct fuel injection system -09-26 by Felix Köhler Institut für Fahrzeugtechnik und Mobilität Antrieb/Emissionen PKW/Kraftrad On behalf
Air Pollution. Copenhagen, 3 rd September 2014. Valentin Foltescu Project manager air quality European Environment Agency
Air Pollution Copenhagen, 3 rd September 2014 Valentin Foltescu Project manager air quality European Environment Agency Air pollution, transport and noise MAWP Strategic Area 1.1 Objective To support and
Priority School Building Programme
UPDATE Includes June 2013 changes to FOS Priority School Building Programme Making sense of the new Priority School Output Specification from the Education Funding Agency. How is the output specification
SENSORS FOR AIR QUALITY MONITORING MARCEL ZEVENBERGEN SR. RESEARCHER GAS AND ION SENSORS
SENSORS FOR AIR QUALITY MONITORING MARCEL ZEVENBERGEN SR. RESEARCHER GAS AND ION SENSORS Health and Lifestyle as Application Driver IMPROVE ILLNESS MANAGEMENT ENABLE HEALTH MANAGEMENT ( What if these systems
Health and the environment: addressing the health impact of air pollution
1 EXECUTIVE BOARD EB136/CONF./9 Rev.1 136th session 29 January 2015 Agenda item 7.2 Health and the environment: addressing the health impact of air pollution Draft resolution proposed by the delegations
EMISSIONS OF AIR POLLUTANTS IN THE UK, 1970 TO 2014
STATISTICAL RELEASE: 17 DECEMBER 2015 EMISSIONS OF AIR POLLUTANTS IN THE UK, 1970 TO 2014 There has been a long term decrease in the emissions of all of the air pollutants covered by this statistical release
Electrostatic or Electronic: Know the Facts By Robert P. Scaringe, P.E., Ph.D., ---President of Mainstream Engineering
Electrostatic or Electronic: Know the Facts By Robert P. Scaringe, P.E., Ph.D., ---President of Mainstream Engineering HVAC system air filter upgrades are one way contractors can simultaneously increase
Mechanical and Natural Ventilation
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
Fläkt Woods Building Future
Energy, Expertise and Environment with Fläkt Woods Fläkt Woods Building Future Saving energy in building ventilation You must save 20% on energy before 2020. Following the Kyoto protocol the European Union
Extra Low Energy Housing in Ireland How far should we go to the Passive House? Jonathan Jennings Head of R&D Kingspan Century Homes
Extra Low Energy Housing in Ireland How far should we go to the Passive House? Jonathan Jennings Head of R&D Kingspan Century Homes Current Status % CO 2 emissions Transport 30% Agriculture 2% Housing
GEA Niro Pharmaceutical GMP Spray Drying facility. Spray drying process development and contract manufacturing. engineering for a better world
GEA Niro Pharmaceutical GMP Spray Drying facility Spray drying process development and contract manufacturing engineering for a better world GEA Process Engineering 2 GEA Niro PSD-4 Chamber cone in clean
Take Action on Asthma. Environmental triggers of asthma and allergies
Take Action on Asthma Environmental triggers of asthma and allergies What are asthma and allergies? They are both conditions where the body reacts to substances commonly found in the air. Asthma is a very
ANSI/ASHRAE 52.2-2007
The Updated Air Filter Standard ANSI/ASHRAE 52.2-2007 Koch Filter Corporation...Durable. Reliable. Versatile. Bulletin No. K-ASH52.2-09 In recent years, the air filter industry has changed important portions
INTERACTIONS: ENERGY/ENVIRONMENT Fossil Fuel Energy Impacts on Health - Helena Ribeiro
FOSSIL FUEL ENERGY IMPACTS ON HEALTH Helena Ribeiro Department of Environmental Health, Faculdade de Saúde Pública, Universidade de São Paulo, Brazil Keywords: Fossil Fuel, Combustion, Air Pollution, Respiratory
Swedish Regulations, BBR and Compulsory Ventilation Checks (OVK)
Swedish Regulations, BBR and Compulsory Ventilation Checks (OVK) [email protected] Ventilation and airtightness BBR 6:255 Pressure conditions between supply air and extract air installations shall
AQUACIAT2 HYBRID THE COMPACT DUAL-ENERGY SOLUTION HEAT PUMP & GAS BOILER. Cooling and heating capacities of 45 to 80 kw AVAILABLE 2 ND QUARTER OF 2014
AVAILABLE 2 ND QUARTER OF 2014 HEAT PUMP & GAS BOILER C O M F O R T A I R Q U A L I T Y E N E R G Y O P T I M I S A T I O N AQUACIAT2 HYBRID Cooling and heating capacities of 45 to 80 kw THE COMPACT DUAL-ENERGY
The Finnish Classification of Indoor Environment and Material Emissions
The Finnish Classification of Indoor Environment and Material Emissions Jorma Säteri Finnish Society of Indoor Air Quality and Climate, FiSIAQ Finnish Classification of Indoor Environment 2008 An update
Ports of Stockholm meets new environmental requirements with LNG
Ports of Stockholm meets new environmental requirements with LNG Tougher regulations demand new solutions Shipping faces major challenges when the international environmental requirements become tougher.
PROPOSAL AIR POLLUTION: A PROJECT MONITORING CURRENT AIR POLLUTION LEVELS AND PROVIDING EDUCATION IN AND AROUND SCHOOLS IN CAMDEN
PROPOSAL AIR POLLUTION: A PROJECT MONITORING CURRENT AIR POLLUTION LEVELS AND PROVIDING EDUCATION IN AND AROUND SCHOOLS IN CAMDEN Vivek Deva Supervisors: Dr Audrey de Nazelle, Dr Joanna Laurson- Doube