07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM



Similar documents
ROXUL Board Insulation Section Master Guide Specification (CAVITYROCK ) Page 1 April 2016

Product Guide Specification

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

POLYURETHANE LINING AND COATING ON PIPE RAW WATER

Colorado State University. Durrell Center Roof Repair

Fiberglas, Exterior Wall Thermal Insulation

SECTION PRE-ENGINEERED BUILDING BLANKET INSULATION

Product Guide Specification

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

SECTION FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)

ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES. July 1, 2008 Revision 2

RECOATING AND RENEWING SPF ROOFING SYSTEMS

09990 MOLD REMEDIATION, LEAD-BASED PAINT ABATEMENT AND ENCASEMENT OF ASBESTOS

DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION

BRIDGE FIELD PAINTING, REPAINTING, 412 AND PAINT RESIDUE CONTAINMENT. A. Field Painting, Bridge Repainting and Residue Containment:

ALPHA 15-Year Permathane II FR w/granules

SECTION PLAYGROUND SURFACING TILES

EcoTouch Insulation with PureFiber Technology

RTV159. RTV157 and RTV159 High Strength Silicone Adhesive Sealants

Spray Polyurethane Foam Systems for Cold Storage Facilities Operating Between - 40 o C and + 10 o C (- 40 o F and + 50 o F )

SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION CONCRETE BONDING COMPOUND.

A. The CONTRACTOR shall provide pipe coating, complete and in place, in accordance with the Contract Documents.

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

GigaCrete Specification PlasterMax

IS800 Series. Technical Data Sheet IS802, IS803, IS808, IS Description. Key Features and Benefits. Typical Physical Properties

COMMERCIAL BUILDING APPLICATIONS

Roxul Board Insulation Section Master Guide Specification (CAVITYROCK DD) Page 1 October 2013

SECTION XXXXXX TECHNICAL SPECIFICATIONS FOR INSTALLATION OF PROTECTIVE COATINGS FOR MANHOLES, WETWELLS, AND OTHER SANITARY SEWER STRUCTURES

738-B-297 POLYMERIC CONCRETE BRIDGE DECK OVERLAY. (Adopted )

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

Product Information. Tel: x2426 or x2443 Fax:

03/05/14 REVISOR RSI/JC RD3945

ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES

TECHNICAL REQUIREMENTS AND SPECIFICATIONS

The Renewal of Spray Polyurethane Foam and Coating Roof Systems

FLEX-WRAP Foam Pipe Wrap

METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES

Enclosures DuraSystems Barriers, Inc. The Passive Fire Protection Specialists

SCENIC VIEW SV 10 SECTION SOLAR CONTROL FILMS

CONDENSATION. Section Break (Next Page)

Division 9. SignaFlor Pad and Pour Flooring System

BLACK JACK ALL WEATHER ROOF COATING

Scotch-Weld TM. Epoxy Adhesive 1838 B/A Green 1838 B/A Tan 1838-L B/A Translucent. Technical Data February, Product Description

CA-48 TECHNICAL SPECIFICATION

SECTION HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section

SECTION METAL WALL PANELS

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

cement Masonry Cement Engineered for quality and reliability, Lafarge cements for masonry deliver consistent performance. page 2 Lafarge Cement

FIRESTOPPING & SMOKE SEALS

HVAC Super Pro FAQ. Can HVAC SUPER PRO be used on both hard and soft copper and aluminum tubing?

RTV162. Electronic Grade Silicone Adhesive Sealant

Avoiding Air Barrier Pitfalls

THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST

Approved. Property Test/Standard Description. matt (0-35) Flash point ISO 3679 Method 1 27 C calculated IED (2010/75/EU) (calculated)

Construction. 3-part thixotropic epoxy patching mortar. Product Description. Tests

Underwriters Laboratories Testing Information

Meeting the Fire Code with Continuous Foam Plastic Insulation

REHABILITATION OF UNDERGROUND SEWER LATERAL PIPES WITH CURED-IN-PLACE-PIPE LINER SECTION 02542

Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

3 Scotch-Seal TM. Polyurethane Sealant 540 Polyurethane Adhesive Sealant 560. Technical Data July, 2008

s ation lic app ntial Foamular sideor RE uide F Ily G am ation F sul In

NEW ELECTRICAL SUBSTATION Building 300 SECTION ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

Mainline Pipe Rehabilitation Using Cured-in-Place Pipe (CIPP) & Folded Pipe Technology

SECTION COLD-FORMED METAL DECK FRAMING Elevations Steel Deck Framing by Trex

GUIDELINE SPECIFICATIONS

GENERAL SPECIFICATIONS AND GUIDELINES FOR INSTALLATION MASTERLINER CURED-IN-PLACE PIPE SYSTEMS

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

SECTION CEMENTITIOUS COATED FOAMED ROOFING

Technical Data Sheet February 2014

C. Section TESTING LABORATORY SERVICE.

ITEM THERMOPLASTIC MEMBRANE ROOFING

SECTION Formatted Specification for the ULTRAFLOR DIAMATIC Topical Polished Concrete System DRAFT

09/07/07 GLASSFIBER REINFORCED CEMENT (GRC) C. S. I. Spec Master Spec Page 1

A D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA

SECTION SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.

SECTION POLISHED CONCRETE FINISHING. InovaCrete Polished Concrete Floor Finish (GUIDE SPEC)

Scotch-Weld TM. Acrylic Adhesives. DP8405NS Green. Product Data Sheet. Date: March 2014 Supersedes: August 2013

3M Scotchcast Electrical Resin 251 Two-Part, Oven-Curing, Class F, Rigid, Filled, Epoxy Liquid Resin

Mold Preventing I nterior System

Notes. Material 1. Appropriate Flammable Liquids

ICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015.

BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION

SPREFIX SPRAY INSULATION _ in the marine market.

INDUSTRIAL FLOORING INSTALLATION CHALLENGES. James C. Ziegler, ArmorSeal Product Manager Sherwin Williams Cincinnati, Ohio, USA

ROOF CONDENSATION: A COSTLY PROBLEM

Specifications. PermaTone, Inc. Manufacturer s Long Form Specifications Interior Finish Coatings PF-405

3M Thermal Bonding Film AF42

Document Library TS Data Sheet M Windo-Weld Super Fast Urethane. Data Sheet. Public

AUTO COLLISION REPAIR CERTIFICATE I COURSE DESCRIPTIONS. Total: 18 Credit Hours

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM

Moisture and Resilient Floor Covering

Additional Information. Paint Application

PRODUCT DATA SHEET DESCRIPTION:

STANDARD SPECIFICATIONS SECTION CLEANING AND LINING WATER MAINS

10P20-44 High Solids Epoxy Primer

APPENDIX C MOISTURE GUIDELINES & MOISTURE TESTING

Physically Crosslinked Foam Insulation

Transcription:

07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011

SPEC NOTE: This guide specification is intended for use when specifying the Stayflex Corrosion Control and Thermal Insulation System for projects located in the United States. SPEC NOTE: Make any required selections, such as insulation and thermal barrier coating thickness. Certain applications may warrant the use of a topcoat. Contact Preferred Solutions for more information. DISCLAIMER: The manufacturer has reviewed the product information contained in this guide specification. The information is organized and presented to assist the specification writer working on a construction project to select the appropriate products and to save time in writing the project Section. The specification writer is responsible for product selection as well as the use and application of this information and should contact the manufacturer to ensure that all options are available and that the associated specification information is valid and correct. PART 1 - GENERAL SECTION 07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 1.01 SECTION INCLUDES A. Stayflex Corrosion Control and Thermal Insulation System. 1.02 REFERENCES A. ASTM C 518-04 Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter B. ASTM C 581-03 Standard Practice for Determining Chemical Resistance of Thermosetting Resins Used in Glass-Fiber-Reinforced Structures Intended for Liquid Service C. ASTM D 696-03 Standard Test Method for Coefficient of Linear Thermal Expansion of Plastics Between -30ºC. and 30ºC. With a Vitreous Silica Dilatometer D. ASTM D 1621-04a Standard Test Method for Compressive Properties of Rigid Cellular Plastics E. ASTM D 1623-03 Standard Test Method for Tensile and Tensile Adhesion Properties of Rigid Cellular Plastics F. ASTM D 1622-03 Standard Test Method for Apparent Density of Rigid Cellular Plastics G. ASTM D 2126-04 Standard Test Method for Response of Rigid Cellular Plastics to Thermal and Humid Aging H. ASTM D 6226-05 Standard Test Method for Open Cell Content of Rigid Cellular Plastics I. ASTM E 84-08 Standard Test Method for Surface Burning Characteristics of Building Materials 07 21 19-1

J. ASTM E 96/E 96M-05 Standard Test Methods for Water Vapor Transmission of Materials K. ASTM E 2178-03 Standard Test Method for Air Permeance of Building Materials L. UL 1715 Fire Test of Interior Finish Material 1.03 SUBMITTALS A. Informational Submittals 1. Manufacturer s published data sheets showing compliance of all products with properties required by this specification. 2. Manufacturer s installation instructions. 3. Material Safety Data Sheets (MSDS). 4. Applicator certification from as required by Section 1.04 B. 5. Two samples 4 inch by 4 inch of each product. 6. Shop drawings of sheet metal, accessories, or other fabricated items, if required. 7. Field quality control procedures to be utilized by Applicator to assure proper installation of the products. B. Closeout Submittals 1. Maintenance and repair instructions. 1.04 QUALITY ASSURANCE A. Single-Source Responsibility: Provide specified products from a single manufacturer. B. Authorized Applicator of Manufacturer: Contractor shall be a designated Authorized Applicator of, Cleveland, Ohio. Such designation certified in writing by shall be submitted by the contractor. 1.05 MATERIALS DELIVERY AND STORAGE A. Materials shall be delivered in the manufacturer s original, tightly sealed containers or unopened packages, all clearly labeled with the manufacturer s name, product identification, safety information, and batch or lot numbers where appropriate. B. Containers shall be stored out of the weather, direct sun and in compliance with manufacturer s recommendations. 1.06 FIELD CONDITIONS A. Ambient Conditions 1. Do not apply the products if the ambient air or substrate is below 35ºF or when substrate has surface moisture. 07 21 19-2

PART 2 - PRODUCTS 2.01 MATERIALS A. Polyurethane foam insulation shall have the following minimum properties: 1. Insulation Value (ASTM C-518): R-6.5 per inch 2. Compressive Strength (ASTM D-1621): 35 psi 3. Density (ASTM D-1622): 2.0 pcf 4. Tensile Strength (ASTM D-1623): 55 psi 5. Percent Closed Cells (ASTM D-6226): 90% 6. Water Vapor Transmission (ASTM E-96):.97 perms @ 1.47 perms @ 2 7. Fire Ratings (ASTM E-84) a. Flame spread: 20 b. Smoke development: 450 8. Product and Manufacturer: Staycell 245-2.0 polyurethane foam insulation by B. Vinyl-ester thermal barrier coating shall have the following minimum properties: 1. Coefficient of Linear Thermal Expansion (ASTM D-696): 3.6x10-5 in/in ºC. 2. Density (ASTM D-1622): 105 pounds per cubic foot. 3. Water Vapor Permeance @.063 thickness (ASTM E-96): 0.09 grains/hour/square foot 4. Barcol Hardness (ASTM D 2583): >40 5. Fire Ratings A. ASTM E-84 1. Flame spread: 15 2. Smoke development: 250 B. UL 1715 1. The specified Stayflex System shall comply with the 2003, 2006 and 2009 editions of the International Building Code based upon compliance with the UL 1715 fire test standard. 07 21 19-3

PART 3 - EXECUTION 6. Product and Manufacturer: Stayflex 2505 thermal barrier coating by C. Curing agent for thermal barrier coating 3.01 EXAMINATION 1. Specific gravity: 1.007 2. Percent active oxygen: 9% 3. Product and Manufacturer: Hi-Point 90 MEK peroxide catalyst by A. Inspect existing conditions to ensure they are suitable for work to begin. Do not proceed until unacceptable conditions are corrected. B. Ensure items such as hangers for piping and ductwork are installed before begining work. 3.02 PREPARATION A. Loose paint and other surface materials which are easily removable shall be removed by broom brushing, vacuuming, air blowing or similar procedures. B. Primers, if necessary to achieve specified adhesion, shall be applied in accordance with manufacturer s recommendations. C. All substrates shall be free from surface moisture prior to the application of foam insulation. 3.03 APPLICATION A. Staycell 245-2.0 polyurethane foam insulation 1. The foam components (A) and (B) shall be applied in accordance with the manufacturer s instructions. 2. The foam shall be sprayed within the manufacturer s guidelines for temperature, humidity and other atmospheric conditions. 3. The foam shall be sprayed at an average minimum inch thickness. The full thickness of foam applied on any given surface shall be completed in one day. 4. Any damage or defects to the foam shall be repaired prior to applying the thermal barrier coating. B. Stayflex 2505 thermal barrier coating and curing agent 1. The thermal barrier coating and curing agent shall be applied in accordance with manufacturer s instructions. 07 21 19 4

2. Inspection: Prior to the application of the thermal barrier coating, the foam shall be inspected to insure that damages or defects of the foam have been corrected. 3. Application 3.04 QUALITY ASSURANCE A. The thermal barrier coating shall be applied at a rate to achieve an average minimum dry film thickness (DFT) of 1/16 inch (.063 ). B. The thermal barrier coating shall be inspected for defects such as thinly coated or uncured areas. Defects shall be corrected. A. Daily records: The contractor shall keep daily records as to the square feet of surface sprayed each day, quantities of all materials used and thickness and cure tests performed. At least one thickness and cure test shall be conducted on every 500 square feet of covered surface. B. Installed materials evaluation: In addition to verifying the thickness of all installed materials, such materials shall also provide the following characteristics: 1. Staycell 245-2.0 polyurethane foam insulation: A. The cellular structure shall be uniform and not be soft or spongy. B. The foam shall not have areas with hard or brittle sections or improperly proportioned materials. 2. Stayflex 2505 thermal barrier coating and curing agent: A. Proper cure of the coating shall be evaluated approximately 24 hours after spraying. Such evaluation shall be made using Barcol Hardness Tester GYZJ 935. Hardness ratings shall not be less than 40. 3.05 SAFETY REQUIREMENTS A. Contractor shall comply with all provisions of MSDS Sheets for all materials utilized on the project. B. Ventilation, if necessary, shall be provided to assure fresh air is brought into the area being sprayed. Such air shall be exhausted to the outside of the building by utilizing existing fans or by supplemental ventilation. C. Proper disposal of waste materials and containers must be done in compliance with the manufacturer s guidelines and federal, state and local regulations. 3.06 CLEAN-UP A. At the completion of the project, contractor shall clean up and remove from the site all material containers, waste materials and debris. END OF SECTION 07 21 19-5