Technical Bulletin 144. Air Volume Conversions. by:



Similar documents
Technical Bulletin 141. Installation and Maintenance Cost Evaluation. by:

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation

Example Calculations Evaluation for Fine Bubble Aeration System. Red Valve Company, Inc. 700 NORTH BELL AVENUE CARNEGIE, PA

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

Pump Formulas Imperial and SI Units

Aeration Efficiency Guide

MODELING WASTEWATER AERATION SYSTEMS TO DISCOVER ENERGY SAVINGS OPPORTUNITIES By Steven A. Bolles Process Energy Services, LLC

Meriam Instrument LFE Data Sheet

STEPS TO COMPRESSOR SELECTION & SIZING

This will also provide you with the knowledge to insure long life for your Investment

High Altitude HVAC. Silvertip Integrated Engineering Consultants

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08

COMPRESSED AIR ULTRASONIC LEAK DETECTION GUIDE

David Mezzacappa, P.E. SCS Engineers Contractor to U.S. EPA on LMOP

Preferred SI (Metric) Units

Centrifugal Fans and Pumps are sized to meet the maximum

Appendix C: Conversions and Calculations

Vogt Valves The Connection Bulletin for Forged Steel Flow Control Valves CB 15

A quick guide on how to read your utility meters. How to read your gas meter

REVIEW SHEETS INTRODUCTORY PHYSICAL SCIENCE MATH 52

Metric Prefixes Tera- T 10 2 centi- c 10 9 Giga- G 10 3 milli- m 10 6 Mega- M 10 6 micro- µ 10 3 kilo- k 10 9 nano- n

Valve Sizing. Te chnic al Bulletin. Flow Calculation Principles. Scope. Sizing Valves. Safe Product Selection.

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

Gas terminology for business. Gas Terminology. Simplifying energy management.

THE HUMIDITY/MOISTURE HANDBOOK

Vacuum. How It Relates to Refrigeration And Air Conditioning Service

Understanding Energy Bills

10/9/2012. Poultry Farm Water Supply. Alabama Burglar & Alarm System. Industry Upgrades. Drinkers Fans Water Supply

User Guide. The Business Energy Dashboard

User s Manual Laminar Flow Elements

Spreadsheet Program for EPA Method 202 Condensible Particulate Matter Emission Rate and Concentration Calculations

Gas Line Sizing. Z Maximum gas demand shall be determined by adding all of the equipment Btu ratings from appliances connected on the system.

Technical Information

HVAC Calculations and Duct Sizing

Annual & Hourly Cost Detail

Unit Conversions. Ben Logan Feb 10, 2005

User Guide. The Business Energy Dashboard

HVAC FORMULAS. TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32 F. 288,000 BTU/24 hr. 12,000 BTU/hr.

100 cm 1 m. = 614 cm m cm. 1 m 1 in. 1 m cm 1ft. 1 in = 242 in. 614 cm. 242 in 1 ft. 1 in. 100 cm = 123 m

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Practice Tests Answer Keys

Conversion Formulas and Tables

Phenom Hours/Annually

The Precharge Calculator

Understanding Your Bill

Capacity Testing of VRLA Batteries (20 to 200 Ampere-Hours Capacity)

FIRE DAMPER APPLICATION GUIDE

Conversions. 12 in. 1 ft = 1.

Packaged-Products for Parcel Delivery System Shipment 70 kg (150 lb) or Less

RTO UPGRADE PROVIDES COST SAVINGS AND PERFORMANCE IMPROVEMENTS

Energy Audits Waste Water Treatment Plants

EJECTOR AIR REMOVAL SYSTEMS ENGINEERING DATA BULLETIN # PVS ARS PAGE 1 OF 5

Dimensional Analysis

ECO-STAR II. ECO-nomical ECO-logical the ECO-STAR II. Packaged Low NOx Multi-Fuel Burner. Features. Benefits. Combustion Excellence Since 1888 ESII-1

Below are detailed instructions for using the EMS load calculator.

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

Measurement: Converting Distances

Basic Math-Measurement and Conversion Problems

INTERIM UNITS OF MEASURE As suggested by Federal Standard 376B January 27, hectare (ha) Hundred for traffic buttons.

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing

Water Monitoring System Website User Guide

High Volume PM10/TSP Calibration/Verification/Audit Guidance. Issued: 12/15/14 - FINAL

Fan Applications & System Guide

One basic concept in math is that if we multiply a number by 1, the result is equal to the original number. For example,

Turbine Flowmeters for Gas Applications

Greenhouse Cooling. Why is Cooling Needed?

NIFA REGIONAL SAFECON 2006 Manual Flight Computer Accuracy Explanations

Duct Leakage Testing. Ken Helfers, TSI Inc. 2011, TSI Incorporated

SIZING AND CAPACITIES OF GAS PIPING

Chapter 1 Lecture Notes: Science and Measurements

Technical Specification. Generating Set with Waukesha engine burning natural gas

MATHEMATICS FOR WATER OPERATORS

Case Studies: Infrared Heating in Industrial Applications

Fluid Power Formula. These Formula Cover All Fluid Power Applications In This Manual

Exercise Worksheets. Copyright Susan D. Phillips

Grain Drying & Management Bob Schultheis Natural Resource Engineering Specialist University of Missouri Extension

NetApp Data Center Design

I Gotta Know What? A Math Tutorial For Prospective CPO Students. FR = FA times FMR or FR = FA x FMR Volume (V)gallons = Volume (V)cubic feet x 7.

Spray Nozzles. Spray Control. Spray Fabrication. Spray Analysis. A Guide to Optimizing In-Tank Agitation and Mixing Using Eductors

How to Choose the Right Air Compressor

Ways We Use Integers. Negative Numbers in Bar Graphs

THE PSYCHROMETRIC CHART AND ITS USE

MEASUREMENT. Historical records indicate that the first units of length were based on people s hands, feet and arms. The measurements were:

Methods and Equipment for Calibration of Variable Area Meters (Rotameters)

Answers for the lesson Write Linear Equations in Slope-Intercept Form

Pumping Solutions for Concentrated Solar Power

AIRCRAFT PERFORMANCE Pressure Altitude And Density Altitude

For Multi-Parameter Meters see mvx

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

Calculating Total Cooling Requirements for Data Centers

DOUBLE SEAT BRONZE BODY HIGH CAPACITY

Turning HTE Agilent LC/MS Data to Knowledge in 1hr

Measurement. Customary Units of Measure

Educational Technology Advising Aid Master s and Educational Specialist Degree Program Online Educator Focus Area

Professional Thermohygrometer

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

Cloud Model Verification at the Air Force Weather Agency

NDP-50 Specifications

Transcription:

Technical Bulletin 144 Air Volume Conversions by: Environmental Dynamics International Published: 4/2007

DISCLAIMER Technical Bulletins are presented as a service by Environmental Dynamics International headquartered in Columbia, Missouri USA. For additional more information regarding this particular bulletin or your specific aeration application contact Environmental Dynamics International by calling +1.573.474.9456,.474.9456, toll free at +1.877.EDI.AIR8 (877.334-2478), or via email at techbulletins@wastewater.com. 1

TECHNICAL BULLETIN 144 AIR VOLUME CONVERSIONS All aeration calculations require the volume of air to be determined: a. To calculate number and/or size of diffusers. b. To determine number and size of air supply blowers. To simplify the data and communications air volumes have been reported with standard nomenclature and standardized units of measure. There are 2 basic standards or reporting/calculating methods which create confusion: 1. What is the standardized volume condition? 2. Metric units vs. English units. I Standardized Volumes For much of the world the standardized volume of air conditions are based on an accepted standard condition with standardized calculating procedures applied to convert plant or site conditions to standard for the industry. Two conditions are commonly employed and may be used depending upon country. Since these industry conditions are widely recognized it is an easy conversion between these reported conditions. a. Standard Conditions Typical nomenclature for USA and many other countries particularly those reporting values in English units. Standard conditions are defined as the following conditions: 1. Air is the gas. 2. Temperature as 20 C. (68 F) 3. Elevation at sea level. 4. Relative humidity at 36%. 5. Pressure absolute 1 bar (14.7 psi) b. Normal Conditions Typical nomenclature for most parts of the world using metric units of volume. Normal conditions are defined the same as standard conditions of Item a : except measured and reported at 0 C. c. A few exceptions always exist such as a few places using values at 10 C but is very limited. d. To convert between standard or normal air volumes or air volumes at any other temperature is world recognized as Air Volume@ absolute temperature #2 ( C) = Volume @ Temperature #1 ( C) (absolute temp #1) 2

Absolute temperature = 272 C + temperature C EXAMPLE: T 1 = Standard conditions at 20 C typical of USA values. T 2 = Normal conditions at 0 C typical metric value. Volume air at T 1 = V 1 Volume air at T 2 = V 2 Then V 2 air = V 1 (272 + T 2 ) (272 + T 1 ) V 2 air = V1 (272 + 0) (272 + 20) V 2 air = V1 (0.9315) as volume of air at 0 C less than air volume at 20 C. To convert standard conditions volume at 20 C to Normal condition volume. Normal volume = standard volume (0.9315). II Units of Air Volume for Aeration Typically aeration volume of air is expressed per unit of time. The 2 most common units of volume are: a. Standard cubic feet of air/minute abbreviated as scfm, b. Normal cubic meters of air per unit time typically abbreviated as 1. Nm 3 /hr. 2. Nm 3 /min. III Conversion between scfm and m 3 metric values: 1m 3 = 35.31 ft 3 1 hr = 60 minutes Example #1 If at same temperature of 20 C 1 standard m 3 /min = 35.31 standard ft 3 /min 1 standard m 3 /hr = 35.31 cfm = 0.5885 scfm 60 This is typically reported as 1 scfm = 1.7 standard m 3 /hr. 3

Example #2 To convert from scfm to Normal m 3 /hr must address temperature change as shown in I D above. Then 1 standard cfm at 20 C = less Nm 3 at 0 C because of the change in temperature. 1 scfm = 1.7S m 3 /hr (272) Nm 3 (292) Sm 3 1 scfm = 1.584 Normal m 3 /hr 1 Nm 3 /hr = 0.6315 scfm 4