Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power



Similar documents
Power surges can also be generated by equipment in your facility such as:

SANS : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Unified requirements for systems with voltages above 1 kv up to 15 kv

CPS Y S K CPS Y S C

SURGE PROTECTIVE DEVICES

Fundamentals of Power

Power supplies. EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E

How To Understand The Electrical Power Supply Of A Power Supply System

White Paper: Electrical Ground Rules

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Bourns Resistive Products

A series of technology briefs spanning Tyco Electronics product portfolio

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

AN Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC x

Applications. Remote Display Mounting Kits

Product Overview 2Pro AC Devices Provide Overcurrent/ Overvoltage/Overtemperature Protection for AC Industrial and Appliance Applications

SD Series. SD Series Rectifiers. EPC Energy & Power Conversion

Power transformers. Special transformers Railway

APPLICATION NOTE. Prepared by Steve Cherniak Applications Engineering. dt in an inductor (L) will generate

The power of nature, the control of technology From ABB's experience, OVR PV: surge protection in photovoltaic plants

FACTS. Solutions to optimise network performance GRID

RC NETWORKS SALES GUIDE

Transient and Lightning Protection for the Water Industries

Common Power Problems & Power Protection Solutions

Power Quality for Information Technology System

Charged cable event. 1 Goal of the ongoing investigation. 2 Energy sources for the CDE. Content

FILM CAPACITORS FOR ELECTRONIC LIGHTING

AND8229/D. An Introduction to Transient Voltage Suppression Devices APPLICATION NOTE

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Solar Inverters. Ferrites in Renewable Energies: Solar Inverters. customer requirements. Support and flexibility to design custom product to fulfill

Power Quality. Uninterruptible Power Supply

This is a preview - click here to buy the full publication TECHNICAL REPORT

Technical Article MS-2443

Supply Standards: Electricity Supply Standard July JULY 2011 ISSUE 6 UNCLASSIFIED UNCONTROLLED COPY IF PRINTED

Lightning current simulation in the laboratory - parameters, procedures and test equipment -

CATALOGUE SURGE PROTECTION LOW VOLTAGE

Three-phase monitoring relay CM-PFE

Product Data Bulletin

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

How To Choose A Transformer

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Grounding Demystified

Understanding SMD Power Inductors. Application Note. July 2011

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Technical Comparison of On-line vs. Line-interactive UPS designs

Nuclear Power Plant Electrical Power Supply System Requirements

Common Mode Choke Filtering Improves CMRR in Ethernet Transformer Applications. Application Note. June 2011

Design of Bidirectional Coupling Circuit for Broadband Power-Line Communications

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

SURGELOGIC TVSS Surge Protective Devices Enhance System Protection and Reduce Equipment Damage

The reliability of the grid

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Introduction. Harmonics and IEEE 519 Page 1 of 19

Relationship between large subject matter areas

IEEE802.3poep Study Group Revision of isolation requirements in IEEE802.3 clause 33.

AN-6 COMMON MISTAKES IN LIGHTNING PROTECTION OF PHONE LINE INTERFACE CIRCUITS

White paper. ABB solutions for switching and protection of low speed wind turbines

Qualitative Analysis of Power Distribution Configurations for Data Centers

Application Note AN:005. FPA Printed Circuit Board Layout Guidelines. Introduction Contents. The Importance of Board Layout

THE LIGHTNING PROTECTION INTERNATIONAL STANDARD

Power Quality Standards for Electric Service

Electromagnetic Compatibility Considerations for Switching Power Supplies

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

POWER QUALITY IN YOUR HOME

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

Lightning Arresters P KVA P KVA. Description & Installation

DC-DC Converter Basics

DIRECT STRIKE PROTECTION. CAT Terminal, Gold, Model III

Application Note, Rev.1.0, September 2008 TLE8366. Application Information. Automotive Power

APPLICATION NOTE How to Deal with Electrical Noise and Interference in the Measuring Chain using a NEXUS

Inverter / Charger Installation General Operations and AC and DC Connections

Main catalog. System pro M compact Surge and lightning protection solutions with QuickSafe technology

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Line Reactors and AC Drives

Theoretical review. Contents

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

RVH/BCH Data Centres Proposals for Surge Protection and Ventilation

A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS

EMI and t Layout Fundamentals for Switched-Mode Circuits

DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D

Protect your home and family with Advanced Technology from Cutler-Hammer

Application Note AN- 1095

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Cable Discharge Event

Current and voltage measuring relays

Technical reference Key points

The Different Types of UPS Systems

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

Data Assessment for Electrical Surge Protection Devices

Considering the effects of UPS operation with leading power factor loads

Solid-State Relays (SSRs) vs Electromechanical Relays (EMRs)

Which UPS is right for the job?

SurgeShield. Section A: What is SurgeShield?

7-41 POWER FACTOR CORRECTION

surge protection solutions

AN ISOLATED GATE DRIVE FOR POWER MOSFETs AND IGBTs

Transcription:

App Notes ~ Outdoor Power System Design and Cost Considerations 1 Authors Peter Nystrom President TSi Power Corp. Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power Zoned protection strategy Abstract The rapid growth of the world market for telecommunications equipment shows no sign of stopping. Many manufacturers of radio infrastructure and switching equipment are based in the USA, Europe and Japan. Yet, these manufacturers are often not familiar with power quality in places far away from their home countries. The needs for surge protective devices vary from market to market and are especially challenging in the emerging countries. Why? Surge protection in the USA and Europe is based on the assumption that the AC power-line voltage is relatively stable. Developing countries, however, often have inadequate infrastructures for the generation and distribution of electric power. The lack of stable AC power complicates the selection and coordination of surge protective devices considerably. This paper reviews the new IEC surge protection standards and discuss how to achieve coordination of surge protective devices in accordance with IEC 61312 principles.

2 White Papers Introduction IEC standards are used throughout Europe and in many other parts of the world. CE marking is based on such IEC standards and involves both equipment safety and electromagnetic compatibility. Therefore, all electronic equipment carrying the CE label should have been tested to withstand static electricity, electric fast transients and surge voltages. This paper will focus on the surge-voltage aspects of equipment. IEC 61000-4-5 is a Combination Wave consisting of a voltage waveform of 1.2/50 μs with an amplitude of 2000 V in normal mode and 4000 V in common mode and a current wave form of 8/20 μs at 2000 A. The Combination Wave is identical to the U.S. ANSI/IEEE C62.41-1991 Combination Wave with the following exceptions: the ANSI/IEEE voltage is 6000 V and the current is 3000 A. In the IEC standard, the equipment that is tested for surge immunity is referred to as the "vulnerable equipment." All vulnerable equipment must be able to withstand IEC 61000-4-5 without upset, guaranteeing a certain level of surge immunity sufficient for most office environments. The IEC developed a series of standards that apply to enhanced surge protection of equipment and structures in cases, where built-in equipment surge immunity is not sufficient. Telecom installations in outdoor shelters and enclosures are good examples of when enhanced surge immunity is required. This paper will review key aspects of the following IEC standards: IEC 61024-1: 1990 Protection of Structures Against Lightning - Part 1: General Principles IEC 61312-3: Protection Against Electromagnetic Impulse - Part 3: Requirements of Surge Protective Devices. Special problems in developing countries Fluctuating power line voltage Causes Overloaded, inadequate power generation and distribution systems, particularly when large step load changes are present, result in large voltage sags and surges. Voltage fluctuations between 155 V to more than 310 V have been observed in the field. Differences between day- and nighttime voltage of 40 V have also been observed. Such conditions are common in Africa, India, Pakistan and China, as well as in many other areas. Many developing countries need additional power plants and distribution infrastructure. However, political and economic issues are preventing timely power plant expansion, which means the problem is here to stay for the foreseeable future. Effects Sags and undervoltages can cause component overheating or destruction, reducing the life and deteriorates the real reliability as opposed to the estimated reliability, which is based on steady-state conditions of the power supply. Swells and overvoltages can cause component overheating and destruction of metallic oxide varistors (MOVs), silicon-controlled rectifiers (SCRs) and input

White Papers 3 capacitors that are rated too close to the line voltage. Power supply and telecom rectifier manufacturers frequently rate input MOVs at 275 V with the apparent objective of reducing the surge remnant voltage, providing better surge immunity of the power supply. However, TSi Power has observed still-functioning telecom rectifiers where the input MOVs had been completely destroyed by high line voltage. Boost converters can be destroyed by voltage swells that cause increased energy storage in the input filter, which charges the output capacitor to an unsafe level. The charge level is dependent on the value of the output capacitor and the load levels for the DC DC converter connected to the output of the boost converter. Poorly damped EMI filters can dramatically magnify the effects of voltage disturbances. This can result in oscillations inside the EMI filter during transitional conditions. Severe voltage surges may result from energy released when saturated inductors are looking for a path to release energy. Frequent lightning conditions Review of IEC 61024-1 This standard relates to the protection of structures against lightning. A structure can be anything from a high rise building to an outdoor shelter containing telecommunications equipment. IEC 61024 introduces the concept of lightning protection zones (LPZ). Figure 1 below illustrates the basic zone concept. Figure 1 The purpose of LPZs is to divert the surge energy from lightning and other disturbances away from the vulnerable equipment. The majority of the energy should be diverted at the lowest zone boundaries. The number of required zones is determined by the physical properties of the structure and the sensitivity of the vulnerable equipment.

4 White Papers Sensitive equipment that is installed in outdoor shelters, particularly when a poor physical ground is present, requires a higher number of zones. An explanation of basic lightning protection zones follows: LPZ 0A This zone is subject to direct lightning strokes and may have to carry the full lightning current. The unattenuated electromagnetic field occurs here. 100 ka, 10/350 µs 200 A, 0.5 s 25 ka, 0.25/100 µs Figure 2 Figure 2 shows a comparison between the 10 x 350 μs test waveform and lower-energy Combination Wave. LPZ 0B This zone is not subject to direct lightning strokes. The unattenuated electromagnetic field occurs here. LPZ 1 10 kv, 1.2/50 µs 5 ka, 8/20 µs This zone is not subject to direct lightning strokes and currents on all conductive parts within this zone are further reduced from previous zones. The electromagnetic field may also be attenuated depending on the screening measures. LPZ 2 When a further reduction of conducted currents and/or magnetic field is required, subsequent zones can be introduced. In general, the higher the number of zones, the lower the electromagnetic environment parameters.

White Papers 5 LPZ 3 According to TSi Power's interpretation of IEC standards, this zone should contain the protected equipment. The requirement for zone 3 is that the remnant surge voltage does not exceed the test levels specified in IEC 61000-4-5: Combination Wave, 1.2/50 μs, 8/20 μs 2000 A Normal-Mode Voltage: 2000 V Common-Mode Voltage: 4000 V Review of IEC 61312-3 Lightning surges contain significant amounts of energy which needs to be diverted away from the vulnerable equipment. CE-marked electronic equipment is designed with a certain amount of built-in surge voltage immunity in accordance with IEC 61000-4-5. This level of immunity will be sufficient for the majority of office buildings when the vulnerable equipment is located far away from the electric service entrance. As such, equipment that carries the CE mark will work well without surge protection in many environments. However, when the vulnerable equipment is installed close to the electric service entrance or in an outdoor enclosure, particularly in areas with a poor physical ground (such as dry sand or rock), it is often necessary to add external surge protective devices (SPDs). IEC recommends (IEC 61024) that lightning protection zones should be established to successively reduce lightning currents, in stages, down to the built-in immunity of the vulnerable equipment. The number of zones required depends on the structure containing the installation and the vulnerable equipment. IEC 61024 requires that an SPD be installed at each zone boundary. It is important not to exceed the surge current and voltage ratings of individual SPDs. Purpose of coordination The goal of coordination is to progressively reduce the lightning threat in stages (SPD 1, 2 and 3) down to the surge-withstand capability of the vulnerable equipment, without exceeding surge current and voltage ratings of individual SPDs. Coordination concepts IEC 61312 defines four coordination variants. The first three utilize individual single-port SPDs, while the fourth variant is a two-port hybrid design. Variant I Shown in Figure 3 (on next page), the rated voltage of SPDs is identical and coordination is achieved by separating each SPD by means of series impedance.

6 White Papers Figure 3 Variant I is not recommended by the IEC, because it would require approximately 30' (10 m) of wire or separate inductors between each SPD, which is not practical when installing equipment close to the electric service entrance or in outdoor enclosures. Variant II Shown in Figure 4, the rated voltages of SPDs are stepped so that the SPD in the vulnerable equipment has the highest rated voltage and SPDs 3, 2 and 1 have progressively lower rated voltages, assuring that each upstream SPD would divert progressively higher currents. Figure 4 Variant II is difficult to implement since most power supplies, uninterruptible power systems and telecom rectifiers that are rated for 230 V use input SPDs with a 275 V rating. Therefore, stepping down rated voltage would cause SPD 1 and 2 to be destroyed by normal line voltage fluctuations. In fact, fluctuations of plus 10% resulting in 250 V is not unusual.

White Papers 7 Variant III Shown in Figure 5, Variant III includes a component with a non-linear current/voltage characteristic such as a spark gap. The SPD 1 spark gap would divert the majority of the surge current and output a Combined Wave (similar to ANSI/IEEE C62.41-1991, Category B3, Combination Wave, 3000 A, 6000 V) to downstream SPDs 2 and 3. The voltage ratings of SPD 2 and 3 are identical, but each device will handle considerably less current due to the much higher energy handling capability of spark gap SPD 1. Figure 5 Variant III is a better choice than I or II, because the spark gap is insensitive to fluctuations in line voltage. However, spark gap follow-on, short-circuit current may be an issue and MOVs will still be sensitive to line voltage fluctuations. Variant IV Figure 6 Figure 6 shows a two-port hybrid device that incorporates cascaded stages of SPDs internally coordinated with series impedance.

8 White Papers A hybrid device can be designed to maximize performance while reducing the undesirable characteristics of spark gaps and SPDs based on varistor or siliconavalanche-diode technology. The use of a hybrid device eliminates the need to coordinate surge protective devices, but does not eliminate sensitivity to prolonged AC overvoltage. Proposed hybrid device in accordance with Variant IV The purpose of the circuit shown in Figure 7 is to provide the critical functions required for a universal AC power interface in a condensed space for outdoor shelters for cellular, fixed wireless and other telecom equipment. The circuit's major required functions include: Surge protective device coordination for successive reduction of surge currents High energy handling capability Tolerance against high line voltage Adjustment for local nominal voltage variation Low dv/dt rise time Function not dependent on performance of internal protection of vulnerable equipment Figure 7 Discussion of circuit features shown in Figure 7 The protection scheme is designed to work with an outdoor equipment shelter even when vulnerable equipment uses 275 V MOVs as internal protection. In this case, it is impossible to provide coordination in accordance with Variant II. In addition, Variant I is not practical, because the required wiring distances of 30' between SPDs are too short in an outdoor equipment shelter. The spark gap provides primary protection within LPZ 0 and ignites when the surge voltage reaches approximately 2000 V. The series inductance introduces the necessary coordination and provides reliable ignition of the spark gap. The output of the spark gap is a Combination Wave and is easily handled by the circuits in LPZ 1 and 2. Spark gaps can handle considerably more energy than MOV or SAD arrays and are not sensitive to line voltage fluctuations; they are also more cost effective. The major disadvantage of a spark gap is that the follow-on current can cause tripping of upstream circuit protection

White Papers 9 devices. However, new-technology spark gaps based on the arc-chopping principle provide significant performance improvements. The new spark gap technology shown in Figure 8 consists of two electrodes positioned opposite each other, held in place by a barrier and separated by a baffle. This arrangement and pacing of electrodes is called "arc chopping" and provides reliable ignition of the arc, which is then chopped by the baffle into several smaller arcs. Special versions with reduced follow-on current are available for branch circuits and services up to 75 kva. The neutral-to-ground bond provided at the service entrance or by a separate isolation transformer eliminates all surge voltages between neutral and ground, along with the requirement for SPDs between power carrying conductors and ground. The series inductor with primary buck-boost windings provides static adjustment for different nominal voltages that can range from 200 to 250 V. The buck-boost windings can also be controlled automatically if the line voltage is chronically unstable. The series inductor also forms a two-pole filter together with the shunt capacitor. The filter reduces the surge voltage rise time (dv/dt) from 6 kv/μs to 10 V/μs, which provides considerable relief for the vulnerable equipment. The filter which starts conduction well before MOV 1 provides protection against electric fast transients and other line noise. MOV 1, located within LPZ 2, is a 40 mm device rated for 275 V, which is made possible due to the voltage adjustment provided by the buckboost windings on the primary of the series inductor. In other words, MOV 1 is wellprotected against premature failure caused by high nominal voltages. Now available in attractive packaging, these easy-to-replace MOVs provide thermal disconnect and alarms in case of failure. Figure 8

10 White Papers Summary This paper reviews IEC 61024 and 61312 standards for protection of structures against lightning and for coordination of surge protective devices. Line voltage fluctuations that is outside of the typical regulation window of most power supplies occurs in many developing countries. This paper discusses methods for designing an economical power interface that provides hybrid surge protection for demanding international applications. The hybrid circuit provides full coordination of SPDs while being tolerant to line voltage fluctuations. About the Author Peter Nystrom is the president of TSi Power Corporation and has been in the power protection industry for over 30 years. He can be reached at: peter@tsipower.com. TSi Power specializes in manufacturing indoor and outdoor UPS, line conditioners, precision automatic voltage regulators, automatic transfer switches and DC AC inverter systems designed to meet the challenging international power conditions. Copyright held by Intertec International, Inc. Originally published in the Power Quality 97/Power Value 97 Proceeding for the POWER SYSTEMS WORLD 97 Conference held in Baltimore, MD September 1997. TSi Power Corporation 1103 W Pierce Avenue Antigo, WI 54409 USA Tel: +1-715-623-0636 Fax: +1-715-623-2426 Email: sales@tsipower.com Toll free: 1-800-874-3160 Web: www.tsipower.com Copyright 2012 TSi Power Corp. WP-Coordination-of-Telecommunications-SPDs-in-Countries-with-Unstable-AC-Power-2012-06-14.pdf