Ammonia Detection System Codes and Design Specifications. Brian EuDaly, P.E. Calibration Technologies, Inc.



Similar documents
Ammonia Detection System Codes and Design Specifications

TABLE OF CONTENT

Chlorine Gas Detection System Operation & Maintenance


Module 5. Fire and Emergency Alarm System Part I- Basics

Application Requirement

Fire & Security DETECTORS

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

SECTION A... 3 SECTION B... 7

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen

Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure

EXHIBIT A SCOPE OF WORK

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND DETECTION SYSTEM

Element D Services Plumbing

SECTION NOx, CO AND NATURAL GAS DETECTION, MONITORING AND ALARM CONTROL SYSTEMS

NFPA Edition Fire dampers shall be permitted to be installed in exhaust systems in the following situations:

Fire Alarm System Plans Review Checklist Property location Date of Review

SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P

HVAC Processes. Lecture 7

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

THE DETECTION OF GREENHOUSE GASES

WHITE PAPERS. Process Safety Management

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Regulations and Recommended Practices. Introduction. American Petroleum Institute Recommended Practices 2350

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

Ultrasonic Gas Leak Detection

Contents. Introduction

Understanding Alarm Systems

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Data Center Presentation

FIRE ALARM SYSTEM RECORD OF COMPLETION

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

FIRE ALARM SYSTEM RECORD OF COMPLETION

SECTION MECHANICAL: ELECTRICAL: PLUMBING

EXPLORER 4 MULTIPOINT

city of edmonds development information

Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants

Alarm and Detection/Suppression

Interfacing Elevators with Fire Alarm and Sprinklers

Medical Air Systems: Scroll

Commissioning - Construction Documents (Page 1 of 6)

ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW OVERVIEW OF CODE REQUIREMENTS

Carbon Monoxide Detection in Commercial Buildings (

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) Fire Alarm Permit Application

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

Fire Standards & Regulations Are you confused?

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

City of Bettendorf Fire Alarm System Requirements

Refrigeration & HVAC

Fire Pump Plan Review March 2010

Residential & Commercial Alarm Systems by Gross Security, LLC

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Protection Systems. A UTC Fire & Security Company F Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

SECTION FIRE ALARM AND DETECTION SYSTEM

Requirements for Hydrogen Storage and Use

Bold items are particular to the City of Euless

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Laser Diode Gas Sensors

Original Document 10/16/07 Revised 01/30/09 2 nd Revision rd Revision- 12/18/14

UFGS (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

Contact ID as of 2/2/2015

Safety Requirements Specification Guideline

Y7230A CO 2 Alarm System

City of Columbus Department of Building and Zoning Services

PLAN REVIEW GUIDE FOR FIRE ALARM

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system

Statement of Work. 3.0 Details of Service Pre Start-up Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

BERMAD Fire Protection

General Fire Code Requirements Within Commercial Tenant Spaces

NFPA FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Fire Pump Controllers Remote Alarm Panels

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Sustainable Strategies for Rehabilitation Projects: 9th Street Office Building Adaptive Reuse Case Study

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME

Restaurant & café guide

TMO2D with Fault Alarm and Event Log. Software Version 4B (or Earlier) Using the Fault Alarm

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Transcription:

Ammonia Detection System Codes and Design Specifications Brian EuDaly, P.E. Calibration Technologies, Inc.

Ammonia Detection Code Requirements IIAR-2A-2008 ASHRAE 15-2010 NFPA 1 2012 UMC 2012 Preprint IFC - 2012 IMC - 2012 NFPA 72-2010 General Comply with IIAR2, ASHRAE 15 Comply with IMC - 2012 Comply with IIAR2, ASHRAE 15, IFC-2012 Any gas detection systems installed on a fire alarm system shall comply with (same requirements as fire alarm) Machine Room De-energize compressors, pumps, NC valves 40,000 PPM 40,000 PPM or upper limit of detector 40,000 PPM or upper limit of detector 40,000 PPM or upper limit of detector Machine Room De-energize all electrical 40,000 PPM Machine Room Audio Visual Alarms inside room and outside each entrance 25 PPM 1,000 PPM Manual reset inside machine room 1,000 PPM 25 PPM Manual reset inside machine room 25 PPM* Approved locations Machine Room Activate normal ventilation Machine Room Activate emergency ventilation 25 PPM 1000 PPM 25 PPM 1,000 PPM 1,000 PPM 1,000 PPM Manual reset only 1,000 PPM Power and Supervision Per NFPA 72 Per NFPA 72 Dedicated branch circuit, 24 hour UPS or backup generator, trouble signal indicating fault in system. Alarm signal to monitored location Machine Room Concentration Display Refrigerated Areas Audio Visual Yes Yes Yes per NFPA 1 Suggested 1,000 PPM 50 PPM approved location

Ammonia Detection System Layout

Compressor Room (0-250ppm sensors) Room Sensor Action Compressor Room (minimum 2) GG-NH3-250 Compressor Room is the highest risk location in most plants. Using a minimum of two 0-250 ppm sensors for redundancy is necessary. Locate sensors in breathing zone (5 feet off the floor). 25ppm- Alarm to monitored location 25ppm- Horn Strobe outside each entrance and inside room 25ppm- Normal Ventilation 150ppm- Emergency Ventilation

Sensor Technologies Solid-state Electrochemical Infrared Catalytic bead Photoionization Pro s Ammonia specific no false alarms Durable and medium life avg 3 yrs plus Reliable trip levels down to 10 ppm Con s Loses sensitivity over time Hot or wet applications shorten cell life

Compressor Room Shutdown (0-2% sensor) Room Sensor Action Compressor Room Shutdown (minimum 1) GG-NH3-2% (2%=20,000ppm) Designed for electrical shunt trips. Does not replace a lower level sensor (not made for alarming at low levels). 10,000ppm- Redundant Emergency Ventilation. 20,000ppm- Electrical Shunt trip or Deenergize pumps, compressors, and normally closed valves.

Sensor Technologies Solid-state Electrochemical Infrared Catalytic bead Photoionization Pro s Relatively inexpensive Long life 5+ yrs Failsafe Con s Will respond to high levels of other combustible gases Use for high level concentrations only

Sensor Technologies Solid-state Electrochemical Infrared Catalytic bead Photoionization Pro s Specific to target gas no false alarms Durable and long-life Average life 5-10 yrs Con s Expensive No replacement sensor must buy new Can t detect low concentrations-use for high concentration only.

Vent Line (0-1%) Room Sensor Action Vent Line GG-VL-NH3 (1%=10,000ppm) 10,000ppm (1%)- Alarm to monitored location. Alarms below 10,000 ppm (1%) are not advised. Follow mounting instructions. - Locate outdoors. - About 3ft off roof. - Tee-test port facing down.

Sensor Technologies Solid-state Electrochemical Infrared Catalytic bead Photoionization Pro s Durable and long life 5 yrs plus Good for vent line sensors Inexpensive sensor replacement Con s Lowest reliable trip levels: 150 ppm Broad spectrum not specific to NH3 Non-linear

Refrigerated Rooms Room Sensor Action Freezers, Coolers, Docks, Process Areas, Production GG-NH3-100 0-100ppm range gives the most accuracy for the low end alarm set-points. Sensors should be located within 30ft of each potential leak source. Mount in breathing zone (5 feet off floor). 25ppm- Alarm to monitored location. 25ppm- Horn Strobe. 35ppm- Close liquid solenoid valves.

Sensor Technologies Solid-state Electrochemical Infrared Catalytic bead Photoionization Pro s Fast response/recovery times Good for low ppm (0-1,000 ppm) detection Con s Only good for portables Not specific to target gas Broad spectrum smells all VOC s

Calibration Calibration is required every 6 months for OSHA PSM compliance. Detailed documentation or it didn t happen.

Questions? Please.. Ask me some questions!