Profibus DP Network with DeltaV/EMERSON Digital Automation System and Ponto Series Remote I/O



Similar documents
Redundant PROFIBUS DP network with S7-400H System and Ponto PO5063V5 Remote

Ponto Series. A new concept for automation

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

I.S. 1 remote I/O system Redundant coupling via PROFIBUS DP

GW-7552 PRIFIBUS/MODBUS GATEWAY

Fieldbus slave modules with I/Os, DIO

How to make a diagnostic on TeSysT to start the network?

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

Omron I/O Driver (Series 2) Programmable Serial Interface Card

Intelligent RS-485 I/O expansion unit: RU-87Pn Series

SIMATIC S It s the Interplay that makes the difference. Siemens AG All Rights Reserved.

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

Commissioning IDENTControl Compact IC-KP2-2HB17-2V1D Profinet Protocol with a Siemens S7 PLC

DeviceNet Bus Software Help for Programming an Allen Bradley Control System

ZC-24DO CANopen I/O Module: 24 Digital Outputs

L5354 ControlNet Communications Interface

Bristol ControlWave Redundant Control

PNSPO! Modbus Solution CP1H / CP1L / CJ1 / CJ2 / CS1. Version /18/2009

Optimize your simple machines... Modicon M218 Selection Guide

S-series DeviceNet Interface Card

Technical Training Module ( 30 Days)

SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP

Modular I/O system Rugged Modular I/O System Solutions EN certified for railway applications

SCADA and Monitoring for Solar Energy Plant

SIMATIC. ET 200S distributed I/O IM151-1 STANDARD interface module (6ES7151-1AA05-0AB0) Preface. Properties 1. Parameters 2.

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

NXL Series Inverters. HVAC Inverters made simple

ROC800-Series Advanced Pulse Module

How-To-Do. EtherCAT Communication with CPU 300S

CMC-PD01 PROFIBUS DP Slave Communication Card Operation Manual

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit , March 2012

Measuring Temperature withthermistors a Tutorial David Potter

Bioreactor Process Plant Powered by NI LabVIEW and NI CompactRIO

applicomio Profibus-DP

PRODUCT MANUAL LUMENTO X4 LED. LED Controller ZN1DI-RGBX4. Program version: 1.0 Manual edition: a

Alcalde # 1822 Col. Miraflores C.P Guadalajara, Jal. Mexico MX 01 (33) y USA 001 (619) (San Diego, CA.

T-BOXN12R. First steps with T-BOXN12R. You can make it wireless. Date: Version 1.0

6ES7313-5BF03-0AB0. Supply voltages Rated value 24 V DC Yes permissible range, upper limit (DC) circuit breaker type B, min. 4 A

DeviceNet Communication Manual

GE Power Controls FIELDBUS APPENDIX PROFIBUS DP. Doc. No.: ASTAT Plus PB_Appendix-v0

Develop a Dallas 1-Wire Master Using the Z8F1680 Series of MCUs

SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.

How can I. implement a high-availability system? Develop your project. System Technical Guide High Availability solutions

Simplify Data Acquisition with a Built-in LXI Web Server

WinCON8000-R2/R8. Hardware User s Manual

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Application/Connection Examples

PROFIBUS diagnostics and network monitoring

Beckhoff TwinCAT. Configuring the TwinCAT I/O System

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TO-PASS. TO-PASS -FAQ- Remote Monitoring. What is TO-PASS used for? What are the special functions of TO-PASS?

USER MANUAL V5.0 ST100

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no

PROFINET IO Diagnostics 1

UniOP epad33 and epad33t

Compact multiprotocol I/O module for Ethernet 8 digital PNP inputs and 8 digital PNP outputs 2 A TBEN-L1-8DIP-8DOP

DAM Series DAM124 4DIN+8AI+4DO Module Model No.:DAM124 WebSite:

1 Serial RS232 to Ethernet Adapter Installation Guide

CANtrol EC Modular Control System Powerful and versatile

Modular I/O System Analog and Digital Interface Modules

Termination Resistors:

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

PROFINET the Industrial Ethernet standard. Siemens AG Alle Rechte vorbehalten.

GE Intelligent Platforms. PACSystems High Availability Solutions

IntesisBox Modbus Server SAMSUNG Air Conditioners

Versions. Q.station Q.station T. Q.station D. Q.station DT x x

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision [Version 2.2]

SIMATIC S7-300, CPU 315-2DP CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 128 KBYTE WORKING MEMORY 2

SIMATIC. SM 335 High-Speed Analog Input/Output Module for the SIMATIC S7-300

6ES BE01-0AB0 6ES BE01-0AB0

How to use KEPServerEX OPC Server (Kepware) with iologik 4000 (Modbus TCP/IP NA-4010 and Modbus Serial NA-4020/NA-4021)

JUMPFLEX 857 Series ma V ma. Transducers / Relay and Optocoupler Modules

Unidirectional Transmitter/ Receiver Units Introduction

Vibration analysis and monitoring Compact. Powerful. Modern technology.

TAC I/NETTM MR-AHU-HP. Application Specific Controller

Soft-Starter SSW-06 V1.6X - Profibus DP, DeviceNet and EtherNet/IP

USB-500 Series Stand-Alone, Low-Cost Data Loggers

S-series Mass Connection Solutions

Modbus Server SAMSUNG Air Conditioners

Ovation Operator Workstation for Microsoft Windows Operating System Data Sheet

NEW. EVEN MORE data acquisition and test stand automation

High Availability and Safety solutions for Critical Processes

Electronic Control Devices The European Product Catalogue 2007

WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide

Modbus Communications for PanelView Terminals

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings

The GV-I/O Box 8 Ports provides 8 inputs and 8 relay outputs, and supports both DC and AC output voltages.

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

All Analog Outputs, voltage/current 20mA 35mA 5mA 48mA/30mA* *If the analog outputs are not configured, then subtract the higher value.

Cover. SEB SIMOTION Easy Basics. Collection of standardized SIMOTION basic functions. FAQ April Service & Support. Answers for industry.

Manual. MOVIDRIVE MDX61B MOVI-PLC DHP11B Control Card. Edition 09/2005 FA / EN

Module 1 Overview ControlLogix5000

SNAP-SCM-PROFI Communication Module

1 light dimming module

Model: DC-A2IO Advanced HVAC Controller

Evolution in Automation

Computer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

Transcription:

Application Note NAP101 Profibus DP Network with DeltaV/EMERSON Digital Automation System and Ponto Series Remote I/O Summary Description...1 1. Introduction...2 2. Installation...3 3. Configuration...3 3.1 PROFIBUS DP Network Project...3 3.2 PROFIBUS DP Setting...9 4. Maintenance...10 4.1 Diagnostic LEDs...10 4.2 Diagnostic Messages...11 Revisions...11 Description This document describes the installation, configuration and maintenance of a PROFIBUS DP network with distributed I/º The system is assembled with Altus/Ponto Series equipment and DeltaV/EMERSON Automation System. Chapter 1, Introduction, describes the main characteristics of Ponto Series and the devices of a distributed PROFIBUS DP network. Chapter 2, Installation, presents the list of the devices used to system assembling, which is based on Altus and EMERSON equipment. Altus Sistemas de Informática S.A. Página: 1

Chapter 3, Configuration, presents all the steps to create a new project of distributed I/O. The software used to configure and set the network and equipment is the software Exploring DeltaV from EMERSON. Chapter 4, Maintenance, shows the system functionality and the treatment of the diagnostic messages. 1. Introduction The Ponto Series is a distributed control system with remote I/O. It has a flexible architecture that allows the access to remote modules via different fieldbuses. The I/O modules and fieldbuses head can communicate with Altus equipment and CPUs from another manufacturers. Therefore Altus PROFIBUS DP Head PO5063 module can be connected to DeltaV/ EMERSON according following picture. The PROFIBUS DP remote maintenance is simplify by an extensive diagnostic information and hot swap capability in all I/O modules. These characteristics are included in Ponto Series modules. Altus Sistemas de Informática S.A. Página: 2

The picture shows a typical system for distributed controlling. It is based on remote I/O modules and PROFIBUS DP Fieldbus. 1 PROFIBUS DP Slave: PO5063 module PROFIBUS DP Head Altus 2 32 Digital input 24Vdc module 3 16 Digital output relay module 4 Expansion module 5 16 Digital output relay module with fuse 6 Bus terminator 7 Expansion cable 8 PROFIBUS DP Fieldbus 9 PROFIBUS DP Master: DeltaV/EMERSON Controller 2. Installation The PROFIBUS DP network installation includes basic equipment from Ponto Series / Altus and DeltaV / EMERSON manufacturer, according the following table. Equipment Manufacturer Description Controller EMERSON DeltaV Controller Profibus Interface EMERSON Interface Module DeltaV PROFIBUS PO5063 Altus PROFIBUS DP Head PO1010 Altus 32 DI 24VDC Opto Module PO2022 Altus 16 Isolated DO Relay NO Dry Contact Module PO1112 Altus 8 Isolated Universal AI Module AL-2303 Altus PROFIBUS Net Type A Cable DeltaV EMERSON Software Exploring DeltaV The assembling and installation must follow the instruction of each manufacturer, according manuals and installation guides. 3. Configuration 3.1 PROFIBUS DP Network Project The software Exploring DeltaV is used to create and configure the project of a distributed PROFIBUS DP remote I/O network. The DeltaV Controller will be the master of the net. It will not be described the process of DeltaV software installation and license. It is considerate that the software is installed and working properly. The Software DeltaV used for development is the V7.1. version. Altus Sistemas de Informática S.A. Página: 3

(1) Start the software DeltaV (interface Exploring DeltaV). (2) Configure the Controller : PlantWeb Systen Configuration.. CTRL-1(Master). (3) Select the module PROFIBUS DP: CTRL-1 I/O CXX ( posicion). This example will use the position (C07) for the module PROFIBUS DP. (4) Configure Port P01: C07 P01 ( right button / mouse ) Properties. (5) Enable Port P01, set the baud rate and address, which will be the Master PROFIBUS DP address. Altus Sistemas de Informática S.A. Página: 4

(6) Verify if the Slave PROFIBUS DP shows in the hardware catalog (in our case the PO5063 head), otherwise it is necessary to install the GSD file following the next steps. (7) Add the equipment GSD file: Library Profibus DP Devices. (8) Use the right button on Profibus DP Devices and choose Add Device Definition to add the PROFIBUS DP Head PO5063 as Slave PROFIBUS DP module. Altus Sistemas de Informática S.A. Página: 5

(9) In the previously window select the GSD file (from PO5063 module). Each kind of equipment has his own configuration parameter that is define by the manufacturer. The parameters are listed in the GSD file. (10) Now the PO5063 can be added as slave Profibus Device: I/O P01 New Profibus Device. (11) Select PO5063 using the DeltaV Browser. Altus Sistemas de Informática S.A. Página: 6

(12) The PO5063 will appear in the list of Port P01 Devices PROFIBUS DP and can be enable and configured by the window PO5063 Properties. (13) The PO5063 is enable in this window and can be added a description. The address is set according the physical address of the PROFIBUS DP Head (PO5063). (14) With the head already set and addressed it is necessary to add Slots (I/O modules) according the configuration: PO5063 Right button / mouse New Profibus Slot. (15) Once the Slots are inserted (according the I/O modules) it is time to configure and set each Slot. The option Properties of each Signal will set and configure the Slot, according the following picture: Altus Sistemas de Informática S.A. Página: 7

(16) After Exploring DeltaV configuration it is necessary the transference of information to memory. We can check the diagnostic of the PROFIBUS DP Slave according the following picture (DeltaV Controller must be in operation mode and physical connections done): The parameter Diagnostic Messages must be set or reset to avoid the operation mode information as diagnostic message in the PO5063 module. Altus Sistemas de Informática S.A. Página: 8

3.2 PROFIBUS DP Setting The Ponto Series modules need a parameterization to define operation modes. It exist common parameters and specific parameters for each module. The parameters are specified by the GSD file. The PO5063 head has the following common parameters. Parameter Option Description Hot swap disable When the system is turned on all the modules must be connected in the bus. They can t be removed during on line mode operation. Hot swap enable with no start The missing of declared modules on the bus or the remove of the modules during on line Power up system up consistency operation will not affected the power on and head on line mode operation. Operand forcing Disable Output Diagnostic Messages Delay time to module activation Hot swap enable with start up consistency (default) It does not allow operand forcing (default) It allows operand forcing It does not allow output disabling It allows output disabling Status and diagnostic errors (default) Only diagnostic errors No delay time 1 second delay 2 seconds delay (default) 3 seconds delay 5 seconds delay 10 seconds delay All the declared modules must be placed on the bus during the power on of the system. After power on the modules can be replaced for maintenance keeping the head on line operation. The operand forcing by software is not allowed (invalid code). The operand forcing is allowed. The output disabling is not allowed by programming software (invalid code). The output disabling is allowed by. The extended diagnostic messages report the status operation of the head and modules, also indicates errors. The diagnostic messages only report errors. The scan time of the module will be active immediately after physical detection. The scan time of the module will be active 1 second after physical detection. The scan time of the module will be active 2 second after physical detection. The scan time of the module will be active 3 second after physical detection. The scan time of the module will be active 5 second after physical detection. The scan time of the module will be active 10 second after physical detection. The PO1112 has 8 analog inputs and it has the following parameters Parameter Option Description C (default) Temperature unit indicated in Celsius scale. Temperature unit F Temperature unit indicated in Farenheit scale. Conversion time American standard RTD graph according American standard. Curva RTD (default) European standard RTD graph according European standard. Channel X type Channel not active Channel conversion not active. Voltage - 7 options Conversion channel voltage mode. 100 ms (default) Inputs conversion period of 100 milliseconds. 2,5 ms Inputs conversion period of 2,5 milliseconds. Altus Sistemas de Informática S.A. Página: 9

Current - 4 options (default: 0-20 ma) Conversion channel cuurent mode. Thermocouple - 8 options Conversion channel thermocouple mode. RTD - 3 options Conversion channel RTD mode. Resistance - 2 options Conversion channel resistance mode. 1,3 ms not turbo 122 Hz (default) 1,3 ms filter, not turbo, 122 Hz cut frequency Channel X Filter 1,3 ms 780 Hz 1,3 ms Filter, 780 Hz cut frequency 100 ms 1,6 Hz 100 ms Filter, 1,6 Hz cut frequency 1 s 0,16 Hz 1 s Filter, 0,16 Hz cut frequency 10 s 0,016 Hz 10 s Filter, 0,016 Hz cut frequency The technical characteristics of each I/O module must be consult for specific parameters options and descriptions. 4. Maintenance The base design, hot swap characteristics and fully diagnostic information are characteristics from Ponto Series that facilitate the maintenance of the system. The report of failures, diagnostics and operation modes give to the operator fully control to identify and solve any problem. 4.1 Diagnostic LEDs All the Ponto Series modules have diagnostic LEDs to inform status and operation mode by easy and quickly way. The LED DG is a common sign used in all Ponto Series modules. It indicates any abnormality in the operation mode according blinking codes. The LED DG can blink up to 5 times, indicating the status according the following table. LED DG Status Always On Blinks 1x Blinks 2x Blinks 3x Blinks 4x Blinks 5x Always Off Mode Description Module is configured and accessed by the master. Properly operation. The module is not access by the master. This situation automatically disable the outputs. Fuse damage. External power supply (24V) failure. The module has diagnostic (channels). Not used. It will occur only in case of hardware damage in the module, not working LED or the module is not connected in the bus. The PO5063 Utilization Manual must be consulted for complete description of the diagnostic LEDs, possible causes and solution procedures. Altus Sistemas de Informática S.A. Página: 10

4.2 Diagnostic Messages The diagnostic messages can be displayed on HMI or programming software that are connected to the RS232 port of the PROFIBUS DP head. The information will be placed in the memory of the PO5063 head, operand M512 to M641. Total of 210 Operands M or 420 bytes: the first 20 bytes are used with diagnostic system, followed by 400 bytes with modules diagnostic information (40 segments, 1 segment for each module connected on the GBL bus). The PO5063 Utilization Manual must be consulted for a complete description of diagnostic information through RS232 port. The diagnostic messages are transferred to the master via PROFIBUS DP network and they are available for the application or to be monitored through network configuring software. The diagnostic messages can be displayed in the Exploring DeltaV during online mode. The slave PROFIBUS DP must be select to see the information. Revisions Revisão: A Data: 12/11/2003 Tradução: José Lozano Revisão Tradução: Autor: Revisor: Aprovador: Natureza das alterações: Sérgio H. C. Silva Fabiano Barboza / Rosana Casais Luiz Francisco Gerbase Primeira emissão do documento. Altus Sistemas de Informática S.A. Página: 11