User manual ALFANET TEMPLOGGER 16x PT1 Module Several Ranges Description : ALFANET TEMPLOGGER 16x Pt1 Doc.nr.: 71867 Type: Manual Number of pages: 1 Version: V2.4 File: Do71867 ALFANET TEMPLOGGER 16x PT1 v24 EN.wpd Software: 61971 V2.1 By: HN Date: 5-2-214 VDH Products BV - Roden - Holland Signed: File: Doc'7
User manual Document nr. : 71867 Versie : V2.4 ALFANET TEMPLOGGER 16x Pt1 Client : General Pagina : 2 van 1 Table of contents 1. Technical specifications.... 3 2. Functional specifications.... 3 2.1 Installation.... 3 2.2 Operation.... 3 3. Control.... 4 3.1 Controlling.... 4 3.2 Read out.... 4 4. Viewing and changing the parameters.... 4 4.1 Parameter list.... 5 5. Front view.... 7 6. Dimensions.... 7 7. Connections.... 8 8. Adress.... 1 The information contained in this document is assumed to be accurate. However VDH Products BV accepts no liability for eventual mistakes or errors and has the right to change this document without notice.
User manual Document nr. : 71867 Versie : V2.4 ALFANET TEMPLOGGER 16x Pt1 Client : General Pagina : 3 van 1 1. Technical specifications. Type : ALFANET TEMPLOGGER 16x Pt1 Supply : 12Vdc (-5/+1%) Used power : Max. 2mA Control : Through PC Read out : Through PC Inputs : 16x Pt 1 Range Accuracy : Lower Limit Value (LLV).. Upper Limit Value (ULV), see product sticker Type nr. LLV.. ULV Resolution View per 91.42-5.. +5 C,1 C,1 C 91.419-1.. +5 C,2 C 1 C 91.425.. +1 C,1 C,1 C 91.447-5.. +15 C,2 C 1 C 91.467-1.. +5 C,2 C,1 C 91.468-5.. +15 C,2 C,1 C : [+/-1x Resolution] + [+/-,5% of (ULV - LLV)] Example: 91.468 = [+/-,2 C] + [+/-,5 % of 2 C] = +/- 1,2 C Network connections : RS485 V, Line-A, Line-B (2x Twisted-pair shielded min.,5mm 2, length max. 5m) for communication through the ALFANET PC-Interface to the PC. Front : Mat. Chrome polyester sticker Dimensions : 9 x 16 x 58 mm (hwd) Panel cut out : 46 x 16 mm (hw) Operation temperature : -2/+5 C Storage temperature : -2/+6 C Operation RH : 1/+9 % RH non condensing - Provided with memory protection during power failure. - DIN-rail mounting - Equipped with self test function and sensor failure detection. - Special versions are available upon request. 2. Functional specifications. 2.1 Installation. On the front of the ALFANET TEMPLOGGER 16x Pt1 and on the connection diagram is shown how the inputs, power supply and the RS485-network connection should be connected. After the Controller is connected to the power supply, a self test will be done. The Controller is adjustable through the ALFANET PC-INTERFACE on the PC. It is possible to connect a maximum of sixteen ALFANET TEMPLOGGER 16x Pt1s on the network. This will make an total of 16 x 16 = 256 sensors. These modules should have a unique network numbers. This can be adjusted below the terminal cover by DIP-switches from address: 11 till 125. 2.2 Operation. From each sensor the measured value is shown on the PC. The refresh rate is at least two time per minute. When there are big temperature variations, the refresh rate will be higher. It is possible to adjust a minimum and a maximum alarm for each sensor. If an alarm occurs, there will be a warning on the pc and the alarm relay from the PC interface will be activated. It is possible to adjust a time delay for each alarm. The adjusting is per 5 minutes till a maximum of 3 minutes. All measured values and alarms are stored in the log from the PC.
User manual Document nr. : 71867 Versie : V2.4 ALFANET TEMPLOGGER 16x Pt1 Client : General Pagina : 4 van 1 3. Control. 3.1 Controlling. The Controller can only be controlled through the PC. See also the manual from the ALFANET PC-INTERFACE. 3.2 Read out. On the picture below is shown how the module looks like on the PC. Inputs which gives strips, are disabled in the parameters. A warning sign means a alarm situation. There is no special alarm for sensor errors. A short circuit sensor will always give a minimum alarm and a broken sensor will always give a maximum alarm. In case of sensor failures the time delays will be ignored. It is possible to give each sensor it s own name. This name will be used on the screen and into the log. See the manual from the PC-software for instructions about how to enter the names. 4. Viewing and changing the parameters. Through the context menu (= right mouse key) the parameters can be viewed and changed.
User manual Document nr. : 71867 Versie : V2.4 ALFANET TEMPLOGGER 16x Pt1 Client : General Pagina : 5 van 1 4.1 Parameter list. Para- Meter Parameter description Range Standard value 1 2 3 4 5 Sensor 1 present Minimum alarm Sensor 1 Minimum alarm delay Sensor 1 Maximum alarm Sensor 1 Maximum alarm delay Sensor 1 =No, 1=Yes..3 minutes..3 minutes 6 7 8 9 1 Sensor 2 present Minimum alarm Sensor 2 Minimum alarm delay Sensor 2 Maximum alarm Sensor 2 Maximum alarm delay Sensor 2 =No, 1=Yes..3 minutes..3 minutes 11 12 13 14 15 Sensor 3present Minimum alarm Sensor 3 Minimum alarm delay Sensor 3 Maximum alarm Sensor 3 Maximum alarm delay Sensor 3 =No, 1=Yes..3 minutes..3 minutes 16 17 18 19 1 Sensor 4present Minimum alarm Sensor 4 Minimum alarm delay Sensor 4 Maximum alarm Sensor 4 Maximum alarm delay Sensor 4 =No, 1=Yes..3 minutes..3 minutes 21 22 23 24 25 Sensor 5 present Minimum alarm Sensor 5 Minimum alarm delay Sensor 5 Maximum alarm Sensor 5 Maximum alarm delay Sensor 5 =No, 1=Yes..3 minutes..3 minutes 26 27 28 29 3 Sensor 6 present Minimum alarm Sensor 6 Minimum alarm delay Sensor 6 Maximum alarm Sensor 6 Maximum alarm delay Sensor 6 =No, 1=Yes..3 minutes..3 minutes 31 32 33 34 35 Sensor 7 present Minimum alarm Sensor 7 Minimum alarm delay Sensor 7 Maximum alarm Sensor 7 Maximum alarm delay Sensor 7 =No, 1=Yes..3 minutes..3 minutes 36 37 38 39 4 Sensor 8 present Minimum alarm Sensor 8 Minimum alarm delay Sensor 8 Maximum alarm Sensor 8 Maximum alarm delay Sensor 8 =No, 1=Yes..3 minutes..3 minutes 41 42 43 44 45 Sensor 9 present Minimum alarm Sensor 9 Minimum alarm delay Sensor 9 Maximum alarm Sensor 9 Maximum alarm delay Sensor 9 =No, 1=Yes..3 minutes..3 minutes 46 47 48 49 5 Sensor 1 present Minimum alarm Sensor 1 Minimum alarm delay Sensor 1 Maximum alarm Sensor 1 Maximum alarm delay Sensor 1 =No, 1=Yes..3 minutes..3 minutes
User manual Document nr. : 71867 Versie : V2.4 ALFANET TEMPLOGGER 16x Pt1 Client : General Pagina : 6 van 1 Para- Meter Parameter description Range Standard value 51 52 53 54 55 Sensor 11 present Minimum alarm Sensor 11 Minimum alarm delay Sensor 11 Maximum alarm Sensor 11 Maximum alarm delay Sensor 11 =No, 1=Yes..3 minutes..3 minutes 56 57 58 59 6 Sensor 12 present Minimum alarm Sensor 12 Minimum alarm delay Sensor 12 Maximum alarm Sensor 12 Maximum alarm delay Sensor 12 =No, 1=Yes..3 minutes..3 minutes 61 62 63 64 65 Sensor 13 present Minimum alarm Sensor 13 Minimum alarm delay Sensor 13 Maximum alarm Sensor 13 Maximum alarm delay Sensor 13 =No, 1=Yes..3 minutes..3 minutes 66 67 68 69 7 Sensor 14 present Minimum alarm Sensor 14 Minimum alarm delay Sensor 14 Maximum alarm Sensor 14 Maximum alarm delay Sensor 14 =No, 1=Yes..3 minutes..3 minutes 71 72 73 74 75 Sensor 15 present Minimum alarm Sensor 15 Minimum alarm delay Sensor 15 Maximum alarm Sensor 15 Maximum alarm delay Sensor 15 =No, 1=Yes..3 minutes..3 minutes 76 77 78 79 8 Sensor 16 present Minimum alarm Sensor 16 Minimum alarm delay Sensor 16 Maximum alarm Sensor 16 Maximum alarm delay Sensor 16 =No, 1=Yes..3 minutes..3 minutes 11 till 116 Sensor offset sensor 1 till Sensor offset sensor 16-1... 1. K.. -1... 1. K. K... K *) LLV = Lower Limit Value p.e.. -5 C at the range -5..+5 C ULV = Upper Limit Value p.e.. +5 C at the range -5..+5 C
User manual Document nr. : 71867 Versie : V2.4 ALFANET TEMPLOGGER 16x Pt1 Client : General Pagina : 7 van 1 5. Front view. 427 6. Dimensions. 9794
User manual Document nr. : 71867 Versie : V2.4 ALFANET TEMPLOGGER 16x Pt1 Client : General Pagina : 8 van 1 7. Connections. 426
User manual ALFANET TEMPLOGGER 16x Pt1 42152 Document nr. : 71867 Versie : V2.4 Client : General Pagina : 9 van 1
User manual Document nr. : 71867 Versie : V2.4 ALFANET TEMPLOGGER 16x Pt1 Client : General Pagina : 1 van 1 8. Adress. VDH Products BV Telefoon: +31 ()5-3 28 9 Produktieweg 1 Fax: +31 ()5-3 28 98 931 ZS Roden Email: info@vdhproducts.nl Nederland Internet: www.vdhproducts.nl