The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations

Similar documents
Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

Upgrading Path to High Speed Fiber Optic Networks

Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution.

Obsolete Fiber Technology? Not in my Data Center!

Data Center Topology Guide

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center

40/100 Gigabit Ethernet: The Foundation of Virtualized Data Center and Campus Networks

Optimizing Infrastructure Support For Storage Area Networks

InstaPATCH Cu Cabling Solutions for Data Centers

InstaPATCH ZERO Solution Guide

HUBER+SUHNER AG Phil Ward

How To Make A Data Center More Efficient

Living Infrastructure Solution Guide.

AMP NETCONNECT Data Center Cabling Solutions

Data Center Fiber Cabling Topologies and Lengths. Paul Kolesar IEEE HSSG, September 2006

Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand

Plug & Play Gigabit Ethernet Media Conversion Module. Application Note

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions

Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure

Data Center Design for 40/100G

The Need for Low-Loss Multifiber Connectivity

The 8-Fiber Solution for Today s Data Center

Infrastructure for the next three generations

24 fiber MPOptimate Configuration and Ordering Guide

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

TIA Releases Guidelines for Maintaining Polarity Using Array Connectors

High density Fiber Optic connections in the Data Center. Phil Ward Datacenter Product Market Manager. HUBER+SUHNER AG

Secure/Keyed LC System Solutions Overview

SYSTIMAX Solutions. Intelligent Infrastructure (ipatch) Solutions Guide

MIGRATING TO A 40 GBPS DATA CENTER

99 Washington Street Melrose, MA Phone Toll Free Visit us at

Enterprise Networks EMEA. Core Products FOR DATA CENTRES

Security & Surveillance Cabling Systems

Zone Distribution in the Data Center

Data Center Cabling Design Trends

How To Properly Maintain A Fiber Optic Infrastructure

MTP Optical Fibre Configurations

Top of Rack: An Analysis of a Cabling Architecture in the Data Center

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano

Enterprise Networks EMEA. Core Products FOR DATA CENTRES

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

Fiber in the Data Center

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

Pretium EDGE HD Solutions

How To Create An Intelligent Infrastructure Solution

Uniprise Solutions. Ten Good Reasons To Choose CommScope.

Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices

Arista 40G Cabling and Transceivers: Q&A

Arista and Leviton Technology in the Data Center

Understanding Fiber Polarity: Implications at 10G, 40G, & 100G

MPO. Fast Fibre Solution for Data Centres

CommScope Intelligent Building Infrastructure Solutions (IBIS)

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems

ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER

Data Center Market Trends

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram

Accelerating Light. Copper Cabling Solutions. Category 6A

SYSTIMAX Solutions. GigaSPEED X10D Shielded (F/UTP, S/FTP) Solution Guide Europe, Middle East and Africa Regions.

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

Corning Cable Systems Optical Cabling Solutions for Brocade

Patch Cords for Data Center Applications

FDCCI is your mission. CommScope is your answer. Performance, security and efficiency that meet your targets. Data Center Solutions

What to do about Fiber Skew?

A Comparison of Total Costs of Ownership of 10 Gigabit Network Deployments in the Data Center

The ABC of Direct Attach Cables

How To Make A Fibre Cable For A Data Centre

Contract Number NNG07DA20B NASA SEWP IV

Storage Area Management (SAM) Clutter-Free, Super-Efficient Network Infrastructure Management

Network Design. Yiannos Mylonas

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications

Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center

Category 8 Cabling Standards Update

Copper Pre-terminated Assemblies

Overcoming OM3 Performance Challenges

Unified Physical Infrastructure (UPI) Strategies for Data Center Networking

Total Solutions Verification

Data Center Infrastructure Solution

Network Monitoring - Fibre TAP Modules

GigaSPEED X10D Solution How

T1 Backhaul Connectivity Solution All Products :: Application Note

Auxiliary equipment for communication with the EuroProt protective devices

Simplified 40-Gbps Cabling Deployment Solutions with Cisco Nexus 9000 Series Switches

DATA CENTRES NETWORKS

Tapping Technology. Just the Facts about the Pretium EDGE Tap Module

A Guide to Patch Cord Management

Connector and Cable Specifications

PANDUIT is a Technology Developer Partner for Storage Networking Hardware. FIBER OPTIC CABLING SYSTEM SOLUTIONS B EYOND T HE G LASS

DATA CENTRES POWERED BY EXCEL

Transcription:

The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations White Paper www.commscope.com

Contents Introduction 3 CommScope solution overview 3 InstaPATCH 360: The traditional two-fiber application channel 4 InstaPATCH 360: The basic parallel transmission channel 5 InstaPATCH 360: The optimized parallel transmission channel 6 InstaPATCH 360: The two-fiber fan-out channel implementation 7 InstaPATCH Plus/ReadyPATCH: The traditional two-fiber application channel 8 InstaPATCH Plus/ReadyPATCH: The basic parallel transmission channel 8 InstaPATCH Plus/ReadyPATCH: The optimized parallel transmission channel 9 Conclusion 10 www.commscope.com 2

Introduction CommScope offers a variety of pre-terminated fiber solutions that utilize multi-fiber connectors to facilitate rapid deployment of fiber networks in data centers and other high-density environments. Within the SYSTIMAX brand, these solutions are InstaPATCH 360 and InstaPATCH Plus. The Uniprise solution is ReadyPATCH. At the core of all of these solutions is the MPO (Multi-fiber Push On) connector. This connector is defined by IEC-61754-7, Fiber-optic interconnecting devices and passive components Fiber-optic connector interfaces Part 7: Type MPO connector family ; and TIA-604-5-D, Fiber-Optic Connector Intermateability Standard, Type MPO. For Ethernet networking speeds up to 10GB/s, the most common transmission schemes for multimode fiber utilize serial transmission. A typical channel is made of two fibers, with one fiber to carry traffic in each direction. When using multi-fiber connectors, polarity management is necessary to maintain proper send/receive orientation and port numbering at each end of the channel. All of the CommScope solutions are designed around the polarity management method described in ANSI/TIA-568-C as Method B. For Ethernet networking speeds above 10GB/s, the applications standards are specifying parallel optics for multimode fiber networks. IEEE 802.3ba defines the transmission schemes for 40GB/s and 100GB/s. The interfaces for these higher speeds are based on the MPO connector. As such, it is a relatively simple process to upgrade a CommScope pre-terminated solution from 10GB/s to 40GB/s or even 100GB/s. CommScope solution overview Within the SYSTIMAX brand, CommScope currently offers the InstaPATCH 360 fiber solution as the primary pre-terminated solution. From 2003 through 2009, the primary offering within the SYSTIMAX brand was InstaPATCH Plus. There are two main differences in the InstaPATCH 360 and InstaPATCH Plus solutions. First, the size of the module was reduced with InstaPATCH 360 to improve the maximum fiber density in a given rack space. The other change for InstaPATCH 360 was an improvement in connection loss, which allows for longer application support and more flexible network designs. Of particular note, the polarity management method was unchanged. As such, with proper mounting hardware to address the module size difference, the InstaPATCH 360 and InstaPATCH Plus components can be installed in the same channels without polarity concerns. The only impact to the system would be found in the channel loss expectations. If it is necessary to mix the solutions within an installation, performance would be dictated by the lower solution support limits. The ReadyPATCH solution was introduced into the Uniprise brand in 2008. This solution was identical to the InstaPATCH Plus solution except for some variations in performance and some aesthetic features. In 2011, the ReadyPATCH solution was upgraded to be identical to the InstaPATCH Plus offering. This was done as part of the end-of-life strategy for InstaPATCH Plus. As such, the current CommScope solution offering only includes SYSTIMAX InstaPATCH 360 and Uniprise ReadyPATCH. For legacy installations with InstaPATCH Plus components, the ReadyPATCH components can be used to support the existing footprint. Optionally, InstaPATCH 360 components can be used with appropriate mounting hardware. www.commscope.com 3

InstaPATCH 360: The traditional two-fiber application channel In its basic form, a traditional two-fiber application pre-terminated channel is made up in the following way: MPO trunk cables make up the permanent link portion of the channel. This trunk cable may include fiber counts from 12 to 144 fibers in 12-fiber increments. At each end of the trunk, modules are used to convert the MPO connection on the trunk into multiple two-fiber appearances at the patch panel. These modules can have LC (most common), SC or ST connectors for the duplex channel support. Two-fiber patch cords are plugged into the modules to connect devices or perform a cross-connect in a patching field. Figure 1: This is the traditional two-fiber application channel with InstaPATCH 360. In Figure 1: The trunk cables are LazrSPEED 550 InstaPATCH 360 trunk cables with 24 fibers (FGXMPMPAF). The modules are InstaPATCH 360 LazrSPEED standard modules with 24 LC ports (360DM-24LC-LS). The patch cords are LazrSPEED 550 LC to LC, fiber patch cord, 1.6mm duplex, plenum (FDXLCLC42) Regarding polarity considerations, the TIA Method B system does not require different cords within the channel. With other polarity management methods, it may be necessary to specify different cords at each end of the channel. www.commscope.com 4

InstaPATCH 360: The basic parallel transmission channel When migrating to 40GB/s, the trunk cables can be re-purposed to carry the parallel optics traffic by removal of the modules and patch cords, replacing them with MPO pass-through panels and MPO equipment cords. The MPO pass-through panels (shown above) are InstaPATCH 360 Distribution Panel, 360DP-2MPO, 2xMPO (360DP-2MPO). The equipment cords are LazrSPEED 550 InstaPATCH 360 array cord, MPO (female) to MPO (male) 12-fiber (FQXMPMXGD). Regarding polarity considerations, the TIA Method B system does not require different cords at each end of the channel. With other polarity management methods, it may be necessary to specify different cords at each end of the channel. The other consideration that requires attention is the gender of the MPO connector. Specify the equipment cords with one end as an un-pinned MPO (female) and the other end as a pinned MPO (male) connector. The female end will plug into the active equipment. The male end will plug into the pass-through panel adapter. In the event that the channel contains a cross-connect, specify the array patch cord with pinned MPO (male) connectors on both ends: The cross-connect cords are LazrSPEED 550 InstaPATCH 360 array cord, MPO (male) to MPO (male), 12-fiber (FQXMXMXGD). Figure 2: This is the basic parallel transmission channel with InstaPATCH 360. www.commscope.com 5

InstaPATCH 360: The optimized parallel transmission channel The IEEE 802.3an application standards for 40GB/s utilize a 4x4 parallel transmission scheme. This application uses eight fibers (four for transmit and four for receive), but is designed to run on 12-fiber channels. If the basic parallel transmission channel previously discussed is deployed, it is important to realize that four of 12 fibers (33 percent) will remain dark while supporting 40GB/s channels. In an optimized parallel transmission channel, the fibers in the trunk cable can be fully utilized through the use of the 4x4 parallel modules. These modules are used in place of the MPO pass-through panels on each end of the trunk cable. The module is designed to receive three MPO equipment (or cross-connect) cords on the front side. The dark fibers are dropped from use, resulting in full utilization of the fibers in the two MPO trunk connectors on the rear of the module. Replace the 360DP-2MPO pass-through panels with the MPO 4x4 parallel module: The MPO 4x4 Parallel module is the InstaPATCH 360 4x4 LazrSPEED standard parallel module (360DM-4X4P-LS) (shown above). In this configuration, the equipment cord should be specified with both ends having un-pinned MPO (female) connectors. The female end will plug into the active equipment and into the module. The equipment cords are LazrSPEED 550 InstaPATCH 360 array cord, MPO (female) to MPO (female) 12-fiber (FQXMPMPGD). If a cross-connect is incorporated in the channel, consideration should be given to the functionality of the cross-connect. If it is desirable to be able to administer the 40G circuits independently, install the 4x4 parallel modules on the ends of the trunks at the cross-connect. In this case, the cross-connect cords would be the same gender as the equipment cords in this section (female to female). If 4x4 parallel modules are not installed, the three 40G circuits can only be administered as a collective group to a common set of two other trunks. Figure 3: Here is an optimized parallel transmission channel with InstaPATCH 360. www.commscope.com 6

InstaPATCH 360: The two-fiber fan-out channel implementation Under certain conditions some two-fiber pre-terminated cabling may be deployed without the modules at the ends of the channel. This scenario works best when all of the fibers will be immediately placed into service and when they all serve equipment ports that are in close proximity to each other. One example where this occurs is in support of blade servers where each blade or rack of blades may have multiple fiber ports. Upon initial installation, it is likely that all fibers will be placed into service immediately and all fiber ports will be within a single shelf or rack. In this case, the modules and patch cords can be replaced with a fan-out cable assembly. The channel is made up in the following way: MPO trunk cables make up the permanent link portion of the channel. This trunk cable may include fiber counts from 12 to 144 fibers in 12-fiber increments. At one (or both) ends of the trunk, fan-out cable assemblies are used to convert the channel from MPO connections into duplex connections (LC, SC or ST). If the fan-out cable assemblies are not used on both ends of the channel, it is necessary to use the modules and patch cords where the fan-out cables are not used. Additionally, if a crossconnect is included in the channel, it is most common to use the modules and patch cords from the traditional network. Figure 4: Here is an example of a two-fiber fan-out channel with InstaPATCH 360 fan-out cables. In Figure 4: The trunk cables are LazrSPEED 550 InstaPATCH 360 trunk cables with 24 fibers (FGXMPMPAF). The modules are InstaPATCH 360 LazrSPEED standard modules with 24 LC ports (360DM-24LC-LS). The patch cords are LazrSPEED 550 LC to LC, fiber patch cord, 1.6mm duplex, plenum (FDXLCLC42). The MPO pass-through panels are InstaPATCH 360 distribution panel, 360DP-2MPO, 2xMPO (360DP-2MPO) The fan-out cables are LazrSPEED 550 MPO (female) to LC, InstaPATCH 360 array cord, 12-fiber, plenum (FQXMPLCGD). One is needed for each 12-fiber increment. Migration of this implementation to 40GB/s can be accomplished by replacing the fan-out cables, modules and patch cords with the components from the Basic Parallel or Optimized Parallel transmission channels. www.commscope.com 7

InstaPATCH Plus/ReadyPATCH: The traditional two-fiber application channel Utilizing InstaPATCH Plus or ReadyPATCH modules and trunk cables, the traditional two-fiber application channel is shown in Figure 3. Figure 5: This is the traditional two-fiber application channel with InstaPATCH Plus/ ReadyPATCH. In Figure 5: The trunk cables are LazrSPEED 550 ReadyPATCH trunk cables with 24 fibers (FYXMPMPAF). The modules are ReadyPATCH LazrSPEED standard modules with 24 LC ports (RFE-MOD-024-5K-MPO-LC02). The patch cords are LazrSPEED 550 LC to LC, fiber patch cord, 1.6mm duplex, plenum (FDXLCLC42). Regarding polarity considerations, the TIA Method B system does not require different cords within the channel. With other polarity management methods, it may be necessary to specify different cords at each end of the channel. www.commscope.com 8

InstaPATCH Plus/ReadyPATCH: The basic parallel transmission channel When migrating to 40GB/s, the trunk cables are re-purposed to carry the parallel optics traffic by removal of the modules and patch cords, replacing them with MPO pass-through panels and MPO equipment cords. The MPO pass-through panels are InstaPATCH CommScope 2 MPO adapter panels (RFE-PNL-2MPO) (shown above). The equipment cords are LazrSPEED 550 ReadyPATCH array cord, MPO (female) to MPO (male) 12-fiber (F2XMPMXGD). Regarding polarity considerations, the TIA Method B system does not require different cords at each end of the channel. With other polarity management methods, it may be necessary to specify different cords at each end of the channel. The other consideration that requires attention is the gender of the MPO connector. Specify the equipment cords with one end as an un-pinned MPO (female) and the other end as a pinned MPO (male) connector. The female end will plug into the active equipment. The male end will plug into the pass-through panel adapter. In the event that the channel contains a cross-connect, specify the array patch cords with pinned MPO (male) connectors on both ends: The cross-connect cords are LazrSPEED 550 ReadyPATCH array cord, MPO (male) to MPO (male), 12-fiber (F2XMXMXGD). Figure 6: Here is an example of a basic parallel transmission channel with InstaPATCH Plus/ReadyPATCH. www.commscope.com 9

InstaPATCH Plus/ReadyPATCH: The optimized parallel transmission channel. In an optimized parallel transmission channel, the fibers in the trunk cable can be fully utilized through the use of the 4x4 parallel modules. These modules are used in place of the MPO pass-through panels on each end of the trunk cable. The module is designed to receive three MPO equipment (or cross-connect) cords on the front side. The dark fibers are dropped from use, resulting in full utilization of the fibers in the two MPO trunk connectors on the rear of the module. The MPO 4x4 parallel module is the ReadyPATCH 4x4 LazrSPEED standard parallel module (RFE-MOD-4x4-P-LS) (shown above). In this configuration, the equipment cord should be specified with both ends having un-pinned MPO (female) connectors, which will plug into the active equipment and the module. The equipment cords are LazrSPEED 550 ReadyPATCH array cord, MPO (female) to MPO (female) 12-fiber (F2XMPMPGD). If a cross-connect is incorporated in the channel, consideration should be given to the functionality of the cross-connect. If it is desirable to be able to administer the 40G circuits independently, install the 4x4 parallel modules on the ends of the trunks at the cross-connect. In this case, the cross-connect cords would be the same gender as the equipment cords in this section (female to female). If 4x4 parallel modules are not installed, the three 40G circuits can only be administered as a collective group to a common set of two other trunks. Figure 7: This is an optimized parallel transmission channel with InstaPATCH Plus/ReadyPATCH. www.commscope.com 10

Conclusion Because the InstaPATCH 360, InstaPATCH Plus and ReadyPATCH solutions are based on the MPO connector and Method B Polarity, the upgrade path from two-fiber channels to 40GB/s parallel optics channels is simple and easy. Standard MPO pass-through panels and standard equipment cords allow for use of existing trunk cables. The 4x4 parallel modules allow maximization of the fiber investment through full utilization of the trunk fibers. Management of polarity is optimal, as the Method B solution does not require different fiber mapping at each end of the network. www.commscope.com Visit our Web site or contact your local CommScope representative for more information. 2013 CommScope, Inc. All rights reserved. All trademarks identified by or are registered trademarks or trademarks, respectively, of CommScope, Inc. This document is for planning purposes only and is not intended to modify or supplement any specifications or warranties relating to CommScope products or services. WP-106443-EN (1/13)