Holly STATCOM FACTS to replace critical generation, operational experience



Similar documents
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Topics. HVDC Fundamentals

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

ENERGY AND ENVIRONMENTAL SAVINGS IN STEEL MAKING BY MEANS OF SVC LIGHT

HVDC Light and development of Voltage Source Converters

Asia Pacific Regional Power Quality Seminar March 2005, Marriot Putrajaya, Malaysia. Voltage Source Converter based Power Quality Solutions

The design and performance of Static Var Compensators for particle accelerators

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

FACTS. Solutions to optimise network performance GRID

SVC LIGHT: A POWERFUL MEANS FOR DYNAMIC VOLTAGE AND POWER QUALITY CONTROL IN INDUSTRY AND DISTRIBUTION.

2012 San Francisco Colloquium

HVDC-VSC: transmission technology of the future

STATCOM Application at VELCO Essex Substation

HVDC Light, a tool for electric power transmission to distant loads

Electrical Considerations for HVDC Transmission Lines. Joe Mooney, PE

Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

Application of SVCs by CenterPoint Energy to Address Voltage Stability Issues: Planning and Design Considerations

HVDC 2000 a new generation of high-voltage DC converter stations

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Control Development and Modeling for Flexible DC Grids in Modelica

Transmissão em Corrente Contínua

Solar Power Plant Design and Interconnection

Magnus Callavik, ABB Power Systems, HVDC, Västerås, Sweden Phone: +46(0)

HVDC Technology for Large Scale Offshore Wind Connections

Introduction. Harmonics and IEEE 519 Page 1 of 19

Brochure Introducing HVDC

Voltage Stability Improvement using Static Var Compensator in Power Systems

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

APPLICATION CASE OF THE END-TO-END RELAY TESTING USING GPS-SYNCHRONIZED SECONDARY INJECTION IN COMMUNICATION BASED PROTECTION SCHEMES

Product Data Bulletin

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

Nuclear Power Plant Electrical Power Supply System Requirements

Current and voltage measuring relays

White Paper. Fiber Optics in Solar Energy Applications. By Alek Indra. Introduction. Solar Power Generation

What Is Regeneration?

Electric utilities may vary in their application of end-to-end testing

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

Voltage Source HVDC Overview Mike Barnes Tony Beddard

AN ISOLATED GATE DRIVE FOR POWER MOSFETs AND IGBTs

Transformers. Special transformers Reactors products

ABB PSPS Erich Steinmann; Generator control-2013

B4-102 CROSS SOUND CABLE PROJECT SECOND GENERATION VSC TECHNOLOGY FOR HVDC

Analysis of AC-DC Converter Based on Power Factor and THD

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

High-Megawatt Converter Technology Workshop for Coal-Gas Based Fuel Cell Power Plants January 24, 2007 at NIST

Wide Area Monitoring Current Continental Europe TSOs Applications Overview

Offshore Platform Powered With New Electrical Motor Drive System

SECTION VARIABLE FREQUENCY DRIVES

Typical Data Requirements Data Required for Power System Evaluation

Principles of Adjustable Frequency Drives

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

Recent Siemens HVDC Activities Yuriy Kazachkov Siemens PTI

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Renewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS)

Summary of Electric Transmission Assessment Report

Power transformers. Special transformers Railway

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

2012 San Francisco Colloquium

How To Improve Power Quality

System Protection Schemes in Eastern Denmark

Project description. Power Electronics for Reliable and Energy efficient Renewable Energy Systems

Renewable Energy Grid Integration

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208

Power Quality & Custom Power

Voltage Regulator SPAU 341 C. Product Guide

Line Reactors and AC Drives

How To Improve Power Quality

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

TDA4605 CONTROL CIRCUIT FOR SWITCH MODE POWER SUPPLIES USING MOS TRANSISTORS

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

HVDC. A firewall against disturbances in high-voltage grids. Lennart Carlsson

Future grid infrastructure Field tests of LVDC distribution

Introduction to The Trans Bay Cable Project

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM

Local Back-up Protection for an Electric Power System

Current Limiting Protector For Systems rated kV and continuous currents through 5000A.

Table of Contents. TransformerIQ FAQs 1

Earth Fault Detection Basics in Theory

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

HVDC Light It s time to connect

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

Analysis of the Effect of Tap Changing Transformer on Performance of SVC

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Evaluating AC Current Sensor Options for Power Delivery Systems

Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM

Transcription:

Holly STATCOM FACTS to replace critical generation, operational experience A. Oskoui, B. Mathew, Member, IEEE, J.-P. Hasler, M. Oliveira, Member, IEEE, T. Larsson, Member, IEEE, Å. Petersson, E. John, Member IEEE Abstract Austin Energy plans to decommission an old oiland gas-fired plant near downtown Austin, Texas, USA. In addition to providing the generation capacity, an important reason the four-unit Holly plant has been kept in operation is to stabilize the voltage on the transmission system. Retirement of the power plant without a reliable dynamic reactive source would have a negative impact on the transmission system voltage stability. A special requirement in Austin Energy s case is recovery from voltage sags where a fast response is necessary at low voltages, i.e. transient voltage recovery. Furthermore, physical limitations related to aesthetics, electromagnetic field emissions, and audible noise had impact on the solution to be implemented. Transmission planning studies determined that the voltage requirements could be met using a STATCOM. This paper provides details on the background, an overview of the STATCOM technology, and shows results from the first period of operation of the Holly STATCOM, delivered by ABB. Index Terms AC-DC power conversion, Converters, Insulated gate bipolar transistors, Power conditioning, Power control, Power system dynamic stability, Static VAR compensators, Pulse width modulation, STATCOM, SVC Light, Transient voltage recovery, Voltage control, Voltage source converter FACTS IGBT PWM STATCOM VSC A I. NOMENCLATURE Flexible AC Transmission System Insulated Gate Bipolar Transistor Pulse Width Modulation STATic var COMpensator Voltage Source Converter II. INTRODUCTION USTIN Energy plans to decommission an old oil- and gas-fired power plant near downtown Austin, Texas, USA. The power plant was constructed in the 96s. In addition to providing the generation capacity, an important reason the plant has been kept in operation is to stabilize the voltage on the transmission system. Retirement of the power plant without a reliable dynamic reactive source would have a A. Oskoui (e-mail: arastou.oskoui@austinenergy.com) and B. Mathew (email: biju.mathew@austinenergy.com) are with Austin Energy, Austin, TX, USA J.-P. Hasler (e-mail: jean-philippe.hasler@se.abb.com), M. Oliveira (email: marcio.oliveira@se.abb.com), T. Larsson (e-mail: tomas.x.larsson@se.abb.com) and Å. Petersson (e-mail: ake.n.petersson@se.abb.com) are with ABB, Västerås, SE-72 64, Sweden negative impact on the transmission system voltage stability. Flexible AC Transmission System (FACTS) technology was considered as a possible solution for the problem. A special requirement in Austin Energy s case is the recovery from voltage sags where a fast response is necessary at low voltages. Physical limitations of the urban site included low electro-magnetic fields and audible noise emissions, which were specified as special requirements of the installation. An initial study showed that the needs could be met using a compact STATic COMpensator (STATCOM). ABB won the bid in competition with other suppliers. ABB s STATCOM solution has the brand name SVC Light, indicating the close relation to ABB s HVDC Light as both are based on Voltage Source Converter (VSC) technologies. A STATCOM is specially suited for supplying full compensating current at very low AC network voltages and has the ability to compensate for unbalances. The STATCOM design features also include a minimum footprint and effective electromagnetic screening, both of which were required in this application. III. STATCOM TECHNOLOGY The principal component of the STATCOM is the VSC. This technology has been used for many years primarily in motor drives. The last years, however, an increasing number of plants for considerably higher power and voltage, based on the VSC technology have been built for both industrial [-4] and power system [5-8] applications. The Holly STATCOM is based on ABB s SVC Light platform, a concept utilizing the so-called Neutral Point Clamping (NPC) converter, a threelevel converter topology that combines high controllability with robustness against grid disturbances. In addition, the power losses are moderate thanks to the employed switching frequency. For converter control and modulation, different switching schemes are available. ABB has chosen a control scheme based on Pulse Width Modulation (PWM). The high frequency switching control, which for the Holly STATCOM is set at 2 times the fundamental frequency, provides a fast and extremely robust VSC control. This is particularly required during severe faults on the power system. Moreover, compensation of voltage unbalance can be achieved without the installation of low order harmonic filters. To allow for use of a compact high-power VSC with sufficiently high E. John (email: eric.john@us.abb.com) is with ABB, Raleigh, NC, USA

2 switching frequency, the Insulated Gate Bipolar Transistor (IGBT) is the most suitable component available. Using IGBTs and high frequency PWM switching assures excellent performance during network faults. Network faults have proved to be quite troublesome for thyristor based (GTO, IGCT) solutions. The VSC inherently has a symmetrical current operating range. This is favorable from a STATCOM point-of-view as the system can be optimized for fast response both in the inductive (i.e. over-voltage suppression) as well as capacitive (i.e. under-voltage support) modes while minimizing the losses. Passive filters provide harmonic filtering for the higher harmonic frequencies generated by the converter, and offset the STATCOM range some 5 in the capacitive range. Furthermore, additional control of external devices such as mechanically switched capacitor banks and tap changers can be incorporated in the control system. Specifically for the Holly STATCOM application, control of an On Line Tap Changer (OLTC), three 38 kv 3.2 capacitor banks and one 69 kv 3.2 capacitor bank have been incorporated in the control system. For future projects, it is also possible to control other types of equipment such as for instance shunt reactors. 3.2 38 kv bus 3.2 CF2, CF22 5 Fig.. Holly STATCOM single line diagram. 32 kv bus VSC +/-95 3.2 IV. THE HOLLY STATCOM INSTALLATION A. STATCOM Rating The power plant to be retired is located on Holly Street near downtown Austin. The STATCOM is partially built on top of a reinforced old oil tank near the Holly power plant, at the Pedernales substation. The STATCOM consists of a VSC inherently symmetrically rated at +/- 95 MVA and 5 of filters seen from the Pedernales 38 kv bus. In total this gives an operating range from 8 inductive reactive power to capacitive reactive power. There are also the three 38 kv capacitor banks each rated at 3.2 for providing steady-state reactive power support to the grid. Including the three 38 kv capacitor banks, the reactive power range is 8 inductive to just above 2 capacitive. The dynamic portion of this is two times the VSC rating of 95, or 9. Fig. 2. Holly STATCOM layout ) Valve hall 2) Enclosed 32 kv equipment B. Main circuit description Figure shows a simplified single line diagram of the Holly STATCOM (including the dual redundant transformers and the three 38 kv capacitor banks) and Figure 2 shows the layout. The entire installation can be seen in the photo shown in Figure 3. It is worth noting that the entire secondary voltage circuit (at 32 kv) is placed indoors. As always the converters are indoor-type of equipment, but in this installation the phase reactors and the passive harmonic filters are enclosed as well. The principal reason for enclosing the phase reactors and the passive harmonic filters is the need for screening, both electromagnetic and acoustic. However, the enclosure also made it possible to meet requirements on varmint proofing. 38 kv transformers Filter enclosure 38 kv cap banks Valve hall and control room Fig. 3. Holly STATCOM

3 C. Operating strategy The STATCOM utilizes the ABB MACH2 control system, a common control platform used for all ABB FACTS and HVDC Projects. The MACH2 controller inherently has the capability to automatically take actions for switching in and out the three 38 kv mechanically switched capacitor banks. This operating strategy forces the fixed capacitor banks to be the major producer of reactive power support during slow varying conditions in the system. The strategy leaves the STATCOM ready to rapidly respond with dynamic reactive power support to disturbances occurring during power system contingencies. This applies to both over-voltage suppression and under-voltage support. The STATCOM control system also switches an existing 69 kv capacitor bank as well as the tap-changer position of a 69/38 kv auto-transformer. These voltage control mechanisms are slower than the switching controls of the 38 kv banks and are designed to improve the slow voltage profile on the 69 kv system and to minimize reactive power flow through the auto-transformer. D. Site considerations in the design The local site conditions included a residential neighborhood and as such the STATCOM design had to meet strict requirements on electromagnetic emissions and acoustic noise. The extended building proved to be a cost effective solution for screening and it also provided excellent varmint proofing of the installation. In addition to enclosing the harmonic filters and phase reactors, the transformers utilize a two-wall design for audible noise reduction. In addition to residential housing, the aerial photo in Figure 3 shows that the STATCOM is in the close proximity of existing facilities (e.g. piping) belonging to the Holly power plant. It became a true design challenge to fit all of the equipment in the space available. However, the Holly STATCOM installation is an example that a single-converter STATCOM scheme can be built considerably smaller than its nearest relatives in the FACTS family, i.e. the multi-converter based STATCOM or the SVC. program for preliminary evaluation of the control functions implemented in the Holly STATCOM. These tests were later repeated during factory validation tests and during commissioning. An example of these tests is verification of the response of the STATCOM current controller and is shown in the following plots. In this case, the STATCOM was operated in open-loop, i.e. with constant reactive power generation. Initially, the STATCOM operating point was around 5, with reactive power generated only by the harmonic filters. A step function with an amplitude of.5 p.u. was then applied to the reactive current reference. Figure 4 shows the results obtained with a time-domain simulation program while Figure 5 presents the results obtained at the site. Fig. 4..5 per-unit step response at reactive current reference. Time-domain simulation. a) VSC reactive current reference b) VSC reactive current instantaneous value c-e) VSC three-phase currents and 32 kv bus voltages V. SIMULATIONS COMPARED TO REALITY In the Holly STATCOM project, a number of studies were performed to verify the STATCOM performance. The studies covered for instance STATCOM dynamic performance with a focus on voltage sag ride-through and low AC voltage conditions, capacitor bank switching with back-to-back switching and outrush currents, transmission system power flow, harmonics, sound propagation and reliability. The simulations were mainly performed in PSCAD, PSS/E and other proprietary software. The results were seamlessly incorporated in the system design. Many of the simulated results were also verified in the field during extensive system tests on site. Some details are given in the remainder of the paper. Before commissioning of the equipment, a complete STATCOM model was built in a time-domain simulation Fig. 5..5 per-unit step response at reactive current reference. Test performed at site. a) VSC reactive current reference b) VSC reactive current instantaneous value c-e) VSC three-phase currents and 32 kv bus voltages

4 In addition to the consistency in the results, the plots also show the very fast response of the VSC current controller, providing thus almost instantaneous reactive power support to the system. This feature is particularly useful in the event of faults in the power system, as presented in the next section. VI. OPERATIONAL EXPERIENCE The Holly STATCOM was commissioned in the fall of 24. Design and constructions activities prior to energization went smoothly and even put the project ahead of the time schedule. However, during the time following the first energization, a number of IGBTs failed virtually without any clear reason. Fault tracing eventually determined the reasons for the high IGBT failure rate. The semiconductors are switched on and off (IGBTs) and supervised (IGBTs and diodes) via fiber optic cables. The fiber optic cables are intended to be attached to the electronic boards at the same potential. For the Holly STATCOM, the design of the light guide contact had changed from previous SVC Light projects and a metal piece of the connector now lacked a defined potential. The electromagnetic environment inside the valve enclosure by its nature has a high disturbance level. This lead to partial discharges that sometimes delivered a false pulse to the IGBT electronics. These pulses would normally not have disturbed the electronic circuits. However, a second reason for the IGBT failures was identified. An integrated circuit was found to have different properties compared to earlier batches. A short pulse, as created by the disturbance, was prolonged and was sometimes long enough to be detected as a turn-off pulse. If this happened during a conduction interval, the IGBT position picked up a very high voltage resulting in the immediate failure of the triggered IGBT. Both of the above reasons were mitigated with minor modifications, which were implemented on site. After a onemonth trial operation, the STATCOM successfully went into commercial operation. Some of the expected results have been reported in a previous section and in an earlier publication [9]. Here the results will be further discussed. Two cases are shown in the following that illustrate the STATCOM dynamics and performance during remote faults captured by the Transient Fault Recorder (TFR), integrated with the MACH2 control system. The high performance fault recorder can sample and trigger on any internal control signal without any external wiring. The first case occurred during the period of tests of the control system. The benefit of the STATCOM s support to the transmission system was demonstrated during the severe thunderstorms that hit central Texas area in November 24. There were several faults of about 5 cycle duration on the 38 kv system that resulted in the STATCOM to produce its maximum capacitive output. Figure 6 shows some plots related to one of these faults, obtained from the TFR. The capacitor bank control was disabled at the instant of the disturbance and the initial STATCOM operating point was close to. This event showed also the need for adjusting the deadband of the AC voltage regulator during the return of the STATCOM to its pre-fault operating point. This is verified in the third plot, corresponding to the VSC current reference signal after time t= s. Some days later, a fault closer to the STATCOM occurred at the adjacent 69 kv system around t =. s in Figure 7. The bottom plot shows clearly a drop on phase B voltage at the 38 kv bus. The STATCOM responded to the voltage reduction by maximizing its capacitive output. Despite the clear unsymmetrical nature of the disturbance, reflected also to the DC side of the VSC, the VSC currents are symmetrical during the fault, which is a feature that can only be achieved by employing PWM switching. After the fault has been cleared, the current is ramped down to the initial pre-fault value in a controlled manner. The STATCOM is then ready to support the grid if a new disturbance should occur. An additional feature in the STATCOM control is the FACTS Online web-based module used for on-line diagnostics and monitoring over the Internet. This feature in the control gives notification to selected support personnel by e-mail following minor disturbances and also by phone messages following critical disturbances. Information from the MACH2 control is made available for engineering analysis over the Internet. This includes information such as operational status of the STATCOM, event and fault information, disturbance records, etc. The benefit of on-line monitoring is that support engineers have direct access to the same diagnostic information as is available in the local Human-Machine IV_A [PU] IV_B [PU] IV_C [PU] US_A [PU] US_B [PU] DC_SUM [PU] IREF_QLIM [PU] US_C [PU].5.5 -.5 - TFR HOLLY 2423 8;47;3_84 -.5.4.5.6.7.8.9..2 2.5 2.4 2.3 2.2 2..4.5.6.7.8.9..2.5 -.5.4.5.6.7.8.9..2.5.5 -.5 - -.5.4.5.6.7.8.9..2 Time [s] Fig. 6. Example of STATCOM response during a transmission line fault a) VSC three-phase currents b) DC voltage c) VSC reactive current reference calculated by the control system d) 38 kv three-phase voltages

5 IV_A [PU] US_A [PU] IV_B [PU] US_B [PU] IV_C [PU] DC_SUM [PU] IREF_QLIM [PU] US_C [PU].5.5 -.5 - -.5.9.95.5..5.2.25.3 2.5 2.4 2.3 2.2 2..9.95.5..5.2.25.3.5 -.5.9.95.5..5.2.25.3 2 - TFR HOLLY 2429 8;37;2_26.CFG -2.9.95.5..5.2.25.3 Time [s] Fig. 7. STATCOM response during a fault on the adjacent 69 kv system. a) VSC three-phase currents b) DC voltage c) VSC reactive current reference calculated by the control system d) 38 kv three-phase voltages Interface (HMI) of the MACH2 system, regardless of location should a disturbance occur. Figure 8 shows one of the FACTS Online displays available over the Internet. Common practice for high voltage VSC, is to utilize valves containing a stack of series connected semiconductor devices in order to reach a sufficient voltage rating. Such stacks normally contain more semiconductor devices than the number required for operation in all specified conditions. The number of extra devices is used as redundant positions. If semiconductor failures occur during operation they are shortcircuited and the converter can remain in operation as long as the number of failed IGBTs is less than the number of redundant positions. Should all redundant IGBTs fail and then an additional IGBT fails, the plant would normally trip. For critical applications such as the Holly STATCOM, this is unacceptable. To continue operation beyond the redundancy, a new solution has been implemented in the Holly STATCOM. If the redundant semiconductor device fails, the DC voltage is slightly reduced to allow the remaining components to stay within their rating and operation can be maintained. With this method, the capability of reactive power absorption by the VSC is not affected in the inductive region. However, operation in the capacitive region may be slightly reduced. The major benefit is an increased availability of the VSC and converting forced outages to deferred or planned outages. For the five months after the start of operation, the STATCOM availability has been % without any forced trips due to the installation itself. The IGBT failures do have ceased and there has been no de-rating of the STATCOM. Fig. 8. FACTS on line view in an Internet browser

6 VII. CONCLUSIONS As reported and demonstrated in this paper, FACTS devices can replace the dynamic reactive support of critical generation with several benefits regarding transient voltage recovery, economical and environmental aspects, operation and maintenance costs, etc. The technology is mature and provides a robust system for mitigating grid disturbances. The Holly STATCOM has after acceptance tests shown very high performance and reliability during the initial months it has been in operation. VIII. ACKNOWLEDGEMENT The work and efforts of all people involved in the different phases of the project are greatly acknowledged. No one mentioned and no one forgotten. IX. REFERENCES [] R. Grünbaum, T. Gustafsson, U. Olsson, SVC Light: Evaluation of first installation at Hagfors, Sweden, CIGRÉ conference, paper 3/4/36-3, Paris, France, 2 [2] T. Larsson, B. Ratering-Schnitzler, SVC Light: A utility s aid to restructuring its grid, IEEE PES winter meeting, Singapore, Jan. 2 [3] R. Grünbaum, T. Gustafsson, J.-P. Hasler, T. Larsson, M. Lahtinen, STATCOM, a prerequisite for a melt shop expansion performance experiences, IEEE Power Tech, Bologna, Italy, 23 [4] R. Grünbaum, J.-P. Hasler, B. Thorvaldsson, FACTS: Powerful means for dynamic load balancing and voltage support of AC traction feeders, Power Tech, Porto, Portugal 2 [5] T. Larsson, Å. Petersson, A. Edris, D. Kidd, R. Haley, F. Aboytes, Eagle Pass Back-to-Back tie: a dual purpose application of voltage source converter technology, IEEE summer meeting, Vancouver, Canada, 2 [6] U. Axelsson, A. Holm, C. Liljegren, M. Åberg, K. Eriksson, O. Tollerz, The Gotland HVDC Light project experiences from trial and commercial operation, CIRED conference, Amsterdam, The Netherlands, June 8 2, 2 [7] B. D. Railing, J. J. Miller, P. Steckley, G. Moreau, P. Bard, L Ronström, J. Lindberg, Cross Sound cable project second generation VSC technology for HVDC, CIGRÉ conference, Paris, France, Aug. 29 Sept. 3, 24 [8] M. P. Bahrman, J. G. Johansson, B. A. Nilsson, Voltage source converter transmission technologies The right fit for the Application, IEEE PES general meeting, Toronto, Canada, July 3 8, 23 [9] E John, A. Oskoui, Å Petersson, Using a STATCOM to retire urban generation, IEEE PCSC meeting, New York, USA, Oct. 24 X. BIOGRAPHIES Arastou Oskoui graduated from NED Engineering University with a Bachelor of Electrical Engineering and University of Texas at Austin with Master of Science degree in Electrical Engineering. His employment experience includes five years with AMI Systems, six years with Lower Colorado River Authority in Relay Engineering, three years with Ralph M. Parson Engineering Consultants and for the last ten years with Austin Energy. He is currently Director of Engineering and Technical Services at Austin Energy s Electric Service Delivery organization. Biju Matthew graduated from Texas A&M University in College Station with a Bachelor of Science in Electrical Engineering in 985. He received a Master of Science in Electrical Engineering from the University of Texas at Austin in 988. He started with Austin Energy in 987 in the System Controls area and later joined the Transmission Planning group in 988. He has worked in all facets on Transmission Planning, which includes participation in several ERCOT Task Forces. Since 22, he has served as lead Transmission Planning Engineer for the group. Jean-Philippe Hasler received his M.Sc. degree in Electrical Engineering from the Ecole Polytechnique Federale de Lausanne, Switzerland in 986. Mr. Hasler joined ABB in 986 where he was developing control systems and protection algorithms for multi-terminal HVDC. Since 993 he is conducting power system and control studies for different FACTS applications. Marcio M. de Oliveira (M 995) received his M.Sc. in Electrical Engineering in 992 from the Federal University of Rio de Janeiro. He received his Ph.D. in High Power Electronics in 2 from the Royal Institute of Technology in Stockholm, Sweden. Mr. Oliveira joined ABB in 2 and is working with system design and power system studies for reactive power compensation plants. Tomas Larsson (S 992, M 999) received his M.Sc. in Electrical Engineering in 99 and his Ph.D. in High Power Electronics in 998, both from the Royal Institute of Technology in Stockholm, Sweden. Mr. Larsson joined ABB in 998 where he presently is involved in projects concerning Voltage Source Converters, reactive power compensation and flicker mitigation. Åke Petersson received his M.Sc. degree in Electrical Engineering from Chalmers Institute of Technology, Gothenburg Sweden, in 982. Mr. Petersson joined ABB (at that time ASEA) in 982 and has over the years held various engineering positions related to the application of power electronics in high voltage electrical systems. Presently he is focusing on the application of FACTS applications in transmission grids. Eric M. John (M 995) graduated from the Rensselaer Polytechnic Institute with a BS in Electric Power Engineering and Duke University s Fuqua School of Business with an MBA. His employment experience includes three years with Westinghouse Power Generation working with Power Quality and FACTS. He joined ABB in 998 and has worked with power quality and system design of FACTS devices. He is currently the US marketing manager for FACTS with ABB Inc. of Raleigh, North Carolina.