BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

Similar documents
2012 NFPA 70E. Ten Most Important Changes. John A. DeDad

Understanding Arc Flash

NFPA 70E Updates Affect Your Most Valuable Assets

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

ELECTRICAL & ARC FLASH SAFETY PROGRAM

PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

Introduction to Arc Flash

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

misconceptions about arc-flash hazard assessments

ARC Flash Boundary & NFPA-70E Requirements PPE Program

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS

2008 Eaton Corporation. All rights reserved.

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.

What s up with Arc Flash?

Campus Safety Procedure Electrical Safety

! WARNING Arc Flash and Shock Hazard Appropriate PPE Required

PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Part 1 System Modeling & Studies for Existing Systems

A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software

UL Validated Testing of Arc-Resistant Motor Control Centers

Procedure Number Arc Flash Hazard Calculation and Required Protection Revision 5. TVA Safety Procedure Page 1 of

Electrical Safety Program

Electrical Safety Program

Analyzing Electrical Hazards in the Workplace

TAMPA ELECTRIC COMPANY ENERGY SUPPLY ELECTRICAL SAFETY PROGRAM

Demystifying arc flash hazard management

SALISBURY ASSESSMENT SOLUTIONS

Safety By Design. Strategies for Electrical Contractors

Hampshire College. Lockout/Tagout and Electrical Safety Program and Procedures

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

How to reduce exposure to arc flash hazards

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

Technical Guide. SKM Arc Flash Line Side vs. Load Side

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA

Safety, Health, and Environmental Standard

Roadmap to Compliance with NFPA 70E Arc Flash Requirements

OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010

Job Site Electrical Safety A Matter of Life and Death

How to Build a Safe and Effective Electrical Maintenance Program

Choosing the Best Solution for Reducing Arc Energy

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

UNIVERSITY OF CENTRAL FLORIDA ELECTRICAL SAFETY PROGRAM

ELECTRICAL SAFETY PROGRAM

Low Voltage Switchgear

Environmental Health & Safety Electrical Safety Program

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Low Voltage Circuit Breakers. Arc flash hazards

Using Infrared Sightglasses to Protect Against Arc-Flash Exposure

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

3053 Electrical Safety Training Program Course Outline

OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance

ELECTRICAL SAFETY / ARC FLASH PROGRAM

Arc Flash Energy Mitigation Techniques

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

Electrical Safety in the Marine Environment

Understanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment

Arc Flash Overview. Arc-Flash Hazard. Who is Eaton. Engineering Studies ABSTRACT. Eaton PSE s

Arc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E.

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Installation Instructions for Alarm Module Kit A043F059

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

Evaluating Water-Damaged Electrical Equipment

ELECTRICAL SAFETY RISK ASSESSMENT

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Arc Flash Mitigation & Selective Co-ordination

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

Common Sense and Knowledge Approach to Electrical Safety

OSHA & ARC FLASH HAZARD ANALYSIS

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection

Electrical Safety Program. Electrical Safety Program Audit (Appendix: X) Performed By: Date:

Sample - No Commercial Use

NFPA 70E SYNOPSIS ARC FLASH WHITE PAPER BY SYDUL HAQUE ELK ENGINEERING ASSOCIATES, INC.

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment

Requirements for Electrical Installations

Myths and Facts on Complying with NFPA 70E's Clothing Requirements By Hugh Hoagland

Transcription:

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety standards when selecting PPE or evaluating hazards.

What is an electrical arc flash? How do I calculate the danger posed by an arc flash? How do I protect myself and others from an arc flash?

TYPES OF ELECTRICAL FAULTS Bolted Fault: Bolted faults are characterized by a solidly connected fault path causing high levels of current to flow through this solid connection. Arcing Fault: Arcing faults differ in the fact that the current actually flows through ionized air causing an arc.

ELECTRICAL ARC FLASH Flash Temperature: up to 35000 [ºF] Blast Pressure: 500 to 600 [psi] Pressure Wave Velocity: 5500 to 6000 [ft/s]

ELECTRICAL ARC FLASH Injuries 2nd Degree Burn: 176[ºF] @ 0.1[s] 3rd Degree Burn: 205[ºF] @ 0.1[s] Threshold for 2nd Degree Burn: 1.2 [cal/cm 2 ]

ELECTRICAL ARC FLASH Causes of arcing faults: Accidents caused by touching a test probe to the wrong surface. Accidental tool slippage. Sparks due to breaks or gaps in insulation system. Equipment failure due to use of substandard parts, improper installation, or even normal wear and tear. Dust, corrosion or other impurities on the surface of the conductor insulation systems.

ELECTRICAL ARC FLASH 5 to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which the victim is sent to an ordinary hospital. These incidents are so severe the victims require treatment from a special burn center.

ELECTRICAL ARC FLASH HAZARD NFPA 70E Arch Flash Hazard: A dangerous condition associated with the possible release of energy caused by an electric arc FPN No.1: may exist when energized electrical conductors are exposed a person interacting with equipment in such a manner that could cause an electric arc.

What is an electrical arc flash? How do I calculate the danger posed by an arc flash? How do I protect myself and others from an arc flash?

ELECTRICAL ARC FLASH HAZARD Arc Flash Hazard Analysis: A study investigating a worker s potential exposure to arc flash energy, conducted for the purpose of injury prevention and the determination of safe work practices, arc flash protection boundary, and appropriate levels of PPE. Calculations based on NFPA Annex D

ELECTRICAL ARC FLASH HAZARD Arc Flash Hazard Analysis Results: PPE Selection Arc Flash Boundary

ELECTRICAL ARC FLASH HAZARD Arc Flash Boundary: Designed to prevent 2nd degree burns when unprotected during an arc flash. The higher the arc flash energy the greater the boundary. If inside the boundary PPE protection is needed to prevent injury.

STOLL EXPERIMENT Stoll A.M., Greene L.C., Relationship Between Pain and Tissue Damage Due to Thermal Radiation, Journal of Applied Physiology 14: 373-382, 1959 Based on experiments on humans. Used a flame source with varying times of exposure The time and energy was varied to determine a second degree burn threshold relationship.

ELECTRICAL ARC FLASH BOUNDARIES NFPA Annex D: Multiple Methods Lee Method IEEE 1584 Method Software Solutions Requires a complete protection coordination study Important Factors: Available fault current Transformer kva Transformer Impedance Motor Contribution Fuse or Breaker Curves and Settings Conduit Type

31 Engineering Services Breaker Settings Comparison BREAKER/FUSE CURVES CURRENT IN AMPERES CURRENT IN AMPERES 1000 2000 KVA 2000 KVA 2 sets: 500 Fault clears in 8 seconds 1000 2000 KVA 2000 KVA 2 sets: 500 100 3000A MAIN 125E Incident energy = 718 cal/cm 2 100 3000A MAIN 125E 10 1 800A1 IA = 6K IB = 9K No FR class for IE values this high TIME IN SECONDS 10 1 800A1 IA = 6K IB = 9K TIME IN SECONDS 0.10 TX Inrush 2 sets: 500 Fault clears in 0.1 second 0.10 TX Inrush 2 sets: 500 Incident energy 0.01 1 10 100 1K 10K Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw =.97 cal/cm 2 FR class 0 0.01 1 10 100 1K 10K Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw

ELECTRICAL ARC FLASH HAZARD Arc Flash Hazard Analysis Results: PPE Selection Arc Flash Boundary

What is an electrical arc flash? How do I calculate the danger posed by an arc flash? How do I protect myself and others from an arc flash?

ELECTRICAL SHOCK HAZARD Shock Hazard Analysis: A shock hazard analysis shall determine the voltage to which personnel will be exposed, boundary requirements, and personal protective equipment necessary in order to minimize the possibility of electrical shock. Calculations based on NFPA 130.2

ELECTRICAL SHOCK HAZARD Shock Hazard Analysis Results: PPE Selection Approach Boundary

ELECTRICAL PPE PPE Selection: Based on Arc Flash and Shock Hazard FR, Fire Retardant clothing or Arc Flash Suit Arc Flash Suit: A complete FR clothing and equipment that covers the entire body, except for the hands and feet. This includes pants, jacket, and a beekeeper-type hood fitted with a face shield

ELECTRICAL PPE Arc Rating: The value attributed to materials that describes their performance to exposure to an electrical arc discharge. The arc rating is expressed in [cal/cm 2 ] and is derived from the determined value of the arc thermal performance value (ATPV) or energy breakopen threshold.

ELECTRICAL PPE 130.7(C)(10): Category 0 Incident Energy: {0-1.2} [cal/cm 2 ] Shirt (Long Sleeve) *1 Pants (Long) *1 Safety Glasses or Goggles Hearing Protection Gloves (As needed) *1: Non-melting (according to ASTM F 1506-00) or Untreated Natural Fiber

ELECTRICAL PPE 130.7(C)(10): Category 1 Incident Energy: {1.2-4} [cal/cm 2 ] Arc-rated long sleeve shirt Arc-rated pants Arc-rated coverall Arc-rated jacket, parka, or rainwear Hardhat, Safety Glasses, Hearing Protection Leather Gloves Leather work shoes

ELECTRICAL PPE 130.7(C)(10): Category 2 Incident Energy: {4-8} [cal/cm 2 ] Arc-rated long sleeve shirt Arc-rated pants Arc-rated coverall Arc-rated jacket, parka, or rainwear Hardhat, Safety Glasses, Hearing Protection Leather Gloves Leather work shoes Arc-rated flash suit hood, for Cat 2*

ELECTRICAL PPE 130.7(C)(10): Category 3 Incident Energy: {8-25} [cal/cm 2 ] Arc-rated long sleeve shirt Arc-rated pants Arc-rated coverall Arc-rated flash suit jacket, pants, hood Arc-rated jacket, parka, or rainwear Hardhat with FR lines, Safety Glasses, Hearing Protection Arc-rated Gloves Leather work shoes

ELECTRICAL PPE 130.7(C)(10): Category 4 Incident Energy: {25-40} [cal/cm 2 ] Arc-rated long sleeve shirt Arc-rated pants Arc-rated coverall Arc-rated flash suit jacket, pants, hood Arc-rated jacket, parka, or rainwear Hardhat with FR lines, Safety Glasses, Hearing Protection Arc-rated Gloves Leather work shoes

ELECTRICAL HAZARD ANALYSIS Approach Boundaries Shock From Shock Hazard Analysis Arc Flash From Arc Flash Hazard Analysis

ELECTRICAL HAZARD ANALYSIS Arc Flash Protection Boundary: When an arc flash hazard exists, an approach limit at a distance from a prospective arc source within which a person could receive a second degree burn if an electrical arc flash were to occur.

ELECTRICAL HAZARD ANALYSIS 130.7(C)(1) When and employee is working within the Arc Flash Protection Boundary he or she shall wear protective clothing and other personal protective equipment in accordance with 130.3.

ELECTRICAL HAZARD ANALYSIS NFPA 70E defines an unqualified person as simply "a person who is not a qualified person." There are two kinds of unqualified persons: An unqualified electrician who does not know the equipment or has not received safety training on the potential hazards involved. A non-electrician, such as a general maintenance worker or painter, who is not expected to work on live electrical equipment.

ELECTRICAL HAZARD ANALYSIS Shock Hazard Boundary: Limited Approach Boundary: An approach limit at a distance from and exposed energized electrical conductor or circuit part within which a shock hazard exists.

ELECTRICAL HAZARD ANALYSIS Shock Hazard Boundary: Restricted Approach Boundary: An approach limit at a distance from and exposed energized electrical conductor or circuit part within which there is an increased risk of shock, due to electrical arc over combined with inadvertent movement, for personnel working in close proximity to the energized electrical conductor or circuit part.

ELECTRICAL HAZARD ANALYSIS Shock Hazard Boundary: Prohibited Approach Boundary: An approach limit at a distance form and exposed energized electrical conductor or circuit part within which work is considered the same as making contact with the electrical conductor or circuit part.

ELECTRICAL SHOCK BOUNDARIES NFPA NFPA 70E 70E Table Table 130.4 130.4 (C) (C) (a) (a) Approach Boundaries Approach Boundaries to Energized to Energized Electrical Electrical Conductors Conductors or Circuit or Circuit Parts Parts for for Shock Protection for for Alternating Alternating Current Current Systems (all dimensions are distances from energized electrical conductor or circuit parts to employee) Systems (all dimensions are distances from energized electrical conductor or circuit parts to employee) (1) (2) (3) (4) (5) (1) (2) (3) (4) (5) Limited Limited Approach Approach Boundary Boundary b b Nominal System Voltage Exposed Exposed Fixed Restricted Approach Prohibited Approach Nominal System Range, Voltage Phase Exposed Exposed Fixed Restricted Approach Prohibited Approach Range, Phase to Phase 4 to Phase 4 Movable Circuit Part Boundary b Movable Circuit Part Boundary b ; Includes Boundary b Conductor Inadvertent Movement ; Includes Adder Boundary b 50 V Conductor Not Specified Not Specified Inadvertent Not Movement Specified Adder Not Specified 50 V 50 V 300 V Not Specified 3.0 m (10 ft. 0 Not in.) Specified 1.0 m (3 ft. 6 in.) Not Avoid Specified Contact Avoid Not Contact Specified 50 V 300 301 V V 750 V 3.0 m (10 3.0 ft. m 0 (10 in.) ft. 01.0 in.) m 1.0 (3 m ft. (36 ft. in.) 6 in.) Avoid 0.3 m Contact (1 ft. 0 in.) 25 Avoid mm (0 ft. Contact 1 in.) 301 V 750 V 751 V 15 kv 3.0 m (10 ft. 0 in.) 1.0 m (3 ft. 6 in.) 3.0 m (10 ft. 0 in.) 1.5 m (5 ft. 0 in) 0.3 m (1 ft. 0 in.) 0.7 m (2 ft. 2 in.) 25 mm (0 ft. 1 in.) 0.2 m (0 ft.7 in.) 15.1 kv 36 kv 3.0 m (10 ft. 0 in.) 1.8 m (6 ft. 0 in.) 0.8 m (2 ft. 7 in.) 0.3 m (0 ft. 10 in.) 751 V 15 36.1 kv kv 46 kv 3.0 m (10 3.0 ft. m 0 (10 in.) ft. 0 1.5 in.) m 2.5 (5 m ft. (80 ft. in) 0 in.) 0.7 0.8 m (2 (2 ft. ft. 29 in.) in.) 0.40.2 m (1 m ft. (05 ft.7 in.) in.) 15.1 kv 36 kv 3.0 m (10 ft. 0 in.) 1.8 m (6 ft. 0 in.) 0.8 m (2 ft. 7 in.) 0.3 m (0 ft. 10 in.) 36.1 kv 46 46.1 kv kv 72.5 kv 3.0 m (10 3.0 ft. m 0 (10 in.) ft. 0 2.5 in.) m 2.5 (8 m ft. (80 ft. in.) 0 in.) 0.8 1.0 m (2(3 ft. 93 in.) 0.10.4 m (2 m ft. (12 ft. in.) 5 in.) 72.6 kv 121 kv 3.3 m (10 ft. 8 in.) 2.5 m (8 ft. 0 in.) 1.0 m (3 ft. 4 in.) 0.8 m (2 ft. 9 in.) 46.1 kv 72.5 138 kv 145 kv 3.0 m (10 3.4 ft. m 0 (11 in.) ft. 0 2.5 in.) m 3.0 (8 m ft. (10 0 in.) ft. 0 in.) 1.0 1.2 m (3 (3 ft. 310 in.) 1.00.1 m (3 m ft. (24 ft. in.) 2 in.) 72.6 kv 121 kv 3.3 m (10 ft. 8 in.) 2.5 m (8 ft. 0 in.) 1.0 m (3 ft. 4 in.) 0.8 m (2 ft. 9 in.) 161 kv 169 kv 3.6 m (11 ft. 8 in.) 3.6 m (11 ft. 8 in.) 1.3 m (4 ft. 3 in.) 1.1 m (3 ft. 9 in.) 138 kv 145 kv 3.4 m (11 ft. 0 in.) 3.0 m (10 ft. 0 in.) 1.2 (3 ft. 10 in.) 1.0 m (3 ft. 4 in.) 230 kv 242 kv 4.0 m (13 ft. 0 in.) 4.0 m (13 ft. 0 in.) 1.3 m (4 ft. 3 in.) 1.6 m (5 ft. 2 in.) 345 kv 363 kv 4.7 m (15 ft. 4 in.) 4.7 m (15 ft. 4 in.) 161 kv 169 kv 3.6 m (11 ft. 8 in.) 3.6 m (11 ft. 8 in.) 2.8 m (9 ft. 2 in.) 1.3 m (4 ft. 3 in.) 2.6 m (8 ft. 8 in.) 1.1 m (3 ft. 9 in.) 230 kv 242 500 kv 550 kv 4.0 m (13 5.8 ft. m 0 (19 in.) ft. 0 4.0 in.) m 5.8 (13 m ft. (190 ft. in.) 0 in.) 1.3 3.6 m (4(11 ft. ft. 310 in.) in.) 3.51.6 m (11 m ft. (54 ft. in.) 2 in.) 345 kv 363 765 kv - 800 kv 4.7 m (15 7.2 ft. m 4 (23 in.) ft. 9 in.) 4.7 m 7.2 (15 m ft. (234 ft. in.) 9 in.) 2.84.9 m (9(15 ft. ft. 211 in.) in.) 4.72.6 m (15 m (8 ft. 5 ft. in.) 8 in.) 500 kv 550 kv 5.8 m (19 ft. 0 in.) 5.8 m (19 ft. 0 in.) 3.6 m (11 ft. 10 in.) 3.5 m (11 ft. 4 in.) 765 kv - 800 kv 7.2 m (23 ft. 9 in.) 7.2 NFPA m (2370E ft. 9 Table in.) 130.4 (C) 4.9 (a) m (15 ft. 11 in.) 4.7 m (15 ft. 5 in.) Approach Boundaries to Energized Electrical Conductors or Circuit Parts for Shock Protection for Direct Current Voltage Systems (1) (2) (3) (4) (5)

ELECTRICAL HAZARD BOUNDARIES Approach Boundaries Shock From Shock Hazard Analysis Calculations based on NFPA 130.2 Arc Flash From Arc Flash Hazard Analysis Calculations based on NFPA Annex D

ELECTRICAL HAZARD BOUNDARIES 130.2(D)(1) Working at or close to the limited approach boundary: Where one or more unqualified persons are working at or close to the limited approach boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn them to stay outside of the limited approach boundary.

ELECTRICAL HAZARD BOUNDARIES 130.2(D)(2) Entering the limited approach boundary: Where there is a need for an unqualified person(s) to cross the limited approach boundary, a qualified person shall advise them of the possible hazards and continuously escort the unqualified person(s) while inside the limited approach boundary. Under no circumstances should the unqualified person(s) be allowed to cross the restricted approach boundary.

What is an electrical arc flash? How do I calculate the danger posed by an arc flash? How do I protect myself and others from an arc flash?

HAZARD RISK CATEGORY CLASSIFICATIONS What if the hazard analysis process has not been completed? You can use the Hazard Risk Category Classifications 130.7(C)(9)

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Tasks Performed on Energized Equipment Hazard/Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools Panelboards or Other Equipment Rated 240 V and Below- Note 1 Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 0 N N Circuit breaker (CB) or fused switch operation with covers on 0 N N Circuit breaker (CB) or fused switch operation with covers off 0 N N Work on energized electrical conductors and circuit parts, including voltage testing 1 Y Y Remove/Install CBs of fused switches 1 Y Y Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 0 N N Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 0 N N Work on energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the panelboard 1 Y Y

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Tasks Performed on Energized Equipment Hazard/Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools Panelboards or Switchboards Rated.240 V and up to 600 V (with molded case or insulated case circuit breakers) - Note 1 Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 1 N N Circuit breaker (CB) or fused switch operation with covers on 0 N N Circuit breaker (CB) or fused switch operation with covers off 1 Y Y Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y Work on energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the panelboard 2 Y Y

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Tasks Performed on Energized Equipment Hazard/Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools 600 V Class Motor Control Center (MCCs) - Note 2 Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 1 N N CB or fused switch or starter operation with enclosure doors closed 0 N N Reading a panel meter while operating a meter switch 0 N N CB or fused switch or starter operation with enclosure doors open 1 N N Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 0 Y Y Work on control circuits with energized electrical conductors and circuit parts >120 V or below, exposed 2 Y Y Insertion or removal of individual starter buckets from MCC- Note 3 4 Y N Application of safety grounds, after voltage test 2 Y N Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts)- Note 3 4 N N Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) - Note 3 1 N N Work on energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the motor control center 2 Y Y

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Tasks Performed on Energized Equipment Hazard/Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools 600V Class Switchgear (with power circuit breakers or fused switches) - Note 4 Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 2 N N CB or fused switch or starter operation with enclosure doors closed 0 N N Reading a panel meter while operating a meter switch 0 N N CB or fused switch or starter operation with enclosure doors open 1 N N Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 0 Y Y Work on control circuits with energized electrical conductors and circuit parts >120 V or below, exposed 2 Y Y Insertion or removal (racking) of CBs from cubicles, doors open or closed 4 N N Application of safety grounds, after voltage test 2 Y N Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 4 N N Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 2 N N

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Tasks Performed on Energized Equipment Hazard/Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools Other 600 V Class (277 V through 600, nominal) Equipment - Note 2 (except as indicated) Lighting or small power transformers (600 V Maximum) Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 2 N N Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 1 N N Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y Application of safety grounds, after voltage test 2 Y N Revenue Meters (kw-hour at primary voltage and current) insertion or removal 2 Y N Cable trough or tray cover removal or installation 1 N N Misc Equipment Cover removal or installation 1 N N Work on energized electrical conductors and circuit parts, including voltage testing 2 Y Y Application of safety grounds, after voltage test 2 Y N Insertion or removal of plug in devices into or from busways 2 Y N

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Tasks Performed on Energized Equipment Hazard/Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools NEMA E2 (Fused contractor) Motor Starters, 2.3 kv through 7.2 kv Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 3 N N Contractor operation with enclosure 0 N N Reading a panel meter while operating a meter switch 0 N N Contractor operation with enclosure door open 2 N N Work on energized electrical conductors and circuit parts, including voltage testing 4 Y Y Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 0 Y Y Work on control circuits with energized electrical conductors and circuit parts >120 V, exposed 3 Y Y Insertion or removal (racking) of CBs from cubicles, doors open or closed 4 N N Application of safety grounds, after voltage test 3 Y N Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 4 N N Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 3 N N Insertion or removal (racking) of starters from cubicles of arc-resistant construction, tested in accordance with IEEE C37 20.7 doors closed only 0 N N

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Tasks Performed on Energized Equipment Hazard/Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools Metal Clad Switchgear, 1 kv through 38 kv Perform infrared thermography & other non-contact inspections outside the restricted approach boundary 3 N N CB Operation with enclosure doors closed 2 N N Reading a panel meter while operating a meter switch 0 N N CB Or fused switch or starter operation with enclosure doors open 4 N N Work on energized electrical conductors and circuit parts, including voltage testing 4 Y Y Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 2 Y Y Work on control circuits with energized electrical conductors and circuit parts >120 V or below, exposed Insertion or removal (racking) of CBs from cubicles, doors open or closed 4 Y Y Insertion or removal (racking) of CBs from cubicles, doors open or closed 4 N N Application of safety grounds, after voltage test 4 Y N Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 4 N N Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 3 N N Opening voltage transformer or control power transformer compartments 4 N N

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Tasks Performed on Energized Equipment Hazard/Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools ARC Resistant Switchgear Type 1 or 2 (for clearing times of <.05 with a perspective fault current not to exceed the Arc resistant rating of the equipment) CB operation with enclosure doors closed 0 N N Insertion or removal (racking) of CBs from cubicles, doors open or closed 0 N N Insertion or removal of CBs from cubicles with door open 4 N N Work on control circuits with energized electrical conductors and circuit parts 120 V or below, exposed 2 Y Y Insertion or removal (racking) of ground and test device with door closed 0 N N Insertion or removal (racking) of voltage transformers on or off the bus door closed 0 N N

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Tasks Performed on Energized Equipment Hazard/Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools Other Equipment 1kV Through 38 kv Metal-enclosed interupter switch gear, fused or unfused Switch operation of arc-resistant-type construction, tested in accordance with IEEE C37.20.7, doors closed only Switch operation, doors closed 0 N N Switch operation, doors closed 2 N N Work on energized electrical conductors and circuit parts, including voltage testing 4 Y Y Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) 4 N N Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) 3 N N Outdoor disconnect switch operation (hook stick operated) 3 Y Y Outdoor disconnect switch operation (gang-operated, from grade) 2 Y N Insulated cable examination, in man hole or other confined spaces 4 Y N Insulated cable examination, in open area 2 Y N

HAZARD RISK CATEGORY CLASSIFICATIONS Table130.7(C)(9): Table 1 Notes a) Rubber insulating gloves rated for the maximum line-to-line voltage upon which work will be done. (b) Insulated and insulating hand tools are tools rated and tested for the maximum line-to-line voltage upon which work will be done, and are manufactured and tested in accordance with ASTM zg 1505. Standard Specification for Insulated Hand Tools. (c) Y = yes (required), N = no (not required) (d) For systems rated less than 1000 volts, the fault currents and upstream protective device clearing times are based on an 18 in. working distance. (e) For systems rated 1 kv and greater, the Hazard/Risk Categories are based on a 36 in. working distance. (f) For equipment protected by upstream current limiting fuses with arcing fault current in their current limiting range (1/2 cycle fault clearing time or less), the hazard/risk category required may be reduced by one number. Specific Notes (as referenced in the table): 1. Maximum of 25 ka short circuit current available ; maximum of 0.03 sec (2 cycle) fault clearing time. 2. Maximum of 65 ka short circuit current available ; maximum of 0.33 sec (2 cycle) fault clearing time. 3. Maximum of 42 ka short circuit current available ; maximum of 0.33 sec (20 cycle) fault clearing time. 4. Maximum of 25 ka short circuit current available ; maximum of up to 0.5 sec (30 cycle) fault clearing time.

BRANDON AND CLARK INC. ELECTRICAL CONTINUING EDUCATION