THE DEVELOPMENT OF SOLAR ENERGY-GAS COUPLING SYSTEM (SCADA) IN BUILDINGS



Similar documents
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump.

HUB RADIATOR HYBRID. Multi-energy hybrid system to produce heating and DHW. Multi-energy hybrid system to produce heating, cooling and DHW

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

Study on the Auto Air Conditioning Controller Testing System Based on Lab Windows/CVI

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

California Solar Initiative (CSI) Thermal Program Metering Installation Guide

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

HVAC Processes. Lecture 7

CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS

System integration oriented data center. planning. In terms of ATEN's eco Sensors DCIM solution

SWIMMING POOL HEAT PUMP Owners Manual

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

Condensing Boiler Efficiency

Congratulations! Your unique solar monitor ID is located on your monitoring unit as seen on this page.

LMS The modular management system for condensing boilers. Control Products & Systems OEM. Answers for infrastructure.

imagine SOLAR AIR CONDITIONING MADE EASY

Combined Cycle Control Overview

The product segments Heating, ventilation, air conditioning. Control Products & Systems OEM. Answers for infrastructure.

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

The natural ombination

Seeing by Degrees: Programming Visualization From Sensor Networks

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3

Split Controller. User Manual SM-SS-F 2009/01/04

Natural geothermal energy.

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Thermostat with display

Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov to Mar. 15, 2004.

How Ground/Water Source Heat Pumps Work

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

NOVEL ENERGY PROVISION SYSTEM FOR THE SUSTAINABLE CONNECTED HOME

Solar Combisystems Changes on the market place since Task beginning

Failure code manual. content

ROTEX gas hybrid heat pump. A strong team.

Energy savings in commercial refrigeration. Low pressure control

RVR Hybrid System Installer Instructions RVR Hybrid System Controller Installation Instructions

ENERGY PRODUCING SYSTEMS

Daikin Altherma hybrid heat pump. The natural combination

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Process Alarm Solutions

What you can expect from your Solar Hot Water System

ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -

The District Energy Manager and Classroom Heating

PELLEXIA COMFORT ENVIRONMENT COMPATIBLE

A Roof Integrated Solar Heating System Without Storage

The Central Solar Heating Plant with Aquifer Thermal Energy Store in Rostock - Results after four years of operation

SCADA and Monitoring for Solar Energy Plant

CGC s Hybrid System Loop Control

Transient Analysis of Integrated Shiraz Hybrid Solar Thermal Power Plant Iman Niknia 1, Mahmood Yaghoubi 1, 2

Metering and Monitoring Service Packages Technical Supplement

Think Automation and beyond... IDEC WindSRV. KEPServerEX OPC Server

Design and Research of Control System of the Large-Scale Accumulator Blow Molding Machine Based on PLC

Hybrid heat pumps. saving energy and reducing carbon emissions

ECOCIAT. Domestic hot water heat recovery unit

Aerona Air Source Heat Pumps

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

EKON BMS HVAC system. Simply Smart. Touch Screen Controller. Going green. Wireless. Wireless Thermostat with Light Switch

Smile. The All-In-One Heating Controller

PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2014/07) en

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

European test facilities for solar combisystems and heat stores

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions

Research on the Air Conditioning Water Heater System

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

How to choose a heat pump and use it wisely

Multi Drum Heat Storage By John Canivan

Design of UPS Battery Remote Monitoring System

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

REMOTE MONITORING AND CONTROL OF THE KAKKONDA GEOTHERMAL POWER PLANTS

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

FREQUENTLY ASKED QUESTIONS (SOLAR WATER HEATER)

SOLEL SUNCOOLER SOLAR-POWERED AIR-CONDITIONING / HEATING SYSTEM

Computer Controlled Vortex Tube Refrigerator Unit, with SCADA TPVC

HEATING, VENTILATION & AIR CONDITIONING

Nordic Heat Pump Product Guide

INTEC Engineering GmbH Heating Solutions for the Marine Industry

1 General information

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

Factory owners must ensure the boiler is:

Making Your Home Ready For Solar Water Heating

DAikin Altherma low temperature heat pump. end user leaflet

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

PART 11: START-UP PROCEDURES FOR THE INSTALLER

Vitocaldens 222-F Compact Gas-Hybrid appliance

Link-Up. Solid Fuel Association Guide to Central Heating.

Recent Technologies in Nuclear Power Plant Supervisory and Control Systems

Design and Implementation of SCADA System Based Power Distribution for Primary Substation ( Monitoring System)

Portable Air Conditioner

Synergy of demand water heaters with solar and radiant floor heating

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: Fax:

Theta Dual service BFC, SGE, SGS for 20/30/40 kw heating capacity

Building Energy Systems. - HVAC: Heating, Distribution -

Contents. Introduction

User Manual Network connection and Mobics Dashboard (MIS) software for Dryer Controller M720

Baxi Combi 130 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Combination Boiler

Transcription:

THE DEVELOPMENT OF SOLAR ENERGY-GAS COUPLING SYSTEM (SCADA) IN BUILDINGS Xu Hui 1, Cai Yingling 2, Yang Huizhen 3 1 College of Mechanical Engineering, Shanghai University of Engineering Science, Shanghai201620, China 2 College of Mechanical Engineering, Shanghai University of Engineering Science, Shanghai201620, China 3 College of Mechanical Engineering, Shanghai University of Engineering Science, Shanghai201620, China Abstract The system mainly use wall-mounted gas boiler and give priority in use of solar energy in order to maximize the utilization of solar resources. The excess heat will be added to domestic water when the heat for floor radiant heating is enough. The PLC of Siemens is set as slave computer in the monitoring system and it is used to collect thermal parameters such as temperature, flow rate, etc. by temperature sensors, pressure sensors and flow rate sensors. WinCC is set as the host computer to monitor the operating conditions of the entire system. Real-time tracing, monitoring and alarming function can be achieved based on the SQL database, which has realized archive management of the date. The system has been debugged after the whole experiment platform is completed, and the running state of the system shows that this system has high reliability and good stability. Keywords: Solar Energy, Gas, PLC, WinCC, Database --------------------------------------------------------------------***------------------------------------------------------------------ 1. INTRODUCTION Development of renewal energy and clean energy is becoming an inevitable tendency of energy structure transform, which is in conformity with China's current situation. As one of the cleanest energy, solar energy is also an inexhaustible source. However, the characteristics of solar energy such as intermittent, instability, low energy flux density, etc. lead to instability of the solar thermal system. Wall-mounted gas boiler can very convenient and quickly to provide hot water for daily life and heating to buildings, but it s not only benefit to realize the energy conservation and environment protection goal but also consume lots of gas by using wall-mounted gas boiler to heat the building alone. Coupling the two kinds of clean energy (solar energy and gas) can learn from each other. And this coupling not only fully utilized the solar energy but also alleviate the shortage of the non-renewable gas. Obviously, this method has great potential for energy saving. The temperature of the fluid is a critical parameter on the study of the solar energy-gas coupling system and provides basis for mode switching of the entire system. The measurement of temperature has important significance for solar energy-gas coupling system s control and operation. Therefore, control method and application of solar energy-gas coupling system will be discussed in this paper [1-3]. 2. OPTIMIZATION DESIGN OF SOLAR ENERGY-GAS COUPLING SYSTEM Solar energy-gas coupling system includes four main parts. It is solar-collector system, auxiliary system of gas, terminal system of users, monitoring system, respectively. The solarcollector system is mainly used to collect solar energy and ensure the system operate safely and normally. Auxiliary system of gas is mainly used to make up the shortage of solar energy when the weather is bad or large energy is needed, and it can supply heating quickly. Terminal system of users is mainly used to regulate and control the priority level or complementary of hot water storage tank and gas water heater. Monitoring system is mainly used to ensure the whole system can be controlled and measured, and then regulate and control the flow direction and flow rate of hot water according to the needs of users. The hardware of the system is mainly composed by plate solar collector, hot water storage tank, wall-mounted gas boiler, heating fan coil unit, three-way valve, pumps, etc [4-5]. Based on the previous research and standing on the shoulder of the technology of solar energy storage and gas application has becoming more and more mature, the solar energy-gas coupling system was put forward in this article. The system is different from the single traditional heating mode or merely simple superposition of two systems. Based on the data feedback of energy consumption monitoring system, the water in the hot water storage tank will be heated according to actual demands of users, based on the local weather condition and take full advantage of the extra heat of floor radiant heating which provided by solar energy and gas, the efficiency of the entire system will be improved by this way. The system has good practicability and requires a small initial investment. Traditional heating system has some shortages such as large area occupied, large amount of resources consumption, etc. The most important defect in ground source heat pump (GSHP) is the unbalance load of summer and winter which lead to the imbalance of ground temperature-field. According to the coupling system not only these problems will be solved, but also the usage of resource will be improved. The system schematic is shown in figure 1. Volume: 04 Issue: 05 May-2015, Available @ http://www.ijret.org 92

Collector T4 Tee value1 A T6 Tee value2 Gas boiler 1 2 3 4 5 a b 1 Heating water inlet 2 Domestic hot water inlet 3 Gas inlet 4 Heating water outlet 5 Domestic hot water outlet T1 T5 B Pump B1 T2 Floor radiant heating Cold water inlet Pump B2 Fig -1: Schematic diagram of solar energy-gas coupling system 3. DESIGN OF MONITORING SYSTEM 3.1 Regulations of the Solar Energy-gas Coupling System Control 3.1.1 The Solar-Collector System The water in the storage tank will be heated by hot water in the solar-collector system. Temperature difference control method is adopted in this circulation system. When the temperature of heat media difference between the inlet temperature named T1 and outlet temperature named T2 is larger than 8 (it can be set at the range of 5-8 by the users), the circulation pump (B1) of solar-collector will be started after 3 minutes to accelerate the process of heat transfer in order to meet the demands of users. When the temperature difference is less than 3, delay 3 minutes and then turn off circulation pump (B1) until the temperature difference is in steady state. Only in this control method, the frequent start and stop of the B1 pump caused by surge temperature can be avoided. It s unnecessary to run the solar-collector system when the day is a rainy day or it s a foggy day. That is because the solar energy in these weather of less open value for the system in this case. The solarcollector system also will be turned off to avoid the irreversible damage to the storage tank caused by excessive temperature and influence the performance of the system in late stage if the temperature of T4 is larger than 75. The control flow chart is presented in figure 2. Collector Heating medium input Circulation pump B1 Heating medium output Fig -2: The flow chart of solar thermal system 3.1.2 The System of Domestic Hot Water The hot water provided to the users will be offered by the solar-collector system or the wall-mounted gas boiler system. The hot water and cold water in the storage tank will be stratified due to the density difference caused by different temperature, and the hot water will in the upper of the storage tank. The tee valve will be turned on in the direction of (b) and provides domestic hot water to users directly if Volume: 04 Issue: 05 May-2015, Available @ http://www.ijret.org 93

the temperature of T4 is larger than 60. However, if the temperature of T4 is less than 60, the tee valve will be turned on in the direction of (a) and the water in the storage tank will be delivered to the wall-mounted gas boiler and be heated, then it will be provided to users as domestic hot water. There is a supply valve at the bottom of the storage tank to replenish the water which has been consumed. The control flow chart is presented in figure 3. Hot water N Tee value Temperature>Default Gas Boiler Y Cold water inlet Domestic hot water DHW outlet Fig -3: The flow chart of domestic hot water system 3.1.3 Radiant Floor Heating System After the water was heated by the wall-mounted gas boiler and flow into the radiant floor heating system, if the temperature of outlet water (T6) is larger than the upper temperature in the storage tank (T4), it is worth recycling the heat of return water. At this time, the tee valve will be turned on in the direction of (B) and the water will flow into the exchange coil to heat the water in the storage tank. This heat recycle method can maximize the utilization of the heat. However, if T6 is less than T4, the tee valve will be turned on in the direction of (A) and the heat of return water will flow into the wall-mounted gas boiler to be heated, and then go to next cycle. Improve the water temperature by water tank Gas boiler Heating water outlet Pipe coiler Tee value Heating return water temperature>water tank outlet temperature Y N Fig -4: The flow chart of gas heating hot water system 2.2 Design of Controlling Software Design of software for the slave computer is based on the S7-200 of Siemens. The corresponding programs have been completed by programming software of Siemens (STEP 7- Micro/Win V4.0). There is variety of peripheral modules of S7-200 of Siemens and these modules can combine lots of controlling systems flexibility which can complete all requirements. For example, this system is combined with three EM231 RTD modules and one EM231 analog input module. It is easily to maintain these kinds of system, and these systems also have self-diagnosis function and can monitor themselves very well. The working state for the inner element of the system can be monitored by the programs that have been written. The fault location can be found easily and solved by this function coupling with the targeted programs and its self-diagnosis function. The maintenance time will be shortened and the maintenance cost of the system will be cast [6]. The structure control chart of the system is presented in figure 4. Volume: 04 Issue: 05 May-2015, Available @ http://www.ijret.org 94

The control procedure written by PLC has two control mode, which is automatic model and manual mode. When the automatic model is started, the circulation pump of solarcollector (B1) and the circulation pump (B2) of domestic hot water will be turned on and the tee valve 1/2 will be turned on in the direction of (B/b) at the same moment to promote the water in this loop heating system circulate. Three minutes later, whether turn on or not the B1 pump is decided by the temperature difference between outlet temperature of solar-collector and the average temperature of the storage tank, the start-stop type of domestic hot water will be decided by the users demands, and the direction of the tee valve is decided according to the temperature. When the manual model is started, the start-stop type of pump B1 and B2 and the direction of the tee valve are decided according to users demands. Manual model is set to ensure users can control avoided the problem that there is something wrong with the automatic model. Solar energy Temperature difference control Monitoring and control Demand side of domestic hot water Tee control Gas Demand side of heating hot water Residual heating Fig -5: Schematic diagram of the structure control of system 3.3 Design of Monitoring Software The host computer monitoring system adopted in this system (HMI)is developed by the configuration software (SIMATIC WinCC7.0) of Siemens, and the data archiving is completed by the normal database of Microsoft SQL Server 2000. This software also has the function of a Web browser which can realize remote monitor and adjust the real-time dynamic picture function. The software can communicate with the slave computer by OPC (OLE for Process Control). Main functions of this testing system will be described in the following chapters. (2) Standardize the image design: automatic model and manual mode have been designed according to design principles and unprofessional user s demands. The interface of functional modules is very clear and the buttons is few. It can reduce the invalid operation, disoperation etc. to ensure the system operate security and stability. Monitor the key variables such as temperature and pressure on-line and alarm in time by the built-in alarming function of WinCC. The configuration software will alarm and the B1 circulation pump will be forced to turn off when the export temperature of solar-collector is larger than 95 or less than 5. (1) The simulation of the solar energy-gas coupling system: the design of the interface for the solar energy-gas coupling system will bring the workflow more intuitive to present in front of the users. It includes circulation circuit of heating collection, circulation circuit of the radiant floor heating and circulation circuit of domestic hot water. This paper has developed dynamic results of the critical parts for coupling heating system with WinCC7.0, according to technological requirements and simulates the real-time working state of the entire system. Volume: 04 Issue: 05 May-2015, Available @ http://www.ijret.org 95

(3) The Monitor Interface is Presented As Follows Fig -6: Monitoring interface 3.4 Framework of the Monitoring System The host computer collects the real time date from PLC in this system. The monitoring system mainly includes graphical interface, parameters detection interface, process control and corresponding security mechanism. The structure diagram for the monitoring system is shown in figure 7. Fig -7: The structure of monitoring system Volume: 04 Issue: 05 May-2015, Available @ http://www.ijret.org 96

Temperature/ Gas consumption/m 3 Cooling water/ml IJRET: International Journal of Research in Engineering and Technology eissn: 2319-1163 pissn: 2321-7308 4. THE DESIGN OF SIGNAL SYSTEM AND COMMUNICATION SYSTEM Communication in this monitoring system is mainly composed of two kinds: communicate between the configuration software of WinCC and database; communicate between the configuration software of WinCC and the slave computer (PLC). However, WinCC cannot communicate with PLC directly, the communication can be achieved with OPC. Through connection the configuration software of WinCC and database, WinCC will read directly the date collected by the slave computer to the database, and it is convenient to store and access to the data. It s necessary to build a communication between external variables and the database when WinCC communicates with the date. The external variables in this system mainly include the import and export temperature of the solarcollector, the import and export temperature of the heat medium, the import and export temperature of gas, the flow rate of the solar-collector, etc. We need to import external variables into the software of PC ACCESS to ensure both can communicate normally when WinCC communicating with PLC. And the PPI communication protocol is used between PLC and IPC, 9600 baud rate, RS232 communication mode, the local address 2, serial port address COM2, data bit 8, stop bit 1, the rest is set to default setting. 5. EXPERIMENT MEASUREMENTS AND ANALYSIS Start the software of PLC, and load the relevant program in the CPU of PLC after completing the preliminary inspection work of solar energy-gas coupling system. Then start the configuration software of WinCC, and check if or not the communication between PLC and WinCC is effect. After the communication is normal, enter the main interface of monitoring system, and select manual mode, you can test the relative part is normal or not. And you can switch to manual mode to automatic mode after all equipment can work normally. After switching to the automatic mode, the system will be in accordance with the decision rule of automatic mode to control the action of water pump and tee valve. Now excerpt partial data of gas boiler heating system for the following analysis, and the data record of gas heating loop as shown in Table 1. Table -1: The results of gas heating loop Date Time Supply water Return water Gas consumption Cooling Outside temperature temperature m 3 water ml temperature 15-03-02 9:40:09 33.52 24.82 173 180 13.11 15-03-02 10:00:09 31.23 25.85 117 120 14.21 15-03-02 10:20:09 33.99 26.24 102 100 18.22 15-03-02 10:40:09 40.71 27.88 96 100 19.83 15-03-02 11:00:09 32.42 28.35 86 80 15.27 15-03-02 11:20:09 42.77 27.75 101 80 14.39 This test is the floor radiant heating test of wall-mounted gas boiler in winter, and the specific test process is shown in Fig.8. 80 70 60 Water-supply temperature Return water temperature Outside temperature Gas consumption Cooling water 180 160 140 200 180 160 140 50 120 120 40 30 20 10 100 80 60 40 20 12:20 14:20 16:20 18:20 20:20 22:20 Time 100 80 60 40 20 Fig -8: Process of gas heating loop Volume: 04 Issue: 05 May-2015, Available @ http://www.ijret.org 97

Fig.8 indicates that the consumption of gas and the emission of condensate are more due to the low indoor temperature at the time of the wall-mounted gas boiler has just opened. And then the consumption of gas and the emission of condensate are gradually decreasing with the gas system movement and the indoor temperature increased. Due to the intermittent operation of wall-mounted gas boiler, the supply water temperature swells and subsides while the return water temperature is stable. The detection system measured data, such as temperature, flow rate and so on has a good stability and accuracy form the above data. 6. CONCLUSION Solar energy-gas coupling system can realize 24-hour nonstop running, and it can also take advantages of solar energy minimize the consumption of gas during the day on the premise of guarantee the room comfort. This will lay the foundation for establishing a scientific optimization method of solar energy-gas coupling system through constructing the solar thermal system and wall-mounted gas boiler heating system, overcome the disadvantages of the produced during the separate operation, improve the overall system efficiency, achieve energy conservation and emissions reduction. In this paper obtained the following conclusions: (1) According to the design requirements of solar energy-gas coupling system, the related optimization design of the interface of monitoring system based on the configuration software of WinCC is carried out; users can more intuitive operation and observation the system running state. (2) By analyzing the data from the monitoring system, the stability and accuracy of the system to collect data is verified. This will provide a solid foundation for solar energy-gas coupling system. (3) Combined solar energy and gas has changed the traditional heating mode which is solar energy or wall-mounted gas boiler individual heating, and achieve real energy conservation and emissions reduction, which provides reliable basic data for domestic leading technology of solar energy coupling gas hot water and heating system demonstration project in Shanghai area. [3]. Chen Zhiguang,Qin Chaokui. Analysis of a hybrid water supplying system with solar collector and fuel gas [J]. Acta Energiae Solaries Sinica, 2011, 32(11):1652-1655. [4]. Zhang Chen. Research in Baoding area of solar wall mounted gas boiler heating system [D]. Hebei University, 2014. [5]. Mousa S Mohsen. On integrated solar water heating system [J]. International communications in heat and mass transfer, 2002, 29(1). [6]. Yu Junjie, Zhang Wei. PLC and HMI Applications in the Network Control[J],Control and Instruments in Chemical Industry, 2014, No.3, pp344-346. BIOGRAPHY Xu Hui (1989- ), male, master of engineering, research direction for renewable energy application in buildings. E-mail: 135177974@qq.com ACKNOWLEDGEMENTS This project is sponsored by Shanghai University of Engineering Science Innovation Fund for Graduate Students (No.E1-0903-14-01020) REFERENCES [1]. De Winter F.Energy consumption impacts of backup gas firing efficiency, tank standby losses, and pilot flame energy consumption in two-tank solar-gas DHW systems, subjected to the typical DHW consumption of the single family home [J]. Renewable Energy, 1996, 9 (1-4):714 719. [2]. Sun Jindong, Tong Baohua. Analysis and comparison of performance of residential water heater [J]. Journal of Beijing Institute of Civil Engineering and Architecture, 2004, 20(2):45 49. Volume: 04 Issue: 05 May-2015, Available @ http://www.ijret.org 98