INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER



Similar documents
Electric Water Heater

OTF Oil Fired Pool Heater

CARING FOR YOUR WATER HEATER

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

TURBOPOWER Low NO X WATER HEATER

Boiler and Burner Cleaning and Servicing Specifications

Oil and Coolant Circulating Heating System. Model - OCSM


Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

INDIRECT WATER HEATER. Installation and Operating Instruction Manual

Air Conditioner Water Heater Model ACWH18

OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE

Tankless Water Heater

Trouble Shooting. Pump

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

The Bradford White. Save this manual for future reference. (To be performed ONLY by qualified service providers)

USE & CARE MANUAL. Non-Metallic Electric Water Heater. Residential Electric Models Gallon Capacity

SERVICE MANUAL Order No.WH0911S001V0

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL

INSTALLATION INSTRUCTIONS Air Spring Kit Ford F250/F-350 Single Wheel 2WD Ford F350 Dually 2WD IMPORTANT NOTES

GeniSys 12V. Model Description / Applications. Advanced 12 Vdc Burner Control

Installer s Guide 18-AH39D1-13

SunMaxx Solar Filling Station Operating Instructions

ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL

AMX300 DirectConnect Mixing Valve Kits

SERVICE MANUAL. Flammable Vapor Ignition Resistant Water Heaters. Gas Water Heaters. Troubleshooting Guide and Instructions for Service

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Air Spring Kit Ford F250 Single Wheel 4WD Ford F350 Dually 4WD (2011 F350 Single Wheel 4WD use p/n 6113)

MINI-BRUTE II HOT WATER POWER WASHER MODEL# MBII

LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATER INSTALLATION & OPERATING INSTRUCTION MANUAL

18SP653* EPA04 and EPA98 MBE 4000 High Pressure Fuel Line and Transfer Tube Installation

Installation and Operating Instruction Manual

Fleck Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET

How To Fix A Car With A Carbide Engine

Use & Care Manual. Electric Water Heaters. With Installation Instructions for the Installer. Single and Double Element Models, Gallon

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

CALIFORNIA PROPOSITION 65 WARNING:

INSTANT HOT WATER RECIRCULATING SYSTEM

I N S T A L L A T I O N I N S T R U C T I O N S F O R T H E H i l k o i l Energy S aving Hot Water Kit

Your safety and the safety of others are very important.

PRODUCT: WASHER / WASHER-DRYER COMBO MODEL: AW 120 / AW 122 / AW 125 AWD 120 / AWD 121 / AWD 129

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:

Mini Tank. Electric Mini Tank Water Heaters WM-1.0 WM-2.5 WM-4.0 WM-6.0. Installation and Operating Instruction Manual

SHC 2.5, SHC 4 MINI-TANK ELECTRIC WATER HEATERS INSTALLATION INSTRUCTIONS FOR THE LICENSED PLUMBER SHC 2.5 SHC 4. English. English

Cleaning Instructions for Burner, Pilot Assembly, and Emitter Screen Series:

CHAPTER 9: WATER HEATING

Mini Tank water heater Electric undersink Water heaters GL GL 4 - GL 6+

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

Section 7 Adjustment, Repair and Replacement

Commercial Gas Water Heaters

Water Heaters. Use & Care Manual. Electric Point of Use IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

Service Manual Models: 502, 752, 1002, 1302,

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

2010 Residential Water Heater Replacement Check List

ENGINE FUEL FUEL FILTER... FUEL HEATER... INJECTOR... SUPPLY PUMP... COMMON RAIL... FUEL PRESSURE LIMITTER...

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT CHEVROLET/GMC VANS FOR

PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

CEILING CASSETTE FAN COIL UNIT

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Electric & Gas Water Heaters

UNIT 7: PLUMBING KEY CONCEPTS. 1. Identify tools for plumbing. 2. Location of shutoff valves for the main and individual fixtures

Cooling system components, removing and installing

Cleaning Instructions, Pilot Replacement and Valve Change. Model No.: Natural Gas

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

INSTALLATION AND OPERATION MANUAL DIRECT VENT GAS WATER HEATER

I N S T ALLATION INSTRUCTIONS & HOME OWNERS MANUAL IMPORTANT SAFETY INFORMATION

NITROUS TRANSFER PUMP INSTRUCTIONS

Cooling system components, removing and installing

Fuel Injection Pump, Rotary ( )

Sun Bandit Hybrid Water Heater Installation, Operation and Solar Hybrid Energy Systems Patent(s) Pending

ENGINE COOLING SYSTEM

WINTERIZING YOUR HOME PLUMBING AT BLUE RIDGE SHORES

One Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty

RESIDENTIAL ELECTRIC WATER HEATER OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS

Boiler Plan II Table of Contents

User's Instructions. Alpha HE CB25/33 and HE SY25

Electric Mini Tank Water Heaters WM-2.5 & WM-4.0

Fire Hydrant Troubleshooting

ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL

Evaluate, Clean, and Tune Guidance

Oregon Fuel Injection

OIL-FIRED WATER HEATERS 72E 73E 190E 241E 361E 541E

WATER HEATERS. If your water heater tank is leaking, then your course is clear: buy a new unit. But if it isn t, your answer is less obvious.

Not required for most applications Not required for most applications High pressure ( provided) High pressure ( provided)

Heat Pump Water Heater IOM Manual

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

ASME Packaged Indirect Fired Water Heater

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

REMOVAL AND INSTALLATION

Transcription:

INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER Installation and service must be performed by a qualified service installer, service agency or the gas supplier. Oil Gas/Oil Gas IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, OPERATION AND MAINTENANCE OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL OTHER PROVIDED INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING THIS UNIT. TO THE INSTALLER: After installation, these instructions must be given to the equipment user or left near the appliance. SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain important information that will help you in maintaining and operating this appliance. PVI INDUSTRIES, LLC - Fort Worth, Texas 76111 - www.pvi.com - Phone 1-800-433-5654 PV500-4 08/15

TABLE OF CONTENTS 1. Safety Considerations 2. Typical Construction 3. Typical Mounting of Units 4. Electrical 5. Startup Procedures and Operation 6. Initial Firing and Adjusting of Burners 7. Maintenance 8. Instructions for Removal and Cleaning of TURBOPOWER Module Warranty forms ship separately with each product. 2 PV500-4 08/15

1 SAFETY CONSIDERATIONS TURBOPOWER WATER HEATERS IMPORTANT SAFETY NOTE It takes only 5 seconds of skin contact with 140 F water to cause a second degree burn! You must protect against high water temperatures at all lavatories, tubs, showers and other points of hot water contact. Accidental scalding from high water temperatures is a greater risk in some types of installations. Some examples are: HOMES FOR THE MENTALLY HANDICAPPED HOMES FOR THE PHYSICALLY HANDICAPPED HOSPITALS AND NURSING HOMES ELDER CATE FACILITIES AND REST HOMES ORPHANAGESAND CHILD CARE FACILITIES OTHER INSTALLATIONS WHERE RESPONSE TO CONTACT WITH HOT WATER MAY BE SLOWER OR WHERE THE DANGER OF HOT WATER CONTACT IS GREATER Thermostatically controlled mixing valves must be used in the design of the potable hot water system. Potable hot water should be tempered to no more than 110 F when used for bathing or other personal use. Good engineering practice mandates the use of thermostatically controlled mixing valves set at 120 F to keep the delivered water temperature below scalding temperatures. 3 PV500-4 08/15

2. TYPICAL CONSTRUCTION TURBOPOWER WATER HEATERS Figure 4-1 1. Flue stack * 7. Gas inlet 2. Temperature limiting device 8. Gas line * (set at 200 F) 9. Drip leg * 3. Upper operating thermostat 10. Burner (set at 130 F) 11. Flue collector 4. Operating thermostat 12. Optional rear module access (set at 120 F) 5. Control switch(es) and fuse(s) 6. Gas valve (* Not furnished by PVI) For connection points on oil pumps, see Section 10 or specific burner manufacturer's installation and maintenance instructions. IMPORTANT: Clearances to unprotected combustible material must be 6" minimum at top, sides and rear, and 24" in front. Clearances for servicing and inspection must be 18" minimum at sides and rear and 24" minimum in front. 4 PV500-4 08/15

3. TYPICAL MOUNTING OF UNITS The semi-instantaneous units may be installed as a hanging or wall-mounted unit if desired. Eye bolts or threaded rods can be used suspending the units using the pre-punched slots in the skid runners. See figures 4-2 and 4-3. TYPICAL CEILING MOUNTED UNIT FIGURE 4-2 TYPICAL WALL MOUNTED UNIT FIGURE 4-3 5 PV500-4 08/15

4. ELECTRICAL 1. Wiring to the unit should conform to the National Electrical Code or the code legally authorized in your locality. A fused disconnect switch should be used for water heater control. 120V 1 phase, 60 Hz service wiring connections are located in the enclosure on the water heater. Some models may additionally have high voltage connections located on the burner. NOTE: Use only copper wire of proper sizing for incoming service. Damage resulting from use of aluminum wiring will be excluded from coverage under the warranty of this unit. 2. Be certain that high and low voltages are connected to the correct points; also, check rotation of motors on three phase models. The burners are shipped separately from the heaters and are provided with connecting wires in conduit to be connected after burner is in placed in combustion chamber. Wires and terminal block connections are marked for simplified hookup. 5. START-UP PROCEDURES AND OPERATION CAUTION: Do not relight pilot or start burner with combustion chamber full of gas or oil vapor, or with very hot combustion chamber. 1. The burner manufacturer's installation and service manual start-up procedures for the individual burner on your water heater may be part of this manual or will be shipped with the burner. Study the information carefully and follow the burner manufacturer's recommendations. 2. Because of the many different burners and control systems, the instructions in this section are general information and refer to the water heater with either power gas, oil or combination gas/oil burner installed. 3. Fill the water heater tank with water. Open the relief valve or a nearby hot water faucet to allow air in the tank to escape. Be sure all connections into the tank are tight as leaks at tank fittings will damage the insulation. 4. The thermostats are labeled as to their function. The temperature limiting device is set at 200 F. The thermostats are set at the factory at 130 F on the upper operating thermostat. Adjustment may be made by turning the thermostat dial to the desired temperature. WARNING: Water temperatures over 125 F can cause severe burns instantly or death from scalds. 6. INITIAL FIRING AND ADJUSTING OF BURNER 1. The following procedure is the quickest and best means of starting and adjusting the burner for efficient operation. 2. The following test equipment is required: a. Stack temperature gauge. b. Manometer for checking gas pressure. c. Draft gauge for determining draft in stack. d. CO tester (gas only). e. CO2 tester. f. AC/DC multimeter with a 20,000 ohm/volt DC rating. g. Ammeter. h. Oil pressure gauge (100-350 psi) (oil only). i. Vacuum gauge (0-30" Hg.) (oil only). j. Smoke spot tester (oil only). NOTE: Emergency shutoff can be made by turning off the fuel inlet shutoff valve marked by installing contractor. 3. Drill ¼" test hole in stack approximately 3" from the heater vent connection (before the draft regulator). 4. Refer to start-up instructions for the burner supplied with your appliance. They may be included as part of this manual or may be shipped with the burner. 6 PV500-4 08/15

7 MAINTENANCE 1. A preventative maintenance program should be established to assure a long, trouble-free life of the water heater. 2. To control sediment and scale buildup in the water heater, the tank should be flushed at two- or three-month intervals depending on water conditions in your location. To flush, turn off electrical disconnect switch to prevent the burner from operating. Open the drain valve and allow water to flow through the tank until it runs clear. Close the drain valve and turn the electrical switch on. Between tank flushes, draining two or three gallons from the tank on a weekly basis will also help prevent the accumulation of sediment. 3. A scale of lime will normally form and accumulate in the heater during operation. The lime is formed from the natural chemicals in the water that precipitate out during the heating cycles. Some water supplies contain more of these chemicals than others, and the scale buildup will occur more rapidly. Other factors affecting the scale buildup are the amount of hot water used and the temperature of the water. The more hot water used, the more fresh water containing the scale-forming chemicals is brought into the tank. As the temperature of the water increases, the rate of scale deposited will be increased. Sediment and scale accumulations on heating surfaces will reduce the water heater's ability to transfer heat to the stored water. When the heating energy from the burner cannot be effectively transferred to the water in the tank, the metal will overheat. Overheating will cause the metal in the heating surfaces to overheat and lose structural strength. Over time, this will result in leakage. Since PVI cannot control the use of the water heater, water conditions, or maintenance, the warranty on the TURBOPOWER heat exchanger does not cover poor performance, structural failure, or leaking due to an excessive accumulation of scale. (the tank warranty is not affected by an accumulation of scale.) 4. Should a firetube leak for any reason, consult the factory for instructions. NOTE: Condensate coming from the tubes on a cold start is normal and does not indicate a leaking tube. This condensate will appear at the fitting in the lower part of the flue collector. 5. The tank has an opening suitable for inspection and cleaning use. (See Figures 4-1 and 4-4.) The tank should be inspected for scale buildup through this opening. If scale is present, it can be loosened with a highpressure stream of water. The smaller pieces can be flushed through the drain and the larger pieces removed by hand. The frequency of inspections will be determined by the rate of scale buildup. We recommend 30-60 day intervals. 6. Periodic inspections and check-out of the burner ignition system, control system and fuel valve operation (for tight close-off) should be made. Refer to the burner installation instructions for recommendations. When oil burners are used, the flue tubes and flue baffles should be inspected periodically and cleaned if necessary. A maladjusted oil burner producing excessive smoke will result in soot collecting in the flue tubes. Once sooting starts, it accelerates rapidly and will eventually block air movement through the flue tubes. 7. Examine the venting system at least once each year for proper connections and alignment. Oil the blower motor and wipe oil and dust from the burner at regular intervals. The blower inlet will collect dust from the air during operation. Clean the blower wheel when necessary. The burner should be cleaned each year according to burner manufacturer's recommended procedures. Inspect all parts and make replacements when necessary. Check wiring for loose connections and burned wires. 8. The temperature and pressure relief valve should be checked at regular intervals to determine its condition for safe operation. The openings inside the valve may become inoperative. If the valve does not open and close properly when tested, it must be replaced. Replace relief valve with a like kind or one meeting the requirements stated on the rating decal located adjacent to the relief valve mounting location. CAUTION: The relief valve is a primary safety device. 9. Extended shutdown of the appliance and restarting are as follows: a. Turn off all power on fuel supplies. b. Drain and flush tank as previously discussed. c. Tag power switch(es) that fuel is off and tank is empty. d. Refill tank with water and energize fuel and power switch(es) to restart. Reset all controls and conduct start-up of the appliance as discussed on page 4. 7 PV500-4 08/15

8. INSTRUCTIONS FOR REMOVAL & CLEANING OF TURBOPOWER MODULE NOTE TO OPERATOR This TURBOPOWER unit may be equipped with an efficiency indicator which provides you with information pertaining to the efficiency and cleanliness of the TURBOPOWER heating section. This unique dial indicator is located at the flue outlet of each module. A reading in the green "Efficient Operation" zone indicates that the unit is operating at peak efficiency and the heating surfaces are clean. A reading in the yellow "Marginal Operation" zone indicates the unit is operating at less than peak efficiency because of a build-up of precipitant on the heating surfaces. As a yellow reading occurs, the TURBOPOWER module's heating surfaces should be cleaned to return the unit to its original level of efficiency. Should a reading in the red "Inefficient Operation" zone occur, cleaning of the heating surfaces is mandatory to prevent damage to those heating surfaces. To offer an additional measure of protection, a stack temperature switch may also be installed to shut off the burner should the unit operate in the red zone (500 F) for a prolonged period of time. CAUTION: Bypassing of the stack temperature switch will void all warranties. Refer to Figure 4-4 for removing and cleaning the module. NOTE: On units equipped with rear module access, module cleaning can be accomplished through this opening without removing the module. CAUTION: The TURBOPOWER module is heavy. No attempt should be made to hold, lift or position module without proper equipment capable of handling the weight of the module. 1. Shut off fuel and electrical power supplies. 2. Drain the tank. 3. Disconnect wiring to burner and gas or oil line from burner at incoming union to burner. 4. Remove the four nuts that hold the burner assembly to the module and the bolts that hold the flue collector to the module. Disconnect the stack from the flue outlet on the collector. 5. Carefully remove burner and then flue collector assembly from the module. Pull burner straight out with a slight twisting motion to avoid damaging the combustion chamber refractory material. 6. Remove the bolts on the front tubesheet. Break the seal at the gasket or o-ring from the tank flange and pull the module from the tank. Use extreme caution in handling the module to avoid bending or distorting of the copper fire tubes. 7. The module can now be cleaned with a high pressure hose or an inhibited acid as recommended by your local chemical supplier for removal of scale from the copper. 8. Reinstall the module after it has been cleaned using a new o-ring or gasket. IMPORTANT: The TURBOPOWER module is equipped with special high quality 9/16"-12NC, grade 8 bolts, washers and nuts available only from your PVI representative or directly from PVI. Do not reuse or substitute these special fasteners with similar grade 8 bolts, washers and nuts. Install the flange bolts and nuts with a flat washer under each bolt head and nut. First, snug them in an alternating star pattern. Then, using a calibrated torque wrench, and in an alternating star pattern, tighten the bolts in 2 increments: 95 ft lbs and 145 ft lbs. Use a small amount of silicone RTV to hold the o-ring in place while positioning the module. Apply adhesive sparingly! Contact PVI at 1-800-433-5654 for replacement Fastener Kits and O-Ring Replacement Instructions. 9. When the module is installed, fill the tank with water and check for leaks. 10. Check baffles in the fire tubes. (See Table 4-1.) Position end of baffle even with end of fire tube. 11. Check the insulating seal on the flue collector before replacing in module. The seal on the flue collector is on the edge of the outside diameter where contact is made with the front tubesheet. If damaged, it may be patched with any suitable 400 F insulation material. 12. Reassemble the unit in the same order it was disassembled and return to service. 8 PV500-4 08/15

REMOVAL & CLEANING OF TURBOPOWER REMOVABLE MODULE Figure 4-4 INPUT MBtu/h TURBOPOWER WATER HEATER FLUE BAFFLE LENGTHS GPH Oil 200 1.4 300 2.1 400 2.8 500 3.6 600 4.3 700 5.0 800 5.7 1000 7.2 1200 8.6 1600 11.4 2000 14.3 2400 17.1 2800 20.0 3200 22.8 Table 4-1 FLUE BAFFLE QTY & LENGTH GAS & GAS/OIL OIL 9 PV500-4 08/15

Since PVI cannot control the use of the appliance, water conditions, or maintenance, the warranty on the heat exchanger does not cover poor performance, structural failure, or leaking due to an excessive accumulation of scale MODEL NUMBER: SERIAL NUMBER: INSTALLATION DATE: PVI Industries, LLC 3209 Galvez Ave. Fort Worth, TX 76111 1-800-433-5654 www.pvi.com 10 PV500-4 08/15