Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable



Similar documents
HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems

How to Choose the Right Cable Category

Data Communications Competence Center

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

Ethernet Patch Cord Wiring

Network Design. Yiannos Mylonas

100BASE-SX Fast Ethernet:

with Component Rating A Simple Perspective

CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER

Panduit 28 AWG Patch Cords Installation Guideline

Accelerating Light. Copper Cabling Solutions. Category 6A

White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel

Chapter 4 Connecting to the Internet through an ISP

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

Cabling Standards Update 2014

Implementing Fast Ethernet

The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges

10 Gigabit Ethernet over copper: Unshielded, unprotected?

How To Get 40G Over Copper (Wired) And 40G On Coaxian (Wireless) Cable (Wired Coaxian) (Wired Cable) (Wireline) (Powerline) And 50G Over Coaxian Cable (Wire Coaxian

SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8

Total Solutions Verification

Security & Surveillance Cabling Systems

The Next Generation of Cable Technology. A technology primer from NORDX/CDT By, Eric d Allmen

Specifying an IT Cabling System

Ethernet 102: The Physical Layer of Ethernet

Things You Must Know About Gigabit Ethernet 1. Understanding Gigabit Ethernet

Fast Ethernet and Gigabit Ethernet. Computer Networks: Fast and Gigabit Ethernet

10GBASE-T SFP+ Transceiver Module: Get the most out of your Cat 6a Cabling

Gigabit Ethernet on Copper Cabling Infrastructures

IT Cabling Solutions

Networks. The two main network types are: Peer networks

Fast Ethernet and Gigabit Ethernet. Networks: Fast Ethernet 1

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

Innovative Connectivity Solution for Maximum Performance and Security

Gigabit Ethernet: Architectural Design and Issues

Trends and Standards in LAN Cabling Systems Intelligent Buildings

Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices

Optimizing Infrastructure Support For Storage Area Networks

Ethernet/IEEE evolution

White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems

10GBASE T for Broad 10_Gigabit Adoption in the Data Center

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

The High Cost of a Low-Cost Cable Certification Tester

PANDUIT TX6 10GIG SHIELDED COPPER CABLING SYSTEM. Innovative Connectivity Solution for Maximum Performance and Security

Power over Ethernet with Panduit Copper Cabling

1000BASE-T: Gigabit Ethernet. over Category. 5 copper. cabling. Acronyms and abbreviations

Christopher Rathgeb ECE 453 Dr. Qi 9/19/2006. Task 1: Make an Ethernet cable yourself.

Category 8 Cabling Standards Update

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

INTRODUCTION TO 100BASE-T: FAST (AND FASTER) ETHERNET

Structured and Point to Point Network Cabling for Industrial Automation

Data Center Architecture with Panduit, Intel, and Cisco

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

Trends In Data Rate And Link Length In Evolving Optical Standards

Top of Rack: An Analysis of a Cabling Architecture in the Data Center

Feasibility Study on High Speed Transmission over UTP Cables

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village

A Comparison of Total Costs of Ownership of 10 Gigabit Network Deployments in the Data Center

Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka

How To Plan A Data Center Network

Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network

Broadband 101: Installation and Testing

Discussion Paper Category 6 vs Category 5e Cabling Systems and Implications for Voice over IP Networks

White Paper. Power over Ethernet Plus Update and Cabling Considerations

SMARTen 24 UTP Patch Panels

Network Cabling Guide

Copper Patch Cords. Impact On Network Performance and Reliability

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

Trends and Standards In Cabling Systems

Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek

How To Get A Better Signal From A Fiber To A Coax Cable

Gigabit Switching Ethernet Media Converters - Product User Guide

PROFINET Diagnostics Software and Tools

Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk

HP ProCurve High-Speed Transceivers Installation Guide

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

10/100/1000BASE-T SFP Transceiver

High Speed Ethernet. Dr. Sanjay P. Ahuja, Ph.D. Professor School of Computing, UNF

40/100 Gigabit Ethernet: The Foundation of Virtualized Data Center and Campus Networks

BICSI :Building Industry Consulting Service International

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT

TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report

Enhanced Category 5 Cabling System Engineering for Performance

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

WHITE PAPER December, 2001

The Need for Low-Loss Multifiber Connectivity

Industry Standards Activity Overview

Transcription:

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable June 10, 2010 Contributors: Yinglin (Frank) Yang CommScope, Inc. Charles Seifert Ixia Ethernet Alliance 3855 SW 153 rd Drive Beaverton, OR 97006 www.ethernetalliance.org 1

Table of Contents Introduction... 2 Executive Summary... 3 Methodology... 4 Testing Configurations and Equipment... 5 Conclusions... 8 Glossary... 8 Introduction As the market adoption of 10 Gigabit Ethernet (10GbE) continuously increases, more customers are deploying Category 6A/ A Unshielded Twisted Pair (UTP) cabling on top of Category 6/ UTP cabling. UTP cabling is the most widely deployed media around the world, supporting both data and voice applications. Even after the 10GBASE-T standard (IEEE Std. 802.3an TM -2006) was ratified with Category 6A/ A UTP cabling as one of the supporting media, there are still discussions in the marketplace regarding assumptions and unanswered questions. Two frequently asked questions are: 1. Can Category 6A/ A UTP cable be mixed with Category 6/ UTP cable in the same bundle? 2. Can 10GBASE-T Ethernet applications co-exist in structured cabling bundles with 1000BASE-T Ethernet applications? These questions are the primary concerns of many customers considering installation of Category 6A/ A UTP cabling and deployment of 10GBASE-T technology. CommScope, Inc, a leading manufacturer of structured cabling systems, and Ixia, a leading manufacturer of Ethernet network testing equipment, are committed to fulfilling customer s needs and facilitating market adoption of 10 Gigabit Ethernet. CommScope and Ixia collaborated to address the reality of mixed-speed Ethernet running over different categories of bundled UTP copper cabling. This white paper summarizes the details from testing worst case scenarios, methodology, system configurations, and equipment. It also addresses the concerns and unanswered question with test data, interpretations, and conclusions. Finally, it presents the reality and value to end-users, designers, consultants, integrators, and installers of Ethernet LAN and structured copper cabling systems. June 10, 2010 Page 2

Executive Summary There are many possible combinations of mixed-speed Ethernet running over different categories of bundled UTP copper cabling. The four worst case scenarios identified for testing are listed in Table 1. The six-around-one configuration is utilized with six Disturber cabling channels bundled around one Victim cabling channel. The Bit Error Ratio (BER) test is conducted on the Victim cabling channel while active traffic is running over the six Disturber channels. The Bit Error Rate (BER) is the ratio of bits received with error to the total number of bits transmitted. All 10G Ethernet PMDs/PHYs including 10GBASE-Tspecifies the same 10-12 BER. The BER test is a Pass when the BER is either zero or less than 10-12 for a statistically acceptable period of time. Table 1 summarizes the BER test results, cable categories and Ethernet speeds for each scenario. Measured BER of Victim BER Test Duration Victim Disturber 1-3 Disturber 4-6 CAT-6A/ A CAT-6A/ A 1 CAT-6/ Scenario 1 0 19 hr 44 min 10GBASE-T 10GBASE-T 10GBASE-T CAT-6A/ A CAT-6A/ A CAT-6/ Scenario 2 0 17 hr 33 min 10GBASE-T 10GBASE-T 1000BASE-T CAT-6A/ A 1 CAT-6/ 1 CAT-6/ Scenario 3 0 18 hr 29 min 10GBASE-T 10GBASE-T 10GBASE-T CAT-6A/ A 1 CAT-6/ CAT-6/ Scenario 4 0 8 hr 35 min 10GBASE-T 10GBASE-T 1000BASE-T 1 Note: when using Category 6/ cabling runs for 10GbE, the channel length is reduced 55 meters or less in accordance with IEEE 10GBASE-T, ISO TR 24750, and TIA TSB-155-A specifications. The test results in Table 1 prove that 10GBASE-T Ethernet as an application running over the Victim Category 6A UTP cabling channel meets or exceeds the IEEE 10GBASE-T BER requirement, while mixedspeed Ethernet (10GbE or 1GbE) runs over the adjacent cables using different cabling categories (Category 6A/ A or Category 6/). So to answer the questions in the Introduction: June 10, 2010 Page 3

Yes, Category 6A/ A UTP cable can be mixed with 1 Category 6/ UTP cable in the same bundle Yes, 10GBASE-T Ethernet applications can co-exist in structured cabling bundles with 1000BASE-T Ethernet applications. Methodology The key concern in the questions stated in the Introduction is alien crosstalk between UTP cabling channels in close proximity to each other. Alien crosstalk is the electromagnetic noise that a cabling channel receives from adjacent cabling channels. If alien crosstalk noise is accumulated to a high enough level it could result in creating errors in network traffic or even the fatal problem of bringing the Ethernet link down, which has many upstream consequences for the IT Infrastructure manager. As UTP cable doesn t have the metallic shielding layer found in Foiled Twisted Pair (FTP) and Screened Twisted Pair (STP) cable, it is fair to raise a question about the capability of UTP cabling to meet alien crosstalk requirements. One way to uncover alien crosstalk is to directly measure it and see if it is within the specifications defined in the ISO/IEC 11801 and ANSI/TIA- 568 standards. A meet spec channel performance is a guarantee that the passive cabling channel is clean and ready for Ethernet transmission. A limitation of measuring alien crosstalk performance is that it only covers the passive portion (the cabling) of a transmission system. It doesn t include the active portions, which are the electronic transceivers at the two ends. A more comprehensive method is to measure the Bit Error Ratio (BER) of a real network transmission system. The BER tests measure the performance of transceivers and cabling channel, plus the PHY and MAC of the link partners on the transmission channels. The Bit Error Ratio (sometimes called Bit Error Rate) is the ratio of bits received with error to the total number of bits transmitted. The IEEE 802.3an- 2006 standard, 10GbE Ethernet over twisted pair cable or 10GBASE-T, specifies a 10-12 BER. The 10-12 BER is defined as one or zero bits received with an error out of 1,000,000,000,000 (one trillion) bits transmitted. The 10-12 BER is specified in the IEEE standards for 10GbE and 1 Gigabit Ethernet (1GbE) over either fiber optic or balanced twisted pair copper media. The 10-12 BER is also adopted by many other standards outside of IEEE, such as INCITS Fibre (T11) representing 10Gigabit Fibre. In brief, the 10-12 BER is the key criteria to assess if a 10GbE Ethernet transmission system works properly or not. The method of measuring BER is chosen from the tests described in this white paper. In order to create a worst case alien crosstalk scenario, the six-around-one cabling bundle configuration is utilized. The six-around-one configuration as shown in Figure 1 is specified in ISO/IEC 11801 amendment 1 and ANSI/TIA- 568-C.2 standards. Each aqua-colored circle in Figure 1 denotes the cross-section of a UTP cable with four pairs of conductors wrapped in the jacket. The solid color and white dots represent a twisted pair. The colors blue, orange, green, and brown match the colors of the twisted pairs in a real cable. June 10, 2010 Page 4

Figure 1 illustrates the Victim cabling channel in the center that receives the alien crosstalk noise generated from the all adjacent Disturber channels. The alien noise level of the Victim channel is the highest among all of the channels in the bundle. The Victim channel has the worst case scenario in terms of alien crosstalk noise coupling. Figure 1 Six-around-one cable bundle configuration The BER tests are conducted on the Victim cable while continuous network traffic runs over the Disturber cabling channels. The tests described in this white paper are conducted using CommScope Category 6A/ A and Category 6/ cabling solutions. All tests are also repeated on the equivalent cabling products from another UTP manufacturer. The purpose is not to show whose products are better, but to demonstrate if the testing results are consistent across different manufacturers products. Testing Configurations and Equipment The testing system configuration is illustrated in Figure 2. A pair of IXIA 400T chassis with 10GbE Load Modules are connected through the Victim channel. The IXIA 10GbE Load Modules can generate full duplex 10Gb/s Ethernet traffic at wire speed at the standard XAUI interface. The pair of PHY evaluation boards (EVKs) converts the Ethernet traffic to the 10GBASE-T layer 1 signals and send out over the victim cabling channel. Meanwhile, the IXIA Load Module can monitor, measure, and analyze the traffic in real time. The IXIA 10GbE equipment is utilized as the bit error ratio test (BERT) measurement system. June 10, 2010 Page 5

Lucent PATCHMAX Lucent PATCHMAX Lucent PATCHMAX Six pairs of EVKs are utilized to generate continuous 10GBASE-T layer 1 patterned signals over the six Disturbers cabling channels. Whenever 1GbE traffic is needed for certain tests, 1000BASE-T network interface cards are utilized over the six Disturber cable channels. The network signals in the Disturber channels are used as the alien crosstalk noise for the IXIA 10GbE system to measure the BER s on the Victim cable. All of the Victim and Disturber cabling channels have a three embedded connection configuration as shown in Figure 3. A connection is defined as a mated combination of an RJ45 jack and an RJ45 plug. The three connection channel configuration is the most commonly seen configuration in data centers. As shown in Figure 3, a structured cabling system includes patch cords, RJ45 jacks and plugs, and a horizontal cable. All of the Category 6A/ A cabling channels used in the test are 100 meters in length from end to end. The Category 6/ channels used to run 1GbE are 100 meters long. However, when using Category 6/ cabling runs for 10GbE, the channel length is reduced 55 meters or less in accordance with IEEE 10GBASE-T, ISO TR 24750, and TIA TSB-155-A specifications that will sustain stable 10GbE Ethernet operations. Patch Panel Patch Panel Patch Panel Patch Cord 1 Patch Cord 2 Horizontal 3 Patch Cord 3 Three connection cabling channel configuration Cable Figure Within any cabling channel of the Victim or the six Disturbers, all the cabling components have the same category rating from end to end. This ensures that a Category 6A/ A channel is constructed with Category 6A/ A cable and apparatus. Similarly, a Category 6/ channel is constructed with Category 6/ components from end to end. There is no mixing of different category June 10, 2010 Page 6

components within a channel. The mixture of different cabling categories occurs in a bundle, not within a channel. In order to mimic the deployment of different category cables in a real world network for mixed speed Ethernet applications, the four testing scenarios are created as shown in Table 2. Description Victim Disturber 1-3 Disturber 4-6 Scenario 1 Scenario 2 Scenario 3 Scenario 4 Represent CAT-6A cabling channels that may exist in close proximity to CAT-6 channels. All of the channels run 10GBASE-T Ethernet. Measure the BER of 10GbE over the Victim Represent CAT-6A cabling channels that may exist in close proximity to CAT-6 channels. The CAT-6A channels run 10GbE while the CAT-6 channels run 1000BASE-T. Measure the BER of 10GbE over the Victim Represent more CAT-6 cables that may exist in close proximity to CAT-6A cables. CAT-6 cable generally has a smaller diameter than CAT-6A cable. When CAT- 6 cables run 10GBASE-T Ethernet, it is the extreme case in terms of alien crosstalk. Measure the BER of 10GbE over the Victim Represent more CAT-6 cables that are deployed in close proximity to CAT-6A cables. Some of the CAT-6 cables run 10GBASE-T while others run 1000BASE- T. Measure the BER of 10GbE over the Victim A A 1 CAT-6 / 10GBASE-T 10GBASE-T 10GBASE-T A A CAT-6 / 10GBASE-T 10GBASE-T 1000BASE-T A 1 CAT-6 / 1 CAT-6 / 10GBASE-T 10GBASE-T 10GBASE-T A 1 CAT-6 / CAT-6 / 10GBASE-T 10GBASE-T 1000BASE-T Table 2 Testing scenarios 1 Note: when using Category 6/ cabling runs for 10GbE, the channel length is reduced 55 meters or less in accordance with IEEE 10GBASE-T, ISO TR 24750, and TIA TSB-155-A specifications. The consistent BER test results are observed across both manufacturers products. June 10, 2010 Page 7

Conclusions An increasing number of 10GBASE-T products have entered the market. Users and designers have been evaluating the appropriate cabling media to support 10GBASE-T technology. Category 6A/ A and 1 Category 6/ UTP cables can be installed in close proximity or even in the same structured bundle. The 10GbE Ethernet application over Category 6A/ A cable will not be impacted by the 1GbE Ethernet application over Category 6/ UTP cable, and vice versa. Therefore, based on the BER tests, no issues or problems are found when mixing high-speed Ethernet operations over different categories of bundled UTP cable. About Ethernet Alliance The Ethernet Alliance is a community of Ethernet end users, system and component vendors, industry experts and university and government professionals who are committed to the continued success and expansion of Ethernet. The Ethernet Alliance brings Ethernet standards to life by supporting activities that span from incubation of new Ethernet technologies to interoperability demonstrations, certification and education. Glossary Category 6A: Telecommunications cabling or cabling components that are specified up to 500 MHz. The set of standards are managed under Telecommunication Industry Association (TIA) A : Telecommunications cabling that is intended to support a class of applications that use bandwidth up to 500 MHz. The set of standards are managed under International Organization for Standardization/International Electrotechnical Commission (ISO/IEC) Category 6: Telecommunications cabling or cabling components that are specified up to 250 MHz. The set of standards are managed under Telecommunication Industry Association (TIA) : Telecommunications cabling that is intended to support a class of applications that use bandwidth up to 250 MHz. The set of standards are managed under International Organization for Standardization / International Electrotechnical Commission (ISO/IEC) ISO/IEC 11801: Information technology - Generic cabling for customer premises ANSI/TIA- 568-series: Telecommunications Cabling Standard June 10, 2010 Page 8

ISO/IEC 11801 amendment 1: Information technology - Generic cabling for customer premises amendment 1 ANSI/TIA- 568-C.2: Commercial Building Telecommunications Cabling Standard; Part 2: Balanced Twisted-Pair Cabling and Components ISO TR 24750: Information technology Assessment and mitigation of installed balanced cabling channels in order to support 10GBASE-T TIA TSB-155-A: Guidelines for the Assessment and Mitigation of Installed Category 6 Cabling to Support 10GBASE-T, 2007: Physical Layer and Management Parameters for 10Gb/s Operation, Type 10GBASE-T PMD: Physical Medium Dependent sub-layer PHY: Physical Layer Device June 10, 2010 Page 9