Outline. Objective. Overview Sanitary Drainage System. Design. Materials



Similar documents
BUILDING SEWER CONNECTION REQUIREMENTS

CHAPTER 11 STORM DRAINAGE

CHAPTER 11 STORM DRAINAGE

Sanitary Sewer Service Guide Information you need to know about sanitary sewer service and how to prevent sewer backups

DIVISION OF WATER QUALITY CONSTRUCTION GRANTS & LOANS SECTION FAST TRACK AUDIT CHECKLIST

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

SRA-125/SRAX-125 Double-Rail Lift-Out Rail System Installation & Service Manual with Parts List

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH Purpose and Application.

Fats, Oil and Grease. Best Management Practices Manual. Information, Pollution Prevention, and Compliance Information For Food Service Facilities

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

SEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

MUNICIPAL WASTEWATER PUMP STATION DESIGN PROBLEMS AND SOLUTIONS

Chapter 9 Sanitary Sewers

Town House Center Highway North Huntingdon, PA 15642

MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS

Beacon Hill Sewer District Standard Specifications

Element D Services Plumbing

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

SANITARY SEWER SPECIFICATIONS

SECTION STORM DRAINAGE SYSTEM

SECTION 3 SANITARY SEWER DESIGN

SUFFOLK COUNTY DEPARTMENT OF HEALTH SERVICES TOXIC/HAZARDOUS MATERIAL TRANSFER FACILITY DESIGN GUIDELINES

Wilo SP Series Submersible Sump Pumps ECS. ECS ECS ECS Installation and operating instructions

SECTION FACILITY STORM DRAINAGE PIPING

SEPTIC SYSTEMS. 1. Building sewer connects the building plumbing to the septic tank.

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

How To Maintain A City Sewer System

Prevention through Design: Eliminating Confined Spaces and Minimizing Hazards

Suffolk County Department of Health Services. Division of Environmental Quality

1. Conductivity < 15 micro ohms/cm 2. ph of 6.0 to Nonvolatile TOC content < 1.0 ppm

SECTION STORM DRAINAGE TABLE OF CONTENTS

Guidelines for Precast Concrete Grease Interceptors

PMA ONLINE TRAINING Venting for Plumbing Systems

Wastewater Collection System Supplemental Design Standards for Capital Improvement Program Projects

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES SITE UTILITIES

PLUMBING ROUGH IN INSPECTION

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

Understanding and Caring for Your Septic System

ATTACHMENT 12 CONTAINERS

APWA: shall refer to the American Public Works Association. ASTM: shall refer to the American Society for Testing and Materials.

GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS AND INTERCEPTORS

Top 10+ Mistakes of DWV plumbing design

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

Terry Biederman, PE- Director of Public Works Greg Gucwa, PE- Principal Johnson and Anderson Engineering

Please also see 10 golden rules for correct Saniflo installation on

Checklist for plans to Construct, Alter or Repair An Individual Subsurface Sewage Disposal System

Design Specifications & Requirements Manual

LS 2540 SEWER LATERALS AND INSPECTION TEES

Oil and Coolant Circulating Heating System. Model - OCSM

Village of St. Louis Sewer Back-up Policy

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

RULE ORGANIC COMPOUNDS - WASTEWATER COLLECTION AND SEPARATION SYSTEMS

DIVISION 4300 STORM DRAINAGE

SECTION STORM DRAIN SYSTEM

Sewage Compliance Form Instructions

Improper storage of potential pollutants will increase the risk of water pollution that may occur because of spills.

CITY OF GOLDEN DEPARTMENT OF PUBLIC WORKS, ENVIRONMENTAL SERVICES DIVISION

SANITARY & WASTE WATER PUMPING SYSTEMS. Now you can install kitchen, bathroom, laundry and commercial facilities almost anywhere.

Crawford Inspection Services C.C.B. #

San Antonio Water System Standard Specifications for Construction ITEM NO SLIP-LINING SANITARY SEWERS

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT

Florida Department of Environmental Protection

SHORELINE SANITATION

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

National Precast Concrete Association

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor

THE CORPORATION OF THE CITY OF COURTENAY BYLAW NO A bylaw to amend Storm Sewer Bylaw No. 1402, 1986

General Information. Applications

Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL

State of Connecticut Department of Public Health RADON PROGRAM

31. ECO-INFO -- SEPTIC SAFE PROTECT YOUR HEALTH AND ENVIRONMENT YOUR SEPTIC PUMP-OUT SYSTEM with SELF ASSESSMENT TROUBLE SHOOTING GUIDE

Design of Sewage Pumping Stations by John Zoeller, PE, CEO/President

LOADING DOCK EQUIPMENT. A. Section Concrete Forms and Accessories: Placement of anchors into concrete.

R E S I D E N T I A L H O U S I N G

How To Make A House Safe

Specifications for Residential Property Owners Connection to New Public Sewer

Module 7: Hydraulic Design of Sewers and Storm Water Drains. Lecture 7 : Hydraulic Design of Sewers and Storm Water Drains

Improper storage of fuel on construction sites will increase the risk of water pollution that may occur as a result of leaks or spills.

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

SWIMMING POOL, SPA, & HOT TUB GUIDELINES

Medical Air Systems: Scroll

Backup Sump Pump Systems. 1 NEXT

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

DRY CLEANING PLANTS REQUIREMENTS FOR INSTALLATION AND OPERATION

Vision Home Inspection

Hazardous Waste Accumulation, Storage, & Labeling

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

Jay R. Smith Mfg. Co.

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

A HOMEOWNERS GUIDE ON-SITE SEWAGE MANAGEMENT SYSTEMS

DISTRIBUTION PIPING MATERIALS: BUILDING HYDRONIC SYSTEM MANAGEMENT. Jim Riley, Texas A&M University February 10, 2015

CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN

HELIPORT FUEL/WATER SEPARATOR MODEL H-200

MODEL INSTALLATION INSTRUCTIONS

Conlift1, Conlift2, Conlift2 ph+

Transcription:

1

Outline Objective Overview Sanitary Drainage System Standard References Design Materials 2 SAWEA) Workshop 2010

Objective Address the minimum requirements for Sanitary Sewers System that are located in Saudi Aramco facilities 3

General Overview of Sanitary Drainage System 4

Overview of Sanitary Drainage System Business Residence Manhole Vent Vessel Manhole Vessel Air gap Funnel s Cleanout Catch Basin Cleano ut Water Seal Water Seal CB Manhole Manhol e C B Vent Wate r Seal Local Main Sewer Line Manh ole Pumps Force Main Pipe CB Typical Catch Basin (CB) Pump Bases Water Treatment Plant Oily Water Lift station 5 SAWEA) Workshop 2010 5

Sanitary Drainage System Sewer Line Building Typical Manhole

References Saudi Aramco Engineering Standards SAES-A-104 SAES-B-068 SAES-G-005 SAES-H-002 SAES-H-003 SAES-L-105 SAES-M-006 SAES-Q-001 SAES-S-020 SAES-S-060 SAES-S-070 SAES-Z-004 Wastewater Treatment, Reuse & Disposal Electrical Area Classification Pumps Internal and external Coatings Coating Requirements for Concrete Surfaces Piping Material Specifications Security and General Purpose Fencing Design and Construction of Concrete Structures Industrial Drainage and Sewers Plumbing Code Installation of Utility Piping Systems Supervisory Control and Data Acquisition (SCADA) System. 7

References Saudi Aramco Materials System Specifications 01-SAMSS-029 01-SAMSS-034 12-SAMSS-024 RTR (Fiberglass) Sewer Pipe and Fittings for Gravity Flow RTR(Fiberglass) Pressure Pipe and Fittings Fiber-Reinforced Plastic (FRP) Manhole and Access Covers with Frame 8

References Saudi Aramco Standard Drawing AB-036380 Sanitary Sewer Manhole Precast Concrete Plan, Section and Detail Saudi Aramco General Instruction GI-0151.006 Implementing the Saudi Aramco Sanitary Code 9

References Industry Codes and Standards American National Standards Institute ANSI A14.3 Safety Requirements for Fixed Ladders American Society for Testing and Materials ASTM A53 Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless ASTM D1785 PVC Plastic Pipe, Schedules 40, 80, and 120 ASTM D2564 Solvent Cements PVC Plastic Piping Systems ASTM D2665 PVC)Plastic drain, Waste, and Vent Pipe and Fittings ASTM D2855 Making Solvent Cemented Joints with PVC Pipe ASTM D3212 Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals ASTM D3311 Drains, Waste, and Vent (DWV) Plastic Fittings Patterns ASTM D3350 Polyethylene Plastics Pipe and Fittings Materials ASTM F585 Insertion of Flexible Polyethylene Pipe into Existing Sewers 10

Wastes Prohibited for Discharge into Public Sewers Rain water, surface water, ground water, roof run-off, subsurface drainage, or cooling water 11

Wastes Prohibited for Discharge into Public Sewers Unpolluted industrial process water Liquid or vapor having a temperature more than 65 C (149 F). Water or waste containing more than 100 parts per million by weight of animal fat, vegetable fat, oil, or grease. Hydrocarbon solids, liquids or gases or any other flammable or explosive solids, liquids or gases. Any garbage that has not been properly shredded. 12

Pipe clogged due to chemical waste 13

Pipe damaged due to high temperature liquid or vapor Waste 14

Wastes Prohibited for Discharge into Public Sewers Ashes, cinders, sand, mud, straw, shavings, metal, glass, rags, feathers, tar, plastics, wood, paunch manure, or any other solid or viscous substance capable of causing obstruction to the flow in sewers or causing other interference with the proper operation of waste disposal facilities. waters or wastes having a ph lower than 5.5 or higher than 9.0 or having any other corrosive property capable of causing damage or hazard to structures, equipment, and personnel associated with the waste disposal facilities. 15

Wastes Prohibited for Discharge into Public Sewers Waters or wastes containing a toxic or poisonous substance in sufficient quantity to injure or interfere with any sewage treatment process. Any noxious or malodorous gas or substance that is capable of creating a public health impact. 16

Sizing Gravity Public Sewers Each gravity public sewer shall be designed to carry the Peak Flow Rate (PFR) Peak Flow Rate (PFR) which is the average flow rate (AFR) multiplied by the appropriate peaking factor (PF) 17

Sizing Gravity Public Sewers Peak Flow Rate (PFR) = Average Flow Rate (AFR) X Peaking Factor (PF) The Average Flow Rate (AFR) shall be determined for each building or facility served. Peaking factors (PF's): For an AFR from 0 to 24,000,000 liters per day: PF = (0.00163)(AFR)² - (0.08790)(AFR) + 2.90 18 For an AFR >24,000,000 liters per day: Use PF = 1.73

Sizing Gravity Public Sewers Gravity public sewers shall have the following characteristics: The minimum velocity shall be 0.77 m/s (2.5 ft/s) at 75% of full flow rate. The slope should be continuously down hill, without low points or high points. The maximum depth-of-flow shall not exceed 75% of the internal pipe diameter at the applicable PFR. 19

Gravity Public Sewers The minimum size of a public sewer shall be 200 mm (8 inch) nominal diameter Public sewers shall be laid in a straight line between manholes 20

Gravity Public Sewers Pipe shall not reduce in size in the direction of flow 21

Gravity Public Sewers DWV (drain, waste and vent) type fittings shall be used in gravity flow system 22

Gravity Public Sewers No elbows, wyes, or other fittings that change the direction of sewers between manholes shall be permitted 23

Gravity Public Sewers The maximum distance between manholes for public sewers shall be 90 meters (295 feet) No portion of a sewer system and no discharge from a sewer system shall be located within 15 meters (50 feet) of any well, spring, or other source of potable water supply 24

Gravity Public Sewers Public sewers that are parallel to potable water lines shall be separated from such lines by a minimum distance of 3 m Public sewers be located below the potable water lines 25

Sanitary manholes shall have a minimum inside diameters: 1.2 m for straight run manholes with a pipe diameter size of 600 mm or less 1.8 m for straight run manholes for pipes larger than 600 mm diameter 1.8 m for junction manholes 26

Gravity Public Sewers The building sewer point of connection shall be 0.6 m (2 feet) from the building external wall 27

Lift Stations Lift stations receives 1800 cubic meters per day (475,560 gallons per day) or larger flows based on daily AFR shall be: Wet well/dry well type and shall be housed in a building Shall have odor / ventilation control 28

Lift Stations Pumps Lift stations shall use two or more pumps The group of pumps shall consist of an operating pump or a group of equal capacity operating pumps, and one equal capacity standby pump All pumps shall be specifically designed for pumping sewage and shall be capable of passing a 75 mm (3 inch) sphere Pumps shall be nonclog type 29

Lift Stations Pumps Pumps with suction lifts are prohibited. Exception Self-Priming Pumps for small lift stations (under peak flow rate of 475,000 gallons per day) can be used as specified below: Maximum suction lift 6 meters (20 feet) between low-low liquid level and pump centerline 30

Lift Stations Pumps Submersible pumps for small lift stations (under peak flow rate 475,000 gallons per day) 31

Lift Stations Pumps Submersible pumps for small lift stations shall have the following additional requirements: 316 stainless steel guide rails and chain for maintenance removal. Steel monorail and manual hoisting equipment to facilitate removal of the pumps Two separate upper and lower mechanical seals with moisture detector between seals Rag removal by bar screen or in-channel grinder on wet well inlet, or grinder (chopper) pump on 50 mm (2 inch) discharge pumps 32

Lift Stations Pumps Open drive shaft pumps and motors with enclosed type drive shafts are not acceptable The pumps shall be spaced to prevent vortexing cavitations when the pumps are operating It shall be possible to remove the pumps without disturbing the discharge piping Bolted-down steel hatches shall be provided for the removal of each pump and for personnel ingress/egress into the wet well 33

Lift Stations Wet Well Operating Volume Sizing Wet well operating volume shall be sized to the following equation: V = C T (Q)/4 Where: V = minimum required capacity m³ (gallons) C T = minimum time in minutes of one pumping cycle between successive motor starts (Minimum CT shall be 15 minutes) Q = pump capacity, m³/min (gallon/minute) 34

Wet well lift stations volume design The wet well volume must include enough volume To prevent suction vortexing with at minimum of 0.5 meter (1.64 feet) vertical distance between the pump intake and the bottom of the operating volume For controls to operate properly For high-level alarms 35

Wet well lift stations High liquid level shall be at least 300 mm (12 inch) below the invert of the lowest incoming sewer A corrosion resistant access firmly affixed to the interior wet well wall. Ladders shall be handrail type that meets ANSI A14.3 Grab bars are prohibited. Ladder shall be of fiberglass material or plastic coated aluminum. 36

Wet well lift stations Shall be of air tight construction Shall have a minimum size of 75 mm (3 inch) gooseneck vent Vent shall terminates not less than 3 m above the lift station deck level Emergency pump connections shall be provided on the inlet sewer and on the force main 37

Wet well Lift Stations Concrete shall have a minimum compressive strength of 35 MPa (5000 psi) for water retaining structures Steel reinforcing bars in concrete shall be epoxy coated Electrical and electronical equipment and wiring shall be suitable for Class I, Zone 1 Wet well ends /corners shall be sloped 10 degrees and the floor slop shall be not less than 1:65 (1.5%) to the pump intakes and have a smooth finish. 38

Wet Well/Dry Well Lift Stations The dry well shall have a forced ventilation system The dry well shall have an automatic sump pump with a standby pump that returns spills or wash-down water to the wet well The dry well deck shall have removable access covers for the removal of pumps and/or motors 39

Wet Well/Dry Well Lift Stations Pump motors shall be Totally Enclosed Fan Cooled (TEFC) Pumps shall non-clog The drive shaft shall have safety guards The drive shaft shall have intermediate bearings with structural supports as required to prevent excessive vibration Stainless steel greasing tubing shall be provided to grease any intermediate bearings 40

Lift Stations Power Supply Each lift station shall have two independent power supply sources, each fed from separate transformers The power supply sources shall be interconnected with an automatic transfer switch to provide a continuous source of power to the lift station. Emergency generator may also be used as a second power source. 41

Lift Stations Control Systems Control systems shall consist of Wet well liquid level sensing devices A motor control panel An alarm system 42 SAWEA) Workshop 2010

Lift Stations Control Systems Sensors for a duplex pump system shall be set to provide the following: a) Low Level Sensor: All pumps off b) First Level Sensor: Lead pump on c) Second Level Sensor: Both pumps on d) High Level Sensor: Actuate high level alarm 43

Lift Stations motor control panels NEMA Type 1 motor control enclosures with gasketed doors shall be used inside of buildings. Circuit breakers shall be provided for each motor Motor starters shall be full voltage, nonreversing magnetic, with overload relay protection Control transformers equipped with an integral fuse block for secondary protection shall be provided for each starter 44

Lift Stations motor control panels shall have the following features: Liquid level controls shall be off/on switch devices that open and close in response to predetermined liquid elevations and that cause the pump(s) to start or stop Submersible pumps shall have probes within the oil reservoir for the purpose of detecting a leakage of the outer seal of the motor. A warning light, a test light, and a test push button shall be provided for each motor 45

Lift Stations motor control panels Each lift station pump shall be fitted with a dedicated flow transmitter The flow transmitter shall be installed on the pump discharge piping, upstream of connection to common pump header piping The high level alarm shall be actuated before starting the stand-by pump 46

Lift Stations motor control panels If the Centralized Operation Building is available : lift stations shall be linked via SCADA systems to be monitored Programmable Logic Controllers (PLC's) shall be provided for lift stations 47

Lift station force mains Force mains shall be based on effluent velocity between.77 m/s and 5 m/s Force main shall be at least one pipe size larger than the pump discharge size Thrust blocks shall be provided for underground force mains All force main connections to a gravity sewer system shall be through a manhole 48

Materials Acceptable Piping Materials for Gravity Sanitary Sewer Piping Reinforced Thermosetting Resin (RTR) fiberglass pipes High Density Polyethylene (HDPE) PVC 49

50