MUNICIPAL WASTEWATER PUMP STATION DESIGN PROBLEMS AND SOLUTIONS
|
|
|
- Ethel Elliott
- 9 years ago
- Views:
Transcription
1 MUNICIPAL WASTEWATER PUMP STATION DESIGN PROBLEMS AND SOLUTIONS Presented at: WEFTEC 2006 Dallas, TX October 24, 2006 New England Water Environment Association Meeting Westford, MA September 12, 2006 Virginia Water Environment Association Annual Meeting Roanoke, VA May 2, 2006
2 MUNICIPAL WASTEWATER PUMP STATION DESIGN PROBLEMS AND SOLUTIONS INTRODUCTION In the Northern Virginia suburbs of Washington DC rapid residential growth has resulted in the need for construction of numerous municipal wastewater pumping stations. Municipal pump stations in Northern Virginia typically are submersible type pump stations with a design capacity between from 100 gpm to 1 MGD. The design requirements for submersible type pump stations continue to evolve to address construction and operation problems. This paper identifies several of these problems and the solutions that have been implemented in the design of several recently constructed wastewater pump stations in Northern Virginia. The author has prepared this paper based on his 32 years of experience in wastewater pump station design in the Northern Virginia Area. Contact: Jeff Chapin, P.E Arlington Boulevard Fairfax, VA Phone: (703) Fax: (703) METHODOLOGY Each of the identified pump station design problems is listed below by number with the corresponding design solution indicated under the problem. PROBLEMS AND SOLUTIONS 1. Concrete Corrosion Protection Problem: Until recently, most pump stations in Northern Virginia were constructed of concrete. Typically the wet well interior and exterior concrete surfaces received two coats of a coal tar epoxy coating to protect the concrete from the corrosion due to hydrogen sulfide in the influent sewage. Experience has indicated that concrete corrosion will result if either the coal tar epoxy is not properly applied, or is not reapplied when it deteriorates over time. It is very difficult to reapply coal tar epoxy, because usually the pump station wet well can not be taken out of service. Solution: New pump stations include a high density polyethylene (HDPE) liner on the interior of the concrete surfaces exposed to wastewater for corrosion protection. This liner is provided as an option by the precast concrete suppliers and the concrete is formed around the outside of the liner. Following installation of the lined precast concrete structure a certified welder field welds the seams and welds around pipe penetrations to assure that the HDPE liner prevents sewer gas from attacking the concrete. Another alternative is to utilize precast polymer concrete structures. Polymer concrete utilizes epoxy to bind the aggregate instead of cement. Thus the polymer concrete is not susceptible to corrosion due to sewer gas.
3 2. Corrosion Resistant Materials: Problem: Previous pump station designs included the use of galvanized steel and coated metal components in areas susceptible to hydrogen sulfide in influent sewage. After several years the metal components corroded and had to be replaced. These items included piping, pump guide rails, supports, grating, hand rails, stairs, bar screens, bolts, weirs, ladders, slide gates and other items. Solution: Type 316 stainless steel is specified for guide rails, brackets, bolts, nuts, structural steel, supports, and stairs. Fiberglass grating and ladders are specified. Aluminum hatch covers and slide gates are still specified because they are light way and durable, but they are susceptible to corrosion over time. The exterior of ductile iron piping is epoxy coated. Corrosion resistant materials should also be specified for electrical components. 3. Pump Protection from Influent Sewage Debris Problem: Most of the older pump stations had the influent sewer entering directly into the wet well and relied on the ability of the submersible pumps to pump a 3 inch diameter solid. Some pump stations had a basket screen attached to the influent sewer inside the wet well to try to protect the pumps from damage. However, the screens have to be manually lifted out of the wet well and cleaned by hand often to be effective. Solution: In order to assure that the pumps are adequately protected, new submersible pump stations in Northern Virginia often include a comminutor vault preceding the wet well. Raw wastewater entering the pump station flows through the comminutor vault influent channel which is equipped with a grinder. The grinder is a hydraulically driven horizontal screen and cutter assembly. The rotating screen directs solids toward and into the cutters where the influent solids are ground into fine particles to protect the downstream pumps. The grinder 5hp hydraulic power pack is located in a fiberglass enclosure mounted on top of the comminutor vault. In the event the grinder must be taken out of service, slide gates are provided to direct comminutor vault influent flow to a bypass bar screen. Also, in the event flow backs up upstream of the grinder the influent channel wall has an overflow notch just upstream of the bar screen. The bar screen is constructed of stainless steel bars and must be manually cleaned with a rake. The comminutor vault is a 12 ft. diameter precast concrete manhole with an HDPE liner. Stainless steel alternating tread stairs are used for access to the bottom of the vault. All lighting and electrical equipment is explosion proof inside the vault. A ventilation fan is provided on top of the comminutor vault. 4. Pump Selection Based on Total Dynamic Head Calculations Pumps are selected based on total dynamic head (TDH) calculations which can lead to improper sizing unless the Engineer carefully considers the exact pipe inside diameter, the Williams Hazen flow coefficient (C), and the location of high points in the force main. Each of these factors is discussed as follows:
4 Inside Pipe Diameter: Typically in Northern Virginia force main piping is either double cement lined ductile iron pipe or PWC pipe per AWWA C-900. The inside pipe diameter may vary considerably depending on the type of pipe selected. For long force mains extending two or more miles in length this can result in a significant difference in friction head component of the TDH. Solution: Determine the type of force main to be constructed and the exact inside pipe diameter in preparing TDH calculations. If the force main could be either ductile iron pipe, PVC or some other material, the TDH calculations should be prepared for each possible pipe material to make sure that the selected pump is adequate for all pipe materials. Williams Hazen flow coefficient (C): For new ductile iron pipe a C factor of 140 is often used in TDH calculations to estimate friction head in the force main when it is first placed in service. A C factor of 120 is often used to estimate the friction head in the force main after several years of operation. Pump selection based on a C factor of 140 alone will result in a pump that may be undersized when the force main pipe C factor decreases due to increased roughness of pipe internal surfaces over time. If the pump selection is based on a C factor of 120, the pump may pump too high a flow rate at startup because the new smooth pipe C factor is actually 140. This can result in overloading the pump motor. Also, it is important to note that field measurements of the actual C factors for old force mains which have been in continuous service for over 25 years has indicated that the C factor has decreased to approximately 100. Solution: For new pump stations, prepare TDH calculations based on the initial new pipe C factor and the anticipated C factor after the force main has been in service for several years. When expanding the capacity of existing pump stations which have been in service for many years, the actual C factor of the force main should be determined by field measurements. Problem involves a Force Main High Point near the pump station: Typically the TDH calculations are based on the entire length of force main pipe from the pump station to the discharge point. However, when pumping from one valley over a hill to a gravity sewer on the other side of the hill it is important to consider whether or not there is free fall in the down hill segment of the force main such that the downhill length of pipe does not need to be considered in the TDH calculations. If the static head from the high point to the discharge point exceeds the full flow headloss in the downhill segment of force main, sewage should flow by gravity through the force main similar to a gravity sewer instead of as a full pipe under pressure. Failure to recognize this condition in long force mains with a high point near the pump station can result in the selection of much higher capacity pumping equipment than actually required, and in significantly higher pumping rates than anticipated.
5 5. Energy Efficient Operation Problem: Common pump station design practice over the past 50 years has been to provide two pumps sized for the peak design flow rate, one of which is a standby pump. For pump stations with long force mains, the friction loss when operating at the design peak flow rate is excessive, resulting in high energy costs. Energy efficiency is becoming a very important consideration in pump station design. The Town of Purcellville East End Pump Station in Loudoun County, VA was equipped with two 75 hp submersible pumps which cycled on and off at the peak design flow rate of 600 gpm at 127 feet TDH. Sewage is pumped through an 8-inch force main, 4,572 feet long with friction headloss of 39 feet and excessive energy costs from frequent pump cycling on and off due to sewer infiltration/inflow. Solution: A small 10 hp submersible jockey pump was installed in the wet well to operate almost continuously through the day at a flow rate of approximately 100 gpm. This lower flow rate significantly reduced the friction loss and energy requirements while providing reliable service. The friction headloss was reduced from 39 feet to 2 feet. The larger pumps only operate a few times a day during peak flow periods in the morning and evening which is sufficient to flush out solids in the force main. Power costs were significantly reduced based on three years of operation. 6. Pump Station Appearance Problem: For many years pump stations were designed to be functional with little attention given to the exterior appearance and the impact on the surrounding community. Many of the new pump stations in Northern Virginia are located next to new homes costing over $700,000 or next to attractive commercial development. Standard utility buildings with barbed wire exterior fencing are often unacceptable to the developers in Northern Virginia. Solution: The pump station control building exteriors include stone faced block walls or other features to match the surrounding development architecture. Ten foot high black galvanized steel picket fence is used with an extended top slanted for security. 7. Surge Protection Problem: When the pumps cycle off or there is a power failure, high surge pressures can damage piping. Solution: Soft start/stop electrical control equipment significantly reduces surge pressures. As backup protection a surge relief valve is often installed at each pump station in the event of a power failure or a failure of the soft start/stop equipment.
6 8. Rehabilitation of Existing Pump Stations Problem: Fairfax County has a program to rehabilitate four to eight pump stations every few years under one construction contract as necessary. After approximately 20 years of service they have found that parts are no longer available for electrical controls, and pumps and valves need to be replaced. Also, the building structures, roads and electrical service are often in need of replacement. The pump station must be maintained in continuous service through construction and thus constructability issues must be identified in the design process. Solution: Based on over 15 recent pump station rehabilitation projects, a typical scope of work can be identified for construction rehabilitation. Each pump station needs to be examined separately to determine what rehabilitation measures are needed. Pumps and valves and other mechanical equipment items are replaced. Typically, dry pit submersible pumps are used to replaced shaft pumps. New electrical controls are installed. Corrosion resistant materials are installed to replace corroded materials or epoxy coatings are applied to existing surfaces. Structural and architectural improvements are identified. The construction phasing and temporary pumping requirements are identified in the contract documents for construction. An existing 20 MGD wet well/dry well pump station with vertical shaft pumps was expanded to 40 MGD capacity with dry pit submersible pumps while maintaining continuous operation. This was achieved by first installing two of the submersible pumps in the wet well and providing a temporary force main. Once this temporary pumping system was operations, all of the equipment in the dry well was replaced with new equipment. Once two of the four dry pit submersibles were installed in the dry well, the two pumps in the wet well were removed and also installed in the dry well to complete the project. 9. Prevention of Leakage into the Pump Station Structures Problem: Cracks or joints in precast concrete manhole structures used to construct new pump stations can result in groundwater leakage into the pump station which must be pumped to the treatment facility resulting in unnecessary costs and reduced capacity. It is often difficult to permanently seal such cracks or joints after construction is completed and the pump station is in service creating a confined space. This is especially true for deep pump stations. Solution: All weather butyl joint sealant materials are available for effective sealing precast concrete joints exposed to high groundwater pressures. Butyl sealants are rubber based and exhibit physical properties such as rebound, compression, low temperature and high temperature flows that are all required for long term sealing performance. This joint material was effectively used at the 50 foot deep Morris Farm Pump Station in Prince William County to prevent leakage. Other methods of sealing the joints and concrete surfaces are also available including bentonite.
7 10. Odor Control Problem: Sewage piping designed for future ultimate design flows is often way oversized for initial flows resulting in long pipe retention times and septic odors. Solution: Chemical feed addition at pump stations can help minimize odor problems throughout the downstream sewer system. Bioxide chemical solution has been utilized at several new pump stations to minimize odors. The Bioxide material utilizes the inherent ability of the facultative bacteria normally present in wastewater to metabolize hydrogen sulfide and other odor-causing, reduced sulfur containing compounds. The material provides nitrate-oxygen to the wastewater to support this biochemical mechanism. This nitrate-oxygen is applied via nitrate salts. The material shall be chemically stable, allowing continuous removal of sulfide contributed by side streams downstream of the application point. The pump station design includes a pad mounted Bioxide chemical storage tank and automatic chemical feed equipment. 11. Provisions for Future Expansion Problem: The rapid growth experienced in Northern Virginia over the past few years can result in pump stations being undersized to convey projected flow rates. If provisions for future expansion are not included in the design, the entire pump station or major components of the pump station may have to be replaced. Solution: Provisions for future expansion include the selection of pumps with higher than required motor horsepower to allow the future installation of larger diameter impellers capable of pumping increased flows. The Morris Farm Pump Station in Prince William County was almost over capacity at start up because of the addition of unanticipated sewage flows from a new elementary school which was supposed to be served by an adjacent gravity sewer system. Fortunately, by adding a larger impeller the additional flow could be accommodated without any other changes. Other considerations include sizing the force main, generator set, wet well, electrical service and other components to allow some increase in capacity without causing problems during initial operation. 12. Grit Deposition in Wet Wells Sized for Future Flow Rates Problem: The design criteria for submersible pump wet well sizing can lead to excessive grit deposition in the wet well due to initial low flow conditions. The grit can result in serious odor problems and is difficult to remove. Solution: Provide temporary solid concrete block filler in the wet well areas subject to grit deposition or provide baffle walls to reduce the wet well area during initial low flow conditions. In the future when the flows approach the design flow rate, the blocks or baffle walls can be removed. CONCLUSION The planning and design of new municipal wastewater pump stations or rehabilitation/expansion of existing pump stations requires careful consideration of potential problems and possible solutions presented above.
8 Municipal Sewage Pump Station Design Problems and Solutions presented by: Jeff Chapin, PE October 24, 2006 Session 28
9 Morris Farm Western Prince William County, Virginia
10 Prince William County Service Authority Morris Farm Pump Station 928 GPM Capacity
11 Prince William County Service Authority Morris Farm Pump Station
12 Corrosion Sewer Gas Corrodes Concrete and Metal Components
13 Prince William County Service Authority Morris Farm Pump Station Grinder Vault with HPDE Liner & Stainless Steel Stairs
14 Prince William County Service Authority Morris Farm Pump Station Grinder
15 Prince William County Service Authority Morris Farm Pump Station Grinder Hydraulic Power Drive
16 Prince William County Service Authority Morris Farm Pump Station Bypass Bar Screen
17 Prince William County Service Authority Morris Farm Pump Station Wet Well
18 Prince William County Service Authority Morris Farm Pump Station Valve Vault
19 Prince William County Service Authority Morris Farm Pump Station Control Building & Standby Generator
20 Prince William County Service Authority Morris Farm Pump Station Control Building Panels
21 Odor Control Prince William County Service Authority Morris Farm Pump Station Bioxide Tank
22 Construction Problems Commuter Vault Wet Well Valve Vault Meter Vault Potential for Differential Settlement Potential for Water Leakage Typical Submersible Pump Station Section View Prince William County, Virginia
23 Watertight Structures 250 gpm Camp Glenkirk Pump Station
24 Rock Excavation Prince William County Service Authority Broad Run Pump Station Rock Saw
25 Potential Problems & Solutions Lift Chain Enters Volute Short Chain Length Power Cable Excessive Flexing Short Cable Length Cavitation With 2 Pumps Running At Low Speed Pump Head Does Not Overcome System Head Air Entrainment From Concentric Reducer On Pump Suction Piping Check 2 Pump Curve Check Pump Curve At Low Speed Use Eccentric Reducer
26 Energy Efficiency Improvement at Purcellville East End Pump Station Original Pump System Two 75 hp Submersible Pumps 600 GPM Pumping Rate Significant Infiltration & Inflow 4,572 Feet of 8-inch Force Main Friction Headloss = 39 feet Excessive Surge With Frequent Pump Starts
27 Installation of Small Pump
28 Energy Efficiency Improvement at Purcellville East End Pump Station Improvements: Added a new 10 hp submersible pump Rated 120 gpm at 90 feet TDH Friction Headloss = 2 feet Cost of Pump and Controls Installed = $6,500 Benefits: Less Surge from Frequent Stop Starts Operation at Lower Head Reduces Energy Consumption Eliminates current surges when 75 hp pump starts
29 Design Calculation Pitfalls Force Main Profile
30 Grease Problems 2.9 MGD Pump Station Wet Well
31 Pipe Clogging Sonar Image 30 Pipe
32 Appearance Town of Leesburg Goose Creek Pump Station
33 20 MGD to 40 MGD Expansion Existing 20 MGD Pump Station Dry Well
34 Installation of Larger Pumps Expansion to 40 MGD Pump Station Dry Well
35
36 Grit in Wet Well 100 MGD Pump Station
37 Conclusion Corrosion Resistant Materials Watertight Structures Minimize Settlement Check Design Calculations Consider Grease & Grit Energy Efficiency Constructability
Wastewater Collection System Supplemental Design Standards for Capital Improvement Program Projects
Wastewater Collection System Supplemental Design Standards for Capital Improvement Program Projects March 2013 i Metropolitan Sewer District of Greater Cincinnati Wastewater Collection System Supplemental
HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS
HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS Shiwei William Guan, Ph.D. Vice President, R&D and International Business Madison Chemical Industries Inc. 490
Terry Biederman, PE- Director of Public Works Greg Gucwa, PE- Principal Johnson and Anderson Engineering
DON T JUST REHAB IT, RENEW IT! WATERFORD TOWNSHIP, MICHIGAN IMPROVEMENTS TO A 3.0 MGD SEWAGE PUMPING STATION Terry Biederman, PE- Director of Public Works Greg Gucwa, PE- Principal Johnson and Anderson
Sewer Rehabilitation Design Requirements
Sanitary Sewer Overflow (SSO) Control and Wastewater Facilities Program Sewer Rehabilitation Design Requirements City of Baton Rouge/Parish of East Baton Rouge Department of Public Works Submitted by Prepared
Before H 2 Town of South Windsor, CT Evaluates Large Diameter Concrete Pipe
Before H 2 Town of South Windsor, CT Evaluates Large Diameter Concrete Pipe September 11, 2012 NEWEA Collection Systems Conference Presented by: Laurie L. Perkins, PE Dennis A. Dievert, PE C. Frederick
DIVISION OF WATER QUALITY CONSTRUCTION GRANTS & LOANS SECTION FAST TRACK AUDIT CHECKLIST
DIVISION OF WATER QUALITY CONSTRUCTION GRANTS & LOANS SECTION FAST TRACK AUDIT CHECKLIST CERTIFICATION 1. Did the engineer submit a certificate of completion utilizing the appropriate page of the issued
Module 9: Basics of Pumps and Hydraulics Instructor Guide
Module 9: Basics of Pumps and Hydraulics Instructor Guide Activities for Unit 1 Basic Hydraulics Activity 1.1: Convert 45 psi to feet of head. 45 psis x 1 ft. = 103.8 ft 0.433 psi Activity 1.2: Determine
Flygt Ball Check Valves
4/13 Supersedes: 6/96 The basic purpose of a check valve is to permit flow in one direction, prevent flow in the opposite direction and perform this function automatically and with minimum maintenance.
Design of Sewage Pumping Stations by John Zoeller, PE, CEO/President
Design of Sewage Pumping Stations by John Zoeller, PE, CEO/President This article provides guidelines for designing municipal pumping systems. There are three types of sewage handling systems: 1. Municipal
Appendix S Pump Station Evaluation
Appendix S Pump Station Evaluation Technical Memorandum Date: October 12, 2001 To: Re: Orange County Utilities Task 6.4 Raw Wastewater Pump Stations 1.0 Summary In accordance with Task 6.4 of the Orange
Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29
_02 A centrifugal with a 12 in. diameter impeller requires a power input of 60 hp when the flowrate is 3200 gpm against a 60 ft head. The impeller is changed to one with a 10 in. diameter. Determine the
Specifications for Residential Property Owners Connection to New Public Sewer
Specifications for Residential Property Owners Connection to New Public Sewer Spalding Tract property owners are required to connect to the community sewer system when construction is complete and the
Emerging Technologies in Wastewater Collection Systems
Keville Enterprises Emerging Technologies in Wastewater Collection Systems Douglas McCutchen, CCM Brian Karmasin, P.E., BCEE CMAA Annual Conference Oct 2008 San Francisco, California Today s s Presentation
SECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
Chapter 4 - Preferred Alternative...25
Preliminary Design Report Chapter 1 - Background... 1 Introduction... 1 Condition Assessment... 1 Reliable Capacity... 2 Forcemain Header Structural Integrity... 2 Wetwell Corrosion... 2 Manhole Corrosion...
Waste Collection Systems
Waste Collection Systems System Maintenance and Repair Maintenance and Repair Training Objectives To gain an understanding of: System Maintenance and Repair vocabulary System Maintenance and Repair techniques
CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS
CCU Engineering Specifications Section 003300 Effective Date: Nov. 1st, 2011 Page 1 of 5 PRECAST CONCRETE PRODUCTS PART 1 - GENERAL The following specification is intended for use for the design, selection
SECTION XXXXXX TECHNICAL SPECIFICATIONS FOR INSTALLATION OF PROTECTIVE COATINGS FOR MANHOLES, WETWELLS, AND OTHER SANITARY SEWER STRUCTURES
1.00 PART 1 GENERAL 1.01 SCOPE A. It is the intent of this contract to install a 100% solids epoxy monolithic coating to the walls, benches and inverts of all manholes and the specified surfaces of other
Module 7: Hydraulic Design of Sewers and Storm Water Drains. Lecture 7 : Hydraulic Design of Sewers and Storm Water Drains
1 P age Module 7: Hydraulic Design of Sewers and Storm Water Drains Lecture 7 : Hydraulic Design of Sewers and Storm Water Drains 2 P age 7.1 General Consideration Generally, sewers are laid at steeper
SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER
Village of Shorewood, Wisconsin SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER Prepared By: Thomas A. Zoulek, P.E., LEED A.P. Vice President Mid City Plumbing & Heating
DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL
DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION A. Furnish and install all storm drains, including manholes, inlets, service lines and other appurtenant
Outline. Objective. Overview Sanitary Drainage System. Design. Materials
1 Outline Objective Overview Sanitary Drainage System Standard References Design Materials 2 SAWEA) Workshop 2010 Objective Address the minimum requirements for Sanitary Sewers System that are located
SECTION 08000 STORM DRAINAGE TABLE OF CONTENTS
SECTION 08000 STORM DRAINAGE 08010 DESIGN A. Location B. Sizing TABLE OF CONTENTS 08020 MATERIALS A. Pipe Materials B. Structure Materials C. Installation D. Inlets and Outlets 08030 INSPECTIONS AND TESTING
Module 3: Sewer Material Lecture 3: Sewer Material
Module 3: Sewer Material Lecture 3: Sewer Material [NPTEL, IIT Kharagpur, Prof. M.M.Ghangrekar, Department of Civil Engineering Page 1 3.0 SEWER MATERIAL 3.1 Important Factors Considered for Selecting
Rehabilitation or Replacement? That Is The Question
Rehabilitation or Replacement? That Is The Question Chris L. Windley PE Greg Anderson, PE 94th Annual Conference November 18, 2014 Overview Project Background Existing Sewer Condition Flow Projections
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
Wastewater Collection Practice Test #3 Page 1 of 15
Wastewater Collection Practice Test #3 Page 1 of 15 1) A 54 in. storm sewer flowing half full, at a velocity of 1.35 Ft./sec., will discharge how much flow into a creek in MGD? 13.85 MGD 10.73 MGD 1.85
Town House 11265 Center Highway North Huntingdon, PA 15642
APPENDIX C SPECIFICATIONS FOR THE CONSTRUCTION OF BUILDING LATERAL SANITARY SEWERS DECEMBER 2004, INCLUDING AMENDMENTS ADOPTED ON FEBRUARY 6, 2008 AND APRIL 2, 2008; EFFECTIVE ON MAY 1, 2008 Town House
BSM MOTOR DRIVEN CENTRIFUGAL PUMPS
PRINCIPLE OF OPERATION A hydraulically and dynamically balanced impeller with raised vane sections discharges liquid as a result of the centrifugal force developed in rotation. The head developed is entirely
Rehabilitation Alternatives. MWEA Collection System Seminar October 1, 2009
Rehabilitation Alternatives MWEA Collection System Seminar October 1, 2009 Overview Types of Rehabilitation Trenchless Categories On-Line Replacement In-Situ Options Selecting the Best Solution Types of
CONFIRMING WET WEATHER TREATMENT FACILITY HYDRAULIC DESIGN WITH PHYSICAL MODEL STUDY
CONFIRMING WET WEATHER TREATMENT FACILITY HYDRAULIC DESIGN WITH PHYSICAL MODEL STUDY TONY YEE, PE JARED HUTCHINS, PE METROPOLITAN SEWER DISTRICT OF GREATER CINCINNATI BLACK & VEATCH WET WEATHER TREATMENT
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
MODEL 300505 INSTALLATION INSTRUCTIONS
WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 [email protected] Your pump has been carefully packaged at the factory to prevent damage during shipping.
Module 3 : Sewer Material. Lecture 3 : Sewer Material
1 P age Module 3 : Sewer Material Lecture 3 : Sewer Material 2 P age 3.1 Important Factors Considered for Selecting Material for Sewer Following factors should be considered before selecting material for
Theory, Application, and Sizing of Air Valves
Theory, Application, and Sizing of Air Valves VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX. (630) 941-8042 www.valmatic.com 1 THEORY, APPLICATION,
SECTION 02763 POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.
SECTION 02763 PART 1 G E N E R A L 1.01 SECTION INCLUDES A. Repairs to existing sewer lines by replacing short lengths of failed pipe. 1.02 UNIT PRICES A. Measurement for point repairs is on a unit price
SECTION 33 41 13 PUBLIC STORM UTILITY DRAINAGE PIPING
SECTION 33 41 13 PUBLIC STORM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Storm drainage piping, fittings, and accessories at proposed station areas and locations other than under and immediately adjacent
SANITARY SEWER BACKUP. Causes & Prevention
SANITARY SEWER BACKUP Causes & Prevention A. PURPOSE The purpose of this publication is twofold: 1. It provides homeowners with basic information on the causes of sanitary sewer backups. 2. It provides
SPECIFICATIONS FOR SEWER PIPE AND LINING INSERTION - TRENCHLESS; GENERAL GUIDELINES (As Provided by NASSCO)
SPECIFICATIONS FOR SEWER PIPE AND LINING INSERTION - TRENCHLESS; GENERAL GUIDELINES (As Provided by NASSCO) 1 Intent: The intent of trenchless sewer pipe Insertion is to rehabilitate the existing sewer
Repairs Made With Under Pressure Installations Can Offer Reduced Risks And Expenses
Repairs Made With Under Pressure Installations Can Offer Reduced Risks And Expenses They also give the community a built-in re-entry system for future monitoring and repair. BY BRETT HANES According to
SANITARY SEWER SPECIFICATIONS
SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,
SANITARY SEWER SYSTEM ASSESSMENT
SANITARY SEWER SYSTEM ASSESSMENT What is this tool? The Sanitary Sewer System Assessment is a form that helps your utility identify and document all of the components in your utility s sanitary sewer system.
Wastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,
PART 6 - STANDARD DESIGN AND CALCULATION FORMS 6.1 SANITARY SEWER DATA SHEET
PART 6 - STANDARD DESIGN AND CALCULATION FORMS 6.1 SANITARY SEWER DATA SHEET Name of Municipality or Sewer District Name of Project Original Township and Lot Number Name of Engineer of Firm Preparing Plans
PACKAGE TERTIARY FILTER SYSTEM SPECIFICATIONS MODELS TF-2-6-C THROUGH TF-2-35-C
PACKAGE TERTIARY FILTER SYSTEM SPECIFICATIONS MODELS TF-2-6-C THROUGH TF-2-35-C Pollution Control Systems Inc. (PCS) is pleased to provide the following equipment specifications for your consideration.
Jay R. Smith Mfg. Co.
Jay R. Smith Mfg. Co. Automatic Backwater Valve SMITH CUSTOMER DRIVEN FLOOD-GATE FEATURES Index Page Flood-Gate Features and Applications 2 How Flood-Gate Works 3 Flood-Gate Operation & Approvals 4 Valve
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
FY08 SEWER POINT REPAIRS BID TABULATION
6-07-831 Page 1 of 12 1 FOR CLEANING AND TELEVISING EXISTING SEWERS, AS SPECIFIED, ANY REQUIRED CLEANING, ANY LOCATION, ANY LENGTH OF SEWER, COMPLETE IN PLACE, FOR VARIOUS PIPE DIAMETERS. A. EXISTING "
CITY OF DAYTON DEPARTMENT OF WATER 42-INCH SANITARY SEWER REHABILITATION
CITY OF DAYTON DEPARTMENT OF WATER 42-INCH SANITARY SEWER REHABILITATION 42-INCH SANITARY SEWER REHABILITATION WHAT WE WILL DISCUSS TODAY: Project Justification & Evolution (high level/not a chemistry
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
The checklist utilized by the Authority will be similar to that which is shown below. Project Name: Location: Consulting Engineering Firm:
Page 1 of 6 Section 1. PURPOSE This policy is an Engineering checklist of the Local Review Program for sanitary sewer improvement projects by the Bedford Regional Water Authority ( Authority ). Section
Storm Sewer Trenchless Upgrade Alternatives and Recommendations
Storm Sewer Trenchless Upgrade Alternatives and Recommendations Background Approximately 1,930 feet of the 40-inch and 42-inch CMP storm sewer pipe from manhole M22 to manhole M12 will be evaluated for
Coast Trunk Sewer Rehabilitation Project for the Orange County Sanitation District
Coast Trunk Sewer Rehabilitation Project for the Orange County Sanitation District Paul F. Wilson 1 and Robert J. Warren 2 1 1525 Faraday Ave, Suite 290, Carlsbad, California, USA 92008; e-mail: [email protected].
SRA-125/SRAX-125 Double-Rail Lift-Out Rail System Installation & Service Manual with Parts List
SRA-125/SRAX-125 Double-Rail Lift-Out Rail System Installation & Service Manual with Parts List For MG, WG, WGL, and Grinder Pumps for Effluent & Sewage CAUTION! Read these safety warnings first before
SEPTIC SYSTEMS. 1. Building sewer connects the building plumbing to the septic tank.
SEPTIC SYSTEMS Who Has A Septic System? Approximately 30 percent of Connecticut s population is served by on-site subsurface sewage disposal systems (a.k.a. septic systems). This means a large percentage
What Does A Sump Pump Do?
Wastewater Products Automatic submersible cast iron sump pump Ideal for high volume water removal applications Heavy duty cast iron construction For years of service and reliability Clog-resistant design
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
Force Main Condition Assessment: New Technologies & Case Studies
Force Main Condition Assessment: New Technologies & Case Studies Andy Dettmer, Ph.D., P.E. CMOM Workshop August 19, 2014 2 1 Three takeaways 1. Most of your force mains are good 2. We can pinpoint the
Septic System Design Manual
Septic System Design Manual Prince George s County Health Department Largo Government Center 9201 Basil Court, Suite 318 Largo, Maryland 20774 (Office) 301-883-7681 (Fax) 301-883-7266 (January 2007) Table
Vertical selfpriming Side-Channel Pumps Type WPV
Vertical selfpriming Side-Channel Pumps Type WPV FIELD OF APPLICATION The side-channel pumps are selfpriming and operate more economically (better efficiency) than normal centrifugal pumps when handling
SECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
Appendix A: Acceptable pipe and fitting materials
Watercare Services Limited Water and Code of Practice Content from the NZS 4404:2010 Land development and subdivision infrastructure has been reproduced for use in the Infrastructure Design s Manual for
SECTION 812 SEWER LINE, MANHOLE AND WET WELL CLEANING
812-1 SCOPE OF WORK: SECTION 812 SEWER LINE, MANHOLE AND WET WELL CLEANING a. The Contractor shall provide all labor, materials, equipment, and incidentals necessary to perform the cleaning of sewer lines,
Pure Performance. Steady 1300 Series
Pure Performance Steady 1300 Series Available EASY TO SELECT, QUICK DELIVERY, THE RIGHT PUMP FOR YOUR NEEDS Oustanding Value EFFICIENT, POWERFUL Reliable SOLIDS HANDLING, CONTINUOUS RUNNING 2 Readily available
Texas Commission on Environmental Quality Page 1 Chapter 217 - Design Criteria for Domestic Wastewater Systems
Texas Commission on Environmental Quality Page 1 217.31. Applicability. SUBCHAPTER B: TREATMENT FACILITY DESIGN REQUIREMENTS 217.31-217.39 Effective August 28, 2008 This subchapter details the design values
VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6
- B 1 Product Detail Engineering Data... B2 Structural Support... B6 Engineering Specifications... B9 - B 2 Engineering Data REMARK: Do not use for construction. Refer to factory certified dimensions &
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
Stainless Steel Perimeter Recirculation Systems Engineered supply and return systems for swimming pools, water features and aquatic facilities.
Stainless Steel Perimeter Recirculation Systems Engineered supply and return systems for swimming pools, water features and aquatic facilities. Whether it is new construction, renovation or operation,
pvc well casing & drop pipe
CertainTeed pvc well casing & drop pipe PVC Well Products Sure Fit PVC well casing and drop pipe have gained broad acceptance since their introduction almost 40 years ago. Today, due to its outstanding
812-3 LIMITATIONS: b. No fire hydrant shall be obstructed or used when there is a fire in the area.
812-1 SCOPE OF WORK: SECTION 812 SEWER LINE, MANHOLE AND WET WELL CLEANING a. The Contractor shall provide all labor, materials, equipment, and incidentals necessary to perform the cleaning of sewer lines,
Rehabilitation of an Aging Concrete Reservoir Adit Tower
Rehabilitation of an Aging Concrete Reservoir Adit Tower Raymond S. Tombaugh, Senior Coatings Consultant KTA-Tator, Inc. and Mongkol Mahavongtrakul, P.E. Corrosion Control Contract Manager San Francisco
FY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation
644-10-569 Page 1 of 9 1 FOR CLEANING AND TELEVISING EXISTING SEWERS, AS SPECIFIED, ANY REQUIRED CLEANING, ANY LOCATION, ANY LENGTH OF SEWER, COMPLETE IN PLACE, FOR VARIOUS PIPE DIAMETERS. A. EXISTING
OAR52 A-1 (September, 1981)
APPENDIX A SEWER PIPELINES (1) MINIMUM REQUIREMENTS FOR SEWER - PIPELINES (a) Capacity: Sewers shall be of such diameter as to pass without overflow, bypass, or back flow onto damageable property of a
Installation of Large Diameter Buried Pipes
Installation of Large Diameter Buried Pipes Sullivan (Sully) Curran P. E., Executive Director I. Introduction and Scope There is an ongoing need to provide designers, specifiers, engineers, consultants
Standards for Water, Sewer, and Sewage Lift Station Design
Standards for Water, Sewer, and Sewage Lift Station Design February 2015 Edition I. Plan Format Requirements General Requirements Water Line Requirements Sewer Line Requirements II. III. IV. Water Design
Most agencies think about cleaning because of debris in the line.
Most agencies think about cleaning because of debris in the line. If we have an effective cleaning program there should not be a lot of debris in the line after the line is cleaned and tv d for acceptance.
ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING
ATTACHMENT 3: SPECIFICATION FOR SEWER CLEANING 1.0 General 1.1 The work covered by this section consists of providing all labor, equipment, material and supplies, insurance, accessories, tools, transportation,
SECTION 3 SANITARY SEWER DESIGN
SECTION 3 SANITARY SEWER DESIGN 3.1 GENERAL DESIGN CRITERIA 3.1.1 Requirement for Sanitary Sewer 3.1.2 Design Approval 3.1.3 IEPA Permit Required 3.1.4 Differentiation Between Public and Private Sanitary
STANDARD SPECIFICATIONS SECTION 02512 CLEANING AND LINING WATER MAINS
STANDARD SPECIFICATIONS SECTION 02512 CLEANING AND LINING WATER MAINS PART 1 GENERAL 1.1 DESCRIPTION A. Section includes requirements for cleaning and lining existing cast iron and ductile iron water mains
53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:
Division 53: Slip-Lining of Existing Sewer Line 53.01 GENERAL: This section includes all labor, materials, transportation, equipment necessary to rehabilitate by means of Instituform deteriorated sections
Pumps SELECTION OF A PUMP
Pumps SELECTION OF A PUMP A water system needs to move the water produced from the source to its customers. In almost all cases in Minnesota, the source is at a lower elevation than the user so the water
STRUCTURES. 1.1. Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.
STRUCTURES 1. General. Critical structures may impact the integrity of a flood control project in several manners such as the excavation for construction of the structure, the type of foundation, backfill
Section 2100-Trenching and Tunneling
SECTION 5200 - STORM SEWER PART 1 - GENERAL 1.01 SCOPE: This Section covers installation of storm sewer mains and culverts. Topics include permits and fees, trench widths, pipe laying, bedding, initial
FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com
FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,
UNDERGROUND INFRASTRUCTURE SPECIALISTS TABLE OF CONTENTS
U UNDERGROUND INFRASTRUCTURE SPECIALISTS TABLE OF CONTENTS 3. COMPANY PROFILE A growing company excelling in the fields of infrastructure repair and maintenance. 6. MANDREL TESTING Individually approved
BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.
SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION
LOWER NORTH OUTFALL SEWER AND NORTH OUTFALL SEWER REHABILITATION USING AMERON S T HAB METHOD
www.norcalpug.com LOWER NORTH OUTFALL SEWER AND NORTH OUTFALL SEWER REHABILITATION USING AMERON S T HAB METHOD Bob Fisher and Lance Stracner Ameron Protective Lining J.R. Pipeline Co Inc. Abstract: The
DIVISION 4300 STORM DRAINAGE
DIVISION 4300 STORM DRAINAGE SECTION 4305 STORM SEWER PART 1 - GENERAL 1.01 SCOPE This section covers the construction of storm sewers for the collection and transport of stormwater runoff. 1.02 REFERENCES
HYDROVEX. CSO, SSO and Stormwater Management Specialist Products and Services for North America
HYDROVEX CSO, SSO and Stormwater Management Specialist Products and Services for North America A long tradition in excellence John Meunier Inc. has been serving North American municipalities and industries
2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS
2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS Water system improvements proposed for inclusion into Western s service area shall be designed in accordance with all appropriate AWWA standards, include
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
N-PUMP SERIES FOR MAXIMUM RELIABILITY AND EFFICIENCY IN WASTEWATER HANDLING. Flygt
N-PUMP SERIES FOR MAXIMUM RELIABILITY AND EFFICIENCY IN WASTEWATER HANDLING Flygt The Concept N-Pump series. Bringing NEW levels of efficiency to wastewater handling applications Reduced pumping efficiency,
A Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
Installation Manual. Solar Pool Heating System. Read the complete manual before beginning the installation
Solar Pool Heating System Installation Manual Read the complete manual before beginning the installation 1. Sizing the System Visit www.techno-solis.com to size the system using the sizing calculator.
STANDARD SPECIFICATIONS SECTION 02956 CLOSED CIRCUIT TELEVISION INSPECTION OF SEWER MAINS, MANHOLES AND LATERALS
STANDARD SPECIFICATIONS SECTION 02956 CLOSED CIRCUIT TELEVISION INSPECTION OF SEWER MAINS, MANHOLES AND LATERALS PART 1 GENERAL 1.1 DESCRIPTION A. Section includes requirements to execute internal closed
Collection Systems Technology Fact Sheet Sewers, Conventional Gravity
United States Environmental Protection Agency Collection Systems Technology Fact Sheet Sewers, Conventional Gravity DESCRIPTION Sewers are hydraulic conveyance structures that carry wastewater to a treatment
ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application.
ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application. Article II provides rules governing the allowable connection to the City POTW and the construction and inspection of
DEPARTMENT OF ENVIRONMENTAL QUALITY
PROJECT IDENTIFICATION DEPARTMENT OF ENVIRONMENTAL QUALITY City of Burton Sanitary Sewer Collection System Improvements State Revolving Fund (SRF) Environmental Assessment April 2015 Applicant: Authorized