IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS



Similar documents
INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010

Understanding Arc Flash

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

2012 NFPA 70E. Ten Most Important Changes. John A. DeDad

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Introduction to Arc Flash

What s up with Arc Flash?

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

Electrical Safety Program

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS

PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM

misconceptions about arc-flash hazard assessments

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

Electrical Safety Program

Environmental Health & Safety Electrical Safety Program

Part 1 System Modeling & Studies for Existing Systems

3053 Electrical Safety Training Program Course Outline

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work

Electrocution Hazards

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA

Cal/OSHA Guide to. Electrical Safety. Cal/OSHA Consultation Service Research and Education Division of Occupational Safety and Health

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

ELECTRICAL SAFETY PROGRAM

NFPA 70E Updates Affect Your Most Valuable Assets

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

OSHA & ARC FLASH HAZARD ANALYSIS

Roadmap to Compliance with NFPA 70E Arc Flash Requirements

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance

Hampshire College. Lockout/Tagout and Electrical Safety Program and Procedures

UNIVERSITY OF CENTRAL FLORIDA ELECTRICAL SAFETY PROGRAM

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E

Arc Flash Energy Mitigation Techniques

PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT

ARC Flash Boundary & NFPA-70E Requirements PPE Program

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

Top Commercial / Residential Electrical Requirements *

UL Validated Testing of Arc-Resistant Motor Control Centers

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

ELECTRICAL SAFETY / ARC FLASH PROGRAM

Title: Grounding and Bonding Rev-01

Electrical Grounding. Appendix C

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

Installation Instructions for Alarm Module Kit A043F059

Analyzing Electrical Hazards in the Workplace

2008 Eaton Corporation. All rights reserved.

SALISBURY ASSESSMENT SOLUTIONS

Campus Safety Procedure Electrical Safety

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

! WARNING Arc Flash and Shock Hazard Appropriate PPE Required

NESC Update. James R. Tomaseski International Brotherhood of Electrical Workers

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH

Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST

Electrical Contractors. and the. New Jersey. Rehabilitation Code

OSHA 29CFR1910 Subpart S

ELECTRICAL & ARC FLASH SAFETY PROGRAM

Questions and Answers for Heating and A/C Contractors

Notes. Material 1. Appropriate Flammable Liquids

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Safety By Design. Strategies for Electrical Contractors

Low Voltage Switchgear

Electrical Safety in the Marine Environment

ELECTRICAL SAFETY RISK ASSESSMENT

Choosing the Best Solution for Reducing Arc Energy

Voltage Detection and Indication by Electric Field Measurement

SALISBURY ASSESSMENT SOLUTIONS

How to reduce exposure to arc flash hazards

Requirements for Electrical Installations

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

Presented by: Rich Perry Marsh Risk Consulting

LOCKOUT/TAGOUT (LOTO) SAFETY PROGRAM

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

Instructions for Safe Use

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

Electrical Safety Requirements

Laboratory Safety Guideline Electrical Safety

Job Site Electrical Safety A Matter of Life and Death

Transcription:

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 paul@occsev.com OCCUPATIONAL SERVICES, INC.

BACKGROUND Update Update to 29CFR1910 Subpart S Electrical Safety Standards First update since 1981 Reliance Reliance on NFPA 70E, STANDARD FOR ELECTRICAL SAFETY REQUIREMENTS FOR EMPLOYEE WORKPLACES 2

3

BACKGROUND Areas Areas to be addressed Electrical Installations Work Practices for working on live equipment Safety Related Maintenance Requirements 4

PRESENTATION OBJECTIVES Understand the revised electrical safety requirements and how they will impact the management and engineering control of electrical hazards in general industry. 5

PRESENTATION OBJECTIVES Describe Describe the components of the revised Subpart S Electrical Safety Standard and illustrate the similarities and differences between the existing and new regulation. 6

PRESENTATION OBJECTIVES Apply Apply the revised requirements in the industrial setting. 7

PRESENTATION FORMAT Requirements Applying to both existing and new regulation. Additional requirements per NFPA 70E How companies are complying. 8

SAFETY REQUIRMENTS FOR ELECTRICAL INSTALLATIONS

ELECTRICAL INSTALLATIONS General Requirements OSHA General Industry 1910.302-1910.308 1910.308 Construction 1926.402-1926.408 1926.408 NFPA: NFPA 70E, Chapter 4, Articles 400-450 450 10

ELECTRICAL INSTALLATIONS General Requirements OSHA & NFPA (similarities) Electrical Insulation Heating Arcing Marking 11

MARKING & IDENTIFICATION Markings required by OSHA 12

Electrical Panel PNL Designation Circuit Breaker Identification Circuit Breaker Numbers 13

Marking of Wires 14

ELECTRICAL INSTALLATIONS General Requirements OSHA & NFPA (Similarities) Workspace Requirements for < 600 Volts Requirements for >600 Volts 15

Workspace about low voltage equipment Energized Parts 3 Non-Energized Parts Energized Parts 3 3 Energized Parts Guard (wood or plasterboard) 16

Workspace about low voltage equipment Energized Parts 3 Energized Parts 0-150 Volts Energized Parts 4 Energized Parts 151-600 Volts 17

Workspace-600 V 4 18

Workspace about high voltage equipment Energized Parts 6 Non-Energized Parts 25,001 Volts-75kV Energized Parts 8 Non- Energized Parts >75 kv 19

Workspace-26 kv 6 20

Elevation of Unguarded Energized Parts Above Workspace Nominal Voltage Minimum Elevation 601-7500 8 6 7501-35,000 9 >35 kv 9 +0.37 /kv above 35 kv 21

ELECTRICAL INSTALLATIONS General Requirements OSHA & NFPA (Differences) NFPA Requirements for Interrupting Rating Requirements for Circuit Impedance 22

ELECTRICAL INSTALLATIONS Impedance Impede: : to slow the movement. Grounding conductor must have low impedance to trip a circuit or fuse. 23

Impedance Equations Z=R Hot +R Ground Where: Z is Impedance (Ohms) R Hot is Resistance of Ungrounded Conductor (Ohms) R ground is Resistance of Grounding Conductor (Ohms) 24

Impedance Equations I=V/Z Where: Z is Impedance (Ohms) V is Voltage of System I is Current (Amps) 25

Example 1 A 120 V outlet has been rated at 0.25 ohm over the hot conductor but 5.75 ohm over the grounding conductor. A 30 amp circuit breaker has been installed on the circuit. Will the circuit breaker trip if it detects a problem? 26

Example 1 (Answer) Z=6 Ohm I=20 amps Will the circuit breaker trip if it detects a problem? NO! 20 amps < 30 amps, therefore the circuit breaker will NOT trip. 27

ELECTRICAL INSTALLATIONS Wiring protection & design OSHA & NFPA (Similarities) Identification of conductors Polarity of connections Grounding Methods System Equipment 28

Ungrounded Conductor Grounded Conductor Grounding Conductor 29

Equipment Grounding Conductor 30

ELECTRICAL INSTALLATIONS Wiring Protection & Design OSHA & NFPA (Differences) NFPA GFCI protection for personnel in Bathrooms Rooftops Kitchens 31

GFCI 32

ELECTRICAL INSTALLATIONS Wiring Protection & Design OSHA OSHA & NFPA (Differences) NFPA Outlet Outlet devices shall not have an ampere rating less than the load to be services. 33

Example 2 A receptacle is rated at 20 amperes. The circuit is rated at 15 amperes. Are we in compliance with the requirements for outlet devices? Yes No or No 34

ELECTRICAL INSTALLATIONS Hazardous Locations OSHA & NFPA (Similarities) Class I-Flammable I Liquids Class II-Combustible Dusts Class III-Combustible Fibers 35

ELECTRICAL INSTALLATIONS Hazardous Locations OSHA & NFPA (Similarities) Division 1-Conditions 1 will be present Division 2-Conditions 2 may be present 36

Class I, Division 1 37

Example 3 What is the Proper Classification for a storage room, which will contain closed drums of chemical product containing Acetone and Isopropyl Alcohol (OSHA Classification)? 38

Example 3 (Answer) Class: I Division: 2 39

ELECTRICAL INSTALLATIONS Hazardous Locations OSHA & NFPA (Differences) NFPA now reclassified Class I divisions into zones 40

ELECTRICAL INSTALLATIONS Class Class I, Zone O Ignitable concentrations of flammable gases and vapors are present continuously Examples: Tanks Tanks which contain flammable liquids Spraying Spraying or coating enclosures Open Open vessels containing flammable liquids 41

Class I, Zone 0 (inside tank) 42

ELECTRICAL INSTALLATIONS Class Class I, Zone 1 Ignitable concentrations of flammable gases and vapors are likely to be present under normal operating conditions May exist because of repair or maintenance or because of leakage Locations adjacent to Class I, Zone 0 43

ELECTRICAL INSTALLATIONS Class Class I, Zone 1 Examples: Areas Areas where flammable liquids are transferred from one container to another Adequately vented drying rooms 44

Class I, Zone 1 (outside tank) 45

ELECTRICAL INSTALLATIONS Class Class I, Zone 2 Ignitable concentrations of flammable gases and vapors are NOT likely to be present under normal operating conditions Flammable liquids are normally confined to closed containers Locations adjacent to Class I, Zone 1 locations 46

ELECTRICAL INSTALLATIONS Class Class I, Zone 2 Examples: Flammable liquids or flammable gases are used, but would become hazardous only in the event of an accident or unusual operating condition 47

Example 4 What is the Proper Classification for a storage room, which will contain closed drums of chemical product containing Acetone and Isopropyl Alcohol (NFPA Classification)? 48

Example 4 (Answer) Class: I Zone: 2 49

ELECTRICAL INSTALLATIONS Hazardous Locations OSHA & NFPA (Differences) Equipment Operating Temperature Requirements for Class I equipment 50

Temperature Classification of Class I Equipment Temperature Class T1 T2 T3 T4 T5 T6 Max. Surface Temperature <450 C <300 C <200 200 C <135 C <100 C <85 C 51

Electrical Installations NFPA vs. OSHA OSHA NFPA Reference 1910.301-308 NFPA 70E, Chapter 4 Markings & Identification Workspace Impedance requirements Polarity & Grounding GFCI for restrooms & rooftops Hazardous Locations Class I Divisions Class I Zones 52

What companies are doing for compliance (Electrical Installations) Ensure Ensure equipment installation complies with NFPA 70E Ensure Ensure equipment modification complies with NFPA 70E 53

SAFE WORK PRACTICES

SAFETY RELATED WORK PRACTICES General Requirements OSHA General Industry 1910.331-1910.360 1910.360 Construction 1926.415-1926.417 1926.417 NFPA: NFPA 70E, Chapter 1, Articles 100-130 130 55

SAFETY RELATED WORK PRACTICES Working Working on or near energized electrical parts OSHA & NFPA (similarities) Employees may work with on live energized electrical equipment IF it meets the following criteria: 56

WORKING ON LIVE PARTS (OSHA & NFPA) Increased or additional hazards include interruption of life support equipment, deactivation of emergency alarms, shutdown of hazardous location ventilation systems, or removal of illumination for an area. 57

WORKING ON LIVE PARTS (OSHA & NFPA) Because of infeasibility due to equipment design or operational limitations including testing of electrical circuits that can only be performed with the circuit energized and work on circuits that form an integral part of a continuous industrial process that would otherwise need to be completely shut down in order to permit work on one piece of equipment. 58

WORKING ON LIVE PARTS (OSHA &NFPA ) Employer can demonstrate the de- energizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. 59

SAFETY RELATED WORK PRACTICES Working Working on or near energized electrical parts OSHA & NFPA (similarities) Qualified Person: : ones familiar with the construction and operation of the equipment and hazards involved 60

SAFETY RELATED WORK PRACTICES Working Working on or near energized electrical parts OSHA & NFPA (similarities) Qualified Persons shall be trained in the following: 61

QUALIFIED PERSON TRAINING The The skill necessary to distinguish exposed energized parts from other parts of electrical equipment The The skills necessary to determine the nominal voltage of exposed energized parts Approach distances Personnel Protection 62

What companies are doing for compliance (Training) Classroom training on specific requirements of the standard Personnel protection Flash protection boundaries On the job training specific to job duties 63

SAFETY RELATED WORK PRACTICES Working Working on or near energized electrical parts OSHA & NFPA (Differences) Approach Boundaries OSHA Applies to when qualified persons are working in the vicinity of overhead lines NFPA applies to all work on live parts Employer must perform a Flash Hazard Analysis 64

APPROACH BOUNDARIES Exposed Energized Part Flash Protection Boundary Prohibited Approach Boundary Prohibited Space Restricted Space Limited Space Restricted Approach Boundary Limited Approach Boundary 65

Approach Limits Nominal System Voltage Range Flash Protection Boundary Limited Approach Boundary (Limited Space)-Exposed Fixed Circuit Part Restricted Approach Boundary (Restricted Space) Prohibited Approach Boundary (Prohibited Space) 50 V to 300 V 3.5 ft 3.5 ft Avoid Contact Avoid Contact 301 to 750 V 3.5 ft 3.5 ft 1 ft 1 in 751 to 15 kv 5 ft 5 ft 2 ft 2 in 7 in 15.1 kv to 36 kv 6 ft 6 ft 2 ft 7 in 10 in 36.1 kv to 46 kv 8 ft 8 ft 2 ft 9 in 1 ft 5 in 66

67

Flash Hazard Alerting 68

Flash Hazard Alerting 69

Example 5 What is the flash protection boundary requirement when working on a live 120 V system? 70

Example 5 (Answer) 3.5 feet 71

What companies are doing for compliance (Flash Protection Boundaries) Set-up flash protection boundaries based on the equipment nominal voltage Place Place flash protection boundary requirements in written program and equipment specific procedures Enforce Enforce flash protection boundary requirements 72

What companies are doing for compliance (Flash Protection Boundaries) Flash Protection Boundary: Limited Approach Boundary: Restricted Approach Boundary: Prohibited Approach Boundary: PPE Hazard Level: 73

SAFETY RELATED WORK PRACTICES Working Working on or near energized electrical parts OSHA & NFPA (Similarities) Personnel Protection OSHA refers to Subpart I requirements which refer to ANSI & ASTM standards NFPA also refers to applicable ANSI & ASTM standards 74

Voltage Protection Gloves 75

Lineman Sleeves 76

Voltage Rated Tools 77

Personal Protective Equipment OSHA OSHA & NFPA (Differences) NFPA gives direction according to risk hazard categories Risk Hazard Categories for protective apparel is dependant on the arc thermal protection value of the garment HRC HRC 0-ATPV 0 = N/A HRC HRC 1-ATPV 1 = 5 cal/cm2 HRC HRC 2-ATPV 2 = 8 cal/cm2 78

HAZARD RISK CATEGORY CLASSIFICATIONS Hazard Risk Category Classifications: Panelboards Rated 240 V and below Task (assumes equipment is energized & work is being done within the flash protection boundary) Hazard/ Risk Category V-Rated Glove V-Rated Tools Remove/Install CBs or fused switches 1 Y Y Removal of bolted covers (to exposed bare, energized parts) 1 N N 79

HAZARD RISK CATEGORY CLASSIFICATIONS Protective Clothing & Equipment Hazard/Risk Category Number Protective Systems for Hazard/Risk Category 0 1 Natural Fiber T-Shirt (short sleeve) Shirt (long sleeve) Pants (long) X X X X 80

Example 6 A qualified person will perform install circuit breakers on a 208 Volt panel board? 1. What is the Hazard/Risk Category? 2. One type of protective clothing needed? 3. Are V-rated gloves needed? 4. Are V-rated tools needed? 81

Example 6 (Answer) 1. What is the Hazard/Risk Category? 1 2. One type of protective clothing needed? Natural Fiber Long Pants ATPV = 5 cal/cm2 3. Are V-rated gloves needed? Yes 4. Are V-rated tools needed? Yes 82

What companies are doing for compliance (PPE) Perform Perform risk hazard analysis according to NFPA standards Place Place PPE requirements in written program and equipment specific procedures Enforce Enforce use of PPE when entering flash protection boundary 83

SAFETY RELATED WORK PRACTICES OSHA OSHA & NFPA (Differences) NFPA 70E Electrical Safety Program The employer shall implement an overall electrical safety programs that directs activity appropriate for voltage, energy level, and circuits. Establish Energized Electrical Work Permit System 84

ELECTRICAL SAFETY PROGRAM Components Maintenance of Electrical Hazards Control of Electrical Hazards Procedures 85

ELECTRICAL SAFETY PROGRAM Maintenance of Electrical Hazards Methods of inspection Maintenance of electrical system integrity Assessment of employees ability to perform work 86

ELECTRICAL SAFETY PROGRAM Control Control of Electrical Hazards Training Identification of tasks to be performed on or near energized parts Use and identification of of precautions appropriate for environment 87

ELECTRICAL SAFETY Procedures PROGRAM Approach limits PPE to be used Insulating tools and equipment to be used 88

What companies are doing for compliance (Written Program & Procedures) Equipment specific procedures Establish Establish energized electrical work permit program Establish Establish Energized Electrical Work Permit System 89

ENERGIZED ELECTRICAL WORK PERMIT Building Name Date: Work to be performed: Electrical PNL # Qualified Persons Involved: 1. 2. 3. 4. a. Purpose of task b. Qualification and number of employees involved. c. Approach limits. 1. Qualified Person Minimum Working Distances 2. Flash Protection Boundaries d. Other safe work practices, which will be used. Flash Protection Boundary: Limited Approach Boundary: Restricted Approach Boundary: Prohibited Approach Boundary: e. PPE to be used. f. Insulating materials/tools to be used. PPE Hazard Level: 0 1 2 3 4 Voltage Rated Gloves: 00 0 1 2 3 4 Voltage Rated Tools: Y N g. Electrical diagrams. 90

Safety Related Work Practices NFPA vs. OSHA Reference Working on Live Parts Qualified Person/Training Approach Boundaries ALL work OSHA 1910.331-360 NFPA NFPA 70E Chapter 4 Personal Protective Equipment Electrical Safety Program Energized Electrical Work Permit Refers Subpart I Risk Hazard According to Voltage 91

92

93

94

95

96

97

98

99

100

101

102

THE END 103