PANASONIC TROUBLE SHOOTING GUIDE



Similar documents
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

14. Troubleshooting Guide

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Failure code manual. content

ABNORMAL OPERATION Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

Split and Multi Split air conditioners Service information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

Simple Self-Diagnosis by Malfunction Code

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM EXPLOSION VIEW 12 6.

HEATER, AIR CONDITIONING AND VENTILATION

Haier Air conditioner

Instruction manual for Firstline FCS12000CH

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

, User s Manual

SERVICE & MAINTENANCE MANUAL

SMM. Installation Operation Maintenance

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Technical service manual 2009

SiBE D-Series / E-Series. [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

Midea Commercial Air Conditioner Malfunction Handbook

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM EXPLOSION VIEW 16 6

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

SiUS Service Manual. RZR-P, RZQ-P(9) Series Cooling Only / Heat Pump R-410A 60Hz

USER S MANUAL. Duct Type Series. Free Joint Multi Air Conditioner (Cooling and Heating) FUEA Series E S F I P D G DB A(1) ENGLISH ESPAÑOL

SERVICE & MAINTENANCE MANUAL

SWIMMING POOL HEAT PUMP (THP 55, THP 100, THP 120, THP 170) INSTALLATION AND USER GUIDE

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

Fault Code Check List

york air-conditioning products Residential & VRF News 2015

HITACHI INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS

Split Air Conditioner

Aerona Air Source Heat Pumps

AIR-CONDITIONER SPLIT TYPE

Technical service manual

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

evo+ Installation, Service & Troubleshooting DUCTLESS SYSTEM

HEAT SIPHON ANSWERBOOK

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

A/C-HEATER SYSTEM - AUTOMATIC

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

Oil and Coolant Circulating Heating System. Model - OCSM

Technical Information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

SiUS Service Manual. Inverter Pair FTXS-L Series FDXS-L Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump

How To Measure Temperature On A Thermostat

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC

Troubleshooting Your Refrigerator

technical data air conditioning systems RXS E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

SERVICE MANUAL INDOOR UNIT

User s Information/Installation Instructions

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump

10 tips for getting more reliability from your air-conditioning system [reliability]

SWIMMING POOL HEAT PUMP Owners Manual

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SiUS Service Manual. Inverter Pair Wall Mounted Type K-Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump

Install Guide CT101. Caution. Caution

USER S MANUAL HSC-24A

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

Room Air Conditioner SVC MANUAL(General)

AIR CONDITIONER Duct Type OPERATING MANUAL

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

HP switch LP switch Discharge thermo Comp. Surface thermo

FULL DC INVERTER SYSTEMS

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book

Operating Instructions Air Conditioner

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

How To Wire Wire Wire A Power Supply On A Powerline (Powerline) From A Powerstation To A Powerplant (Powerplant) (Powerplant) (Control Board) (Wire) (Switchboard) (Wired) (

AIR CONDITIONER (SPLIT TYPE)

How To Power A Car With A Fan And A Fan (Power)

AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

4 Alarm and info. Alarm. Yes Warning. No Information No Reset alarms > No Current list > Alarm log list > Delete alarm log > No

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type )

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March Emerson Electric Co. All rights reserved.

SWIMMING POOL HEAT PUMP

SERVICE MANUAL INDOOR UNIT

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.

Heat Pump Installation, Maintenance and Service Manual

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

Transcription:

A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling mode both pipes should be between 0 and 10C - the suction line should sweat, but not freeze In heating mode both pipes should be between 30 and 60C Pipework should be refrigeration quality Look for restrictions. They could cause compressor failures. Outdoor Unit Discharge Temperature should be between 50 and 70C Suction Temperature should be between -3 and 4C Check Suction Line is sweating in cooling - problem if not! Hot Recip. Compressor = PROBLEM Sweating/Frost on expansion line - undercharged Indoor Unit Is it level? Have we adequate drainage? Smells are always due to site conditions or drains. Flashing lights? = Fault Diagnostics - see over When were the filters last cleaned? Is the unit too large/small (between 5/20 air circs/hr) Is the air short cycling? Controller Is it a wired or wireless handsets. Is the handset too far away? When were the batteries changed last? With wired handset, check for interference. Is the unit in Emergency Mode? Check unit and controller channels compatible Wiring Interconnecting comms wiring is low voltage If you have 230V live, check you have a neutral as well Check Mains and comms cable not swapped round Multi linked systems must be set up as such Check voltage drops! Check it isn t down to Earth! Interconnecting cables should be circular crimped Every unit has an Emergency (marked Auto (Off/On) button Wire E 1 2 3 4 Pressing this for less than five seconds initiates Emergency Operation Cool Only Earth Live Neutral N/A N/A Pressing this for seven seconds initiates Test Cooling Heat Pump Earth Live Neutral Heating Defrost Pressing this for ten seconds initiates Test Heating Inverter Earth Live Neutral Comms N/A Sensor Resistances - Use to check Thermistor Sensor readings are the same for both indoor and outdoor units. If the fault code suggests the sensor is a problem but you get Sensor At 10C At 20C At 30C a sensor reaading as to the righ then either the Connection or Indoor Air All 30K 0hms 18K 0hms 12K 0hms PCB is at fault Indoor Pipe All 40K 0hms 25K 0hms 16K 0hms Outdoor Air Singles 30K 0hms 18K 0hms 12K 0hms Outdoor Pipe Singles 10K 0hms 6K 0hms 3K 0hms Compressor Singles 100K 0hms 60K 0hms 40K 0hms All Outdoor Multis 40K 0hms 25K 0hms 16K 0hms 136

Fault Diagnostics Fault Codes are only used on Inverter Systems. Both Single and Super Multi Inverter Systems use the same fault codes as below. Outdoor Codes are ONLY used by the Super Inverter Multi systems models 23 and 27, NOT single systems. When a Fault Occurs the Timer Lamp wil start flashing and the unit stops Turning the Power Off will reset the unit but will not clear the fault code The unit will remember up to three fault codes. To fund the fault code Ensure power is on at the unit and point the remote controller at it so a signal can be received For single systems (CSE and CSXE) press the CHECK button for more than 5 seconds For Multi systems (CSME) press the Timer Setting Up Arrow for more than five seconds H11 will appear on the Remote Control Display - this indicates that Interrogate Mode is Operational Use the Timer Setting Up and Down Arrows to scroll between fault codes until four beeps are heard - this shows the Fault Code Fault Codes are cleared from memory by setting Test Cooling and shorting the RESET terminals in the controller battery compartment. Code Outdoor LEDS - CU3E23 & CU4E27 Only Meaning Likely Cause Reference LED 1 LED 2 LED 3 LED4 H11 Off Off Off Off Comms Failure Faulty Wiring or other problem with ID to OD communication H12 Off Off Off Off ID/OD Compatibility Problem Over or Underindexed multi system H14 Off Off Off Off Indoor Air Sensor Faulty Sensor Disconnected, Faulty or Contacts Dirty H15 Off Off Off Off Compressor Sensor Faulty Sensor Disconnected, Faulty or Contacts Dirty H16 On On Off Off Current Transformer Problem Power Transistor Module or Outdoor PCB Faulty. Very Low Gas H19 Off Off Off Off Indoor Fan Motor Locked Fan Motor of Indoor PCB Failure H21 Off Off Off Off Float Switch Operated Check Drainage H23 Off Off Off Off Indoor Pipe Sensor Faulty Sensor Disconnected, Faulty or Contacts Dirty H27 Off Off Off Off Outdoor Air Sensor Faulty Sensor Disconnected, Faulty or Contacts Dirty H28 Off Off Off Off Outdoor Pipe Sensor Faulty Sensor Disconnected, Faulty or Contacts Dirty H30 Off Off Off Off Outdoor Discharge Sensor 1 Faulty Sensor Disconnected, Faulty or Contacts Dirty H32 Off Off Off Off Outdoor Discharge Sensor 2 Faulty Sensor Disconnected, Faulty or Contacts Dirty H33 Off Off Off Off Incorrect Connection Voltage Indoor or Outdoor Voltage Incorrect/Faulty Wiring H34 Off Off Off On Outdoor Heat Sink Sensor Faulty Sensor Disconnected, Faulty or Contacts Dirty H36 Off Off Off Off Outdoor Gas Sensor Faulty Sensor Disconnected, Faulty or Contacts Dirty H37 Off Off Off Off Outdoor Liquid Sensor Faulty Sensor Disconnected, Faulty or Contacts Dirty H39 Off Off Off Off Abnormal Indoor Operation Incorrect Piping or Expansion Valve Problem H41 Off Off Off Off Abnormal Wiring or Piping Wiring or Piping Crossed ona Twin System H97 Off Off Off Off Outdoor Fan Failure Outdoor Fan Motor or PCB Failure H98 On Off On On Indoor Coil Overheat (Heat Mode) Dirty Filters or Indoor Coil. Very High Room Temperature H99 On Off On On Indoor Coil De-Ice (Cool Mode) Dirty Filters or Indoor Coil. Low Gas Charge or Low Ambient Temp F11 On Off Off Off Reversing Valve Failure Faulty Reversing Valve, Coil or Outdoor PCB F17 On Off On On Standby Units Freezing Multi Only. Expansion Valve Leakage F90 On Off Off On PFC Failure Problem with Inverter or Compressor F91 Off Off On On Refrigeration Cycle Problem Low Gas or Blockage F93 Off On On Off Compressor Abnormal Revolution Compressor Running Incorrectly F95 Off Off Off Off Outdoor Coil Overheat (Cool Mode) Dirty Condensor Coil, low gas or blockage F96 Off Off Off Off IPM or Compressor Overheating Excess or Low Gas Charge or dirty heat exchanger F97 On On On On High Discharge/Compressor Temp Low Gas Charge or Failed Compressor F98 Off On Off On Overcurrent Protection Outdoor Heat Exchanger Problem. Excess Gas F99 Off Off On Off DC Overcurrent Protection Outdoor PC, Power Transistor or Compressor Failure None On On Off On Control Box Overheating Maintenance Required on OD Unit For models CU3E23 & CU4E27 only there is a Green LED which normally flashes If this is LIT then turn the power Off then On again. If it still does not flash the Outdoor PCB is Faulty. If this is Off then there is a problem with the power supply. All prices shown are retail and are exclusive of VAT at 17.5% Air Conditioning Guide 137

Panasonic Free Style Products General comments for Pipework, Indoor & Outdoor Units In general the Free Style product follows the notes for US Systems These are shown on page 140. Model specific comments and Fault Codes are shown here. Wiring Schedule At Handset press RUN then TEST BUTTONS Series E 1 2 3 4 At OD UNIT press TEST HEAT or TEST COOL button R22/R407C Earth Live Neutral Comms Comms Unit will run for 30 minutes in test mode R410a Earth Live Neutral Comms Comms For R410a models gas pipe temp will be displayed. Sensor Resistances Use these to check sensors Sensor At 0C At 10C At 20C At 30C All values in KOhms R22/407C Air Sensor 67K 40K 25K 16K R22/407C Pipe Sensor 67K 40K 25K 16K R410a Air Sensor 51K 30K 19K 12K R410a ID Pipe 67K 40K 25K 16K R410a OD Disch 168K 101K 63K 40K R410a OD Pipe (X3) 16K 10K 6K 4K Fault Diagnostics Older Style FS Units R22 First generation series 11NP Series with E style fault codes Press check on the Wired Controller to call up the Fault Codes. Fault Code Indoor Unit PCB Meaning At Remote LED1 LED2 LED3 Of Fault Code E1 Flash Flash Flash Signal from RC to ID Unit faulty E2 Lit Float Switch E3 Lit Air Sensor Faulty E4 Lt Pipe sensor Faulty Second Generation 21NP Series with F Fault Codes Press Check on the Wired Controller to call up the Fault Codes Fault Code Indoor Unit PCB Outdoor Unit PCB Meaning At Remote LED1 LED2 LED3 LED4 LED1 LED2 LED3 LED4 Of Fault Code F2 Lit Lit Lit Lit Float switch F3 Lit Lit Indoor Air Sensor Faulty F4 Lit Lit Indoor Air Sensor Faulty F5 Lit Lit Lit Lit Lit Signal from RC to ID faulty F5 Lit Lit Lit No Signal from ID to RC F6 Lit Lit Lit Lit Signal from ID to OD faulty F6 Lit Lit Lit No Signal from Od to ID F13 Lit Lit Lit OD Unit Overcurrent Protection F15 Lit Lit Lit HP Switch F18 Lit Lit Lit Outdoor Pipe Sensor Faulty Third Generation 32JP Models and Later Press Check on the Wired Handset and use the Fault Codes on the next page. Please Note: The LED codes shown are not applicable to R22/R407c units but the F codes are 138

Fault Codes FS Series Current Models R410a Pressing Check on the wired remote while CHECK is flashing will give the Fault and the address of the unit with the Fault Pressing Timer Set with the fault displayed will display a second code giving further information (detail code) Pressing Check for 5 seconds will check past faults On wireless handsets press the temp up for 5 seconds to enter error check mod Scroll through the codes using the temp up button until a beep is heard from the indoor unit Press set and repeat until the full code is displayed F Code Detail Outdoor LED Meaning Display Display 302 303 304 305 306 307 308 309 Of Code F15 O1 Flash Flash Flash Flash See Note 1 Drain Failure F16 O1 Flash See Note 1 Louvre Failure F17 O1 See Note 1 Option Problem F17 O2 Flash Flash Flash See Note 1 DC Fan Motor Failure F20 O1 Flash Flash See Note 1 ID Air Sensor F20 O2 Flash Flash Flash See Note 1 RC Air Sensor F21 O1 Flash Flash Flash See Note 1 ID Pipe Sensor F25 O1 Only for Older Models with LEDS 1-6 See Note 1 Addressing Incorrect F26 O1 Flash Flash Flash See Note 1 RC Comms Problem F27 O1 Flash Flash Flash Flash See Note 1 ID - OD Comms Disconnected ID F27 O2 Only for Older Models with LEDS 1-6 See Note 1 ID - OD Comms Connection ID F27 O5 Flash Flash Flash Flash Flash See Note 1 ID - OD Comms Connection ID F27 O1 Flash Flash Flash ID - OD Comms Disconnected OD F27 O2 Only for Older Models with LEDS 1-6 ID - OD Comms Connection OD F27 O5 Flash ID - OD Comms Connection OD F29 O1 Only for Older Models with LEDS 1-6 ID PCB Setting F30 O1 Flash ID/OD Capacity Incorrect F30 O2 Flash Flash Phase Rotation F31 O1 Flash Low Pressure F31 O2 Flash High Pressure F31 O6 Flash Flash Reversing Valve F31 O8 Flash Flash Indoor Coil Iced F31 O9 Flash Flash Flash Gas Leak F31 10 Flash Flash Flash Low Gas, Valve Shut or Blockage F32 O3 Flash Flash Inverter Low dc Volts F32 O4 Flash Flash Flash Inverter IPM F32 O5 Flash Flash Compressor Overcurrent F32 O6 Flash Flash Flash Compressor Disch Temp High F32 O8 Flash Flash Flash Inverter PFC F32 O9 Flash Flash Inverter High dc Volts F32 10 Flash Flash Flash Compressor Rotation Problem F33 O1 Only for Older Models with LEDS 1-6 Compressor High Current F33 O2 Only for Older Models with LEDS 1-6 High Discharge Temp F35 2 Flash Flash OD dc Fan Motor Locked F40 O1 Flash OD Outlet Sensor F40 11 Flash Suction Temp F40 21 Flash Flash OD Liquid Sensor F40 31 Flash Flash Flash Defrost Sensor F40 51 Flash Flash Discharge Sensor F40 41 Only for Older Models with LEDS 1-6 Discharge Sensor F40 61 Only for Older Models with LEDS 1-6 OD Pipe Sensor F41 O2 Flash Flash Flash HP Switch F41 O3 Only for Older Models with LEDS 1-6 Heating HP Switch F41 11 Flash Flash Low Pressure Sensor F42 O1 Only for Older Models with LEDS 1-6 Compressor Current Sensor F42 11 Flash Flash Current Sensor Open F44 O1 Flash Flash Inverter IPM Sensor F49 O1 Only for Older Models with LEDS 1-6 OD PCB Setting Faulty F49 O2 Only for Older Models with LEDS 1-6 OD PCB Setting Faulty Note 1: LED308 is lit if the master unit is the problem or 309 for the slave LED 301 is lit when power is supplied to the PCB All prices shown are retail and are exclusive of VAT at 17.5% Air Conditioning Guide 139

A General Guide To Urban Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling mode the suction line should sweat, but not freeze In heating mode both pipes should be between 30 and 60C Pipework should be refrigeration quality Look for restrictions. They could cause compressor failures. Outdoor Unit Discharge Temperature should be between 50 and 70C Suction Temperature should be between -3 and 4C Check Suction Line is sweating in cooling - problem if not! Hot Recip. Compressor = PROBLEM Sweating/Frost on expansion line - undercharged Indoor Unit Is it level? Have we adequate drainage? Smells are always due to site conditions or drains. Flashing lights? = Fault Diagnostics - see over When were the filters last cleaned? Is the unit too large/small (between 5/20 air circs/hr) Is the air short cycling? Controller Is it a wired or wireless handset. Is the handset too far away? When were the batteries changed last? With wired handset, check for interference. Is the unit in Emergency Mode? Check unit and controller channels compatible Wiring Interconnecting comms wiring is low voltage If you have 230V live, check you have a neutral as well Check Mains and comms cable not swapped round Multi linked systems must be set up as such Check voltage drops! Check it isn t down to Earth! Interconnecting cables should be circular crimped Selecting Emergency Mode is done at the Indoor and Outdoor Unit PCB. It bypasses the Control Sensors and should not be done for more than 30 minutes. Indoor PCB - Switch SS1 to Emergency Setting Wire E 1 2 3 Outdoor PCB - Switch Emergency Switch 1 to ON All Earth Live Neutral Comms Outdoor PCB - Switch Emergency Switch 2 to Cool or Sensor Resistances Use to check Thermistor Air and Pipe sensors apply to indoor AND outdoor units. Sensor At 10C At 20C At 30C The discharge sensor is only in the outdoor unit. Air Sensor 40K 0hms 25K 0hms 16K 0hms If the fault code suggests the sensor is a problem but you Pipe Sensor 40K 0hms 25K 0hms 16K 0hms get a sensor reading as to the right then either the connection Discharge Sensor 480K 0hms 293K 0hms 184K 0hms or PCB is at fault. TECHNICAL SUPPORT: 08705 218218 140