TROU BLE SHOOTING VIKING ALARM VALVES
|
|
|
- Ada Newton
- 10 years ago
- Views:
Transcription
1 TROU BLE SHOOTING VIKING ALARM VALVES 1
2 TROUBLESHOOTING THE VIKING MODEL E, F, AND G ALARM VALVES What are the symp toms of the sys tem? 1) Are alarms ring ing in ter mit tently? a) It is prob a bly the aux il iary valve clap per rub ber that has worn out, and now you have a metal to metal seat, and wa ter is leak ing by and out to the wa ter mo tor gong. Suggest in spect ing the aux il - iary valve clap per and re plac ing it if the rub ber face is worn or gone. The cus tomer must use an aux il iary valve set ting tool to ad just the aux. valve clap per. b) Air is trapped in the sys tem pip ing 1) Has the sys tem re cently been drained down and re filled? If so, it may have been filled too quickly, and air was trapped in side. The air can be com pressed when a surge in pres sure hap pens, then the air com presses, causes the clap per to re-close, and it will con tinue to cy cle this way, each time there is a surge, and it will fill the re tard cham ber, then cause in ter mit tent alarms. 2) Does the valve have a re tard cham ber? If yes, then does it have a cir cuit closer vent trim if there is no wa ter mo tor gong on the retard cham ber? A cir cuit closer vent trim is used to vent the pres sure switch mounted on top of the re tard cham ber. With out the cir cuit closer vent trim, it acts the same as when a straw is put into a glass of wa ter and your thumb is held on top. When you re move the straw from the glass, the wa ter stays in the straw un til you remove your thumb. The cir cuit closer vent trim does the same thing by break ing the vac - uum in the re tard cham ber. 2
3 VIKING MODEL E ALARM VALVE 3
4 VIKING MODEL F-1 ALARM VALVE 4
5 VIKING MODEL G-1 ALARM VALVE 5
6 VIKING MODEL B-2 RETARDING CHAMBER (OBSOLETE) 6
7 VIKING MODEL B-2 RETARDING CHAMBER (OBSOLETE) 7
8 TROUBLESHOOTING THE VIKING MODEL E, F, AND G ALARM VALVES, CONTINUED What are the symp toms of the sys tem 3) Re tarding Cham ber (con tin ued) Have the or i fices in the Model B Re tarding Cham ber been checked to see if they are open? Plugged or i fices will also cre ate a vac uum in the re tard cham ber trim and cause the alarms to ring ei - ther in ter mit tently or con stantly, as the vac uum can not be bro ken if the drain or i fice is plugged at the bot tom of the re tard cham ber. Note:The orifice at the bot tom of the model B Re tard Cham ber is part of the drain plug as sem bly. To re place this orifice, the com plete drain plug as sem bly must be re moved and re placed. the re tard cham ber must be heated up, so that the drain plug as sem bly can be re moved. (The heat ex pands the re tard cham ber, and then the drain plug as sem bly can be bro ken away from the re tard cham - ber. Re mem ber that these re tard cham bers have been in ser vice for a long time, and they are prob - a bly quite rusted.) Note: Model E Alarm Valves have a very small hand hole cover which makes it difficult to access the aux il iary valve clap per. Therefore, un less the cus tomer only needs to re move the aux. valve clap - per or clap per rub ber, the valve would need to be re moved from the riser and dis as sem bled. There is no rea son to day to do this, as there are no other ser vice able parts avail able. Re placing the valve with a cur rent model is the best fix for this sit u a tion. 8
9 TROUBLESHOOTING THE VIKING MODEL H, H2, AND J-1 ALARM VALVES What are the symp toms of the sys tem? 1) Are the alarms ring ing in ter mit tently? Once again, in ter mit tent alarms are usually caused by air being trapped in the sys tem. If the sys tem is a new in stal la tion or has re cently been added on to or re vised, then it is very likely that air is trapped in the sys tem, and it causes the clap per on the EZ Riser or H, H2 or J-1 to open and close (cycle), thereby caus ing in ter mit tent alarm ing. The con trac tor will have to go back, drain down the sys tem, open all aux il iary drains, then re-fill it, shut ting off each low point drain when a steady stream of wa - ter flows from it. Stacking an other C-1 re tard cham ber on top of the orig i nal one may also help to ab sorb the cy cling alarm wa ter, al low ing it to run to drain be fore it can ring the alarm. When does the cy cling oc cur? There may be a fire pump test go ing on at the time of the cy cling, and the pump could be causing surges in the wa ter pres sure. There also may not be a cir cuit closer vent trim on the re tard cham - ber, if there is no wa ter mo tor alarm gong. Therefore, a cir cuit closer vent trim would break the vac - uum in the re tard cham ber, re liev ing the trapped pres sure on the pres sure switch. 9
10 VIKING MODEL H-2 ALARM VALVE 10
11 VIKING MODEL J-1 ALARM VALVE 11
12 TROUBLESHOOTING THE VIKING MODEL H, H2, AND J-1 ALARM VALVES, CONTINUED 2) Is there an in ter mit tent alarm when the in spec tor s test valve is opened? There may be some air trapped in the sys tem, causing air com pres sion in the pip ing, and the clap per of the alarm valve will cy cle open and closed when there is a flow equiv a lent to only one sprinkler. One way to try and al le vi ate this prob lem is to sug gest that the con trac tor in stall a ball valve in the in spec - tor s test line, rather than a globe valve, as the ball valve does not re strict the wa ter flow like a globe valve would. Make the pip ing 1 all the way out to the sprin kler test or i fice can also help the sit u a - tion, as NFPA does not al low for pip ing smaller than 1 on sprin kler sys tems other than for res i den - tial. NFPA 13 does allow for an in ter mit tent alarm any way,(see NFPA 13, 1996 Edi tion, Para , this para graph. does not state that a con stant alarm is re quired, only that it results in an au di ble alarm within 5 min utes af ter the flow be gins, and un til such flow stops.) 12
TECHNICAL DATA. NOTES: For use with Trim Chart on page 27 b. (open fold-out)
De cem ber 6, 1999 Trim 27 a MODEL J-1 ALARM CHECK VALVE VERTICAL TRIM Maximum 250 PSI WWP This Trim Chart is for use with the following Viking Trim Sets Valve Size Standard* Trim P/N Foam System** Trim
Maintenance and Trou ble shoot ing Guide
SGH Steam Gen er ating Hu mid i fiers Maintenance and Trou ble shoot ing Guide IMPORTANT: Read and save this guide for future reference. This guide to be left with equipment owner. SL-14060 Form # 99-427
INSTALLATION INSTRUCTION
FORM# 571C-0411 (571C-0610) I - SHIP PING AND PACK ING LIST Package 1 of 1 contains: 1 - Economizer Assembly 1 - Fresh Air Hood w/ Filter 1 - Control Package 1 - Barometric Relief Hood 1 - Filter Access
SM 3300 - Interface modules
Vissersdijk 4 4301 ND Zierikzee The Netherlands Tel. +31 111 413656 Fax. +31 111 416919 www.deltapowersupplies.com DELTA ELEKTRONIKA B.V. SM 3300 - Interface modules Mod els Description INT MOD M/S Master/Slave
Child Abuse and Ne glect
Child Abuse and Ne glect A guide for par ents in volved in child abuse or ne glect cases in New Jersey 2015 Le gal Ser vices of New Jer sey Le gal Ser vices of New Jer sey makes this pub li ca tion avail
SM 3300 - Series 3300 W DC POWER SUP PLIES
Vissersdijk 4 4301 ND Zierikzee The Netherlands Tel. +31 111 413656 Fax. +31 111 416919 www.deltapowersupplies.com DELTA ELEKTRONIKA B.V. SM 3300 Series 3300 W DC POWER SUP PLIES One or Three phase input
ES 150 - Series 150 W DC POWER SUP PLIES
Vissersdijk 4 4301 ND Zierikzee The Netherlands Tel. +31 111 413656 Fax. +31 111 416919 www.deltapowersupplies.com DELTA ELEKTRONIKA B.V. ES 150 - Series 150 W DC POWER SUP PLIES Mod els Volt age range
3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
TECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
LSNJ...justice for all
a g l Educa t Le H LSNJ io...justice for all n s a n d b o ok Copyright 2010 Legal Services of New Jersey All rights reserved. No part of this handbook may be reproduced without permission. For further
Wet System. Technical Manual for Operation, Maintenance, and Troubleshooting
Wet System Technical Manual for Operation, Maintenance, and Troubleshooting October, 2008 Form No. F_010508 Page II October 15, 2008 Table of Contents Page I. DESCRIPTION 3 II. APPLICATIONS 4 III. REQUIREMENTS
ASCENT TM Integrated Shipment Management
ASCENT TM Integrated Shipment Management Software Solutions Production mail Shipping systems Copier systems Facsimile systems Mailing systems Management services Financial services Consulting Supplies
Potter Electric Sprinkler Monitoring Training Manual
R Potter Electric Sprinkler Monitoring Training Manual 1 #8704200D 2 Contents Foreword... 4 Introduction... 5 Fire Alarm Signals... 6 Types Of Sprinkler Systems... 7 Wet Pipe Sprinkler Systems... 8 Straight
Diameter 3" 4" 6" 8" Flange type PN 16 PN 16 PN 16 PN 16. Orange-red ( RAL 2002) Height (cm) 27,70 26,30 28,70 29.70
Description Usually, a wet alarm valve station comprise: a Rolland wet alarm valve linked to the water motor gong. a set of valves and by pass used to test the system. a drain valve. a test valve gauges
SM 6000 - Se ries 6000 W DC POWER SUP PLIES DELTA ELEKTRONIKA B.V. Mod els Volt age range Cur rent range. Three phase input
Vissersdijk 4 4301 ND Zierikzee The Netherlands Tel. +31 111 413656 Fax. +31 111 416919 www.deltapowersupplies.com DELTA ELEKTRONIKA B.V. SM 6000 - Se ries 6000 W DC POWER SUP PLIES Three phase input Mod
BERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
Wet alarm valves. Wet alarm valves. FM trim
Description Usually, a wet alarm valve station comprise: - a Rolland wet alarm valve linked to the water motor gong. - a set of valves and by pass used to test the system. - a drain valve. - a test valve
Installation, Maintenance, & Repair Series 909, LF909, 909RPDA, LF909RPDA Reduced Pressure Zone Assemblies Reduced Pressure Detector Assemblies
Watts 909 OSY shown Designed for inline servicing RP/IS-909/909RPDA Installation, Maintenance, & Repair Series 909, LF909, 909RPDA, LF909RPDA Reduced Pressure Zone Assemblies Reduced Pressure Detector
' Jan. 24, 1967 E. M. WOODFORD 3,300,697 HYDRAULIC STARTI-NG DEVICE FOR AN ELECTRIC MOTOR WHICH DRIVES HEAVY MACHINE ELEMENTS.
' Jan. 24, 1967 E. M. WOODFORD 3,300,697 HYDRAULIC STARTI-NG DEVICE FOR AN ELECTRIC MOTOR WHICH DRIVES Filed Nov; 21, 1963 3 Sheets-Sheet l vyhuii I / f: all; I Ti * ////////////. j y l l -_ \ s/e/wssr
Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
(12) Patent Application Publication (10) Pub. No.: US 2003/0035525 A1 Wu et al. (43) Pub. Date: Feb. 20, 2003
(19) United States US 20030035525A1 (12) Patent Application Publication (10) Pub. No.: US 2003/0035525 A1 Wu et al. (43) Pub. Date: (54) (76) (21) (22) SYSTEM AND METHOD FOR DISTINGUISHING TELEPHONE NUMBER
TRANSLATING CIRCUITS
' mg. 7, 1923. I > _ 1,463,795 J. R. CARSON TRANSLATING CIRCUITS Filed Oct. 10, 1918 \ \w 7 INVEN TOR. ATTORNEY. ' ' ; 55 Patente ug. 7, 1923. 1,463,795 STATS PATENT OFFKIE. _ JOHN R. CARSON, OF'NEW YORK,
TROUBLESHOOTING FLOW CHART
TROUBLESHOOTING FLOW CHART Revised and updated on January 16, 2003, by Tony Leger and Automation Lab Technology. FACScan(FC)\FACSort(FST) FACScalibur (FCB) Fluidics/Pneumatics troubleshooting guide DCM
A. 70 National Electrical Code (NEC). B. 72 National Fire Alarm Code. C. 90A Installation of Air Conditioning and Ventilating systems.
SECTION 280513 % FIRE ALARM SYSTEM 1.0 This section is intended to define the general configuration, layout, installation and testing re quirements for the various fire alarm systems at the University
Pr o d u c t In f o r m at i o n V008.0
AGF Manufacturing Inc. Pr o d u c t In f o r m at i o n V008.0 Reliability, Versatility, Code Compatibility BK002 COLLECTa ndrain The COLLECTa ndrain family of products are anti-trip drum drips that prevent
BERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
Brake Lock Application Guide
Brake Lock Application Guide Many commercial vehicles, as well as recreational and off-highway vehicles, require that they remain stationary while performing the functions for which they were designed.
RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID
MODEL SH SUBMERSIBLE SOLIDS HANDLING PUMP INSTALLATION AND SERVICE MANUAL. For use with product built with Marathon motor.
MODEL SH SUBMERSIBLE SOLIDS HANDLING PUMP INSTALLATION AND SERVICE MANUAL For use with product built with Marathon motor. NOTE! To the installer: Please make sure you provide this manual to the owner of
TUITION, FEES AND OTHER FINANCIAL INFORMATION General Information
TUITION, FEES AND OTHER FINANCIAL INFORMATION General Information The ex penses for each se mes ter will vary ac cord ing to the per sonal needs of the stu dent and the course of study pur sued. The tu
Real Life Online Seminars. HEART of Accounting. The. John W. Day, MBA. A 4-hour course for non-accountants!
Real Life Online Seminars The HEART of Accounting TM A 4-hour course for non-accountants! John W. Day, MBA Real Life Online Sem i nars Pres ents The HEART of Account ing A 4-Hour Step-By-Step Course That
Model RV-1 Pressure Relief Valve 2 to 8 Inch (DN50 to DN200), 250 psi (17,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description
Technical Services 00-3-932 +-0-7-220 www.tyco-fire.com Model RV- Pressure Relief Valve 2 to Inch (DN50 to DN200), 250 psi (7,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description The
MODEL BQ TECHNICAL BULLETIN BQ-TB 12-14 BACK PRESSURE / RELIEF REGULATOR FEATURES APPLICATIONS CAUTION
TECHNICAL BULLETIN 12-14 MODEL BQ BACK / RELIEF REGULATOR The Model BQ is a relief regulator suitable as a back pressure regulator or bypass valve for controlling inlet pressures between 5 and 300 psig
FIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)
Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0.6 bar -to- 1.9 bar) Max 3. Reset externally. Cover removal is not
WAR NING S E C TION 1 : INTR ODUC TION HIG H V OLT AG E S C AN K ILL. 1.2.2 TC -V2 digital controller. 1.1 S afety P reca utions (WAR NING S )
S E C TION 1 : INTR ODUC TION 1.1 S afety P reca utions (WAR NING S ) T his manual covers the ins tallation, operation and maintena nce of the T C S 3P 125 Automatic T rans fer S witch. It is intended
lert AMarket solutions to public policy problems
Fraser lert AMarket solutions to public policy problems April 21 The Canadian Consumer Tax Index, 21 Main Conclusions The Canadian Consumer Tax Index tracks the total tax bill of the average Canadian family
MODEL HP-1+6+S HP-S-DIFF-TB 03-16 TECHNICAL BULLETIN "HIGH" PRESSURE DIFFERENTIAL REDUCING REGULATOR CAUTION FEATURES
TECHNICAL BULLETIN HP-S-DIFF-TB 03-16 ISO Registered Company MODEL HP-1+6+S "HIGH" PRESSURE DIFFERENTIAL REDUCING REGULATOR Model HP-1+6+S is a heavy duty, high pressure reducing differential regulator.
THE PASCHAL PROCLAMATION. Longer form of the Paschal Proclamation
The Deacon, after incensing the book and the candle, proclaims the Easter Proclamation (Exsultet) at the ambo or at a lectern, with all standing and holding lighted candles in their hands. The Easter Proclamation
Division 21. Fire Suppression
21 00 00. Fire Suppression For campus projects that require a fire suppression system shut down in a campus facility, a Shut Down Procedure of Fire Safety System Sheet must be completed and filed seven
IMPACT SPRINKLER TROUBLESHOOTING GUIDE
RAIN USE AND OPERATION BIRD IMPACT SPRINKLER TROUBLESHOOTING GUIDE The diagrams below depict typical Rain Bird sprinklers with all available controls. Your particular model may have only some of these
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
8 plumbing. plumbing. 2010 PulteGroup, Inc. All Rights Reserved.
8 90 2010 PulteGroup, Inc. All Rights Reserved. drains All the water you use leaves the home through a drain. Maintaining drains prevents clogging, overflows, water damage, and other problems. care and
KODAK VERSAMARK, INC.
KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF
ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL
ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL The Viking Corporation 210 N Industrial Park Road Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:
EFSN Training i Module 1. 90 Minutes
Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007
TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES 301.010 ANNUAL SERVICE TEST FOR FIRE HOSE EFFECTIVE: OCTOBER 2007 The Department will test all fire hose annually. The testing of fire hose determines its serviceability.
Fire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
TECHNICAL DATA. 30a. September 18, 2009 1-1/4-8 (DN32 - DN200)
September 18, 2009 30a 1. DESCRIPTION Viking EasyPac Commercial Riser Manifold Assemblies are available in sizes 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 6 and 8 for commercial systems. They are available with an
Carburetion Troubleshooting Quick Reference Guide
Carburetion Troubleshooting Quick Reference Guide SERVICE DIAGNOSTIC OVERVIEW A logical, planned approach can move service work through a repair center in a smooth and efficient manner. Fueled by information
MULTILINK 8 IN PUTS 8 OUTPUTS INTERFACE/PERIPHERAL ML-8
MULTILINK 8 IN PUTS 8 OUTPUTS INTERFACE/PERIPHERAL ML-8 In stal la tion and user man ual Soft ware Ver. 1.02 Man ual N 18926 Rev. A The information in this manual replaces any previously published information.
WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS
GAP.14.1.2.2 A Publication of Global Asset Protection Services LLC WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS INTRODUCTION A hydrant or other large-volume flow test is necessary for proper water
5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
Chapter 7 Hydraulic System Troubleshooting
Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic
Quik Lining Systems Heater Owners Guide
Quik Lining Systems Heater Owners Guide Quik Lining Systems, Inc is pleased to present the Quik Heater, an innovative heater used to cure cured in place pipe for sewer laterals. The unit is the most cost
Installation and instruction manual for Laing DDC pumps
Installation and instruction manual for Laing DDC pumps Application The Laing DDC series pumps are primarily used for the circulation of cooling liquid in liquid cooled computers. Construction - The Laing
NOTICE TO INSTALLER: Instructions must remain with installation. SECTION: 6.10.072. visit our web site: www.zoeller.com DATE INSTALLED: MODEL NUMBER:
NOTICE TO INSTALLER: Instructions must remain with installation. SECTION: 6.10.072 Product information presented here re fl ects con di tions at time of publication. Consult factory regarding discrepancies
FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS
FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS To be used in conjunction with the Fire Protection Association Australia FPS4-2000: Agreement
Section 2 COYOTE Splice Case Series
COYOTE Splice Case Series: Section 2 Section 2 COYOTE Splice Case Series Table of Contents COYOTE Splice Case...2-2 Capacities...2-4 Accessories...2-5 Tools...2-7 COYOTE Splice Case for Hi-Count Applications...2-8
Fire Sprinkler Monitoring & Releasing Systems
Fire Sprinkler Monitoring & Releasing Systems Training Manual Contents Foreword...3 Introduction...4 Glossary/Definitions...5 Symbols...10 Codes and Standards...13 Fire Alarm Signals...15 Types Of Sprinkler
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
SM 800 - Se ries 800 W DC POWER SUP PLY
Vissersdijk 4 4301 ND Zierikzee The Netherlands Tel. +31 111 413656 Fax. +31 111 416919 www.deltapowersupplies.com DELTA ELEKTRONIKA B.V. SM 800 Se ries 800 W DC POWER SUP PLY Mod els Volt age range Cur
RE MOTE AC CESS TO ATOMTEX 1125A IN STRU MENT
Nu clear Tech nol ogy & Ra di a tion Pro tec tion: Year 2013, Vol. 28, No. 1, pp. 97-101 97 RE MOTE AC CESS TO ATOMTEX 1125A IN STRU MENT by Vlade UROŠEVI] Faculty of Technical Science, University of Kragujevac,
IRS-CB. In stal la tion and Pro gram ming Man ual. Soft ware Ver. 1.0.6 Man ual n 18942 Rev. A
In stal la tion and Pro gram ming Man ual Soft ware Ver. 1.0.6 Man ual n 18942 Rev. A The in for ma tion in this man ual re places any pre vi ously pub lished in for ma tion. Sicep re serves the right
Technical Data. Installation
Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems General Description The Figure 51 (1) Riser Manifolds
I-768 FireLock NXT Dry Valve
HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR EASY FUTURE REFERENCE WARNING WARNING Failure to follow instructions and warnings can cause product failure, resulting in serious personal injury and
INSTALLATION INSTRUCTIONS GEO-BOOSTER TM
Table of Contents General Description 1 Parts list 1 Installation 2 New Ground Loop 2 Retrofit 4 Temporary 6 Troubleshooting 8 INSTALLATION INSTRUCTIONS GEO-BOOSTER TM General Description The Geo-Booster
Hot, Warm and Cold Mineral Water Cooler [Models Cool18, Cool25, Cool36, Cool50, Cool75, Cool100]
Hot, Warm and Cold Mineral Water Cooler [Models Cool18, Cool25, Cool36, Cool50, Cool75, Cool100] PLEASE READ BEFORE INSTALLATION TO PREVENT DAMAGE TO THE COOLER HOT WATER TANK STEAM EXAUST VENT (CAUTION!)
Float and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
This instruction is valid for all ACD pump models shown on page 2
Screw pumps ACD Maintenance and Service Instruction This instruction is valid for all ACD pump models shown on page 2 Contents Page List of components 2 Exploded view/ordering code 3 Service intervals
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style
LED BUILT-IN MODULES. LUGA Shop 2013 LED Modules COB for Retail Environments. LUGA SHOP 2013 HiCRI. 2000 lm TO 5000 lm. LUGA SHOP 2013 HiCRI
LED BUILT-IN MODULES LUGA SHOP 2013 HiCRI 2000 lm TO 5000 lm LUGA SHOP 2013 HiCRI LED MODULES COB FOR RETAIL ENVIRONMENTS WU-M-461, -462, -464 HiCRI Typical Applications Integration in reflector luminaires
Guidelines for operation of minimum flow control valves
Guidelines for operation of minimum flow control valves Holter Regelarmaturen GmbH & Co KG Helleforthstr. 58-60 D-33758 Schloß Holte-Stukenbrock 05/2005 List of contents I. Minimum flow control valves...
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
UN-436. In stal la tion and Pro gram ming Man ual. Soft ware Ver. 1.2.0 Man ual n 19969 Rev. A
UN-436 In stal la tion and Pro gram ming Man ual Soft ware Ver. 1.2.0 Man ual n 19969 Rev. A The information in this manual replaces any previously published information. Sicep reserves the right to modify
US 20140196633A1 (19) United States (12) Patent Application Publication (10) Pub. N0.: US 2014/0196633 A1 Shaw (43) Pub. Date: Jul.
US 20140196633A1 (19) United States (12) Patent Application Publication (10) Pub. N0.: US 2014/0196633 A1 Shaw (43) Pub. Date: Jul. 17, 2014 (54) SECONDARY CONTAINMENT PALLET (52) US. Cl. HAVING FLEXIBLE
PC1131 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
STAINLESS STEEL TANK TABLE OF CONTENTS TROUBLESHOOTING... 1 TESTING WATER TEMPERATURE... 3 TANK & JACKET ASSEMBLY... 4.
TABLE OF CONTENTS STAINLESS TROUBLESHOOTING... 1 TESTING WATER TEMPERATURE... 3 & JACKET ASSEMBLY... 4 SST Section 052506 1 Troubleshooting performed by untrained personnel could result in electrical
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
SW/SD/VS33 & 50 Submersible Sump/ Effluent Pumps
Pump Installation and Service Manual SW/SD/VS33 & 50 Submersible Sump/ Effluent Pumps SD33 SW33 VS33 SW50 SD50 VS50 NOTE! To the installer: Please make sure you provide this manual to the owner of the
Maxi Pressurisation Units (Maxi, Maxi Plus & HP)
Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Installation and Maintenance Instructions Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5
Installation, Maintenance, & Repair Series 909 and LF909 Reduced Pressure Zone Assemblies
Installation, Maintenance, & Repair Series 909 and LF909 Reduced Pressure Zone Assemblies Sizes: 3 4" 2" (20-50mm) RP/IS-909S! WARNING Read this Manual BEFORE using this equipment. Failure to read and
Appendix D: Guidelines for Collaborative Study Procedures To Validate Characteristics of a Method of Anal y sis
Appendix D: Guidelines for Collaborative Study Procedures To Validate Characteristics of a Method of Anal y sis {Note: These guide lines in cor po rate sym bols, ter mi nology, and rec om men da tions
80UHG. Service Literature
Service Literature Corp. 9728 L12 Revised 01 2002 80UHG 80UHG series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with tubular heat exchangers formed
Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk
1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance
*6/12. Nov. 24, 1953, L. L. BILLAR 2,660,621 OU/S L. BILL/4R. Filed July 14, 1950 IDENTIFICATION CODE ON SOUND RECORDS. 2 Sheets-Sheet l INVENTOR
Nov. 24, 1953, L. L. BILLAR 2,660,621 Filed July 14, 1950 *6/12 IDENTIFICATION CODE ON SOUND RECORDS 2 Sheets-Sheet l _ '22 A 2/5 VACUUM TUBE AMP. OU/S L. BILL/4R INVENTOR Nov. 24, 1953 L. 1.. BILLAR 2,660,621
Description of functions
Description of functions Laddomat 21 is designed to......allow the boiler to reach a high working temperature soon after firing....to preheat the cold tank water in the bottom of the boiler so that the
TOOL SVC NUMBERS: 250-2598, 250-2600 SVC CONTENTS ITEM QTY DESCRIPTION PART NUMBER 1 1 CUTTING TOOL 250-2598 2 1 EXTRACTION TOOL/PART# 250-2600
07-08 TOYOTA FJ CRUISER, 05-09 SIENNA, 06-08 SCION TC PART NUMBER: 250-1732 1 CRUISE CONTROL KIT TOOL SVC NUMBERS: 250-2598, 250-2600 2 2 1 BASE KIT CONTENTS ITEM QTY DESCRIPTION 1 1 CONTROL SWITCH ASSEMBLY