1 Design recommendations FOR PUMP STATIONS WITH LARGE CENTRIFUGAL FLYGT WASTEWATER PUMPS
2 2
3 Contents Flygt large centrifugal pumps introduction General considerations for sump design Xylem standard sump Sump dimensions. Required sump volume. Minimum stop levels Installation tips Installation tips for submerged pumps. Installation tips for dry installed submersible pumps Importance of duty point Systems Engineering This brochure is intended to help application engineers, designers, planners and users of sewage and stormwater systems incorporating submerged and submersible, dry installed Flygt pumps. A proper design of the pump sump in such installations is crucial. Two important design requirements to be met are: preventing significant quantities of air from reaching the impeller, and disposal of settled and floating solids. The Flygt standard pump sump can be used as it is, or with appropriate variations to meet the requirements of most installations. Pump and sump are parts of an overall system that also includes a variety of structures and other elements such as ventilation systems and handling equipment. Operating costs can be reduced with the help of effective planning and suitable operation schedules. Xylem personnel and publications are available to offer guidance in these areas. Transient analysis such as air chamber dimensioning, valve selection, etc. should also be considered in wastewater pump station design. These matters are not addressed in this brochure, but we can offer advice on these topics. Please consult with our engineers to achieve optimum pump performance, maximum pump life, and a guarantee that product warranties are met. The design recommendations are only valid for Flygt products. Xylem assumes no lia bility for non-xylem equipment. 3
4 Flygt large centrifugal pumps introduction Flygt large centrifugal submersible pumps have been used in a variety of applications all over the world. Pumps can be either submerged or dry installed. Applications include wastewater pumping stations in a variety of sizes as well as intake stations to treatment plants, storm water pumping, irrigation, mine applications, shipyards and more. Flygt dry installed pumps provide easy maintenance of the pump. The motor and impeller assembly can easily be lifted out of the pump volute for overhaul and repair. The submersible pump/motor unit provides the possibility of a flood proof pumping station for safe operation at all times. Flygt submersible centrifugal pumps offer important advantages such as: Compact motor and pump unit No separate lubrication system Low operation sound level The N variant of impeller offers sustained efficiency and enhanced reliability due to a unique hydraulic design Flood proof pumping stations even for dry installed pumps Automatic connection and disconnection for submerged installations allows for fast and easy installation, inspection and service Minimal station superstructure Our submerged pumps are installed on a discharge connection bolted to the pit floor. The pump is guided to its position with double permanently installed 3 pipes. The connection is automatic and needs no visibility. The pump is just lowered onto the discharge connection and is held in position by its own weight. Retrieval of the pump is equally simple. General considerations for sump design Ideally, the flow of fluid into any pump should be uniform, steady, and free from swirl and entrained air. Lack of uniformity can cause a pump to operate at a lower efficiency rate. Unsteady flow causes the load on the impeller to fluctuate, which can lead to noise, vibration and bearing problems. Swirl in the pump intake can cause a significant change in the operating conditions for a pump, and can produce changes in the flow capacity, power requirements and efficiency. It can also result in local vortex-type pressure reductions that induce air cores extending into the pump. This, and any other air ingestion can cause reductions in pump flow and fluctuations of impeller load which result in noise and vibration with consequent physical damage. Additionally, these fluctuations can impact process loads in other parts of the system. 4
5 The design of a sump should not only provide proper approach flow to the pumps, it should also prevent the accumulation of sediments and surface scum in the sump. The following points must be considered: Flow of water from the sump entrance should be directed toward the pump inlets in such a way that the flow reaches the inlets with a minimum of swirl and energy loss. In order to prevent the formation of air-entraining surface vortices in the sump, the walls must be designed and built to avoid stagnation regions in the flow. A properly placed wall close to the inlet can reduce the tendency toward localised swirl and vorticity. The water depth must also be great enough to suppress surface vortices. Although excessive turbulence or large eddies should be avoided, some turbulence does help to prevent the formation and growth of vortices. Sediment, which could be foul, must not accumulate within the sump. Stagnant regions, or regions of such low velocity where sedimentation might occur, must be avoided. A sloping floor and fillets or benching often help to prevent sedimentation. For large variations in flow, part of the sump can be dedicated to low inflows with a lower floor level and a small pump. Consult Xylem for an optimum sump design. Surface scum, floating sludge and small debris can accumulate in any relatively calm region of the water surface; and this material must be pumped away. The water level should be lowered as much as possible at intervals to increase both velocity and turbulence. However, air should not be drawn into the pump. Please consult with an Xylem engineer in order to achieve optimum pumping performance. The occasional increases in flow velocity will also assist in preventing the accumulation of sediment on the floor. Station inflow often approaches the wet well at a relatively high elevation. In such cases, the liquid may fall a significant distance as it enters the sump. Such a drop can also occur whenever the pumps have lowered the liquid level in the sump to the point at which all pumps are about to be switched off. Therefore, the path between the sump entrance and the pump inlets must be sufficiently long for the air to rise to the surface and escape before reaching the pumps. The energy of the falling water should be dissipated sufficiently so that excessively high and irregular velocities do not occur within the sump. This can be accomplished with properly designed and correctly positioned baffle walls. The sump should be as small and as simple as feasible to minimise construction costs. However, a minimum sump volume may be specified for other reasons, such as to provide for a minimum retention time, or to ensure that only a certain number of pump starts per hour occur. Principles to be adopted in the design of any sump are given in a number of design guides or codes of practice for example, both the American Hydraulic Institute and the British Hydromechanics Research Association have published such guides. Nevertheless, whenever a new design departs significantly from established configurations, model tests of the sump and its approaches should be considered. Xylem standard sump A sump designed in accordance with this brochure is smaller than a conventional sump. Consequently, there may be less buffer volume to accommodate transient variations of the flow rate. Nor is there extra retention volume to store the inflow in excess of the total pump capacity (the pipe volumes are usually much larger than any pump station volume). A proper design of a complete pump station should therefore consider all critical aspects of operation. Of course, the pump capacity must match the extreme inflows to minimise the risk of flooding. Often flow characteristics of the feeding sewer system should also be analysed. The control system for the pumps must also provide protection in the event of a power failure. Precise level sensors are crucial if the sump volume is minimised in accordance with the recommendations in the preceding section. The discharge pipe work should be designed to prevent flooding by the return flow when the pumps are stopped also in emergency situations. The effects of possible pressure surges should be minimised by appropriate design of the control devices. 5
6 A1 A2 To avoid pre-swirl into the pump chamber, the inlet pipe must have a straight length of five pipe diameters upstream from the sump. The exact sump design varies with the number of pumps and pump size. The central front high-level entry sump design is referred to as type A1. In this configuration, the flow does not have to make a horizontal turn, which might induce mass rotation in the sump. A specially designed baffle wall minimises air entrainment due to falling water. The flow from the inlet pipe strikes the partition wall then flows down into the inlet chamber through the slot in the floor of the baffle. The slot distributes the flow evenly toward all the pump inlets. The partition wall is high enough to ensure that the flow does not surge over it. Although the flow in the inlet chamber is highly turbulent, various materials can collect there. In such cases, side overflow weirs or side gaps may be used to carry away debris and thus prevent its accumulation. (The top of the partition wall, or parts of it should be below the highest start-level of any of the pumps to allow transport of the floating material into the pump chamber). If the piping system and the sump location do not allow for a front entry inlet a side entry inlet with a baffle wall modified with ports can be used. This configuration is referred to as type A2. In this design, the baffle wall redirects the incoming flow and distributes the flow evenly toward the pumps through the ports. At high inlet, it is recommended to have a baffle on the inlet chamber floor, purposed to break flow jet when the water level in the station is low. Equipping the sump with fillets, baffles, and/or benching is often beneficial depending on the number of pumps and their size. Therefore, please consult with Xylem for an optimum sump design. 6
7 Circular sump Double sump B2 Reverse oriented pumps Construction alternatives Distributing the flow evenly to all pumps over the width of the sump can present problems if the number of pumps is more than four. In such cases, a double sump may be more suitable. For deep sumps, using a circular outer structure can be advantageous from a construction viewpoint. Inside such a structure, individual pump sump modules similar to those used for the compact sump can be accommodated. Please contact Xylem for advice of compact sump designs with a central front low-level entry. In type B2, with a straight baffle wall, the sewer is below the normal water level in the sump, or an open channel supplies the sump. In the absence of falling flow in the entrance, no intense entrainment of air takes place. Consequently, the inlet chamber can be greatly simplified because its only task is to distribute the flow evenly to the pumps. In dry pumps application, it is recommended to have vertical baffles between suction pipes, to protect mass rotation in the wet well. Sometimes there is a need to locate the riser pipe in the center of the stations or locate the outlet in another direction where reversed pump orientation can be a solution. This picture shows an extract of a reverse orientation wastewater pumping station design. When operated in combination with recommended pump control philosophies optimal pumping conditions are achieved providing sump floor cleaning for transportation of solids. 7
8 Sump dimensions The sizing diagram is valid for pumping stations up to four pumps, which may all be duty pumps. Tolerances of ±10 % on the sump dimensions shown in the table below are acceptable provided that the combined effect of the departures does not lead to velocities significantly higher than those for the standard sump. Flow per pump refers to one pump duty point for maximum total flow (in a common pressure pipe). D F C E B A Please note that in this flow region is also sump design recommendations for the mid range product line are applicable. A1 Submerged A1 Dry
9 A2 Submerged A2 Dry B2 Submerged B2 Dry
10 Required sump volume The required live volume of the sump, V, i.e. the volu me between the start level and the stop level of the pump, depends upon such factors as the cycle time for the pump, T, the pump capacity, Q, and the rate of the inflow, q. For one pump and for variable inflow rate, the shortest cycle time occurs if q = Q/2 which gives the minimum required volume of the sump: The minimum cycle time, (Tminimum) is determined by the number of pump starts with regard to the mechan ical stress from the temperature rise in the motor. T = 3600 / starts per hour Sump design type A1, A2, B2 The recommendations are valid for the Flygt pump sump design for two, three or four pumps, installed either in semi permanent (P) or permanent wet well (T). It is valid for all four positions of the pumps at all combination of pumps in duty, though exceptions in the recommendation are made for the straight baffle wall. It is assumed that at least one pump is assigned as a stand-by pump and only in extreme cases all four pumps run simultaneously. When the location of the inlet pipe is unsymmetrical, at low level, or the last part is less than five straight pipe diameters, higher stop levels to suppress vortices should be applied according to the recommendations for non-optimal inflow (see graph: Low level front entry). For a pumping station with identical pumps, the required volume is smallest if the pumps start in sequence as the water level rises due to increasing inflow, and stop in sequence as the water level drops due to decreasing inflow. To minimize the required sump volume, the last pump to start should be the last pump to stop, i.e. cyclic alternation. Minimum stop levels The pumps can be stopped at the same water level but a time delay between the stops is important to avoid high immediate flow changes and pressure transients in the discharge pipes. The following minimum stop level recommendations prevent vortices and air pene tration through to the pump intakes. For a short period of time the level could be less, e.g. during the sump cleaning cycle. Submergence to pump inlet Submergence to pump inlet A1 A1 m 1,9 1,7 1,5 1,3 1,1 0,9 0,7 High level central front entr y, L -shaped baffl e 0,5 0,5 1 1,5 2 2,5 3 1st pump stop out of 3 pumps running Flow/pump m 3 /s 1st pump stop out of 2 pumps running One pump stop level m 2,3 2,1 1,9 1,7 1,5 1,3 1,1 0,9 0,7 Low level front entr y, of f -set front entr y, L -shaped baffl e 0,5 0,5 1 1,5 2 2,5 3 1st pump stop out of 3 pumps running Flow/pump m 3 /s 1st pump stop out of 2 pumps running One pump stop level 10
11 Submergence to pump inlet A2 m 2,7 2,5 2,3 2,1 1,9 1,7 1,5 1,3 1,1 0,9 0,7 Side entry, L-shaped baffle 0,5 0,5 1 1,5 2 2,5 3 1st pump stop out of 3 pumps running Flow/pump m 3 /s 1st pump stop out of 2 pumps running One pump stop level where: NPSHav Available suction pressure due to atmospheric pressure, temperature, water level in the sump and inlet losses. NPSHreq The pressure required to obtain a trouble free operation in terms of cavitation, the value is determined by the NPSH curve for the pump. The available suction head has to be greater than the suction head required by the pump. The available suction head in a wet-installed pump application is: NPSHav = Hatm + Hsump Hev Submergence to pump inlet B2 m 2,7 2,5 2,3 2,1 1,9 1,7 1,5 1,3 1,1 0,9 0,7 Side entry, straight baffle wall 0,5 0,5 1 1,5 2 2,5 3 Stop level for one of outer pumps Flow/pump m 3 /s when 4 pumps running 1st pump stop out of 3 pumps running 1st pump stop out of 2 pumps running One pump stop level While for a dry installed application, the dynamic head losses in the inlet pipe have to be taken into account. Consequently the relation for the available suction head becomes: NPSHav = Hatm + Hsump Hloss Hev Note that NPSHreq has to be fulfilled according to the paragraph below. Net Positive Suction Head NPSHav The positive head required on the suction side of the pump to secure safe operation in terms of cavitation is determined by the NPSH (net positive suction head) curve. The basic condition to be fulfilled in all application where rotating hydro machines, such as pumps are used is: NPSHav > NPSHreq where: Hatm Atmospheric pressure Hsump Difference in level between centerline of the impeller and liquid surface in the sump Hev Evaporation pressure of the liquid Hloss Dynamic head loss in inlet pipe system 11
12 Installation tips Submerged pumps The following are some general installation guidelines for submersible pumps: To avoid check valve cavitation, the valve should not be located at an elevation greater than 8 meters (approximately 27 feet), above the pump discharge. To facilitate maintenance and protect the cable, a trough in the floor is recommended for station cable runs (refer to local electrical codes). The cable support bracket/strain relief sheathing should be mounted for easy access, i.e. within reach under the hatch. When a pipe or a hose is used to protect the cable, it should not cover the cable all the way into the control panel as evaporating explosive gases from the wastewater entering the cabinet could be harmful (refer to local codes). Wastewater gas can cause relay oxidation. It is therefore beneficial to locate the control panel in a ventilated environment. To avoid problems with the operation of the level regulators from floating debris, etc. a stillwell, with its opening below the lowest water level, may be used. The pocket in the benching where the discharge connections are can collect sediment. A steel plate or concrete infill benching covering the pocket will prevent that. Dry installed submersible pumps Suction pipe design The position of the suction pipe to the dry installed pump follows the same hydraulic guidelines as for a submerged pump. The submergence of the inlet must be given more attention though, as air can be drawn into the pipe more easily than for submerged pump, which has a volute acting as a vortex suppressor. Accumulated air in the inlet pipe can impair pump operation, and can cause the system to become air bound preventing pumping altogether. For flows over 500 l/s, the inlet pipe should be equipped with an inlet bell to minimize losses and disturbed flow into the pump. To achieve a uniform flow to the inlet of the pump, the suction pipe design should fulfil the following: 1. Provide sufficient NPSHav 2. Minimize friction losses 3. Minimize number of elbows 4. Eliminate vapor from suction pipe 5. Ensure correct pipe alignment 6. Provide automatic air venting downstream of the pump before the Non Return Valve Valve location at the suction pipe To minimize the risk of cavitation, noise and vibration, the valve and the valve seat should be smooth to avoid flow disturbance (gate valves are preferred), and if possible, be located more than five pipe diameters away from the pump. Effects of elbows Elbows in the piping generate dynamic losses and swirling flow and should be avoided whenever possible. To minimize the effects of the elbows, the pre-swirl (which could increase the power requirements for the pump) should be located in one plane as shown in the 360 and 180 pipe configurations
13 The inlet bellmouth To accelerate the flow smoothly into the inlet pipe and reduce inlet losses, the inlet should be provided with a bellmouth. The optimal velocity at the entrance of the bellmouth is 1.7 m/s, (5.6 ft/s) and should be within the following limits. Flow Velocity < 1200 l/s m/s, 3 8 ft/s > 1200 l/s m/s, 4 7 ft/s Installation guidelines for the pump and its piping Avoiding vibration and noise A rotary machine will always be a source of energy for acoustic/vibration disturbance. The pump and/ or motor unit can radiate disturbance to the environment that may excite vibration and cause noise in other parts of the system, pipes etc. With wetwell installed pumps, the medium helps reduce vibration and noise. The design for dry installed pumps must be more carefully analyzed in order to reduce these types of problems. The first rule to follow is that the pump is best operated in the duty area it is designed for normally between 50 % and 125 % of best efficiency point (BEP). In this area, disturbances such as impeller and volute forces, cavitation etc, are kept to a minimum. The standard pump accessories are designed for use with a fixed, stiff installation where the main disturbance frequency will be below the lowest natural frequency and result in low vibration levels. In some cases, a totally fixed design is not enough and the system or parts of it have to be isolated with rubber machine feet, a rubber carpet, flexible pipe joints, etc. When evaluating the system, an analysis of the source of any disturbance can include: Imbalance in the rotating parts. These have a dominating magnitude at the rotation frequency of the pump. Hydraulic forces that are caused by the pressure differences in the volute The passage of the impeller blade past the volute cut water creates both forces on the impeller and pressure pulses in the pipe system at a frequency that is the product of the rotating impeller frequency and the blade number. With this information, it is possible to analyze the system in order to minimize the risk for vibration, i.e. the critical pipe length and the minimum distance for the pipe support to prevent harmonics. Other factors that might create noise are the electric motor, the internal flow itself (turbulence and swirl can cause pipes and valves to radiate noise) and cavitation within the pump or in the pipes/ valves. 13
14 For more information regarding vibration and noise prevention for dry installed pumps, please see Xylem s engineering paper Noise and vibrations from pumping installations. Pump anchoring and piping support guidelines The following guidelines can prevent unwanted vibration: 1) All parts of the system should be anchored so the primary disturbances have frequencies below the lowest natural frequency of the system, including pump, valves, supports and pipes. 2) If the pump and foundation are to be insulated from the pumping station, the following procedure is recommended: a) The weight foundations should be at least two times the weight of the rotating parts. b) Use flexible support, e.g. machine feet or a rubber carpet, between the base and the floor or ground. Importance of duty point In order to achieve the best possible pump operation, and maximize equipment life it is very important to select the correct pump for the duty point in question. The preferred operating region (POR) for most large centrifugal pumps is between 70 % and 120 % of the Best Efficiency Point (BEP), as outlined in the Hydraulic Institute Standards. The Allowable Operating Region, (AOR) from BEP for optimal operation of centrifugal pumps in wastewater applications is between 50 % 125 % of BEP (unless the curve does not have an operational limit) and sufficient NPSH is available. By running the pump outside the AOR the following problems can occur: Unstable operation. Incipient cavitation resulting in impeller erosion, noise or vibration. High radial and axial forces 50% 125% of Qopt c) Use flexible joints for the pipes. d) Anchor the pipes to the floor or to another solid structure. 3) Horizontal and vertical supports should be provided. Extra supports must be provided at heavy components such as valves. 4) For pipe systems with bellows to minimize vibration, the pipe should be supported at the bellows to avoid transference of pressure fluctuations. BEP NPSHr High radial forces Consult Xylem Engineering if operation outside of the AOR is required. 5) Vertical pipe velocities must be kept a level, which prevents the settling of solids. The recommended range is m/sec. 14
15 Systems Engineering Xylem offers in-depth expertise in the design and execution of comprehensive solutions for water and wastewater transport and treatment. Our know-how and experience are combined with a broad range of suitable products for delivering customized solutions that ensure trouble-free operations for customers. To do this our engineers utilize our own specially developed computer programs, as well as commercial, for design and development projects. Scope of assistance includes a thoroughgoing analysis of the situation and proposed solutions together with selection of products and accessories. Additional services: Optimization of pump sump design for our products and specific sites Assistance with mixing and aeration specifications and design of appropriate systems System simulation utilizing computational fluid dynamics (CFD) Guidance for model testing and organizing it Guidance for achieving the lowest costs in operations, service and installation Specially developed engineering software to facilitate designing The range of services is comprehensive, but our philosophy is very simple: There is no substitute for excellence. We also provide hydraulic guidance and assistance for flow-related or rheological issues. Customers turn to us, as well, for analysis of complex systems for network pumping, including calculations for hydraulic transients, pump starts and flow variations. 15
16 1) The tissue in plants that brings water upward from the roots 2) A leading global water technology company We re 12,000 people unified in a common purpose: creating innovative solutions to meet our world s water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efficiently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation Design recommendations. 1. Master For more information on how Xylem can help you, go to xyleminc.com. Flygt is a brand of Xylem. For the latest version of this document and more information about Flygt products visit
Design Recommendations
Design Recommendations For Pump Stations With Large CenTrifugal Flygt Wastewater Pumps 2 Contents Flygt large centrifugal pumps introduction......................................................... 4 General
Design recommendations. for pump stations with large centrifugal wastewater pumps
Design recommendations for pump stations with large centrifugal wastewater pumps General considerations for sump design Design capacity Sump dimensions Required sump volume Installation tips for submerged
Engineering & Expertise Designing pump sumps
Engineering & Expertise Designing pump sumps Large submersible centrifugal pumps Engineering & Expertise Total solution engineering increases operational efficiency Introduction The proper design of the
Engineering & Expertise Designing Pump Sumps
Engineering & Expertise Designing Pump Sumps Formed Suction Intake Engineering & Expertise Total solution engineering increases operational efficiency Introduction The primary function of a propeller pump
Compact pumps from the wastewater experts. FLYGT 3045, 3057, 3068. Power range 0.75 2.4 kw.
Compact pumps from the wastewater experts FLYGT 304, 307, 3068. Power range 0.7.4 kw. Wastewater is unpredictable, Flygt pumps are not If you want a wastewater pump that just works month after month, year
Engineering & Expertise Hydraulic modeling. Computational fluid dynamics
Engineering & Expertise Hydraulic modeling Computational fluid dynamics Engineering & Expertise Total solution engineering increases operational efficiency Introduction Understanding fluid flow inside
Pure Performance. Steady 1300 Series
Pure Performance Steady 1300 Series Available EASY TO SELECT, QUICK DELIVERY, THE RIGHT PUMP FOR YOUR NEEDS Oustanding Value EFFICIENT, POWERFUL Reliable SOLIDS HANDLING, CONTINUOUS RUNNING 2 Readily available
N-PUMP SERIES FOR MAXIMUM RELIABILITY AND EFFICIENCY IN WASTEWATER HANDLING. Flygt
N-PUMP SERIES FOR MAXIMUM RELIABILITY AND EFFICIENCY IN WASTEWATER HANDLING Flygt The Concept N-Pump series. Bringing NEW levels of efficiency to wastewater handling applications Reduced pumping efficiency,
DIVISION OF WATER QUALITY CONSTRUCTION GRANTS & LOANS SECTION FAST TRACK AUDIT CHECKLIST
DIVISION OF WATER QUALITY CONSTRUCTION GRANTS & LOANS SECTION FAST TRACK AUDIT CHECKLIST CERTIFICATION 1. Did the engineer submit a certificate of completion utilizing the appropriate page of the issued
CONFIRMING WET WEATHER TREATMENT FACILITY HYDRAULIC DESIGN WITH PHYSICAL MODEL STUDY
CONFIRMING WET WEATHER TREATMENT FACILITY HYDRAULIC DESIGN WITH PHYSICAL MODEL STUDY TONY YEE, PE JARED HUTCHINS, PE METROPOLITAN SEWER DISTRICT OF GREATER CINCINNATI BLACK & VEATCH WET WEATHER TREATMENT
Module 9: Basics of Pumps and Hydraulics Instructor Guide
Module 9: Basics of Pumps and Hydraulics Instructor Guide Activities for Unit 1 Basic Hydraulics Activity 1.1: Convert 45 psi to feet of head. 45 psis x 1 ft. = 103.8 ft 0.433 psi Activity 1.2: Determine
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
Flygt 3068, 50Hz. Technical Specification
Flygt 3068, 50Hz Technical Specification Table of Contents Table of Contents B-pump...2 Product description...2 Motor rating and performance curves...4 C-pump...6 Product description...6 Motor rating
CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.
CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As
Copa Raked Bar Screen
Copa Raked Bar Screen Mechanically Raked Combined Sewer Overflow (CSO) Screen Key features & benefits Stainless steel with Tivar screen comb 10mm bar spacing Complete range up to 3000 l/sec per screen
Smart Electromagnetic Flowmeter Open channel Flowmeter Detector
Magne3000 PLUS Smart Electromagnetic Flowmeter Open channel Flowmeter Detector Model NNK150/951 OVERVIE The Magne3000 PLUS Electromagnetic Flowmeter is submersible type of flowmeter mainly used for flow
Godwin NC series Dri-Prime pumps
Godwin NC series Dri-Prime pumps now with Flygt N-technology INTRODUCTION 2 We combined the world s most reliable portable pumps with the world s most efficient self-cleaning hydraulics To bring you the
Flygt N-Pumps 3085, 3102 & 3127. For reliable and efficient wastewater handling
Flygt N-Pumps 3085, 3102 & 3127 For reliable and efficient wastewater handling The Concept Flygt N-Pump series Reduced pumping efficiency, high energy and maintenance costs shouldn t be a fact of life
Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29
_02 A centrifugal with a 12 in. diameter impeller requires a power input of 60 hp when the flowrate is 3200 gpm against a 60 ft head. The impeller is changed to one with a 10 in. diameter. Determine the
TECHNICAL BROCHURE B5-33GB 5GB, 7GB, 10GB, 18GB, 25GB, 33GB HIGH PRESSURE MULTI-STAGE BOOSTER PUMP
TECHNICAL BROCHURE B-33GB GB, 7GB, 1GB, 18GB, 2GB, 33GB HIGH PRESSURE MULTI-STAGE BOOSTER PUMP FEATURES Multi-stage Design: Provides steady, quiet, vibration free, operation. Optional Stainless Steel Construction:
Vertical Pumps for the Oil & Gas Industry
Vertical Pumps for the Oil & Gas Industry ITT API Expert ITT Commitment ITT is committed to the Oil and Gas market, which is the largest segment of our business. We have been investing in technology to
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
ROBOT PUMPS RT - TURBOTEX PUMPS
ROBOT PUMPS RT - TURBOTEX PUMPS RT- Turbotex pumps The Robot submersible Turbotex pumps form the ultimate solution in today s pumping technology. The self cleaning blade leading edge effectively deals
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
No compromise. Highest total efficiency wastewater pumping. grundfos se & sl ranges Submersible and dry-installed wastewater pumps
grundfos se & sl ranges Submersible and dry-installed wastewater pumps 0.9-30 kw 2, 4, 6 pole 50Hz No compromise Highest total efficiency wastewater pumping ULTIMATE WASTEWATER PUMPING TECHNOLOGY The renewed
Grant Agreement No. 228296 SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme
Grant Agreement No. 228296 SFERA Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME Capacities Specific Programme Research Infrastructures Integrating Activity - Combination of
CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES
CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES 4.0 PUMP CLASSES Pumps may be classified in two general types, dynamic and positive displacement. Positive displacement pumps
Conlift1, Conlift2, Conlift2 ph+
GRUNDFOS DATA BOOKLET Conlift1, Conlift2, Conlift2 ph+ Small lifting stations 50 Hz CONLIFT1, CONLIFT2, CONLIFT2 ph+ Table of contents 1. Product overview 3 Conlift for condensate applications 3 Applications
Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic energy).
HYDRAULIC MACHINES Used to convert between hydraulic and mechanical energies. Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic
Guidelines for Precast Concrete Grease Interceptors
Guidelines for Precast Concrete Grease Interceptors Purpose Provide an overview of the basic design principals that govern why gravity grease interceptors work Provide a forum for discussion of common
HYDROVEX. CSO, SSO and Stormwater Management Specialist Products and Services for North America
HYDROVEX CSO, SSO and Stormwater Management Specialist Products and Services for North America A long tradition in excellence John Meunier Inc. has been serving North American municipalities and industries
DESCRIPTION OF STORMWATER STRUCTURAL CONTROLS IN MS4 PERMITS
DESCRIPTION OF STORMWATER STRUCTURAL CONTROLS IN MS4 PERMITS Phase I MS4 permits require continuous updating of the stormwater system inventory owned and operated by the MS4. They also include inspection
SIMULATION OF FLOW THROUGH A PUMP SUMP AND ITS VALIDATION
SIMULATION OF FLOW THROUGH A PUMP SUMP AND ITS VALIDATION Tanweer S. Desmukh & V.K Gahlot Civil Engineering Department, M.A.N.I.T,Bhopal E-mail: [email protected], [email protected] ABSTRACT
PUMPS TYPE OF PUMP PRESSURE/FLOW RATING CHARACTERISTICS. Centrifugal Low Pressure/High Flow Flow changes when
PUMPS Pumps provide the means for moving water through the system at usable working pressures. The operation and maintenance of these pumps are some of the most important duties for many water utility
Operation & Maintenance Manual
Manual # OMAV2-SUMP1 High Performance Air & Dirt Separators Manual # 9636-1230 Rev. A Operation & Maintenance Manual 340 West 8 th Street Peru, IN 46970 PH: 765 472 3351 FX: 765 472 3968 www.thrushco.com
The Company. QUALITY WHICH REDUCES PUMPING COSTS For over 45 years, PAPANTONATOS S.A. has focused on the customer s design,
The Company QUALITY WHICH REDUCES PUMPING COSTS For over 45 years, PAPANTONATOS S.A. has focused on the customer s design, manufacturing and service needs in the field of submersible pumps. Our engineering
How To Pump A Pump
Multistage Pumps P, PVa, MP 300 Technical Data Performance range: m Capacities up to 1800m 3 /h (8800USgpm) m Head up to 300m (1000feet) m Max. speed up to 1750rpm Multistage pumps of series MP with smaller
Flygt Aquaview SCADA Software. Safer monitoring and simpler at a glance
Flygt Aquaview SCADA Software Safer monitoring and simpler at a glance Effective control, reduced operational costs Precise and easy control through the user-friendly interface. Innovative solutions from
Grit Removal Systems Simple, low cost, effective grit removal to enhance plant performance
LAKESIDE Water Purification Since 1928 Bulletin #1603 April 2005 Grit Removal Systems Simple, low cost, effective grit removal to enhance plant performance Aeroductor Model L Grit Classifier SpiraGrit
Flashing and Cavitation
As seen in the Summer 2015 issue of MAGAZINE BACK TO BASICS A high-power boiler burner in a co-generation plant Flashing and Cavitation Some of the following questions may seem unrelated, but they all
Pump Selection and Sizing (ENGINEERING DESIGN GUIDELINE)
Guidelines for Processing Plant Page : 1 of 51 Rev 01 Feb 2007 Rev 02 Feb 2009 Rev 03 KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru. (ENGINEERING DESIGN GUIDELINE)
SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
MODEL 300505 INSTALLATION INSTRUCTIONS
WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 [email protected] Your pump has been carefully packaged at the factory to prevent damage during shipping.
BSM MOTOR DRIVEN CENTRIFUGAL PUMPS
PRINCIPLE OF OPERATION A hydraulically and dynamically balanced impeller with raised vane sections discharges liquid as a result of the centrifugal force developed in rotation. The head developed is entirely
TOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?
KNOWLEDGE: K1.01 [3.3/3.5] P21 Which one of the following contains indications of cavitation in an operating centrifugal pump? A. Low flow rate with low discharge pressure. B. Low flow rate with high discharge
VERTICAL TURBINE AND PROPELLER PUMPS
VERTICAL TURBINE AND PROPELLER PUMPS INTRODUCTION Vertical Turbine and Propeller Pumps Model 7000 Series Turbine Pump Model 800 Series Axial Flow Propeller Pump Model 800 Series Mixed Flow Propeller Pump
CHAPTER 3 STORM DRAINAGE SYSTEMS
CHAPTER 3 STORM DRAINAGE SYSTEMS 3.7 Storm Drains 3.7.1 Introduction After the tentative locations of inlets, drain pipes, and outfalls with tail-waters have been determined and the inlets sized, the next
HIGHWAY STORMWATER PUMP STATION DESIGN
Publication No. FHWA-NHI-01-007 February 2001 U.S. Department of Transportation Federal Highway Administration Hydraulic Engineering Circular No. 24 HIGHWAY STORMWATER PUMP STATION DESIGN Technical Report
Instructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version
instrumentation for fluids Electromagnetic sensor Series FLOMID FX Instructions Manual! Conforms with the Pressure Equipment Directive 97/23/EC. 0830 This equipment is considered as being a pressure accessory
Type of Sewer Systems. Solomon Seyoum
Type of Sewer Systems Solomon Seyoum 0 Learning objectives Upon completion of this lecture, the participants will be able to differentiate between types of sewer systems and discuss different aspects of
General Information. Applications
SCREW PUMPS General Information Several centuries BC, Archimedes the Greek philosopher, developed a turning spirally wound tube to raise water to a higher level for irrigation purposes. Over 100 years
TOP 10 NOISE CONTROL TECHNIQUES
TOP 10 NOISE CONTROL TECHNIQUES The following are 10 simple noise control techniques that have wide application across the whole of industry. In many cases, they will produce substantial noise reductions
Storm Drainage Systems 11.9-1
Storm Drainage Systems 11.9-1 11.9 Gutter Flow Calculations 11.9.1 Introduction Gutter flow calculations are necessary in order to relate the quantity of flow (Q) in the curbed channel to the spread of
Module 7: Hydraulic Design of Sewers and Storm Water Drains. Lecture 7 : Hydraulic Design of Sewers and Storm Water Drains
1 P age Module 7: Hydraulic Design of Sewers and Storm Water Drains Lecture 7 : Hydraulic Design of Sewers and Storm Water Drains 2 P age 7.1 General Consideration Generally, sewers are laid at steeper
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
Anti-Cavitation Trim. Eliminates cavitation damage Reduces noise Preserves valve and surrounding pipe systems. singervalve.com
Anti-Cavitation Trim Eliminates cavitation damage Reduces noise Preserves valve and surrounding pipe systems Say Goodbye to Cavitation Damage! Cavitation, a common problem in pumps and control valves,
Aftermarket Technical Service Solutions for Pumping Technologies
Aftermarket Technical Service Solutions for Pumping Technologies HIGH QUALITY OEM PARTS, SERVICE, REPAIR, UPGRADES + RE-RATES: DELIVERING VALUE FOR OUR CUSTOMERS SPX - An Introduction SPX is a Fortune
THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT
THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT Kazuto Otakane, Tokyo Gas Co., Ltd Katsuhito Sakai, Tokyo Gas Co., Ltd Minoru Seto, Tokyo Gas Co., Ltd 1. INTRODUCTION Tokyo Gas s new gas meter,
COUNTERBALANCE VALVES
COUNTERBALANCE VALVES Introduction They are modulating valves which allow free flow into the actuator and then block the reverse flow until they feel a pilot pressure inversely proportional to the load
Residential Plumbing BCN 1058
Residential Plumbing BCN 1058 CHAPTER 7 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System MICHAEL KNOTEK 74 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System PLUMBING FIXTURES
Outlet stabilization structure
Overview of Sedimentation and Erosion Control Practices Practice no. 6.41 Outlet stabilization structure Erosion at the outlet of channels, culverts, and other structures is common, and can cause structural
SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor
INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Tubular Casing Pumps. The Driving Force in Your Cooling Water System
Tubular Casing Pumps The Driving Force in Your Cooling Water System KSB know-how,experience and service... More than 120 years tradition in the design and construction of pumps, valves and relevant systems
Experiment (13): Flow channel
Introduction: An open channel is a duct in which the liquid flows with a free surface exposed to atmospheric pressure. Along the length of the duct, the pressure at the surface is therefore constant and
Emergency Spillways (Sediment basins)
Emergency Spillways (Sediment basins) DRAINAGE CONTROL TECHNIQUE Low Gradient Velocity Control Short-Term Steep Gradient Channel Lining Medium-Long Term Outlet Control Soil Treatment Permanent [1] [1]
KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850
INSTALLATION AND OPERATING INSTRUCTIONS KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850 Product advantages Automatic float switch as water
SECTION 812 SEWER LINE, MANHOLE AND WET WELL CLEANING
812-1 SCOPE OF WORK: SECTION 812 SEWER LINE, MANHOLE AND WET WELL CLEANING a. The Contractor shall provide all labor, materials, equipment, and incidentals necessary to perform the cleaning of sewer lines,
Chapter 3 CULVERTS. Description. Importance to Maintenance & Water Quality. Culvert Profile
Chapter 3 CULVERTS Description A culvert is a closed conduit used to convey water from one area to another, usually from one side of a road to the other side. Importance to Maintenance & Water Quality
Duron UV System YoU adjust to changing conditions it S time YoUr UV SYStem DoeS too
Duron UV System You adjust to changing conditions It s time your UV system does too Your operating conditions change. Duron UV System adjusts. Combining intelligent control with the most advanced UV lamp
Drainage and Grease Management for the Commercial Kitchen
Drainage and Grease Management for the Commercial Kitchen ACO. The future of drainage. The ACO system chain provides drainage solutions to meet the needs of tomorrow s food service facilities. Hostile
Pro-Lift Steel Pile Foundation Repair
Pro-Lift Steel Pile Foundation Repair Pro-Lift Steel Pile Foundation Repair System Pro-lift steel piles are designed for the stresses of Texas soils. They can have multiple steel walls, depending on the
Air Eliminators and Combination Air Eliminators Strainers
Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.
Chapter 9 Sanitary Sewers
Chapter 9 Sanitary Sewers S:/Engineering/Design Standards/Chapter 9 12/29/2014 Section 9.1 Topic General Requirements Chapter 9 Sanitary Sewers Page 9-1 9.2 Plan Submittals 9-1 9.3 Determination of Flow
BASEMENT FLOODING. Prevention Guide for. Homeowners
BASEMENT FLOODING Prevention Guide for Homeowners 1 Did You Know? Floods are the most common hazards in Canada. Water damage is a common cause of loss for homeowner insurance. A heavy rainfall can result
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors
Improving the flood resistance of your home Advice sheet 6: Flood-resilient This sheet provides guidance on identifying different types of floor, assessing the routes floodwater may enter, and describes
C. starting positive displacement pumps with the discharge valve closed.
KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the
Chapter 10. Flow Rate. Flow Rate. Flow Measurements. The velocity of the flow is described at any
Chapter 10 Flow Measurements Material from Theory and Design for Mechanical Measurements; Figliola, Third Edition Flow Rate Flow rate can be expressed in terms of volume flow rate (volume/time) or mass
Does Part of My Basement Floor Have to Be Removed to Install. Where Does the Water from the Sump Pump Go?...Page 5
PROTECTIVE PLUMBING - WHAT IS IT? TABLE OF CONTENTS Protective Plumbing What is it?...page 1 What is Foundation Drainage?...Page 2 What is a Sump Pumping System?...Page 4 Does Part of My Basement Floor
Introduction of Duplex Pump HPD71+71 and Short-Stroke Pump HPV112+112
Shin-ichi Kamimura Komatsu has come up with a high-pressure, large-capacity, duplex swash plate pump, HPD71+71, as the main pump for PC160-7 and a short-length, tandem swash plate pump (short-stroke pump),
2.0 BASIC CONCEPTS OF OPEN CHANNEL FLOW MEASUREMENT
2.0 BASIC CONCEPTS OF OPEN CHANNEL FLOW MEASUREMENT Open channel flow is defined as flow in any channel where the liquid flows with a free surface. Open channel flow is not under pressure; gravity is the
Pumps 101: Operation, Maintenance and Monitoring Basics
White Paper Pumps 101: Operation, Maintenance and Monitoring Basics Daniel Kernan Manager Monitoring and Control Group, ITT Executive Summary Pumps are at the heart of most industrial processes, and the
Open Channel Flow Measurement Weirs and Flumes
Open Channel Flow Measurement Weirs and Flumes by Harlan H. Bengtson, PhD, P.E. 1. Introduction Your Course Title Here Measuring the flow rate of water in an open channel typically involves some type of
Water hammering in fire fighting installation
Water hammering in fire fighting installation Forward One of major problems raised in the fire fighting network installed at Pioneer company for pharmaceutical industry /Sulaymania was the high water hammering
Prevention through Design: Eliminating Confined Spaces and Minimizing Hazards
Prevention through Design: Eliminating Confined Spaces and Minimizing Hazards American Industrial Hygiene Association Developed by the AIHA Confined Spaces Committee Approved by the AIHA Board of Directors
Power Recovery Turbines
Power Recovery Turbines Fixed and Variable Geometry Vertical Horizontal Bulletin PS-90-1 (E) Pump Supplier To The World Flowserve is the driving force in the global industrial pump marketplace. No other
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
BLADDER SURGE CONTROL SYSTEM
PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures
.5.1 MAINTENANCE AND PERIODIC INSPECTION OF DRAINAGE SYSTEMS
.5.1 MAINTENANCE AND PERIODIC INSPECTION OF DRAINAGE SYSTEMS General Drainage systems should be inspected at regular intervals (not less than once a year) and, where necessary, thoroughly cleaned out at
OPERATION & MAINTENANCE MANUAL. for VERTICAL INLINE PUMPS
OPERATION & MAINTENANCE MANUAL for VERTICAL INLINE PUMPS PATTERSON PUMP COMPANY A SUBSIDIARY OF THE GORMAN-RUPP COMPANY PO Box 790 9201 Ayersville Road Toccoa, Georgia 30577 Telephone: 706-886-2101 SAFETY
MICRO HYDRO POWER GENERATING EQUIPMENT
MICRO HYDRO POWER GENERATING EQUIPMENT TOSHIBA TOSHIBA ENGINEERING In general, specifications of hydroelectric power system vary depending upon the installation location. The hydro turbine and generator
Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
Minor losses include head losses through/past hydrants, couplers, valves,
Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within
Pump and Valve Components and Maintenance
Pump and Valve Components and Maintenance Outline: 1. Split case and End Suction pumps, industry in the 21 st century, cost of ownership, and performance tips 2. Split case Pumps features, maintenance,
PBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
SANITARY SEWER SPECIFICATIONS
SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,
VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6
- B 1 Product Detail Engineering Data... B2 Structural Support... B6 Engineering Specifications... B9 - B 2 Engineering Data REMARK: Do not use for construction. Refer to factory certified dimensions &
PRODUCT SELECTOR Pollution Control, Pumping and Rainwater Harvesting Systems
PRODUCT SELECTOR Pollution Control, Pumping and Rainwater Harvesting Systems PACKAGE SEWAGE TREATMENT SYSTEM Clearwater treatment plants are ideal for single houses and employ the well proven aerobic biological