1 THIS IS A DESIGN GUIDE NOT A SPECIFICATION SECTION PART 1 GENERAL Montgomery County Public Schools Facilities Guide DIVISION 16 ELECTRICAL WIRING DEVICES A. Provide a dedicated 20 amp, 208 volt, single phase circuit with a NEMA 6-20R, 20 amp, 208 volt, single phase receptacle for copiers in the Main Office Workroom and in the Media Center Workroom. B. Provide NEMA 5-20R duplex receptacles. Device color: 1. Normal Ivory 2. Emergency Red 3. Data Gray with gray device plate C. Standard receptacle color shall be ivory. Standard device plate color shall be ivory crackle type. D. Acceptable manufacturers Pass & Seymour, Hubbell/Bryant and Leviton. E. Provide the Command Center with emergency power receptacle, telephone outlet, data outlet and PA system microphone. Command Center to be located by MCPS. F. For every radon system pipe, provide a GFCI/weatherproof 20 amp receptacle located on roof for radon equipment. Locations as selected by the Architect. G. Installation detail for receptacles located on roof. See Standard Detail E-8.0 on following pages. H. For Standard Classroom Front Wall Data and Power arrangement. See Standard Detail E-9.0 on following pages I. For Standard Teacher s Station TV/Data/Voice/Power detail. See Standard Detail E-10.0 on following pages J. Goggle Cases require 200 watts. Multiple cases can be connected to one circuit. K. Provide a duplex receptacle on each landing of each stair. L. Kitchen - Provide a push button at the loading dock door connected to a buzzer in the kitchen office. M. Kitchen Hood 1. Provide shunt trip circuit breaker for any electrical equipment located under the hood and connected to the hood fire suppression system. 2. If there is gas feed equipment under the hood, connect gas solenoid valve to the hood fire suppression system to shut off gas. N. Kitchen Provide GFCI receptacles except for refrigerators and freezers. O. Provide mushroom push button for emergency power shut-off for Elementary and Middle Schools in the following areas: 1. Boiler Room 2. Tech Lab P. Provide mushroom push button for emergency power shut-off for High Schools in the following areas: 1. Boiler Room Revised: 4/17/09 WIRING DEVICES
2 THIS IS A DESIGN GUIDE NOT A SPECIFICATION 2. Applied Tech Center 3. Engineering Research & Design Center 4. All Science Rooms 5. Food Sciences Room. Q. In Elementary and Middle Schools, Provide two NEMA 14-50R receptacles for kilns. Provide a two pole 50 amp circuit breaker with 3# #8 ground in 1 conduit. Interlock exhaust fan with kiln switch. See Kiln Wiring Diagram. Standard Detail E-11.0 on following pages. R. In High School Art Rooms, provide four NEMA 14-50R receptacles for kilns. Provide a two pole 50 amp circuit breaker with 3# #8 ground in 1 conduit. Interlock exhaust fan with kiln switch. Similar to Kiln Wiring Diagram. See Standard Detail E-12.0 on following pages. PART 2 RECEPTACLE LAYOUT GUIDELINES A. Before locating the power receptacles, check architectural drawings for type of wall construction, such as drywall and masonry, and make sure that there are no conflicts with other equipment. The outlets boxes shall be symmetrically located according to room layout and shall not interfere with other work or equipment. Also, show any special outlet design details on the drawing. B. All receptacles and outlet boxes shall be flush-mounted in walls and floors unless they have to be surface mounted due to wall or floor construction type. Outlets located outdoors or in damp locations shall be weatherproof (GFCI) type. All receptacles located within 6'of sink shall be GFCI type. Wall mounted receptacles and outlet devices shall be mounted 18" above finished floor or 6" above countertops. When receptacles are mounted in masonry walls, the top of the outlet box shall be in line with the top of a masonry unit (16 above finished floor). All receptacle outlet boxes must be equipped with ground terminal for green bond ground wire. Floor outlets shall be flush-floor type (except in kitchen) with brass cover and lift-up lids. C. The following criteria shall be used to layout receptacles outlet boxes for different areas: 1. Classrooms - Provide two (2) duplex receptacles on each wall 2 minimum 12 feet apart. Also provide five (5) duplex receptacles with orange cover plates for computers; of these, four (4) shall be mounted on the back wall and one (1) on the front wall. Provide one (1) separate dedicated circuit for the five (5) computer duplex receptacles. DO NOT provide clock outlet because battery-pack type clocks will be provided by MCPS, except provide two (2) clock hanger outlets one on each section of gymnasium. Kindergarten and Pre Kindergarten: All receptacles mounted 16 to the top of receptacle shall be GFCI type or be connected to a GFCI circuit breaker. 2. Administration - In each administrative office provide one (1) duplex receptacle on each wall. In the General Office provide one (1) duplex receptacle every 12 ft. along the walls and a floor mounted (flush) combination outlet of quadruplex receptacle and telephone outlet for main counter. Provide a duplex receptacle and telephone outlet for each desk. Provide a dedicated 20 amp, 208 volt, single phase circuit with a NEMA 6-20R, 20 amp, 208 volt, single phase receptacle for copiers in the Main Office Workroom and in the Media Center Workroom. Provide one (1) duplex receptacle with dedicated circuit to emergency panel for sound system console. In health suite, provide two (2) duplex receptacles above sink counter, one (1) dedicated circuit, duplex receptacle for refrigerator, one (1) duplex receptacle near each cot in resting station, and one (1) duplex receptacle near the nurse's station. 3. Corridors - Provide one (1) duplex receptacle every 50'for utility purposes. Provide dedicated circuit for corridor receptacles. Provide maximum two (2) receptacles per circuit. 4. Multipurpose Room - Provide one (1) duplex receptacle every 16'along perimeter walls. In the stage area, provide a minimum of one (1) duplex receptacle on each side wall. Revised: 4/17/09 WIRING DEVICES
3 THIS IS A DESIGN GUIDE NOT A SPECIFICATION 5. Kitchen - Provide power for the kitchen equipment as per kitchen equipment manufacturer's requirements. Before laying out these receptacles and connections, coordinate locations with kitchen equipment layout. In addition, provide additional convenience duplex receptacles on each wall. Provide one (1) duplex receptacle above each walk-in freezer and refrigerator. Provide emergency power for each walk-in freezer and refrigerator. Provide 3/4" empty conduit from each cash register outlet to nearest wall to ceiling space for future data network system. Provide a push button at the kitchen loading dock door connected to a buzzer in the kitchen office. Provide necessary service for Kiosk (high school only) as required. 6. Gymnasium - provide one (1) duplex receptacle every 20'along perimeter walls. The locations for these receptacles should be coordinated with bleachers as well as paddling. Provide one (1) junction box with a single pole-20 amp circuit for a scoreboard and shot clocks. Controls for all electrically operated basketball backstops shall be located at one location in a recessed, key operated box. For folding partition, controls shall be provided on each side of partition and it is to be controlled by two individual at a time, (OSHA requirement). Provide a junction box and receptacle for scoring table next to partition housing. 7. Toilets - Provide one (1) GFCI type duplex receptacle near wash basin in every staff toilet. Do not provide receptacles in student toilets. 8. Boys and girls toilet rooms Provide a junction box and a dedicated 20 amp single phase power circuit for each future hand dryer. Coordinate the number of hand dryers and location with the project Architect. 9. Tech Lab (for middle school only) - Provide receptacles and power requirements for equipment as per manufacturer s requirements. Provide 2-3 additional receptacles. The circuit breakers for the Tech Lab should be shunted at the panelboard. The receptacles and light fixture covers and spray booth at Tech Lab shall conform with NEC Article Applied Tech Center/Engineering Research and Design Center ( high school only) Provide receptacles and power requirement for equipment as per manufacturer s requirements. Provide 2-3 additional receptacles. The receptacles and light fixture covers and spray booth at Tech Lab shall conform with NEC Article 500. Circuit breakers for electric stoves shall be shunted at the panelboard. See Standard Details E-21.0 and E on following pages. 11. For Home Economics/Nutrition Labs/Food Science Lab (high and middle schools only): Provide receptacles and power requirements for equipment as per manufacturer s requirements. Provide 2-3 additional receptacles. Provide shunt-trip for all electrical stoves. See Standard Detail E-23.0 on following pages 12. Media Center a. For shelving located on the perimeter wall, provide duplex receptacles at 12'intervals along the toe space of shelving. b. For circulation desk if it is located in the center of media center provide a stub-up for electrical and network wiring, to serve the receptacle and network outlets. Provide one (1) quad receptacle for each section of circulation desk. Provide one (1) network outlet for circulation desk. Location for all outlets in the circulation desk shall be coordinated with architectural detail drawings. c. For resource room, provide one (1) duplex receptacle and one (1) data outlet for CD ROM. Provide one (1) flush floor-mounted duplex receptacle for projector at an appropriate location as directed by MCPS for viewing the screen. Provide one (1) duplex receptacle and one (1) data outlet for each computer station. Note: If floormounted receptacles are to be used, the floor box shall be flush mounted. Revised: 4/17/09 WIRING DEVICES
4 THIS IS A DESIGN GUIDE NOT A SPECIFICATION d. In material preparation area, provide one 6'-8'length of Wiremold mounted 6 above counter with receptacles spaced every 18. e. Provide a minimum of two (2) duplex receptacles in media specialist's office. f. For media workroom, provide one (1) 30a, 208v, 1 phase, NEMA 6-20R receptacle for copier. Also provide at least one (1) duplex receptacle on each wall of workroom. g. In media storage provide one (1) duplex receptacle on each wall. Receptacle locations should be coordinated with shelving layout. h. For high/middle school directional instructional area/tech information access center, provide one combination data/duplex receptacle for each computer station. i. Provide one 120v, 20 amp 1 phase dedicated circuit junction box for security system for gate (only for high/middle school). 13. Computer Laboratory - For wall mounted computer work- stations, provide wiremold 4000 with divider (upper part to be used for power and lower for network) mounted on wall flush above built-in wall units. See Standard Detail E-7.0 in Section a. A maximum three (3) duplex receptacles are to be connected to each circuit. 14. MDF Room - Provide five (5) quadruplex receptacles with each connected to a dedicated emergency circuit. 15. IDF Room - Provide two (2) quadruplex receptacles with each connected to a dedicated emergency circuit. 16. Communications Laboratory/Support Rooms - A typical communications lab consists of three (3) areas- studio/support room, control room/support room, and headend equipment room. a. For elementary school studio, provide at least four (4) duplex receptacles on each side wall. Provide a separate, dedicated circuit for each receptacle. b. For high/middle school studio - Provide at least two (2) duplex receptacles on each side wall. For production lights (provided by MCPS) provide 3 to 5 grid bars. The grid bars must be furnished and installed by electrical contractor. Above the lighting grid bars provide ceiling mounted recessed duplex receptacles spaced 5'x5'matrix. Provide dedicated circuit for each ceiling mounted receptacle. Coordinate exact layout with MCPS, c. In control room, provide at least two (2) duplex receptacles above countertop. Provide two (2) duplex receptacles on the back wall and one (1) quad receptacle on the sidewall of control room. d. In head-end equipment room provide two (2) duplex receptacles. 17. Science Labs/Chemistry Labs - provide two (2) duplex receptacles, mounted one (1) each side of island below the countertop. Provide one (1) duplex receptacles for each island 6" above countertop for computer. Provide a push button gas valve shut-off at an exit door for the room. Provide a key operated reset at the teacher s desk. See Standard Details E-25.0 and E-26.0 on following pages a. Biology/Physics or other Generic Labs - Provide one (1) duplex receptacles receptacle for each station. Also, provide one (1) duplex receptacles and one (1) network outlet for each computer. Provide a push button gas valve shut-off at an exit door for the room. Provide a key operated reset at the teacher s desk. See Standard Detail E-24.0 on following pages 18. Business Education Suite (High School only) - Business education suite is combination of three areas - model office, computing/word processing room, office/storage. Revised: 4/17/09 WIRING DEVICES
5 THIS IS A DESIGN GUIDE NOT A SPECIFICATION a. Model Office - Model office has capacity of 32 student work stations, and divided in eight (8) modules. For each module provide four (4) duplex receptacles and one (1) data outlet for computers. For instructor s counter provide two (2) duplex receptacles and one (1) data outlet. In addition provide one (1) duplex receptacle every 12'on the parameter of wall. Provide one 30 amp, 1ø, 208 volt NEMA 6-20R outlet for copier. 19. Computing/Work Processing Room - This room has capacity of 32 student stations for word processing. Provide one (1) duplex receptacle for each station. Provide one (1) data outlet to serve four (4) stations. In addition provide one (1) duplex receptacle every 12'on each side wall. 20. Office/Storage - Provide one (1) duplex receptacle and data outlet for each desk location. 21. Cooperative Work Experience (CWE) Classroom (High School only) - On the student work station area provide five (5) duplex receptacles, each 3'on center and two data outlets (6'apart) with 1-1/4" empty conduit to ceiling space. In addition provide two duplex receptacles on other perimeter wall. In the office provide on duplex receptacle one (1) duplex receptacle and data outlet near teacher s desk. 22. Career Child Development (High school only) - Career child development area is a combination of child development laboratory, seminar/personal, family observation and office/storage area. a. The Child Development - Provide two (2) duplex receptacles on each side wall. In addition provide three (3) duplex receptacles and one (1) data outlet on designated wall for computer stations. On the kitchen area provide receptacles with dedicated circuits for microwave oven, refrigerator, and junction boxes w/dedicated circuit for disposal and dishwasher. Also in kitchen area provide two (2) duplex receptacle above counter. All electrical outlets in this area shall be GFCI type duplex receptacles. 23. Seminar/Personal family observation area - Provide two (2) duplex receptacles on each side wall. Provide five (5) duplex receptacles and two (2) data outlets on designated wall for computer stations. a. Office - Provide one (1) duplex receptacle and one data outlet for each desk location. 24. Baseball field/tennis courts (high school only) - Provide one (1) duplex receptacle (GFC)I weatherproof type) for pitching machine for baseball field and tennis court. For tennis courts provide (1) duplex receptacle (twist-lock type) for every two courts. 25. Building Exterior - provide one (1) duplex receptacle (twist-type) on each side of building. Provide GFCI weatherproof type. 26. Staff lounge - provide four (4) GFCI duplex receptacles with each having a dedicated circuit for vending machine, microwave oven, etc. Coordinate location with architectural drawings. 27. Miscellaneous Areas a. In mechanical and electrical rooms, provide one (1) duplex receptacle every 20' along interior of walls. b. In general storage rooms, provide at least one (1) duplex receptacle. c. On the roof provide one (1) duplex GFCI weatherproof type receptacle within 25 feet of each air-handling unit per National Electrical Code requirements. d. Provide one (1) duplex receptacle for each electric water cooler. Revised: 4/17/09 WIRING DEVICES
6
7 Date: 01/29/09 Revised: 03/27/09 TYPICAL TEACHING STATION & FRONT WALL DETAIL FOR TECHNOLOGY MONTGOMERY COUNTY PUBLIC SCHOOL STANDARD DETAIL E9.0 PROVIDE 1-11/4" CONDUIT FROM CEILING SPACE DOWN TO 11B BOX WITH PULL STRING. 4' 5' 16' 4' 12" TACK STRIP ELEMENTARY SCHOOLS ONLY 4'6" 12" TACK STRIP ELEMENTARY SCHOOLS ONLY QUAD ELECTRIC DESIGNATED FOR EMERGENCY POWER (RED) 16" TACK BOARD Tack Board to be 4' wide Wall space permitting. PROVIDE 11B BOX WITH DOUBLE GANG RING EXTENSION FOR DATA/ VOICE/TV CONNECTIONS. MARKER BOARD 16" PROMETHEAN BOARD N.I.C. Provided by others 18" MARKER BOARD TACK BOARD Tack Board to be 4' wide Wall space permitting. 3" MINIMUM OF 32" FROM CORNER OR CABINET TO TACKBOARD FOR BACK TO BACK TEACHING WALLS AND IF NOT BACK TO BACK, 16" WILL BE REQUIRED. PLEASE TAKE NOTE THAT THE DATA & ELECTRICAL BOXES IN THIS ILLUSTRATION THAT ARE AT 16" AT THE BOTTOM OF THE OF THE BOX WILL BE SET AT 16" TO THE TOP OF THE BOX IN PRE-KINDERGARTEN & KINDERGARTEN CLASSROOMS. DUPLEX ELECTRIC DESIGNATED FOR PROMETHEAN BOARD (Grey) PROMETHEAN BOARD TO BE INSTALLED IN FRONT OF MARKER BOARD. AT NO TIME WILL MOUNTING BRAKETS BE ALLWED TO BE ATTACHED TO MARKER BOARD, THEY MUST ATTACH ABOVE AND BELOW MARKER BOARD.
8 ¾ CONDUIT 11/4 CONDUIT WITH PULL WIRE TO CEILING. QUAD ELECTRIC DESIGNATED FOR EMERGENCY POWER (RED) METAL IVORY PLAT PROVIDED BY ELECTRICAL CONTRACTOR. PROVIDE 11B BOX WITH DOUBLE GANG RING EXTENSION. FACEPLATE WITH INSERTS PROVIDED BY OTHERS. Data Data 16" THIS ELEVATION IS FOR PRE-KINDERGARTEN & KINDERGARTEN CLASSROOMS. 16" 3" Data TV Data Voice 16" THIS ELEVATION IS FOR ALL CLASSROOMS ABOVE KINDERGARTEN CLASSROOMS. PLEASE TAKE NOTE THAT THE BOXES IN THIS ILLUSTRATION THAT ARE SET AT 16" TO THE BOTTOM OF THE BOX WILL BE SET AT 16" TO THE TOP OF THE BOX IN PRE- KINDERGARTEN & KINDERGARTEN CLASSROOMS. Date: 10/22/08 TEACHER S STATION TV/DATA/VOICE/ELECTRICAL DETAIL MONTGOMERY COUNTY PUBLIC SCHOOL STANDARD DETAIL E10.0 Revised: 03/27/09
9
10
11
12
13
14
15
GENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
More informationEARLY CHILDHOOD EDUCATION September 30, 2010
EARLY CHILDHOOD EDUCATION September 30, 2010 I. PROGRAM REQUIREMENTS Refer to the project-specific Schedule of Spaces for student stations, square footage, and for any requirements that may differ from
More informationGENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
More informationB. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationSummit Series Single Section and Double Section Homes
Single Section and Double Section Homes SM-01 All New 20 Wides Now Available! SM-08 Units shown with optional features SM-01-4814 42 Bedrooms 41 Bathrooms 648 Sq. Ft. SM-01-5214 42 Bedrooms 41 Bathrooms
More informationREQUIREMENT 5. Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations
Chapter Five: REQUIREMENT 5 Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations 5...covered multifamily dwellings with a building entrance on an accessible
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationGUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
More informationSPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This
More informationSchedule of Maintenance Fees
Schedule of Maintenance Fees Effective July 1, 2015 It is the policy of the Housing Authority of Murray not to charge for NORMAL wear and tear. However, the Housing Authority reserves the right in every
More informationGROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationElectrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
More informationArizona Health Care Association DISASTER PLANNING AND EMERGENCY MANAGEMENT GUIDE POST INCIDENT DAMAGE ASSESSMENT CHECKLIST
It is essential to perform a Basic Damage Assessment (BDA) following an adverse event to help ensure the safety of building occupants as well as prevent additional losses from occurring. This checklist
More informationMONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850
Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:
More informationHOMEOWNER S PERMIT GUIDE
HOMEOWNER S PERMIT GUIDE WHEN IS A PERMIT REQUIRED? Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor P.O. Box 15225 Chesapeake, VA 23328 Phone: (757) 382-6018 Fax: (757) 382-8448
More informationAll Apartments River Village Community Bedroom Bathroom Kitchen Living Room Commons/Hallways/Stairwells Doors Windows
All Apartments Paint cost per linear foot $3.79 Drywall repair per linear foot $10.25 Drywall repair with paint cost per linear foot $14.04 Flooring cost per square foot $8.95 Item Removal Fee (Per Item)
More informationMISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
More informationBUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
More informationELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
More informationElectrical Wiring Technical Bulletin
Electrical Wiring Technical Bulletin Overview In general, SIP construction is easier and more cost effective when things are planned and thought out before the panels are manufactured. This process will
More information1/9/2015 P:\130217-03\Project Management\Program\Ripon Space Program - 7 January 2015.xlsx
MIDDLE SCHOOL Administration Office Principal's Office 200 1 200 Desk, conference table for 4-6 Conference Room 250 1 250 Conference table for 12 Open Office Area 250 1 250 2 Workstations Mail / copier
More informationKITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
More informationAlpha System ADAPTABLE KEWAUNEE LABORATORY FURNITURE. encouraging new discovery
Alpha System ADAPTABLE LABORATORY FURNITURE KEWAUNEE encouraging new discovery Alpha 6 partition modules with Kemresin worktops. Minneapolis, Minnesota Alpha 6 partition modules with Alpha overhead service
More informationBuilding Condition Assessment Report
Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.
More informationPATTERSON ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1945 BUILDING AREA 78,300 SF CURRENT PROGRAM CAPACITY 368 ENROLLMENT 2008 463 WARD 8 PROPOSED PROGRAM CAPACITY 500 Site Plan PATTERSON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationHAMILTON SCHOOL. 1401 Brentwood Parkway, N.E., Washington, DC INITIAL YEAR BUILT 1968 BUILDING AREA
INITIAL YEAR BUILT 1968 BUILDING AREA 187,700 SF CURRENT PROGRAM CAPACITY N/A ENROLLMENT 2008 129 WARD 5 PROPOSED PROGRAM CAPACITY N/A Site Plan HAMILTON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationNYC Department of Education Building Condition Assessment Survey 2014-2015 P.S. 64 (OLD 71) - MANHATTAN, 600 EAST 6 STREET, MANHATTAN, NY, 10009
School: InspectionId Asset Data Inspection Type Building Assessment Survey 204-205 P.S. 64 (OLD 7) - MANHATTAN, 600 EAST 6 STREET, MANHATTAN, NY, 0009 Time In Last Edited 095 ELECTRICAL 205-0-6 08:45AM
More informationFor Models #6-5001, #6-7501, #10-7501 & #10-12K1
EmerGen Switch Manual Transfer Switch Manufactured by CONNECTICUT ELECTRIC SWITCH MFG. CO. 1-800-730-2557 OWNER S MANUAL & INSTALLATION INSTRUCTIONS For Models #6-5001, #6-7501, #10-7501 & #10-12K1 PLEASE
More informationElement D Services Electrical
Service and PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as
More informationFacility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components
Infrastructure Facility Condition Summary Weighted Avg Condition Score Facility Components Systems Surveyor/ Date Done Comments G Sitework.9 Site Improvements Parking Pedestrian Paving Site Development
More informationCHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
More informationPUBLIC RESTROOMS, DESIGN INTENT
PUBLIC RESTROOMS, DESIGN INTENT 1.01 STRUCTURAL A. Where feasible, metal stud partitions will be constructed on a 6 high concrete curb. 1.02 MECHANICAL A. Restrooms will have a minimum of 15 air changes
More informationUniversity of North Carolina at Charlotte Design and Construction Manual Section 3, Annex K, 49er Card Systems ANNEX K 49ER CARD SYSTEMS
ANNEX K 49ER CARD SYSTEMS UNC CHARLOTTE 49ER CARD SYSTEM INSTALLATION AND CONTRACTOR REQUIREMENT SCOPE OF WORK: The following information pertains to the installation and contractor requirements to install
More informationElectrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
More informationORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT
1. SAFETY, HEALTH, CODE 1.1 Structural Requirements, Seismic Stability 1.1.1 Primary Structure 1.1.2 Ceilings 1.1.3 Cabinets, Equipment 1.1.4 Portables 1.2 Fire / Life Safety 1.2.1 Corridor, Separation
More informationINSPECTION GUDELINES
GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit
More informationTop Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
More informationMSBA Guidelines for Science Labs
Massachusetts School Building Authority Steven Grossman Chairman, State Treasurer Katherine Craven Executive Director MSBA Guidelines for Science Labs May 26, 2010 www.massschoolbuildings.org Introduction:
More informationBoard Seminar Facilities. School Year 2012-2013. Submitted by Joseph L. Lisa-Director of Facilities
Board Seminar Facilities School Year 2012-2013 Submitted by Joseph L. Lisa-Director of Facilities High School Installed new fence for Pre-K activities by weight room. Installed new rails and side walks
More informationESTIMATE ORIG. ESTIMATE: TOTAL: $204,249 DATE: 01/15/08 DESCRIPTION OF WORK QUANTITY DIVISION TOTAL
PARTITIONS REGULAR WALLS 9' HIGH 214 LF TENANT DEMISING WALL 150 LF INTERIOR FURRED WALLS 9' 86 LF OFFICE DEMISING WALL 98 LF DOUBLE FRAME RADIUS WALL 18 LF RADIUS SOFFITS 172 LF SOFFIT 76 LF FINISH NEW
More informationUtility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
More informationORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT
1. SAFETY, HEALTH, CODE 1.1 Structural Requirements, Seismic Stability 1.1.1 Primary Structure 1.1.2 Ceilings 1.1.2 Water damage in many classrooms. Replace tiles. 1.1.3 Cabinets, Equipment 1.1.4 Portables
More informationSecurity Systems Intrusion Alarm
Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted
More informationA Residential Owner s Guide to PERMITS. Elgin CITY OF PLANNING & NEIGHBORHOOD SERVICES
A Residential Owner s Guide to PERMITS CITY OF Elgin PLANNING & NEIGHBORHOOD SERVICES CITY OF Elgin A Residential Owner s Guide Welcome! This booklet has been prepared to provide residential property owners
More informationBUNKER HILL ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1970 BUILDING AREA 98,200 SF CURRENT PROGRAM CAPACITY 332 ENROLLMENT 2008 387 WARD 5 PROPOSED PROGRAM CAPACITY 750 Site Plan BUNKER HILL - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationCLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
More informationMinimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
More informationDesign Questionnaire. Design & Style
Designing your kitchen requires not only deciding on décor and colors but also creating a space plan and choosing products that will allow your kitchen to function the way that best suits you. Answering
More informationFinal Walk-Through Checklist
Final Walk-Through Checklist All Aspects Home Inspections Inc 516 731-7213 www.artofinspection.com The final walk-through gives homebuyers an opportunity to inspect a property before closing on the sale
More informationReport Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10
Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 PROPERTY DESCRIPTION PROPERTY INSPECTED: INSPECTION ADDRESS: 4722 Baltimore Avenue
More informationIrvinton Village Apartments 2901 Fulton Houston, Texas 77009 Houston Housing Authority J. Allen Management Managing Agent
Irvinton Village Apartments 2901 Fulton Houston, Texas 77009 Houston Housing Authority J. Allen Management Managing Agent Scope for Irvinton Village Unit #512 Overall Scope: Demolition, Renovation, and
More informationCity of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines
Western Riverside County Code Uniformity Program City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines PHONE (951) 826-5697 3900 Main Street, Riverside, CA 92522
More informationAddition and Renovation Northview Elementary School Design Development Manual
PERU ELEMENTARY SCHOOL DISTRICT 124 Peru, La Salle County, Illinois Addition and Renovation Northview Elementary School Design Development Manual Healy Bender Project No. 10-3113-145 Tab 3 Sheet 3-1.00
More informationOrlando Home Inspection Services
PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com
More informationFacilities Operations Customer Service Standards WORK ORDER PRIORITIES
Facilities Operations Customer Service Standards WORK ORDER PRIORITIES In order to provide fair and consistent maintenance service to all University faculty, staff and students, a work priority system
More informationBuilding Permits: When are they required?
Building Permits: When are they required? Generally, you need to obtain a building permit from the City whenever you construct, enlarge, alter, repair, move, remove, improve, convert, or demolish a building
More informationPresentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals
Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals Les Butler Associate Commissioner for Business and Regional
More informationSPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
More informationNORTH PENN HIGH SCHOOL RENOVATIONS
NORTH PENN HIGH SCHOOL RENOVTIONS PRELIMINRY SCOPE, BUDGET & PHSING CONSIDERTIONS 401 EST HNCOCK STREET LNSDLE, P 19446 PREPRED BY BONNETT SSOCITES INCORPORTED 220 BLDWIN TOWER, 1510 CHESTER PIKE EDDYSTONE,
More informationWhitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.
Building Type Building Code Whitley Classroom Buildings BOCA, UBC, SBCCI, NEC, ADA Structural Support Outrigger construction standard, Whitley model classrooms. Main support beams to be 12 11.8# per lineal
More informationPage 1 of 6 COMPLIANCE CHECKLIST. > Long Term Care Facility - Nursing Unit
COMPLIANCE CHECKLIST Page 1 of 6 > Long Term Care Facility - Nursing Unit The following checklist is for plan review of new long-term care facilities and new additions to existing long-term care facilities.
More informationItems in red were complete 2-22-10. Items in green were complete on 8-2-11. Lined out items are Life Safety Codes.
Office of Safe and Orderly Schools Facility Safety Assessment Dennis Meador, School Facilities Supervisor Mark Hobson, School Facilities Supervisor Division of School Building September 18 19, 2007 Items
More informationESTIMATING PLUMBING, HEATING, VENTILATING, AND AIR CONDITIONING (HVAC), AND ELECTRICAL WORK
C H A P T E R 7 ESTIMATING PLUMBING, HEATING, VENTILATING, AND AIR CONDITIONING (HVAC), AND ELECTRICAL WORK OBJECTIVES After reading this chapter and completing the review questions, you should be able
More informationPLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW
CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,
More information#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check
#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check Zoning laws Deed restrictions on home size, foundation style, roof pitch, etc. Suitability (slope, wetland issues, etc.) Accessibility
More informationElement D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
More information2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationPLUMMER ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1959 BUILDING AREA 69,400 SF CURRENT PROGRAM CAPACITY 481 ENROLLMENT 2008 228 WARD 7 PROPOSED PROGRAM CAPACITY 325 Site Plan PLUMMER - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationSPACE TYPES & REQUIREMENTS
SPACE TYPES & REQUIREMENTS Career and Technical Education (CTE) School Type: E M H 6 7 8 9 10 11 12 Adjacency Diagram Functional Area Descriptions Career and technical education (CTE), formerly professional
More informationSECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
More informationTIPS TO PREPARE FOR MOVING OUT OF YOUR UNIT Cleaning Tips and Price List
TIPS TO PREPARE FOR MOVING OUT OF YOUR UNIT Cleaning Tips and Price List The Residence Life Department wants to provide you with a few handy cleaning tips so that you can leave your room in tip top shape
More informationYour Basement Remodeling Specialist LLC
Your Basement Remodeling Specialist LLC Contents Introduction 3 Remodel Details 4 Basement Bid Scope 5 Financial Arrangements 6 Homeowners Shopping Guide 7 The following is provided with your actual quote:
More informationCity of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage
City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage Property Address: Company Name: Contractor Name: Contractor Address: City: State: Zip: License Number: Phone Number
More informationEXPRESS PERMITS (No Plan Check Required)
EXPRESS PERMITS (No Plan Check Required) Following are the lists of different types of construction for which an express permit can be issued. Express permits can be issued where work does not require
More informationElectrical Service Guidelines
Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4
More informationSub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders
INTRODUCTORY INFORMATION TABLE OF CONTENTS 00 0101 PROJECT TITLE PAGE PROCUREMENT REQUIREMENTS (PROJECT MANUAL) Tab A - Invitation for Bids Tab B - Instructions to Bidders Tab C Bid Form for General Bids
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationBUILDING NAMING RIGHTS
NEW HEALTH SCIENCE BUILDING Davis Applied Technology College METHODSTUDIO INC. BUILDING NAMING RIGHTS NAMING RIGHTS OPPORTUNITIES Building Areas $500,000 Building Naming Right $100,000 LEED Gold Sponsorship
More informationChapter Seven: REQUIREMENT 7. Usable Kitchens and Bathrooms PART A: Usable Kitchens PART B: Usable Bathrooms
Chapter Seven: REQUIREMENT 7 Usable Kitchens and Bathrooms PART A: Usable Kitchens PART B: Usable Bathrooms 7 PART A: Usable Kitchens 7a...covered multifamily dwellings with a building entrance on an accessible
More informationPrinted Monday, August 27, 2007 Inspected By: Michelle Teague. Client Information: Inspection, Condo City Lane Chicago, IL. Inspected 8/22/07 8:00 AM
Pa g e 1 o f 1 5 All About Homes, LLC Michelle M. Teague Owner 312-371-7414 Phone 773-508-6209 Fax www.michelleinspects.com michelle@michelleinspects.com 1725 W. Granville Ave. Chicago, IL 60660 Printed
More informationCooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
More information47 Levencourt Way London SW8 1HR. Tenant: Eric Stevenson Prepared for: Elizabeth Collins
47 Levencourt Way London SW8 1HR Prepared by: John Smith Date of Inspection: 16/03/12 Tenant: Eric Stevenson Prepared for: Elizabeth Collins Inventory & Check In Report Table of Contents Schedule of Conditions...
More informationKitchen Planning Guidelines With Access Standards
Kitchen Planning Guidelines With s 1: Door/Entry The clear opening of a doorway should be at least 32 wide. This would require a minimum 2-10 door. The clear opening of a doorway should be at least 34.
More informationCOST OF WORK FORM. Abbreviations: ea = each, LF = linear feet, SF = square feet, HSF = square feet of living area (including garage conversion space)
COST OF WORK FORM All costs shown are estimates using base grade materials, taxes, and labor. For houses where a higher quality is indicated, the costs should be increased for work requiring upgraded materials.
More informationBuilding Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER
More informationDIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
More informationRESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
More informationHOUSING QUALITY STANDARDS (HQS)
HOUSING QUALITY STANDARDS (HQS) HQS INSPECTIONS Part II Site Inspections 24 CFR 982.401 & 405 1si Rev. 4-20-06 General Conditions All doors and windows accessible to the outside, must have a workable lock.
More informationTYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
More informationFire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
More informationMURCH ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1929 BUILDING AREA 47,700 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 491 WARD 3 PROPOSED PROGRAM CAPACITY 500 Site Plan MURCH - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationR432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose.
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. This rule is promulgated pursuant to Title 26, Chapter 21. R432-5-2. Purpose. The
More informationAttached is one (1) copy of Addendum 1, hereby made a part of the above referenced ITB.
November 6, 2015 Re: 15ITB99898A-CJC, Medical Clinical Cleaning Services Dear Proposers: Attached is one (1) copy of Addendum 1, hereby made a part of the above referenced ITB. Except as provided herein,
More informationCALLOWAY COUNTY SCHOOLS DISTRICT FACILITIES PLAN
DISTRICT "SHELL" SUBMISSION DATE: 4/17/13 (delete following Hearing) KDE "SHELL" RESUBMISSION DATE: 4/19/13 (delete following Hearing) KBE APPROVAL DATE: JUNE 2013 CALLOWAY COUNTY SCHOOLS DISTRICT FACILITIES
More informationElement D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
More informationSilvercrest Introduces the All New S E R I E S. Shown with Optional Dormer Treatment
Silvercrest Introduces the All New Shown with Optional Dormer Treatment BD-01 2 Bedrooms 1 Bathroom 768 Sq. Ft. BD-02 2 Bedrooms 1 Bathroom 768 Sq. Ft. 1 Bradford Series BD-03 960 Sq. Ft. 1066 Sq. Ft.
More information