Service Manual. Brivis StarPro Plus Brivis StarPro Max

Size: px
Start display at page:

Download "Service Manual. Brivis StarPro Plus Brivis StarPro Max"

Transcription

1 Service Manual Brivis StarPro Plus Brivis StarPro Max Service shall be carried out only by Authorised Personnel. This Service Manual must NOT be left with the Owner, or distributed to other persons not permitted to obtain this information by Brivis Climate Systems. Service Manual Starpro MX / HX Series Prototype Issue 2 1

2 SCOPE This Service Manual contains information relevant to servicing a Brivis StarPro Plus heater. It is intended for Service personnel who have received adequate training on Brivis Gas Fired Ducted Central Heaters, in particular Brivis MPS series heaters. The main sections covered include: Heater operation Troubleshooting Servicing Component Removal/Assembly Procedures Technical Specifications Further information on installation and operation of Brivis StarPro heaters can be obtained from the Heating Installer s Manual and Heating Owner s manual Part Number: Note that this is the first issue of this manual, and information on unknown failure modes or problems at the time of printing will not be present. Feedback is highly appreciated to improve the information contained here within. 2

3 Table of Contents 1. Heater Operation Operation Overview Operation Overview Continued NG-2 Control Operation Installer Menu Service Menu Gas Valve Operation Burner Operation Spark Igniter Operation Flame Sensor Operation Combustion Fan Operation Pressure Switch Operation Main Fan Assembly Operation Operation Flow Charts INSTALLATION AND COMMISSIONING TROUBLESHOOTING Fault Code Summary ERROR 30 FAN_LIMP ERROR 32 DATA_Err ERROR 33 MDGV_LIMP ERROR 35 No_SA-THM ERROR 36 BadSA-THM ERROR 40 OHEAT_R-A ERROR 43 OHCooLDwn ERROR 44 RoLLOut ERROR 45 LOW24VOLT ERROR 46 IGR_NOFLM ERROR 47 IGR_BDFLM ERROR 48 LOST_PRES ERROR 49 LOST_FLME ERROR 50 IGN_LKOUT ERROR 51 RLT_NOGAS ERROR 52 FLM_NOGAS ERROR 53 OH_LKOUT ERROR 54 RoL_LKOUT ERROR 55 IGINVALID ERROR 56 PRES_STOF ERROR 57 PRES_STON ERROR 58 PRES_FAIL ERROR 60 MOTOR_O-C ERROR 61 PVCR-STOF ERROR 62 PVCR_STON ERROR 63 PVCR-FAIL Error 64 GAS_LKOUT ERROR 65 MTR_LKOUT

4 3.30 ERROR 66 SVCR_STOF ERROR 67 SVCR_STON ERROR 68 SVCR_FAIL ERROR 69 FUSE_BLOW ERROR 70 SS-SDNERR ERROR 71 SS-STAERR MAIN COMPONENTS SERVICING Gas Valve Servicing Gas Valve Checking and Adjustment (only if required) Combustion Fan Servicing Spark Igniter Servicing Flame Sensor Servicing Pressure Switch Servicing Main Fan Assembly Servicing Unit operation REMOVAL / ASSEMBLY PROCEDURES Burner Assembly Removal Gas Manifold Assembly Removal Gas Valve Removal Pressure Switch Assembly Removal Combustion Fan Removal NG-2 Electronic Control Board Removal Heat Exchanger Removal Flue Terminal Removal Main Fan Assembly Removal Splitting Internal Model Heaters Technical Specifications StarPro Wiring Diagram

5 1. Heater Operation This section provides an overview of the operation of the StarPro Plus/Max series heaters. It is vital that an understanding of how StarPro Plus/Max heaters, and their components, operate in order to service the StarPro Plus/Max Series heater effectively and efficiently. 1.1 Operation Overview The Brivis StarPro Plus/Max series ducted central heater consists of high efficiency (HX) and mid efficiency (MX), internal and external models for use on Natural Gas, and ULPG (universal liquefied petroleum gas). Universal meaning suitable for any composition of propane and butane LPG. The StarPro Plus/Max series heater is an induced draught combustion system, consisting of direct spark ignition with electronic gas modulation to vary the heat output to the desired level. The supply air temperature (air leaving the heater) is monitored via a thermistor located in the duct near the heater outlet, and is continuously monitored by the control. The desired temperature can be set within a suitable range during commissioning. The turn-down ability of the heater gas rate allows for a significant variation in the amount of open outlets in the house. The combustion fan operates at a fixed speed. 5

6 StarPro MX External Heater StarPro HX External Heater 6

7 1.2 Operation Overview Continued During ignition, the gas rate is between an intermediate level and full gas rate, and maintains this rate during the flame confirmation period. After flame confirmation, the gas rate rises to the maximum allowable level, known as the nominal gas consumption (NGC). Once the heater approaches the set supply air temperature, the control modulates the gas rate to maintain the set supply air temperature. The airflow rate is controlled via speed monitoring of the main fan. The room fan can be controlled to any necessary speed. During warm up and cool down, the room fan ramps up and down in speed respectively. During steady state operation the room fan speed runs at the set speed, which is set during commissioning. Feedback is gained via a tachometer known as the speed sensor located on the main fan motor. When adaptive zoning is part of the system and zones are opened or closed by the user, the fan speed adjusts to suit the required airflow rate. Both high efficiency (HX) and mid efficiency (MX) models have an aluminised steel tube & plate primary heat exchanger, and on the HX models this is combined with a tubular stainless steel secondary heat exchanger. To ensure for adequate air for combustion, a vacuum pressure switch measures the vacuum pressure prior to the combustion fan. On HX models a second pressure switch ensures that condensate is freely draining from the heater, and no blockage in the condensate line has occurred. The following provides an overview of the StarPro heater s NG-2 control and main components and how they function. 1.3 NG-2 Control Operation The NG-2 controller has an LCD display and 3 buttons to access information and change parameters. UP SET DOWN The controller has two menus that limit access to relevant personnel. These being the Installer menu and Service Menu. 7

8 1.4 Installer Menu The Installer menu provides information and has parameters that can be controlled by the installer. On power up of the heater, the display will show HTG_OFF ng, if a Brivis Networker wall control is connected, and show SEARCH_nG if an analogue wall control is connected or if no wall control is connected. The installer menu is present as soon as the heater is powered up and initialised. The selection list can be scrolled through by using the SET button. The parameters can be changed by using the UP and DOWN buttons. The following table contains all parameters accessible in the Installers menu. Installer Menu Settings No. Display Appearance Description 1 2 HEATER MAXIMUM FAN SPEED SETTING The number displayed is the fan s default fan speed setting i.e. the RPM the fan is set to run at for normal heating operation. It can be adjusted between a maximum of 1500 and a minimum of 500, and should be set to meet the installation s airflow requirements. It is recommended to use a fan speed between 1000 to 1500, as lower speeds are more likely to result in overheat conditions if the system has not been balanced correctly. COOLING MAXIMUM FAN SPEED SETTING This displays the RPM the fan is set to run at for normal refrigerative cooling. It can be adjusted between a maximum of 1500 and a minimum of ZONING MINIMUM FAN SPEED SETTING This is the minimum RPM the fan will operate to with the maximum outlets closed due to the Networker zoning in heating mode. The default is 950, but it can be adjusted between 500 and is the recommended minimum setting. HEATER IDENTIFICATION NUMBER (Do not alter unless multiple heaters are installed) This parameter is used to identify each heater in priority order when more than one heater is connected on the system. CIRCULATION FAN OPERATION This displays the RPM of the fan motor in circulation mode for fan operation between heating/refrigerative cooling cycles. E.g. when the system achieves the set room temperature and is cycled off by the thermostat, the heater s fan will continue to operate, to circulate the room air. SUPPLY AIR THERMISTOR SET POINT TEMPERATURE This displays the temperature the heater s gas valve will modulate to maintain. The default will vary across the different models, but it can be adjusted between 45º C and 70º C. This should be set to provide a comfortable outlet temperature. 8

9 7 ZONE / REFRIGERATION MODE This is the selection mode for incorporating adaptive zoning and refrigeration onto the system. Parameter Value Description 0 No zone or add-on refrigeration 1 On-board or Brivis Network 506 (240 VAC) or 516 (24 VAC) module relays can be used for zone control only 2 On-board or Brivis Network 506 module relays can be used both for zone control and add-on refrigeration. 3 Brivis Network 506 (240 VAC) or 516 (24 VAC) zone control only with relay number 3 used to switch on another device (e.g. humidifier). 4 Brivis Network 506 (240 VAC) or 516 (24 VAC) zone and add-on control with relay number 3 used to switch on another device (e.g. humidifier). 5. Brivis Network 516 (24 VAC) Zone Control. 4 x 24 VAC zone relays plus the use of the NG-2 board refrigeration output. Note: Requires NG-2 version 50 software to access NET506=5 Refer to Brivis Network 506 module installation instructions and Brivis Networker Advanced Programming manual for further information. Note: All settings are saved automatically as you leave the set up mode. To leave the set up mode and return to normal operation, either leave the control untouched for 20 seconds, or keep pressing the SET button until the normal operation screen resumes, or press and hold the SET button for 3 seconds. 9

10 1.5 Service Menu The service menu can be accessed by following the instructions below: Ensure the LCD displays one of the following before commencing to the next sequence: Heat_##-# - when the heater is running, (where ##- # is the measured supply air temperature in C to one decimal place). HTG_OFF NG when the heater is in standby mode and a Brivis Networker wall control is connected. SEARCH_NG -- when the heater is in standby mode and an analogue wall control is connected. This can be achieved by entering a coded key sequence into the NG-2 control. The Service menu has three modes: Information, Error Log and Service Parameter. Each of these is explained below. To move through the different service modes, press the SET button. Use the UP and DOWN buttons to move through the selection list for each mode. Information Mode The information shown in this mode are the actual details from the sensors and components as they are operating, as distinct to how they have been set to operate. DRV = displays the modulating coil level based on a scale from GAS = 95 - displays the current in ma measured at the modulating coil. S -Air = displays the ACTUAL measured temperature at the supply air thermistor in C to one decimal place. PHASE = displays the current phase angle to the main fan motor. CIRC = displays the ACTUAL main fan RPM. Error Log Mode The Error Log displays the history of logged error information. It displays the details between 2 alternating screens, which includes the error code, time and day of the week when the error was logged ( d0 being Monday and d1 being Tuesday, and so on). Note: the Networker must be set to the correct date and time for the recorded details to be correct. The control has the ability to store 32 error messages (L0 - L31, where L0 is the most recent error, L1 the second most recent, and so on). Service Parameter Mode In Service Parameter mode the parameter number is displayed immediately following the "S" to the left of the LCD. The value of the parameter setting is to the right of the LCD, and can be adjusted by using the UP and DOWN buttons whilst the SET button is pressed. The changed parameter value is automatically saved when the next parameter is selected or the Service menu is exited. Be careful not to hold down the SET button for too long without using the UP and DOWN buttons as exit from the Service Mode will occur. Once all required changes have been made, exit the Service Menu by holding down the SET button for at least 2 seconds. A full list of service parameters are included below. 10

11 rameter umber NG - 2 SERVICE PARAMETERS Description Default Value S1 NG Modulating coil Minimum current level (ma) 30 S2 NG Modulating coil Maximum current level (ma) 115 S3 NG Modulating coil Ignition current level (ma) Factory Set (68 95 ma) S4 Main fan continually check speed on start up 1 S5 Continually check fan speed difference on start up 25 S6 Continually check fan speed difference limit running 50 S7 Heating warm up cut off temperature (ºC) 40 S8 Cool down fan speed gradient time interval (ms) 500 S9 Cool down cut off temprature (ºC) 44 S11 LPG modulating coil minimum current level (ma) 45 S12 LPG modulating coil maximum current level (ma) 160 S13 LPG Modulating coil Ignition current level (ma) Factory Set S14 Cool down minimum temperature before fan cuts out 41 S17 DO NOT CHANGE 600 S18 DO NOT CHANGE C544 S19 DO NOT CHANGE 0 S20 DO NOT CHANGE 500 S21 DO NOT CHANGE 3 S22 Boost control activation temperature difference (º C) 3 S23 Gas control modulation boost control temperature (º C) 65 S24 Heating boost control main fan speed offset (RPM) 0 S25 DO NOT CHANGE 0 S26 DO NOT CHANGE 5000 S27 DO NOT CHANGE 2000 S28 DO NOT CHANGE 0 11

12 MX Unit Components 12

13 HX Unit Components 13

14 1.6 Gas Valve Operation The gas valves function is to provide gas for combustion. The gas valve is a Honeywell VK8105M gas valve, with electronic modulation, to vary the gas flow rate. It consists of two primary main solenoids which open and shut the gas valve, and an electronic modulating solenoid, to vary the gas flow rate. The gas valve is controlled by the NG-2 control. Modulation occurs when the NG-2 control varies the current through the modulation coil on the gas valve. 1.7 Burner Operation The burners are known as In-shot burners. They consist of a venturi, which helps to draw air into the top of the burner, near the injectors. This is known as primary air and is used for gas mixing before combustion occurs. Once the gas and primary air leave the burner port, at the exit of the burner, combustion begins, and secondary air is added to the flame from the suction force developed from the combustion fan. There is a cross lighting gallery near the burner exit, which allows for cross ignition between each adjacent burner. 1.8 Spark Igniter Operation The Spark Igniter consists of a spark probe and earth probe used to create a fixed spark gap (just like a spark plug on a combustion engine). The NG-2 control creates a high voltage through a sparker canister to generate a spark across this gap. This spark gap is located beneath the burner port at one end of the burner rack. Once ignition has occurred and the flame is sensed, the spark igniter stops sparking. 1.9 Flame Sensor Operation The Flame Sensor consists of a single metal probe and is located beneath the burner at the opposite end of the burner rack from the Spark Igniter. When flame is present at this burner, a small electric current passes from the flame sensor through the flame to the closest ground point (either the Burner or Heat Exchanger). The NG-2 control monitors the Flame Sensor current level. If it is within an allowable range, then the controls allows for normal operation. If the current is too low, the gas valve will shut down Combustion Fan Operation The combustion fans primary function is to pull air through the heat exchanger. This air is used to draw the flame into the heat exchanger inlet ports. It is also used to fuel the flames as they leave the burners. If this combustion airflow is reduced, the combustion quality will be reduced and sooting may occur. If the airflow is reduced considerably, then the flames will not be sucked into the heat exchanger and flames will rollout. Fortunately, there are measuring devices to prevent these occurrences from causing an unsafe condition. The combustion fan operates at a fixed fan speed, and is switched on and off by the NG-2 control. When the fan is in operation, the suction effect of the fan creates a vacuum inside the heat exchanger from the heat exchanger inlet ports all the way through to the combustion fan box, which the combustion fan is mounted to. During start-up, the combustion fan performs a pre-purge for approximately 15 seconds. This ensures that there is no un-burnt fuel in the heat exchanger. During this phase, the required quantity of airflow for adequate combustion is confirmed by a vacuum pressure 14

15 switch. If the airflow is not sufficient, then the vacuum pressure will be too low, and the pressure switch will not close, and a pressure switch error will be logged and no ignition will occur. During normal operation the vacuum pressure generated by the combustion fan is continually monitored by the pressure switch. If this vacuum pressure drops too low, then pressure switch will open, the burners will the shut down and an error will be logged. During a normal shut down sequence, the burners will shut down, and the combustion fan will switch off after 5 seconds Pressure Switch Operation PRESSURE SWITCH: The pressure switch is a Cleveland NS2 series diaphragm pressure differential activated switch (AGA Approval Certificate number 7290). MX models have one pressure switch and HX models have two. Combustion Airflow Proving Switch (All models) The pressure switch for proving sufficient combustion airflow is located in the vicinity of the combustion fan and measures the vacuum pressure in the heat exchanger outlet box prior to the combustion fan. If there is insufficient vacuum pressure to ensure for safe and reliable ignition or combustion quality the switch becomes open circuit then the 24 volt line to the gas valve is cut. Condensate Blockage Protection Switch (HX models only) The pressure switch for ensuring the condensate drain is not blocked and filling with water is located in the same location as the Combustion Airflow Proving Switch. The vacuum pressure is measured in the condensate tank through a probe. If the condensate level rises to the point where the combustion quality is unsatisfactory, the vacuum pressure measured by the switch falls below the open circuit pressure and the 24 volt line to the gas valve is cut. 15

16 1.12 Main Fan Assembly Operation ROOM AIR FAN A centrifugal fan and Permanent Split Capacitor (PSC) motor, housed in a metal scroll are used for room air circulation. The room air fan is contained within the fan cabinet. A speed sensor mounted on the motor end plate provides speed feedback to the NG-2 control to maintain the required speed. The NG-2 also controls the timings for the room air fan operation. MOTOR: 21/22 kw models 315 W PSC motor, with 15 F capacitor and mounting brackets incorporating two rubber ring vibration isolators. 30/35 kw models 650 W PSC motor, with 25 F capacitor and mounting brackets incorporating two rubber ring vibration isolators. FAN: 21/22 kw models 9"x7" centrifugal plastic fan wheel. Actual diameter of 225 mm and width of 180 mm. 30/35 kw models 10"x10" centrifugal plastic fan wheel. Actual diameter of 284 mm and width of 265 mm. 16

17 1.13 Operation Flow Charts Heater Start up Flow Chart Heater switched on Combustion fan hold off (2 sec) Pressure Switch Closes Combustion Fan Prepurge (15 sec) Ignition Ignition retry phase activated Flame detect time Has flame been detected within 4.5 seconds? No Yes Flame validate time Has flame been present for 10 seconds? No Yes Initiate main fan hold-off time of 10 seconds. Run at minimum fan speed of 500 rpm Has supply air thermistor reached 40 C (Service parameter S7) within 120 seconds? No Fan speed ramps up Are all zones open or no zones programmed into Networker? No Yes Normal operation continues Thermistor limp mode activated. Heater runs at minimum gas pressure and maximum set fan speed during steady state operation. Yes Run at steady state fan speed (Installer parameter I1) Run at economy fan speed (Installer parameter I3) Steady state operation 17

18 Heater Shut down Flow Chart Heater switched off Gas valve closes Yes Is supply air temperature below 50 C (Service parameter S9) No Combustion fan post-purge (5 sec) Yes Ramp down fan speed by 10 rpm every 0.5 seconds (Service parameter S8) until minimum fan speed of 500 rpm is reached. Minimum fan speed (500 rpm) Is supply air temperature below 41 C No Yes Main fan turns off 18

19 2. INSTALLATION & COMMISSIONING REFER TO HEATING INSTALLER S MANUAL FOR INSTALLATION AND COMMISSIONING INSTRUCTIONS (ISSUE DATE FROM APRIL 2009 ONWARDS, PART# 21918). 3. TROUBLESHOOTING Most failure modes will result in a fault code being logged in the NG-2 control. These faults can be viewed by entering the Service Menu. A brief description of each fault code is shown below, followed by detailed troubleshooting for each fault code. 3.1 Fault Code Summary Below is a list of fault codes to be used for diagnostics and troubleshooting. Fault Code Error 30 LCD Message Description While the main fan is operating the main fan speed sensing signal has been detected as incorrect for more than 200 seconds. Error 32 Board Failure: This fault indicates that parameter data in non-volatile memory could not be accessed and that all parameter data has been restored to default values. Error 33 Error 35 The feedback current from the gas valve modulating coil is not detected for at least the gas valve modulating coil fault delay time interval of 5 seconds even though a drive level is being applied to the coil. The supply-air thermistor has been detected as either open or short circuited for at least the supply-air thermistor fault delay time interval of 5 seconds. Error 36 Error 40 Error 41 Error 42 The temperature registered by the supply-air thermistor did not reach the modulation set point temperature defined by installer setting number 6 within the main fan override time defined by factory parameter number 8. With this default value, during this stage of the thermistor cool down process the main fan will be ramped down by 10 rpm every 500 ms until the absolute minimum fan speed allowed is reached The combustion fan overheat switch has been detected as opened forcing the overheat cool down process to be initiated. So long as this switch remains open this fault condition is reported. The supply air overheat switch has been detected as opened forcing the overheat cool down process to be initiated. So long as this switch remains open this fault condition is reported. The supply air thermistor temperature has exceeded 90 C, forcing the overheat cool down process to be initiated. So long as this temperature is exceeded this fault condition is reported. 19

20 Error 43 Error 44 Error 45 Error 46 Error 47 Error 48 Error 49 Error 50 Error 51 The condition that has forced the overheat cool down process to be initiated has been removed with the remaining cool down process to be completed. During an ignition at the FLAMEDETECT state or thereafter a flame rollout signal is detected and the maximum rollout events allowed has not been exceeded. The heating cycle is forced into its OFF state with a restart initiated. The 24 VAC voltage level has dropped below the threshold level defined by factory parameter number 27 for at least the 24 VAC under threshold level delay time. A transient fault is registered (Code#45) indicating that heating cycle operation cannot be guaranteed with such a low voltage level. During an ignition attempt within the FLAMEDETECT state the flame signal is not detected within the flame detect time interval and the maximum attempts at flame detection during ignition have not been made. The heating cycle will be forced to its OFF state and a restart initiated. During an ignition attempt within the FLAMEVALIDATE state the flame signal is lost within the flame validate time interval and the maximum attempts at flame validation during ignition have not been made. The heating cycle will be forced to its OFF state and a restart initiated. During the ON phase of the heating cycle after the FLUEDELAY state has been processed the combustion chamber pressure switch has opened indicating a pressure loss with the maximum times this is allowed not exceeded. The heating cycle will be forced to its OFF state and a restart initiated. With the gas valve main coil energised flame has unexpectedly been lost, the heating cycle forced into its OFF state with a restart initiated. With no gas being expelled and no ignition source active a flame rollout signal has been detected indicating a problem with the flame rollout sensing circuitry. With no gas being expelled and no ignition source active a flame rollout signal has been detected indicating a problem with the flame rollout sensing circuitry. Error 52 Error 53 Error 54 Error 55 Error 56 Error 57 With no gas being expelled and no ignition source active a flame signal has been detected indicating a problem with the flame sensing circuitry. The number of overheat cool down procedures that have occurred in the cool down activation check time interval has exceeded the maximum allowed. During an ignition at the FLAMEDETECT state or thereafter a flame rollout signal is detected with the maximum rollout events allowed exceeded. The heating cycle is forced into its OFF state with no restart initiated. During an ignition attempt within the FLAMEVALIDATE state the flame signal is lost within the flame validate time interval with the maximum attempts at flame validation during ignition exceeded. The heating cycle will be forced to its OFF state with no restart initiated. With the combustion fan forced on a pressure switch is detected as open after the combustion fan delay time has expired, indicating that the switch is stuck off and did not close when the switch should. With the combustion fan forced off, the pressure switch is detected as closed indicating that the switch is stuck on and is not open when it should be. 20

21 Error 58 Error 60 Error 61 Error 62 Error 63 Error 64 Error 65 Error 66 Error 67 Error 68 Error 69 Error 70 Error 71 During the ON phase of the heating cycle after the FLUEDELAY state has been processed the pressure switch has opened indicating a pressure loss with the maximum times this is allowed exceeded. The heating cycle will be forced to its OFF state with no restart. A motor open circuit fault exists due to the NG-2 controller losing the AC voltage signal supplied to the motor. Board Failure: On energizing the primary valve control relay its contact is not detected as closed within the primary valve control relay contact closed verification time) indicating that it is stuck off. Board Failure: With the primary valve control relay not being energized its contact is detected as closed indicating it is stuck on. Board Failure: While the primary valve control relay should be energized its contact is detected as opened by the primary microcontroller. The gas valve modulating coil current has been detected as exceeding the absolute maximum allowed (160mA) for at least the gas valve modulating coil fault delay time interval. While the fan limp fault is registered and a motor open circuit occurs or an overheat cool down is initiated the motor lockout fault is flagged. Board Failure: The secondary valve control relay contact was not detected as closed within the secondary valve control relay contact closed verification time indicating that it is stuck off. Board Failure: With the secondary valve control relay not being energized its contact is detected as closed indicating it is stuck on. Board Failure: While the secondary valve control relay should be energized its contact is detected as opened by the primary microcontroller. The 24 VAC voltage level has been lost completely possibly due to the 2A fuse being open circuited. Board Failure: This fault indicates that the secondary microcontroller did not shutdown the heating cycle within the heating cycle maximum shutdown delay time allowed in response to a fault condition detected by the primary microcontroller Board Failure: This fault indicates that the primary microcontroller detected an invalid heating cycle state being processed by the secondary microcontroller. The associated fault data value indicates the data value representing the heating cycle state that was detected as invalid. Note: Any further Error codes other than what has been specified are related to a NG-2 Board failure. 21

22 3.2 ERROR 30 FAN_LIMP Reason: The NG-2 has not received the fan motor speed sensor signal required for normal operation. Limp Mode Operation The heater still operates with this error present, though the operation may not give the maximum or best performance. The unit will automatically operate at full fan speed. In FAN_LIMP the heater reverts to timing the ON and OFF fan operation with the fan speed at maximum. The fan ON time = 45 seconds from when the gas valve is energised at the start of the heating cycle. The fan OFF time = 60 seconds from when the gas valve closes at the end of the heating cycle. The fan will not vary speed, as the NG-2 has no fan RPM signal. Service Check List: Perform Fan Speed Sensor Test Check the speed sensor is correctly located in the hub of the motor end plate. Check that the speed sensor loom plug is correctly fitted on the NG-2 terminal marked "TACHO". Check the loom and the connection plug are not damaged. Remove speed sensor from motor end plate and check; That no foreign matter has entered the sensor cap. The sensor PCB is firmly secured within the sensor cap. The 2 sensor probes on the PCB are vertically aligned. The wiring circuit is not damaged. Check for a loose fan impellor on the motor shaft. Replace fan speed sensor Check and or replace the NG-2 module and retest. If all this fails replace NG-2 module and retest. 22

23 3.3 ERROR 32 DATA_Err Reason: The NG-2 has failed to load data on power up, and has reverted to the Default settings. The heater may still operate with this error present. The unit may be used until a service technician attends. Service Check List: Reset the NG-2 module by temporarily changing any installer s parameter then move to the next parameter then back to the parameter and change back to its original value. Check the installer parameters. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 23

24 3.4 ERROR 33 MDGV_LIMP Reason The feedback current from the gas valve modulating coil is not detected for at least the gas valve modulating coil fault delay time interval of 5 seconds even though a drive level is being applied to the coil. Limp Mode Operation The gas valve modulating coil control reverts to open loop mode where the current level supplied to the modulating coil is fixed at 60 ma. Should the feedback signal become available the control reverts back to normal operation. Service Check List Loom connection is loose resulting in intermittent operation check loom continuity at PCB connector loom while still connected to gas valve. Wiggle the loom to check for poor connection. Loom is damaged resulting in intermittent operation check loom continuity at PCB connector loom while still connected to gas valve. Wiggle the loom to check for poor connection. Gas valve modulating coil is faulty check coil resistance is between 82 to C Poor connector on PCB check for looseness on the PCB. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 24

25 3.5 ERROR 35 No_SA- THM Reason: No_S-A_THM means the thermistor circuit is open circuit, and the NG-2 has not received the supply air thermistor sensor signal. Operation Mode: The heater still operates with this error present, though the operation does not give the maximum or best performance. The fan will be timed ON and OFF, operated at the installer set RPM, and the gas valve will be force to the minimum rate. The fan ON time = 45 seconds from when the gas valve is energised at the start of the heating cycle. The fan OFF time = 60 seconds from when the gas valve closes at the end of the heating cycle. Service Check List: Check the supply air thermistor has been installed, and that the loom and/or plug have been connected to the thermistor. Check the supply air thermistor wire loom has not been damaged. Check the thermistor is not faulty, check that the resistance is approx o C. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 25

26 3.6 ERROR 36 BadSA- THM Reason: BAdSA_THM means, the supply air thermistor has a circuit, but has not reached 30 o C. Within 2 minutes of the fan operation commencing, in a normal heating cycle. Operation Mode: The user still has some heating, until the problem can be rectified by a service technician, though the operation does not give the maximum or best performance. In BAdSA_THM fan operation, the unit cannot rely on the thermistor signal, and therefore operates the heater as follows: Fan operates at installer set speed, and the gas valve operates at minimum rate. The fan ON time = 45 seconds from when the gas valve is energised at the start of the heating cycle. The fan OFF time = 60 seconds from when the gas valve closes at the end of the heating cycle. Service Check List: Check the Supply Air Thermistor is installed in the Supply Air duct Check the thermistor is not faulty, check that the resistance is approx o C. Check the Supply Air Thermistor is not located in an unsuitable position within the Supply Air duct. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 26

27 3.7 ERROR 40 OHEAT_R-A ERROR 41 OHEAT_S-A ERROR 42 OHEAT_THM Reason: These errors will appear whilst an over temperature is current, the Over Heat Switch circuit is open, or the thermistor is measuring a temperature greater than 90 0 C. The heater's fan will be forced to operate at maximum speed and the combustion fan will also be operating. All StarPro models have a supply air over heat switch located near the supply air discharge and is activated before the supply air reaches 90 C. This switch triggers at 110 C. StarPro HX models are fitted with an additional over heat switch located in the combustion fan box to prevent the flue temperature exceeding 90 C. This switch triggers at 90 C. These switches directly interrupt the 24 Volt power to the gas valve if over heating occurs. If either or both over temperature switches open circuit indicating over temperature conditions within the Timed Safe Guard Period, then the following will occur during the over temperature condition: The power supply to the gas valve will be terminated. The fan will operate immediately, if not already operating. Once the over temperature condition has cleared and the switch resets, the normal heating cycle can commence again, provided the Networker is still calling for heat. The LCD will display "OHCooLDwn" for the next 60 seconds, alternating with the normal heating cycle displays i.e. HEAT= C 0. This is to indicate the heater has recently reset from an over temperature condition, but has now cooled sufficiently to resume operation: If the Networker turns the call for heat OFF whilst the unit is in over temperature during a normal heating cycle, then after completing the "OHCOOLDWN" 60 second period the fan will then resume the normal CooLDOWN of the heating cycle. I.e. CoolDOWN as in the normal heat cycle according to the supply air outlet thermistor temperature. 27

28 Service Check List: Check the temperature registered at the nearest outlet to the heater, and compare this to the supply air thermistor temperature displayed on the NG-2 module. Check the temperature rise value of the supply air thermistor and nearest outlet temperature, over the room temperature (Return Air intake temperature). A 47 0 C. temperature rise will indicate a true overheat condition. Check there are sufficient outlets open on the duct system. Check the return air filter (if fitted) is sized correctly and is clean. Check that the fan speed is sufficient for the system so that over heating will not result. Check the fan motor is functioning correctly, and is not blocked or obstructed. Check the ducting has not been crushed, damaged or incorrectly sized. Check the return air intake is not subjected to a high temperature from an external source. Check that the supply air thermistor is correctly fitted in the supply air duct. Check the wire loom and plug connections to the switch are not open circuit, i.e. wire fallen off switch. Check the supply air thermistor circuit is not shorted together or earthed. Check the thermistor is not faulty, check that the resistance is approx o C. Check the link circuit on the NG-2 module between terminals 24 V. and STAT is open circuit If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 28

29 3.8 ERROR 43 OHCooLDwn Reason: This error will be displayed during the 60 second maximum fan operation but is always logged following an over temperature error. Service Check List: Check the error log to determine what over heat error has occurred. Refer to Check List of the following error code for diagnosis: i.e. Error Code: 40 OHEAT_R-A, Error Code: 41 OHEAT_S-A, Error Code: 42 OHEAT_THM. 29

30 3.9 ERROR 44 RoLLOut ERROR STAT Reason: During ignition a flame roll out has occurred where the flame has earthed the antiflame roll out (AFRO) bar to the burner assembly. This error display will only be seen on the display while the heater is currently recovering from conditions of flame sensed on the AFRO bar indicating a flame roll out. This is the 10 second shut down period of the gas valve, before the next re-ignition attempt. Service Check List: Operate the heater and observe the behaviour during ignition. Determine which AFRO is causing the roll-out. Rollout on lower AFRO During ignition, measure the ignition burner pressure and ensure it is within specification. Check that the correct injectors have been fitted and the gas type is correct. Check that the vacuum pressure switch is the correct switch and functioning correctly. Check for water gurgle noises being emitted from either the flue or the heat exchanger inlet ports (Water gurgle can be the result of premature condensation or a blocked condensate drain system on HX models) Check if the flue terminal or flue pipe has soot marks, indicating poor combustion and/or a possible blocked heat exchanger. Rollout on Upper AFRO Check the burners for blockage. Check the burners for correct fitment. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. SEE NEXT PAGE FOR FLAME ROLL OUT ANTI FLAME ROLL-OUT 30

31 3.10 ERROR 45 LOW24VOLT ERROR Reason: The 24 volt circuit has been subjected to low voltage, resulting in insufficient 24 Volt output for reliable ignition or operation. This low voltage condition is usually only temporary and may be the result of a power loss or brown out. Service Check List: Check incoming power supply voltage (minimum 200 V). Check if power supply is not from a generator (may not be 50 Hz or might be wave rectified). Check if the 2 Amp fuse blown. Check the transformers secondary voltage output is within specifications. If the Network 506 is connected, check the current output on terminals 24 V and GND does not exceed 0.3 Amp's. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 31

32 3.11 ERROR 46 IGR_NOFLM Reason: This is a result of no flame being sensed by the flame sensor during the flame detect time interval of 4.5 seconds. A re-ignition will occur provided that the number of re-ignition attempts does not exceed 5 in a row. After 5 attempts an Error 50 will be logged and an Ignition Lockout will occur. Service Check List: Start up the heater and check for ignition. If ignition occurs and the heater losses flame within 4.5 seconds, then check the following: During ignition check if the burner flame ignites, but is not confirmed by the flame sensor (A flame symbol is displayed on the NG-2 LCD when flame is sensed). If the flame is not detected by the NG-2 control, then check the following: Check for correct connection of the flame sensor to the burner assembly and NG-2 control. Check for a satisfactory flame from the burner above the flame sensor. Check for continuity between the flame sensing rod and the lead connector. Check the flame sensor rod is located in the correct location as specified in Section xx. Check for correct ignition burner pressure as specified in Section xx and adjust if required. Check power supply polarity is correct. Check the voltage to the gas valve is maintained (i.e. 24Vac) at back of NG-2 gas valve loom plug. A faulty connection may shut off the gas valve. Check the heater has been set for the correct gas type on the NG-2 bridge link. Clean the flame sensor rod and retry ignition. 32

33 ERROR 46 Continued If ignition does not occur then check the following Check for sparking during the ignition process. Ensure that the spark canister is generating a spark signal and there is spark across the ignitor spark gap. Check the gas supply is turned ON at the gas meter, and the appliance gas cock. Check the gas cylinders have gas, and the cylinder valve is open (LPG only). Check that the inlet gas pressure is sufficient during ignition (at least 800 Pa for ignition). Check that the burner pressure during ignition is within specification and adjust if necessary according to the procedure in section xx. If the correct burner pressure can not be achieved: Ensure that the gas valve main coils and modulating coils are receiving sufficient voltage. If not then check the gas valve loom and connection on the NG-2. Check the gas valve coil resistances are within specification: Gas Valve Modulating Coil maximum current Modulating coil winding 20 C Main Coil winding 20 C NG: 115 ma LPG: 160 ma Ω Coil 1: Ω Coil 2: Ω Check the air has been purged from the gas service piping. Check to make sure that the spark gap and location of the ignitor is within specification as described in Section xx. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the gas valve or NG-2 control, and they should be changed individually to prove this. 33

34 3.12 ERROR 47 IGR_BDFLM Reason: A flame has been detected by the flame sensor within the flame detect time of 4.5 seconds, and then the flame has been lost in the flame validate time (10 seconds after flame detection). If this failure occurs 5 consecutive times after an ignition attempt, then an Error 55 is registered and a lockout condition will occur. Once flame has been validated and ignition is successful, the failure count is reset. Service Check List: Operate the heater and observe the behaviour during ignition, in particular the behaviour of the flame at the burner near the flame sensor. During ignition, measure the ignition burner pressure and ensure it is within specification. Check that the correct injectors have been fitted and the gas type is correct. Too much gas flow during ignition can cause violent flame behaviour. Check that the vacuum pressure switch is the correct switch and functioning correctly. Check that the inlet gas pressure is sufficient during ignition (at least 800 Pa for ignition). Check for continuity between the flame sensing rod and the lead connector. Check the flame sensor rod is located in the correct location as specified in Section xx. Clean the flame sensor rod and retry ignition. 34

35 3.13 ERROR 48 LOST_PRES Reason: During the ON phase of the heating cycle after the FLUEDELAY state has been processed the pressure switch has opened, indicating a pressure. The heating cycle will be forced to its OFF state and a restart initiated. If this occurs for 5 consecutive times, the Error 58 Pressure Fail will occur and a manual reset will be required. Service Check List: Vacuum Pressure Checking Procedure Measure vacuum pressure at each pressure switch during normal operation. Monitor the vacuum pressure overtime, as it may fall to a level close to the vacuum pressure that will cause the switch to become open circuit. If vacuum pressure is above specification (All pressure switches) If the vacuum pressure is above the pressure switch s specified value and Error 48 still occurs, then the pressure switch may be faulty and should be replaced. If vacuum pressure is below specification (All pressure switches) Vacuum pressure hoses are not fitted correctly check hose connections. Vacuum pressure hoses have perished and cracked causing vacuum pressure loss check for deterioration. Water trapped in the vacuum pressure hose check for water traps or presence of moisture in hoses. Excessive heat exchanger leakage resulting in vacuum pressure loss check heat exchanger for leakage. If vacuum pressure is below specification (Combustion fan box pressure switch) Flue piping is too restrictive check against allowable flue pipe configuration specification. Flue pipe has collected excessive condensate check for potential collection points (there must be a continual fall back to the heater). If vacuum pressure is below specification (Condensate tank pressure switch HX models only) Condensate tank is not draining properly check drain, check for gurgle noise coming from HX inlet ports. Intermittent failures It is possible that under sever wind conditions that excessive back pressure may cause this error to be logged, particularly on external models). It may also be the result of a blocked condensate drain, but may not be present at the time of servicing due to evaporation within the condensate drain line. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 35

36 3.14 ERROR 49 LOST_FLME Reason: During normal operation after ignition has been validated, if the flame sensor signal has unexpectedly been lost, the heating cycle is forced into its OFF state with a restart initiated and an Error 49 logged. Service Check List: Check gas supply pressure is not too high or low. Check the burners and injectors are clean, producing a properly formed flame. Check the flame sensing rod is clean, and correctly located as specified in section xx. Check for damage or loose connections to the burner flame sensor lead and connector. Check the minimum burner pressure is not below the minimum allowable level. Check the gas valve is providing a continuous steady gas flow to the main burner. Check there is no air disturbance to the burner flames (i.e. fan operation, wind etc.). If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 36

37 3.15 ERROR 50 IGN_LKOUT Reason: This error code indicates the unit has locked out after 5 ignition attempts without the flame being recognised by the flame sensor. Service Check List: Refer to Check List for Error Code 46: IGR_NOFLM. 37

38 3.16 ERROR 51 RLT_NOGAS Reason: This error indicates that the AFRO circuit has detected a flame rollout while the gas valve is not energised, and flame is not expected. Service Check List: Check that the pilot AFRO bar or wiring is not shorted to Earth. Check if a flame is present with the unit turned OFF. Check the gas valve is not jammed open due to malfunction, obstruction or blockage. Check if the 24 Volt power supply to the valve has been turned OFF, as expected in the normal operation. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 38

39 3.17 ERROR 52 FLM_NOGAS Reason: This error indicates that the burner flame has been detected by the flame sensor when the gas valve is not energised, and flame is not expected. Service Check List: Check the pilot burner and/or burner main flame sensor lead is not shorted to Earth. Check if the burner flame is present with the unit turned OFF. Check the gas valve is not jammed open due to malfunction, obstruction or blockage. Check if the 24 Volt power supply to the valve has been turned OFF, as expected in the normal operation. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 39

40 3.18 ERROR 53 OH_LKOUT Reason: This error indicates the unit has had 2 consecutive over temperature conditions, within 15 minutes, after the wall controller is turned OFF and cool down has been completed. Refer to Check Lists for: Error Code 40: OHEAT_R-A Error Code 41: OHEAT_S-A Error Code 42: OHEAT_THM Service Check List: Check if the unit has been operating on a hot day following a power up. Check if the unit is ceiling mounted with a high level return air grille. Check that the fan speed is sufficient for the system so that over heating will not result. Check the fan motor is functioning correctly, and is not blocked or obstructed. Check the unit is not operating in FAN_LIMP mode. Check the gas valve is not jammed open and passing gas when not energised. Check the return air intake is not subjected to high temperature from an external source (i.e. not typical domestic system). Check the wire loom and plug connections to the switch are not open circuit, i.e. wire fallen off switch. Check that the supply air thermistor is not incorrectly fitted in the return air duct. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. SEE NEXT PAGE FOR OVER TEMPERATURE WITH NETWORKER OFF 40

41 ERROR 53 Continued Over Temperature with Networker OFF If an over temperature condition is detected within the Timed Safe Guard Period with the Networker turned OFF, then the fan will start. The LCD for the over temperature switch will display the appropriate switch, until the fan cools the over temperature condition. The LCD will again display "OHCooLDwn" while the fan continues a 60 second fan OFF cycle. If a SECOND subsequent over temperature condition with the Networker OFF is detected, within the Time Safe Guard Period, the controller will again follow the same sequence for an over temperature condition. However, it will go into an Over Heat lockout mode that will require a reset (Reset at the Networker or SET button at the N-G2 module) to restore the unit to normal operation. If an over temperature condition occurs while the unit is in an over heat lockout mode, then the fan will be brought ON for the duration of the over temperature condition, followed by a 60 second fan OFF cycle period. 41

42 3.19 ERROR 54 RoL_LKOUT Reason: This error indicates the unit has locked out, due to 3 consecutive flame roll outs detected, within a heating cycle. Service Check List: Refer to Check List for Error Code 44: RoLLOuT. 42

43 3.20 ERROR 55 IGINVALID Reason: This error indicates the unit has locked out, due to 5 consecutive flame losses (Error 47) during the flame validation stage. Service Check List: Refer to Check List for Error Code 47: IGR_BDFLM. 43

44 3.21 ERROR 56 PRES_STOF Reason With the combustion fan forced on the combustion chamber pressure switch is detected as open after the combustion fan delay time of 15 Seconds has expired indicating that the switch is stuck off and did not close when it should. On HX models, this could be caused by either pressure switch not closing. This may be caused be insufficient vacuum pressure to close the pressure switch (Note: on HX models, both switches must close to prevent this error). Service Check List Vacuum Pressure Checking Procedure (All pressure switches) Measure vacuum pressure at each pressure switch during pre-purge (or force an overheat condition, by breaking the overheat switch circuit, to operate the combustion fan). Perform these pressure checks without the pressure switch connected to the pressure hose. If vacuum pressure is above specification (All pressure switches) If the vacuum pressure is above the pressure switch s specified value and Error 56 still occurs, then the pressure switch may be faulty and should be replaced. If vacuum pressure is below specification (All pressure switches) Vacuum pressure hoses are not fitted correctly check hose connections (for HX models, also check that the hoses are connected to the correct pressure switch). Vacuum pressure hoses have perished and cracked causing vacuum pressure loss check for deterioration. Water trapped in the vacuum pressure hose check for water traps or presence of moisture in hoses. Make sure there is no water in the hose when servicing the system. Excessive heat exchanger leakage resulting in vacuum pressure loss check heat exchanger for leakage. Combustion fan may be faulty check according to procedure in section (Combustion Fan) If vacuum pressure is below specification (Combustion fan box pressure switch) Flue piping is too restrictive check against allowable flue pipe configuration specification including the flue cowl. Flue pipe has collected excessive condensate check for potential collection points (there must be a continual fall back to the heater 20mm rise per Metre). If vacuum pressure is below specification (Condensate tank pressure switch HX models only) Condensate tank is not draining properly check drain, check for gurgle noise coming from HX inlet ports. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 44

45 3.22 ERROR 57 PRES_STON Reason: With the combustion fan forced off, the pressure switch is detected as closed indicating that the switch is stuck on and is not open when it should be. This error will occur prior to prepurge when the NG-2 control checks to ensure that the pressure switch/switches are open before operating the combustion fan. Service Check List: Vacuum Pressure Checking Procedure Measure vacuum pressure at each pressure switch without any combustion fan operation. If vacuum pressure is below the pressure switch closing specification (All pressure switches) If the vacuum pressure is below the pressure switch s specified closing value and Error 57 still occurs, then the pressure switch may be faulty check the switch for continuity and if it is closed with low vacuum pressure (below specification, or no pressure at all) then it should be replaced. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 45

46 3.23 ERROR 58 PRES_FAIL Reason: During the ON phase of the heating cycle after the FLUEDELAY state has been processed the pressure switch has opened indicating a pressure loss (Error 48) 5 consecutive times. The heating cycle will be forced to its OFF state with no restart. A restart will only occur from a manual reset including a power reset. Service Check List: Check that the condensate drain has a continual fall away from the heater and does not contain water. Check that the condensate pipe length is correct length. Refer to Check List for Error Code

47 3.24 ERROR 60 MOTOR_O-C ERROR Reason: This error code indicates the main fan motor is "open circuit". Service Check List: Check the wiring to the motor, and the plug connections are connected satisfactorily. Check for signs of damage to the motor loom or motor extension loom Check that the motor winding resistances are within specifications as shown below. (Note: The resistances specified are when the motors winding temperatures are at 20 C, and will vary if the motors temperature is hotter or cooler). Start Winding 20 C Main Winding 20 C Fasco 315W 80855BNVA-A20 Fasco 650W 80855BPVA-A Ω Ω Ω Ω Check if the motor casing is HOT, indicating the motor's thermal over temperature switch may be tripped. If the motor is hot: Check motor bearings for wear and stiffness. Check the capacitor is the correct size and/or faulty. Check the fan impellor is not damaged, jammed, blocked or obstructed. Check the incoming power supply voltage. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 47

48 3.25 ERROR 61 PVCR-STOF Reason for Error This error code indicates on energising the primary valve control relay its contact is not detected as closed within the primary valve control relay contact closed and indicating that it is stuck off. Service Check List: If Error 61 has occurred in the past on this heater then replace the NG-2 Module For a first time Error 61 reset NG-2 Module then retry heater operation. If NG-2 cannot be reset or if Error 61 reoccurs then replace NG-2 module and retest. 48

49 3.26 ERROR 62 PVCR_STON Reason for Error: With the primary valve control relay not being energised its contact is detected as closed indicating it is stuck on : Lockout Condition ( See Error Code#51) With the heating cycle in the ON PREIGNITION phase the status of a number of inputs is checked by the primary microcontroller. In particular: 1) The state of the flame rollout signal is monitored and if a flame rollout is detected as available this would suggest that the flame rollout sensing circuitry has failed as no flame should be available at this stage (gas valve main coil not energised). Subsequently, a lockout condition (Code#51) is registered forcing the heating cycle back to its OFF state with no post-purge. 2) The state of the primary valve control relay contact is monitored and if it is detected as closed when it should be opened this would suggest that the contact is stuck on as the relay has not been energised yet. Subsequently, a lockout condition (Code#62) is registered forcing the heating cycle back to its OFF state with no post-purge. 3) The state of the secondary valve control relay contact is monitored and if it is detected as closed when it should be opened this would suggest that the contact is stuck on as the relay has not been energised yet. Subsequently, a lockout condition (Code#67) is registered forcing the heating cycle back to its OFF state with no post-purge. 4) The state of the flame signal is monitored and if flame is detected as available this would suggest that the flame sensing circuitry has failed as no flame should be available at this stage (gas valve main coil not energised). Subsequently, a lockout condition (Code#52) is registered forcing the heating cycle back to its OFF state with no post-purge. Service Check List: Reset NG-2 Module Replace the NG-2 module 49

50 3.27 ERROR 63 PVCR-FAIL Reason for Error: While the primary valve control relay should be energised its contact is detected as opened by the primary microcontroller Once the state is entered the primary valve control relay contact state is continuously monitored by the primary microcontroller until the OFF state of the heating cycle is entered If the primary valve control relay contact is unexpectedly detected as opened by the primary microcontroller a lockout condition (Code#63) is registered by the primary microcontroller forcing the heating cycle into the OFF state. Service Check List: If Error 63 has occurred in the past on this heater then replace the NG-2 Module For a first time Error 63 reset NG-2 Module then retry heater operation. If NG-2 cannot be reset or if Error 63 reoccurs then replace NG-2 module and retest. 50

51 3.28 Error 64 GAS_LKOUT Reason for Error: If the supply-air thermistor is not available to provide the necessary feedback signal the gas valve modulating coil is provided with the minimum current drive level according to the gas type being used. This ensures that the heating operates, but at a safe level. While the gas valve modulating coil is being operated and the current through the coil is detected as exceeding the absolute maximum value of 160mA for at least the gas valve modulating coil fault delay, a lockout condition is registered (Code#64). Service Check List: If Error 64 has occurred in the past on this heater then replace the NG-2 Module For a first time Error 64 reset NG-2 Module then retry heater operation. If NG-2 cannot be reset or if Error 64 reoccurs then replace NG-2 module and retest. 51

52 3.29 ERROR 65 MTR_LKOUT Reason: The unit is locked out due to fan motor open circuit (Error 60), and the fan motor speed sensor signal has not been received by the NG-2 (Error 30). OR The unit was operating in FAN_LIMP mode (Error 30), and an over temperature condition has occurred (Error 40, 41, or 42). Service Check List: Refer to Check Lists for Error Code 30, 40, 41, 42 or 60, whichever has occurred. If the error can not be eliminated after performing the above checks, then it may be possible that there is a fault with the NG-2 control board, and it should be changed to prove this. 52

53 3.30 ERROR 66 SVCR_STOF The reason: The secondary valve control relay contact on the NG-2 was not detected as closed within the secondary valve control relay contact closed verification time indicating that it is stuck off If the secondary valve control relay contact is detected as closed within the allotted time, heating cycle control within the primary microcontroller proceeds to the next state FLAMEDETECT. Service Check List: If Error 66 has occurred in the past on this heater then replace the NG-2 Module For a first time Error 66 reset NG-2 Module then retry heater operation. If NG-2 cannot be reset or if Error 66 reoccurs then replace NG-2 module and retest. 53

54 3.31 ERROR 67 SVCR_STON The reason: With the secondary valve control relay not being energised its contact is detected as closed indicating it is stuck on With the primary valve control relay contact detected as closed the secondary valve control relay contact has also been detected as closed even though the relay has not been energised yet. This indicates that the relay is stuck on. Service Check List: If error 67 has occurred in the past on this heater then replace the NG-2 Module For a first time Error 67 reset NG-2 Module then retry heater operation. If NG-2 cannot be reset or if Error 67 reoccurs then replace NG-2 module and retest. 54

55 3.32 ERROR 68 SVCR_FAIL The reason: While the secondary valve control relay should be energised its contact is detected as opened by the primary microcontroller. Once the FLAMEDETECT state is entered the secondary valve control relay contact state is continuously monitored by the primary microcontroller until the OFF state of the heating cycle is entered as is illustrated in the flow chart of FIG c. If the secondary valve control relay contact is unexpectedly detected as opened by the primary microcontroller a lockout condition (Code#63) is registered by the primary microcontroller forcing the heating cycle into the OFF state. Service Check List: If error 68 has occurred in the past on this heater then replace the NG-2 Module For a first time Error 68 reset NG-2 Module then retry heater operation. Replace the gas valve loom and rectifier plug. Replace the gas valve. If NG-2 cannot be reset. 55

56 3.33 ERROR 69 FUSE_BLOW The reason: This error code indicates the 2 Amp fuse on the NG-2 has blown due to a short circuit on the 24 Volt wiring circuit. Short Circuit Over Temperature Circuits If either the supply air Over heat switch is shorted to Earth, then the N-G2 2 Amp fuse will be blown: ERROR If either the return air or supply air switch is shorted together then the switch function is disabled. Service Check List: Check if the 24 Volt internal wiring circuit to the over temperature switches, pressure switch/s and gas valve is not shorted to Earth. Check that any wiring connected to the On-Board relays is not shorted to Earth. Check that any wiring connected to the 24V terminal is not shorted to Earth (i.e. Network 506 module as well as the wiring to the refrigeration compressor relay if applicable). Check the gas valve solenoid coil is not shorted. 56

57 3.34 ERROR 70 SS- SDNERR The reason: This fault indicates that the secondary microcontroller did not shutdown the heating cycle within the heating cycle maximum shutdown delay time (t sdndelay =2.5s) allowed in response to a fault condition detected by the primary microcontroller (See Section , , ). Service Check List: If error 70 has occurred in the past on this heater then replace the NG-2 Module For a first time Error 70 reset NG-2 Module then retry heater operation. If NG-2 cannot be reset or if Error 70 reoccurs then replace NG-2 module and retest. 57

58 3.35 ERROR 71 SS- STAERR The reason: This fault indicates that the primary microcontroller detected a fault with heating cycle state timing within the secondary microcontroller with the associated fault data indicating which state was at fault (See Section ). Service Check List: If error 71 has occurred in the past on this heater then replace the NG-2 Module For a first time Error 71 reset NG-2 Module then retry heater operation. If NG-2 cannot be reset or if Error 71 reoccurs then replace NG-2 module and retest. 58

59 4. MAIN COMPONENTS SERVICING This section contains the procedures for checking and adjusting (if necessary) main components of the heater. This may be required due to a failure or a routine service. 4.1 Gas Valve Servicing The diagram below indicates the measurement and adjustment locations. If adjustment to the gas valve is required, a 8mm and 5mm spanner, or small size adjustable wrench will be required. Maximum Pressure Adjustment Screw Minimum Pressure Adjustment Screw Burner Pressure Test Point Inlet Gas Pressure Test Point 59

60 5. Gas Valve Checking and Adjustment (only if required) To check for correct gas valve settings and operation the following should be performed, and adjustments made when necessary. Inlet Pressure Measurement Loosen the gas inlet test point screw, located on the gas valve as shown in the diagram, and connect a suitable manometer to the test point. Turn on the heater and wait for the flame proving period to finish. Check that the inlet gas pressure is between 1.1 kpa to 3.5 kpa. Pressures below this level can result in incorrect checking and adjustment of the gas valve. If this is the case then this situation should be rectified. Remove the manometer and retighten the inlet test point screw immediately to prevent gas leakage. Low Inlet Pressures It is possible that low inlet pressure can cause: Unreliable ignition if the inlet pressure is below 0.80 kpa at the time of ignition. Underrated heat output Burner Pressure Measurement Loosen the burner pressure test point screw, located on the gas valve as shown in the diagram, and connect a suitable manometer immediately (Note: The heater can still be running from the previous step before loosening the test point). Maximum Burner Pressure Checking Force the gas valve to drive the modulating coil to the maximum level by setting the service parameters as follows (depending on gas type): Natural Gas LPG S1 115 S S2 115 S The maximum burner pressure can now be checked. If the burner pressure is within ±30 Pa of the specified maximum burner pressure, no adjustment is required. If adjustment is required, adjust the maximum burner pressure setting screw on the gas valve (clockwise increases pressure). Minimum Burner Pressure Checking Force the gas valve to drive the modulating coil to the minimum level by setting the service parameters as follows (depending on gas type): Natural Gas LPG S1 30 S11 45 S2 30 S12 45 The minimum burner pressure can now be checked. If the burner pressure is within specifications (Refer to Technical Specifications in Section 6 ), no adjustment is required. If adjustment is required, adjust the minimum burner pressure setting screw on the gas valve (clockwise increases pressure). 60

61 Note: If operating at the minimum burner pressure for greater than x minutes, then temporarily set the Heat fan speed in the Installer menu to 500 RPM. This will prevent premature condensing occurring inside the heat exchanger in non-condensing regions during this procedure. Reset the Heat fan speed back to the previous value. Once the minimum pressure has been set, force the gas valve to operate at high burner pressure as described above under Maximum Burner Pressure Checking, to make sure that the maximum burner pressure is still within specifications. Once both the maximum and minimum burner pressures have been checked, and adjusted if required, set the service parameters back to the default values as follows: Natural Gas LPG S1 30 S11 45 S2 115 S If the gas valve can not be set to the specified maximum and minimum burner pressures, then the gas valve will have to be replaced. Refer to section XX for gas valve replacement. Ignition Burner Pressure Checking If there have been any errors caused by unsatisfactory ignition, such as Error 46, 47, 50 and 55, then it is important that the ignition burner pressure is checked. This can be performed by measuring the burner pressure immediately after ignition has occurred. If ignition does not occur, measure the burner pressure near the end of the sparking period. The ignition burner pressure should be within the range specified in the table below. Ignition Burner Pressure Model Natural Gas LPG MX Pa N/A MX Pa N/A MX Pa N/A HX Pa TBA HX Pa TBA If adjustment is required then the following procedure should be performed: Force the gas valve to drive the modulating coil to the minimum level by setting the service parameters as follows (depending on gas type): Natural Gas LPG S1 30 S11 45 S2 30 S12 45 Now increase service parameter S2 for Natural Gas models, or S12 for LPG models until the gas pressure is within the limits as specified in the Ignition Burner Pressure table above. The value that S2 for Natural Gas, or S12 for LPG, had to be set to obtain an acceptable ignition burner pressure, is to be used to set the Ignition Burner Current parameter (S3 for Natural Gas, or S13 for LPG). Once the ignition gas pressure current is set, set the service parameters back to the default values as follows: Natural Gas LPG S2 115 S

62 5.1 Combustion Fan Servicing General Service 1. Check that the motor s shaft spins freely. 2. While in operation during a prepurge, check for any unusual noise, such as bearing or scraping noise. (Note: The presence of a tinkling sound can be caused by the impellor removing water particles out of the fan housing, which should not be present on MX models). If there is any suspicion of an underperforming combustion fan or that the entire system is resulting in low vacuum pressure, the following should be performed: 1. Isolate the heater s power supply. 2. Check the motor s winding resistance with the wire looms removed. 3. Re-insert the motor s wiring loom. 4. Connect a manometer into the combustion fan vacuum pressure hose to measure the vacuum pressure just prior to the combustion fan. 5. Re-apply power to the heater and force it into an overheat mode to power up the combustion fan. (Warning: Remember the motor operates with 240 Vac.) 6. Measure the combustion fan vacuum pressure, and ensure that it reaches the value as specified in the table below. Voltage/Power 230 VAC / 60 W Combustion Fan Winding 20 C Ω Minimum Allowable Combustion Fan Vacuum Pressure (Pa) MX21 MX30 MX Pa 135 Pa 135 Pa If the vacuum pressure is below the specified values: 1. Check that the flueing is within the allowable specifications. 2. Look for any physical causes of underperformance such as the build up of soot or silicon in the combustion fan housing or flue pipe. Clean if necessary. Servicing while removed It may be required to remove the combustion fan to inspect it totally or to try a new combustion fan. Refer to section xx for removal procedure of the combustion fan. 62

63 5.2 Spark Igniter Servicing Isolate the heater power and gas supply from the unit. Checking the Spark Ignitor Unscrew the spark igniter away from the burner Check Spark Igniter electrode, lead and plug connection Clean igniter probe and make sure there is a spark gap of approx 4 mm. Then reassemble. Checking Spark Igniter location relative to burner face Remove the burner assembly as described in section xx Measure the distances as shown in the diagram below. Installation is a reversal of the removal procedure. 11±1.5 mm 8.5±1.5 mm Sparker probe end is in alignment with burner centreline ±2 mm. 63

64 5.3 Flame Sensor Servicing Isolate the heater power and gas supply from the unit. Checking the Flame Sensor Check that the Flame Sensor rod is clean, located correctly and the lead and plug connection is in good condition. Reassemble. Checking Flame Sensor location relative to burner face Remove the burner assembly as described in section xx Measure the distances as shown in the diagram below. Installation is a reversal of the removal procedure. 12±2 mm 11±2 mm 64

65 5.4 Pressure Switch Servicing Isolate the heater power and gas supply from the unit. Tap into the pressure switch line with a suitable manometer. Check that the pressure switch is opening within the limits specified below as follows: o Measure the vacuum pressure and Make sure the vent hole and bleed hole are clear of any foreign material. Make sure the hoses are free of condensation. Check the hoses leading to the pressure switch are clear of holes Reassemble. Pressure Switch Settings Combustion Airflow Proving Switch Condensate Blockage Protection Switch Model Open Circuit Vacuum Pressure (Pa) Maximum Closing Vacuum Pressure (Pa) Open Circuit Vacuum Pressure (Pa) Maximum Closing Vacuum Pressure (Pa) HX23 165± MX21 140± N/A N/A HX30 140± MX30 115± N/A N/A MX35 115± N/A N/A Vent Hole (2.3 mm) Bleed Hole (0.4 mm) 65

66

67 5.5 Main Fan Assembly Servicing External Models Turn the unit OFF and isolate the power supply. Remove the main fan assembly as described in Section xx. Check for any signs of wear Rotate the fan wheel and check for any irregular noise such as scraping or worn bearings. Clean impellor and motor. Clean housing. Clean heater's fan compartment inner lining. Reassemble. Check all wiring cables and plug connections (including speed sensor). Installation is a reversal of the removal procedure. Internal Models Turn the unit OFF and isolate the power supply. Split the heater as described in the Heating Installer s Manual Move the fan cabinet so that the fan housing can be removed without interfering with the flue piping. Remove fan housing from cabinet. Remove fan assembly from housing. Clean impellor and motor. Clean housing. Clean heater's fan compartment inner lining. Reassemble. Check all wiring cables and plug connections (including speed sensor). Installation is a reversal of the removal procedure. 5.6 Unit operation Check power supply lead is in good condition. Check all gas connections are good and do not leak. Check condensate drain and discharge (HX models only). Check the Networker wiring connection at the unit is in good condition. Check the burner's maximum and minimum operating gas pressure on the test point provided on the gas valve. Check the duct system airflow distribution, balance and adjust as required. Check the unit's selected fan speed (RPM) is appropriate for optimum heat output for the application. Check other accessories fitted to the system (i.e. Network 506, zone dampers) are functioning. Service Manual Starpro MX / HX Series Prototype Issue 2 67

68 6. REMOVAL PROCEDURES Before any of the following assemblies or components can be removed, it is important to isolate the heater s power supply. The heaters roof will also have to be removed by removing 2 screws at each end of the roof. Internal heaters have a top wrap around the service chamber that can be removed for easier access, if required by simply removing the 10 screws off the top wrap. 6.1 Burner Assembly Removal 1. Turn the gas isolation valve off and isolate the heater s power supply 2. Remove the gas valve loom; spark igniter lead, flame sensor lead and AFRO wire from the NG-2 PCB. 3. Remove the gas inlet pipe off the gas valve and move the piping enough to enable the burner assembly to be removed when ready. 4. Remove the gas valve support bracket screw from the heat exchanger main plate, and then remove the bracket. 5. Remove the 4 screws holding the burner assembly to the heat exchanger main plate. 6. The burner assembly can now be removed. Installation is a reversal of the removal procedure with attention to the following points: 1. Ensure that the gas inlet feed-tube is retightened and checked for leaks. 2. Ensure that all looms, wires and leads are not damaged along their length and at the connectors. 6.2 Gas Manifold Assembly Removal 1. Turn the gas isolation valve off and isolate the heater s power supply 2. Remove the gas valve loom from the NG-2 PCB. 3. Remove the gas inlet feed-tube off the gas valve. 4. Remove the gas valve support bracket screw from the heat exchanger main plate, and then remove the bracket. 5. Remove the 4 screws holding the gas manifold to the burner assembly. 6. The gas manifold assembly can now be removed. Installation is a reversal of the removal procedure with attention to the following points: 1. When re-inserting the assembly, ensure that the injectors are inserted into the ring on the top of the burners correctly. 2. Ensure that the gas inlet feed-tube is retightened and checked for leaks. 3. Ensure that the gas valve loom is not damaged along its length and at the connector. 68

69 6.3 Gas Valve Removal 1. Turn the gas isolation valve off and isolate heater s power supply 2. Disconnect the gas valve rectifier and loom. 3. Remove the gas inlet feed-tube off the gas valve. 4. Remove the gas valve support bracket screw from the heat exchanger main plate, and then remove the bracket. 5. Remove the gas valve from the burner manifold by unwinding it in an anti-clockwise direction. 6. Remove the brass adaptor on the gas valve inlet side of the gas valve if the valve is to be replaced. Installation is a reversal of the removal procedure with attention to the following points: 1. Clean any threads of excessive gas thread sealant, which are to be re-assembled 2. If a new gas valve is to be fitted, apply gas thread sealant to the brass adaptor and fingertighten onto the gas valve. 3. Apply gas thread sealant to the burner manifold feed tube nipple and screw on the gas valve, and then tighten. 4. Check for leaks on both sides of the gas valve while in operation. 5. If a new gas valve is fitted, ensure that it is reset, including the ignition gas pressure, as outlined in section xx. 6.4 Pressure Switch Assembly Removal The MX models have only one pressure switch The HX models have 2 pressure switches 1. Isolate the heater s power supply. 2. Remove the hose from the pressure switch. 3. Remove the electrical wires on the pressure switch. 4. Remove the pressure switch bracket screws on the heat exchanger, and then the complete assembly can be removed. 5. Remove the pressure switch fastening screws if the pressure switched are to be replaced. Installation is a reversal of the removal procedure with attention to the following points: 1. On HX models ensure the hoses are reconnected to the correct pressure switch. 69

70 6.5 Combustion Fan Removal Method 1 Partial Fan Removal 1. Isolate the heater s power supply. 2. Remove the electrical lead off the NG-2 board. 3. Remove the flue coupling connected to the combustion fan outlet. 4. Remove the 4 spring clips which holds the 2 halves of the combustion fan together (be cautious of the spring clips becoming projectiles as they are removed. Cup your hand over the clip to avoid injury as it is removed). 5. Remove the top half of the combustion fan, motor and fan wheel together. Installation is a reversal of the removal procedure with attention to the following points: 1. Fasten both halves together with correctly sized cir-clips or e-clips, if the original spring clips are too difficult to fit. Method 2 Complete Fan Removal 1. Isolate the heater s power supply 2. Remove the electrical lead off the NG2 Board 3. Remove 3 screws which fasten the combustion fan down to the combustion fan box. 4. Pry the combustion fan off the box, which will still be fastened by the sealing silicon. Installation is a reversal of the removal procedure with attention to the following points: 1. Clean both surfaces to be re-mated together. 2. Apply sufficient (but not excessive) silicon to the combustion fan s mating surface. Note: For HX models it is very important to ensure that the combustion fan s condensate drain hole is not blocked with silicon when refitting the combustion fan to the combustion fan box. To ensure there is no blockage, once the 3 screws have been tightened, look down the combustion fan outlet with a torch and clean out the drain hole with a suitable tool and piece of cloth to clear the hole of any silicon. 6.6 NG-2 Electronic Control Board Removal 1. Isolate the heater s power supply. 2. Remove the spark igniter lead from the PCB assembly. 3. Remove the 240 volt cover screw, and then maneuver the 240 volt cover from the PCB assembly. 4. Remove all other electrical connections from the PCB assembly. 5. Remove the 2 screws that secure the PCB assembly to the NG-2 support bracket. WARNING: Care should be taken to prevent any damage of the wiring and PCB. Installation is a reversal of the removal procedure with attention to the following points: 1. Ensure all wiring connections are positively located and that no looms have been damaged. 70

71 6.7 Heat Exchanger Removal 1. Isolate the heater s power supply. 2. remove the surround wrap around the service chamber 3. Remove the gas train assembly as described under section xx. 4. Remove the Gas manifold 5. Remove the pressure switch assembly as described under section xx. 6. Remove the NG-2 PCB assembly and NG-2 support bracket (refer to the NG-2 control board removal section for further instructions). The NG-2 support bracket has 3 screws which fasten it to the heat exchanger main plate, which will have to be removed. 7. Remove the supply air duct and remove the condensate hose from inside the unit. 8. Remove the heat 6 screws which hold the heat exchanger down within the cabinet area 9. The heat exchanger can be raised out from the top. 10. If wanting the Heat exchanger to come out of the end of the unit the removal of the supply air duct is required as well as removing the end panel off which the heat exchanger can slide out of the end of the unit. 71

72 6.8 Flue Pipe Removal MX External Models Loosen the Flue pipe hose clamps on the flue coupling at the combustion fan outlet as shown below. Remove the flue terminal and then remove the flue pipe from the heater. Flue Pipe Coupling Flue Pipe Hose Clamps When placing it back into place please make sure that it is sealed tight and no flue gases can escape from the connection. MX Internal Models The flue should be fitted to the flue pipe spigot via a bolted flue sleeve connection. Loosen these bolts sufficiently to allow the flue pipe to be removed from the spigot. Ensure that the flue pipe seal exiting the roof is not damaged. Once reconnected ensure that there are no potential gas leaks from the flue pipe. Also ensure that there as no potential water leaks from outside the building. Flue Pipe Coupling 72

73 6.9 Main Fan Assembly Removal External Models Turn the unit OFF and isolate the power supply. Remove the heater lid by unscrewing the 4 self tapping screws on the cover then lift the cover off. Remove the flue pip assembly as described in Section xx. Remove the fan electrical power loom and speed sensor off the NG-2. Remove the screws that hold the top plate to the cabinet. Remove fan housing from cabinet. Installation is a reversal of the removal procedure. Internal Models Turn the unit OFF and isolate the power supply. Split the heater as described in Section xx. Move the fan cabinet so that the fan housing can be removed without interfering with the flue piping. Remove fan housing from cabinet. Installation is a reversal of the removal procedure. Motor and Plate Removal Remove the screws that attach motor plate to the fan scroll then remove the motor plate, motor and fan wheel assembly from the fan scroll. Remove the fan from the motor by loosening the grub screw from the motor shaft. If the fan wheel is ceased onto the motor shaft then WD-40 and a puller may be required. The motor may be removed from the motor plate if required by removing the bolts and nuts that secure the motor to the motor stator brackets. 73

74 6.10 Splitting Internal Model Heaters The StarPro / MX-HX Internal model heaters can be split in half to allow for ease of installation. To split the heater, follow these simple instructions: Remove the heaters roof after removing the 4 roof screws. Disconnect the speed sensor loom from the control board and remove it from the heat exchanger cabinet. Remove the main fan motor & speed sensor loom access plate located on top of the fan cabinet compartment by removing the single screw. Unplug the main fan loom at the connection located inside the access hole which has just been uncovered. Remove the 2 screws fastening the fan cabinet tabs to the heat exchanger cabinet. These are located at the top of the fan cabinet on the heaters split line. Pivot the fan cabinet upwards high enough to dislodge the lower locking tabs fixed to the fan cabinet near the base. The heater is now split in two. Protect the exposed looms and tabs from damage while the heater is split in two parts. Once ready, reassemble in reverse order. Note: Ensure when reassembling the heater that everything is put back and connected correctly. 74

75 7. Technical Specifications 7.1 Heater Technical Specifications MX21 MX30 MX35 Max Heat Output 21 kw 30 kw 35 kw Max Gas Input 90 MJ/hr 130 MJ/hr 150 MJ/hr Maximum 800±40 Pa 760±40 Pa 760±40 Pa Burner Pressure Minimum Pa Pa Pa Ignition Pa Pa Pa Injector orifice diameter 2.25 mm 2.25 mm 2.4 mm Combustion Fan Vacuum Pressure Switch Setting Vacuum Pressure 20 C) Energy Rating Opening 140±12 Pa 115±12 Pa 115±12 Pa Maximum Closing 172 Pa 147 Pa 147 Pa Internal (no flue connected) TBA TBA TBA External TBA TBA TBA Stars Annual energy consumption 142 MJ/m3/year 144 MJ/m3/year 146 MJ/m3/year Note: Refer to Installers manual for other specifications not displayed in this table. 75

76 7.2 Main Component Technical Specifications Model Fasco 315W BNVA-A20 Fasco 650W BPVA-A12 Power 315 W 650 W Maximum Current 4.2 A 4.3 A Main Fan Motor Capacitor 15±1.5 µf 25±2.5 µf Start Winding 20 C Main Winding 20 C Ω Ω Ω Ω Impellor Size - diam. x width 225 x 180 mm 284 x 265 mm 2.25A Transformer Gas Valve Nominal Voltage/ Maximum Current Secondary Voltage (No Load) (Red VAC Secondary Voltage (No Load) (Black 230 VAC Secondary Voltage (No Load) (Red 230 VAC Modulating Coil maximum current Modulating coil winding 20 C Main Coil winding 20 C 230 VAC / 2.25 A VAC VAC VAC NG: 115 ma LPG: 160 ma Ω Coil 1: Ω Coil 2: Ω Combustion Fan Voltage/Power Winding 20 C 230 VAC / 60 W Ω Supply Air Overheat Switch Fuse 24Vac Opening Closing 24 VAC 2A Fuse 110 ±3.5 C 97 ±4.5 C Fuse 240 VAC Supply Air Duct Thermistor 250 VAC 8A Slow Blow Fuse 10k 25 C 76

77 7.3 Motor Wiring Diagrams Model Fasco 315W BNVA-A20 Fasco 650W BPVA-A12 Power 315 W 650 W Maximum Current 4.2 A 4.3 A Main Fan Motor Capacitor 15±1.5 µf 25±2.5 µf Start Winding 20 C Main Winding 20 C Ω Ω Ω Ω Impellor Size - diam. x width 225 x 180 mm 284 x 265 mm 77

78 7.4 StarPro Wiring Diagram 78

79 79

80 Brivis Acc Network 516 Module Low - Voltage Suitable for all Brivis StarPro MX and HX Internal / External Ducted Gas Heaters This module CANNOT be used on any other model. Requires NG-2 version 50 or higher software for this module to operate the Network 516. Acc Network 516 Installation Instructions The Network 516 Module requires a 240 volt power supply that can be plugged in to via a 3 pin plug. A pre-wired loom is provided to connect to the heaters electronic control module (NG-2), as well as a 25mm electrical conduit to accommodate the zone motor wiring. Ensure the Network 516 mounting position, is within reach of the loom length (1 metre), for the connection to the heater as well as the power supply point (1.5 metre). Use the screws provided to secure the module to the cabinet / structural member. The conduit saddle provided should be used to secure the 25mm conduit to the cabinet back or structural member also, to protect the 240 Volt zone motor wiring. 80

81 Network 516 Mounting positions External models: Mount the Network 516 on the cabinet end, and secure the conduit with the saddle at the back of the unit. Trim and seal the unit's flashing strip around the 25mm conduit to protect the wiring from the weather. Internal models: Mount the Network 506 on the cabinet end, alternatively, the Network 516 can be mounted on adjacent structural members. Wiring the Network 516 to the Heater Route the Network 516 loom to the heaters electronic control module NG-2 using the grommet on the loom where the entry is made into the heaters cabinet. Connect the 6 pin plug to the terminal marked "Option Board" at the NG-2. Programming Network 516 modes The Network 516 setting is selected through the heaters Installer parameters, in the same way other heater adjustments are made. Press the SET button on the NG-2 module to scroll through the displays. To make changes press the up/down buttons. To save changes press the SET button on the NG-2 module. The "NET506= 0" screen will prompt the installer to change the Network 506 mode from the default setting of 0 to NET506=5. 81

82 NET506 Setting Description Heating Add-on Cooling ZoneRelay 1 Not Enabled ZoneRelay 2 Not Enabled Not ZoneRelay 3 Not Enabled Enabled ZoneRelay 4 Not Enabled Heating Add-on Cooling ZoneRelay 1 Enabled as Zone A ZoneRelay 2 Enabled as Zone B Not ZoneRelay 3 Enabled as Zone C Enabled ZoneRelay 4 Enabled as Zone D Heating Add-on Cooling - Enabled ZoneRelay 1 Enabled as Zone A ZoneRelay 1 Enabled as Zone A ZoneRelay 2 Enabled as Zone B ZoneRelay 2 Enabled as Zone B ZoneRelay 3 Enabled as Zone C ZoneRelay 3 Enabled as Zone C ZoneRelay 4 Not Enabled ZoneRelay 4 Enabled for Cooling Control Heating Add-on Cooling ZoneRelay 1 Enabled as Zone A ZoneRelay 2 Enabled as Zone B Not ZoneRelay 3 Not Enabled Enabled ZoneRelay 4 Enabled as Zone D Heating Add-on Cooling - Enabled ZoneRelay 1 Enabled as Zone A ZoneRelay 1 Enabled as Zone A ZoneRelay 2 Enabled as Zone B ZoneRelay 2 Enabled as Zone B ZoneRelay 3 Not Enabled ZoneRelay 3 Not Enabled ZoneRelay 4 Not Enabled ZoneRelay 4 Enabled for Cooling Control Heating Add-on Cooling Enabled* ZoneRelay 1 Enabled as Zone A ZoneRelay 1 Enabled as Zone A ZoneRelay 2 Enabled as Zone B ZoneRelay 2 Enabled as Zone B ZoneRelay 3 Enabled as Zone C ZoneRelay 3 Enabled as Zone C ZoneRelay 4 Enabled as Zone D ZoneRelay 4 Enabled as Zone D 82

83 83

84 84

Thermo Top - Troubleshooting Tree

Thermo Top - Troubleshooting Tree Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?

More information

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND Honeywell Electronic Ignition Troubleshooting Tech Tip April 2007 The Honeywell S8610H Intermittent Pilot Module provides the ignition sequencing, pilot spark, pilot flame monitoring, Pilot Valve (PV)

More information

Fossil fuel heating equipment

Fossil fuel heating equipment Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating

More information

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book USERS GUIDE LOGIC Heat 12, 15, 18, 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

Fault Finder. A Service Engineers. for Warm Air Heating. www.johnsonsandstarley.co.uk. Publication No. ZZ1317-2 April 2015

Fault Finder. A Service Engineers. for Warm Air Heating. www.johnsonsandstarley.co.uk. Publication No. ZZ1317-2 April 2015 Publication No. ZZ 1317-2 April 2015 Publication No. ZZ1317-2 April 2015 A Service Engineers Fault Finder for Warm Air Heating www.johnsonsandstarley.co.uk CONTENTS 1. General Ventilation Information 3

More information

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION 1 2 3 4 5 Inadequate or no earth ground sensed by the Intelli-Vent control. Power supply to Intelli-Vent control has reversed polarity. Pressure switch circuit remaining closed for more than 5 seconds

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........

More information

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner

More information

Luna 3 Comfort Troubleshooting Guide June 2008

Luna 3 Comfort Troubleshooting Guide June 2008 Luna 3 Comfort Troubleshooting Guide June 2008 For Technical Assistance Call: (800)461-4657 WARNING! THIS DOCUMENT IS INTENDED ONLY AS AN EDUCATIONAL TOOL This Troubleshooting Guide, and the instructions

More information

SERVICE INSTRUCTIONS

SERVICE INSTRUCTIONS SERVICE INSTRUCTIONS 18, 20,24, 26L Integrity Electronic Gas Continuous Flow Water Heater TM031 Reevvi issi ion:: B Publissheed:: Feebrruaarryy 0088 871018 871020 871024 871024-B 871024-C 871026 871026-B

More information

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive

More information

For installation guide see reverse of book

For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents

More information

OPERATIONAL CHECKS & SAFETY CIRCUIT DESCRIPTION

OPERATIONAL CHECKS & SAFETY CIRCUIT DESCRIPTION OPERATIONAL CHECKS & SAFETY CIRCUIT DESCRIPTION Integrated control module performs internal checks. Integrated control module displays 8 8 on dual 7-segment display LED s. Integrated control module monitors

More information

Model 7586. Description / Applications. Intermittent Pilot Gas Ignition Control

Model 7586. Description / Applications. Intermittent Pilot Gas Ignition Control PARTS & ACCESSORIES Model 7586 Intermittent Pilot Gas Ignition Control Description / Applications The Beckett GeniSys Intermittent Pilot Gas Ignition Control is a 24 Vac gas ignition and safety control.

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

Rheem Spare Parts Manual. Commercial gas model A631265 Exterior 265L

Rheem Spare Parts Manual. Commercial gas model A631265 Exterior 265L Commercial gas model A631265 Exterior 265L Commercial gas model A631265 Exterior 265L Item Part No. Description 1 221735 Foam cover 2 221914 Anode x 3 (black) 1153mm 2 221924 Anode x 3 (blue) 1153mm 3

More information

E-gas Instant Gas Water Heaters

E-gas Instant Gas Water Heaters The Proven Preferred Choice! E-gas Instant Gas Water Heaters Training & Information Manual: There are important functional and operational differences between the conventional hot water geyser and the

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4

More information

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06 A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner

More information

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating

More information

Frequently Asked Questions. Air Top Diesel Heaters. 2000STC, Evo 40 & Evo 55

Frequently Asked Questions. Air Top Diesel Heaters. 2000STC, Evo 40 & Evo 55 Frequently Asked Questions Air Top Diesel Heaters 2000STC, Evo 40 & Evo 55 Question 1 What power outputs are the heaters available in? There are 3 models 2kW, 4kW and 5.5kW Question 2 What voltage are

More information

G670 Intermittent Pilot Ignition Controls

G670 Intermittent Pilot Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control

More information

OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)

OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12) OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12) Revision 1.0 Page 1 of 50 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE SOLE PROPERTY OF INTERNATIONAL THERMAL RESEARCH, LTD. ANY REPRODUCTION

More information

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model. CELTIC RSc b CUENOD. R8202395-02EN - Edition 02-21/04/2005

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model. CELTIC RSc b CUENOD. R8202395-02EN - Edition 02-21/04/2005 CUENOD Instantaneous Gas Water Heaters Storage Gas Water Heaters SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model CELTIC RSc b R8202395-02EN - Edition 02-21/04/2005 Boilers Solar Panel 69214511 31 CELTIC

More information

MP-4000 Alarm List (Software version 2.4.3 or later)

MP-4000 Alarm List (Software version 2.4.3 or later) Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

SELECTION, APPLICATION AND MAINTENANCE

SELECTION, APPLICATION AND MAINTENANCE DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine

More information

Technical Information

Technical Information Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1

More information

Maxi Pressurisation Units (Maxi, Maxi Plus & HP)

Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Installation and Maintenance Instructions Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5

More information

SL280UHV SERIES GAS FURNACE WARNING

SL280UHV SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could

More information

Service Manual REU - 16 FUA - E. Infinity 16 i. Continuous Flow Water Heater. Important.

Service Manual REU - 16 FUA - E. Infinity 16 i. Continuous Flow Water Heater. Important. Service Manual REU - 16 FUA - E Infinity 16 i Continuous Flow Water Heater Important. Read these instructions carefully before attempting service of this appliance. All work must be carried out by competent

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

Spare Parts List M96A.24SM/B M96A.28SM/B

Spare Parts List M96A.24SM/B M96A.28SM/B *16202390* 162.0239.0 REV5 14/04 2015 Spare Parts List M96A.24SM/B M96A.28SM/B Issue Table description Issue n. of pages Overall view 09/2008 1 C.h. return group and d.h.w. heat exchanger 09/2008 1 C.h.

More information

Evaporative emissions system

Evaporative emissions system just a test. Evaporative emissions system 20-48 Function description of EVAP canister system Depending upon the air pressure and ambient temperature, fuel vapor will form above the level of fuel in the

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

HeatSource HS1800 Heater

HeatSource HS1800 Heater HeatSource HS1800 Heater Vehical Installation & Operating Instructions Propex Heatsource Ltd Unit 5, Second Avenue Buisness Park, Milbrook, Southampton, SO15 OLP Tel: 023 8052 8555 Fax: 023 8052 8800 Website:

More information

80UHG. Service Literature

80UHG. Service Literature Service Literature Corp. 9728 L12 Revised 01 2002 80UHG 80UHG series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with tubular heat exchangers formed

More information

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU Automatic Temperature Control Diagnosis and Repair Diagnosis of Automatic A/C Systems The most common automatic A/C system malfunctions tend to be the result of basic air conditioning problems. These problems

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

800-292-3279 916 638-0828

800-292-3279 916 638-0828 800-292-3279 916 638-0828 http://easycleansystems.com/heaters/heater-parts.html VAL6 KBE5S and KBE5L Service manual KBE5S 1 2 Specifications Type VAL6 KBE5S Heat Output 111,000BTU/h Fuel Kerosene, Diesel

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

Morco House Riverview Road Beverley HU17 0LD

Morco House Riverview Road Beverley HU17 0LD Morco House Riverview Road Beverley HU17 0LD Morco Products Ltd Tel: 01482 325456 Fax: 01482 212869 Email sales@morcoproducts.co.uk Web www.morcoproducts.co.uk Combi Boilers - Poor Hot Water Delivery Combi

More information

High Efficiency Boiler Range Technical Guide

High Efficiency Boiler Range Technical Guide High Efficiency Boiler Range Technical Guide Glow-worm Nottingham Road Belper Derbyshire DE56 1JT Head Office: 01773 824 639 Literature: 01773 596 105 After Sales Service: 01773 596 510 Technical Advice:

More information

Air conditioning, electrical testing

Air conditioning, electrical testing just a test. Air conditioning, electrical testing 01-253 Wire and component test using VAG1598 A test box Special tools and equipment VAG 1598 A test box and VAG 1598/11 adapter cable and VAG 1598/12 VAG1526

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

NAVIEN AMERICA INC. 17855 FITCH AVENUE

NAVIEN AMERICA INC. 17855 FITCH AVENUE Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:

More information

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for

More information

Rinnai Tankless. Water Heater. Troubleshooting Manual

Rinnai Tankless. Water Heater. Troubleshooting Manual Rinnai Tankless Water Heater Troubleshooting Manual WARNING There are a number of live tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

*.ppt 11/2/2009 12:48 PM 1

*.ppt 11/2/2009 12:48 PM 1 Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers

More information

ENGINE COOLING SYSTEM

ENGINE COOLING SYSTEM ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,

More information

PRODUCT DESIGN. 5. Furnace awaits call from thermostat.

PRODUCT DESIGN. 5. Furnace awaits call from thermostat. Goodman / Amana Distinctions Brand Single-Stage 80% or 90% Furnaces White-Rodgers 50A55 Integrated Ignition Control 1. 115 VAC power applied to furnace. 2. Integrated ignition control module performs internal

More information

ECM. Service Guide. www.thedealertoolbox.com

ECM. Service Guide. www.thedealertoolbox.com ECM Service Guide www.thedealertoolbox.com ECM Table of Contents Service Guide Working on the motor with power connected may result in electrical shock or other conditions that may cause personal injury,

More information

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially

More information

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1 Fault codes DM1 Industrial engines DC09, DC13, DC16 Marine engines DI09, DI13, DI16 03:10 Issue 5.0 en-gb 1 DM1...3 Abbreviations...3 Fault type identifier...3...4 03:10 Issue 5.0 en-gb 2 DM1 DM1 Fault

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support

More information

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer

More information

H E A T I N G. Owner s Manual PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USE. Bonus offer when you register your product online brivis.com.

H E A T I N G. Owner s Manual PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USE. Bonus offer when you register your product online brivis.com. H E A T I N G Owner s Manual PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USE Bonus offer when you register your product online brivis.com.au a company Index Introduction..............................

More information

Electronically Controlled Clutchless or Variable Drive Compressors

Electronically Controlled Clutchless or Variable Drive Compressors Electronically Controlled Clutchless or Variable Drive Compressors On many new air conditioning systems, such as Lexus, Cadillac, Chrysler, and others, a new type of compressor has been fitted. There are

More information

Digi-Motor Installation Guide

Digi-Motor Installation Guide Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support

More information

PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator

PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator 3.635.5275.251 IM-P486-19 CH Issue 2 PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator Installation, Start-up and Operation Manual 1. Safety information 2. General product information 3.

More information

NISSAN FIGARO FAULT CODES AND DIAGNOSTICS

NISSAN FIGARO FAULT CODES AND DIAGNOSTICS NISSAN FIGARO FAULT CODES AND DIAGNOSTICS The Nissan Figaro uses an engine management system with the acronym ECCS you ll see it in large letters on the plenum box when you open the bonnet. It stands for

More information

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type

More information

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.

EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. This Troubleshooting Guide covers the electric coolant valve and control

More information

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled

More information

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/ CW-5000/ 5200 Contents Cautions ---------------------------------------------------------------- 3 Parts introduction --------------------------------------------------- 4 Installation ------------------------------------------------------------

More information

DVI 980/982 (Honeywell Nr. S4865) Gas Burner Safety Control

DVI 980/982 (Honeywell Nr. S4865) Gas Burner Safety Control Gas Burner Safety Control For 1- or 2-stage forced draught and atmospheric gas burners, with DC valves Possible flame detectors: - Ionisation probe - Infrared flicker detector 1020.1 - UV flame sensor

More information

Compressor Service & Maintenance Manual

Compressor Service & Maintenance Manual Compressor Service & Maintenance Manual C Series COMPRESSOR (D)C1103 (D)C1203 (D)C2106 (D)C2206 (D)C3210 Copyright 2006 DCI. All Rights Reserved. 92311, Rev. C, 08/13 1 C1000 Series Service & Maintenance

More information

Via Raffaello,33/A - 42100 Reggio Emilia Italia Tel +39 0522.514.461 Fax +39 0522 514469 - E-mail: aftersales@landi-gas.

Via Raffaello,33/A - 42100 Reggio Emilia Italia Tel +39 0522.514.461 Fax +39 0522 514469 - E-mail: aftersales@landi-gas. Trouble Shooting Solving problems with LSI-NSI software Update to version 2.1.0 1/14 Rev.0 2/14 Rev.0 CONTENTS 1.1. Switching from petrol to gas PAGE 4 1.2. Drop at medium-high speeds PAGE 5 1.3. Functioning

More information

Service Manual Models: 150-500

Service Manual Models: 150-500 Models: 150-500 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Armor Water Heater Installation and Operation

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT

More information

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R8216470-01EN - Edition 01-26/10/2009

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R8216470-01EN - Edition 01-26/10/2009 Instantaneous Gas Water Heaters Storage Gas Water Heaters SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model R8216470-01EN - Edition 01-26/10/2009 Boilers CUENOD Renewable 3121488 12 EAA1...... 3124527 25

More information

TSB #: 74 Date: 9/7/2013 HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS

TSB #: 74 Date: 9/7/2013 HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS TSB #: 74 Date: 9/7/2013 Initial Once Read: In this technical bulletin we have listed diagnostic advice relating to the Holden VE/WM HVAC & A/C system. This information

More information

Munchkin Heat Exchanger Maintenance

Munchkin Heat Exchanger Maintenance Munchkin Heat Exchanger Maintenance By: Mike Granahan *Refer to the appropriate boiler manual for your specific model number. Adjustment procedures will vary. Boiler shown below is an HTP Munchkin 80M

More information

PART 11: START-UP PROCEDURES FOR THE INSTALLER

PART 11: START-UP PROCEDURES FOR THE INSTALLER PART 11: START-UP PROCEDURES FOR THE INSTALLER NOTICE It is important to note that the user can adjust the heat curve down by adjusting the central heating temperature to a lower setting. 212 CENTRAL HEATING

More information

Single Channel Loop Detector

Single Channel Loop Detector Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop

More information