UNDERFLOOR AIR DISTRIBUTION
|
|
|
- Chester Maxwell
- 10 years ago
- Views:
Transcription
1 FINAL REPORT NCEMBT UNDERFLOOR AIR DISTRIBUTION AN EXPERIMENTAL COMPARISON OF AIR DIFFUSION PERFORMANCE BETWEEN UNDERFLOOR AIR DISTRIBUTION AND CONVENTIONAL OVERHEAD AIR DISTRIBUTION SYSTEMS AUGUST 2008 Liangcai (Tom) Tan, Ph.D. Brian J. Landsberger, Ph.D. University Of Nevada, Las Vegas Davor Novosel National Center for Energy Management and Building Technologies
2 EXECUTIVE SUMMARY EXECUTIVE SUMMARY A major paradigm of the underfloor air distribution (UFAD) system is that its air distribution characteristics are different than in conventional overhead air distribution (CAD) systems. However, significant thermal gradients have not been observed in several installed UFAD systems; rather the systems appear to perform similarly to CAD systems. Therefore, the UFAD Task Force of the National Center of Energy Management and Building Technology (NCEMBT) recommended that the initial experiments for this task compare the UFAD and CAD system configurations, and specifically determine if the air temperature and velocity gradients are significantly different. The comparison was made with both systems having been designed with an air distribution performance index (ADPI) of greater than 80%. This project covered the laboratory investigation phase of Task 2 where the performance and costeffectiveness of UFAD and conventional air distribution (CAD) systems were compared. To perform the testing, it was necessary to modify and upgrade the current UNLV Building Technologies Laboratory (BTLab) to obtain experimental data related to energy, performance and comfort issues associated with CAD and UFAD systems. The results of laboratory development, testing and qualification revealed that: Conditions maintained in the BTLab were on target, with low enough variation to allow consistent, repeatable testing at the planned input parameters; The measured data were replicable and reliable; The BTLab was qualified to meet the design criteria, and is a unique, state-of-the-art, automated test room for measurement of quality, efficiency, and effectiveness of different heating, ventilating, and air conditioning systems. The results of laboratory designed experiments on UFAD and CAD systems revealed that for systems that are similar to the laboratory set-up: The ADPI values of the UFAD system in half and zero load tests were about 55% to 65%, much lower than test goal of 80% or higher for a properly functioning system. Thus a detailed comparison of temperature and velocity distributions between CAD and UFAD systems with ADPI of 80% or higher at half and zero load conditions was not possible. The full load tests of UFAD systems achieved ADPI values higher than 80%, and a comparison was made. Statistically, there is a significant difference in air velocity and temperature distribution in interior office zones between properly functioning CAD and UFAD systems. The overall air temperature and velocity conditions throughout the occupied zone in CAD systems have less variation than that in UFAD systems. UFAD systems need 35% to 38% more airflow rates than CAD systems to achieve the same average occupied zone temperature of 75 F when the supply diffuser air temperatures are set at the industry standard, i.e., 55 F for CAD systems and 65 F for UFAD systems. For the UFAD systems for this specific room with no carpet or other floor covering on the raised floor tiles and where halogen flood lights were used, 32% of the lighting load and 15 to 30% of the floor heater load is transferred to the underfloor plenum, while 36% of the lighting load and 70 to 85% of the floor heater load account for the room load. The remaining 32% of the lighting load goes directly into the ceiling plenum. NCEMBT
3 EXECUTIVE SUMMARY Based on the ADPI test results, we conclude: The null hypothesis that There are no significant differences in air velocity and thermal distribution in interior office zones between CAD and UFAD systems that are designed to perform at an ADPI greater than 80% is rejected for both full and partial load conditions. For UFAD systems, based solely on ADPI results, the indoor environment is thermally not acceptable under partial load conditions (ADPI lower than 80%) but thermally acceptable (ADPI higher than 80%) under full load conditions, while it is thermally acceptable for both full and partial load conditions in CAD systems. Statistically there are significant differences in air velocity and thermal distribution in interior office zones between CAD and UFAD systems that are designed to perform at an ADPI greater than 80%. However the vertical temperature gradients in both CAD and UFAD systems are below the sensible threshold of most occupants, so from a thermal sensation perspective, they have no significant differences. When subjected to high plenum subfloor or slab temperatures and/or significant plenum air leakage, UFAD systems may consume more energy than CAD systems to achieve the same average occupied zone temperature of 75 F with the supply diffuser air temperatures set at the industry standard, i.e., 55 F for CAD systems and 65 F for UFAD systems, due to increased supply airflow rates and cooling requirements to keep plenum supply air temperatures significantly below 65 F. For UFAD systems, load calculations need to consider both the room load and the UFAD plenum load. The plenum load may be thought of as similar to duct loss heat load in a CAD system, but these experiments show significant load characteristic differences. Among those are the higher transfer of heat load (both lighting and floor) from the room to the plenum through the floor, the transfer of heat to the plenum from the subfloor, and the possibility for significant variations in plenum air temperature and thus higher variation in diffuser discharge air temperature when compared to CAD systems. We recommend additional research for UFAD systems, on: Reduction of temperature variations in the underfloor plenum. Effects of carpet on heat transfer, supply temperature, airflow rate, ADPI values and thermal comfort. Effects of occupancy, office cubicle set-up and equipment on ADPI values and thermal comfort. Effects of diffuser locations and numbers on ADPI values and thermal comfort. Effects of supply air temperature on ADPI and thermal comfort. Effects of a combination of parameters (diffuser location and numbers, supply air temperature and load conditions with carpet and office configuration) on ADPI values and thermal comfort. A protocol for field measurement methods and field data collection for UFAD systems. 2 NCEMBT
4 1. PROJECT OBJECTIVE 1. PROJECT OBJECTIVE The specific objectives for Task 2 were to: Investigate HVAC design, comfort, and energy issues related to UFAD systems; Conduct a series of interactive seminars in conjunction with ASHRAE chapters, to collect current information on the level of UFAD knowledge in the design community; Conduct a preliminary field study of existing UFAD systems in commercial buildings to characterize existing installed UFAD systems, identify areas that may require additional laboratory research, and generate information to develop protocols for future field testing of UFAD systems; Modify and upgrade the current test facility so that in-depth testing can be conducted to obtain laboratory data related to energy, performance and comfort issues associated with UFAD systems; Conduct in-depth laboratory tests to obtain data and answer questions associated with energy, performance and comfort issues related to UFAD systems, and develop test protocols that can be used in future field tests in commercial buildings with UFAD systems; and Develop information for future development of design tools that can be used to compare UFAD and CAD system applications. Three different organizations were contracted to complete these objectives. The Building Diagnostics Research Institute (BDRI) completed objective 2. The principal investigator/presenter was James Woods, Ph.D., P.E. This subtask is complete, and a final report (NCEMBT ) has been published. GARD Analytics completed objective 3. The principal investigator was Roger Hedrick. The University of Nevada, Las Vegas (UNLV) completed objectives 4 and 5. The principal investigator is Liangcai (Tom) Tan, Ph.D. All three organizations contributed toward objectives 1 and 6. This report details the UNLV contribution toward the objectives. NCEMBT
5 2. BACKGROUND 2. BACKGROUND Modern UFAD systems have long been used in Europe and are rapidly gaining acceptance in the United States. In principle, UFAD systems can reduce or even eliminate overhead plenum spaces and sheet metal ducts that make up conventional ceiling air distribution systems. By applying the principle to actual building construction, suppositions were made of reduced construction costs and shortened required deck-to-deck heights in high-rise buildings. However, before such gains can be realized, a number of design issues associated with UFAD systems that have not been fully investigated, need to be resolved. These include: Controlling air temperature and humidity in large open under-floor plenums, Controlling distributed airflow in large open under-floor plenums, Controlling air mixing in occupied spaces served by under-floor plenums, Minimizing the presence of moisture in under-floor plenums to prevent fungal (mold) contamination, and Controlling the propagation of sound in under-floor plenums to prevent a degeneration of speech privacy in occupied spaces. 4 NCEMBT
6 The entire report can be accessed via the following link: 20Distribution_NCEMBT pdf
Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering
Challenges and Failures in Green Building Design Using Under-Floor Air Distribution Ken Urbanek, PE, HBDP, LEED AP Director of Engineering Agenda UFAD Overview Challenges / Failures Steps for a Successful
Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update
AIR DISTRIBUTION FOR COMFORT AND IAQ
AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
UNDER FLOOR AIR DISTRIBUTION (UFAD) SOLUTIONS
UNDER FLOOR AIR DISTRIBUTION (UFAD) SOLUTIONS OVERHEAD SYSTEM UFAD SYSTEM ...... - A product of AirFixture USA I DON T CARE ZONE B R E A T H I N G Z O N E W E L L M I X E D CONSTANT VOLUME DIFFUSER WITH
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
LITERATURE REVIEW OF FLEXIBLE AND ADAPTIVE HVAC DISTRIBUTION SYSTEMS FOR OFFICE BUILDINGS. Xin Yu and Theodore F. Smith
LITERATURE REVIEW OF FLEXIBLE AND ADAPTIVE HVAC DISTRIBUTION SYSTEMS FOR OFFICE BUILDINGS Xin Yu and Theodore F. Smith Department of Mechanical Engineering The University of Iowa Iowa City, Iowa 52242
Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP)
Lee, K.S., Xue, G., Jiang, Z., and Chen, Q. 0. Thermal environment in indoor spaces with under-floor air distribution systems:. Impact of design parameters (5-RP), HVAC&R Research, 8(6), 8 9. Thermal environment
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected]
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected] Learning Objectives 1. Gain familiarity with Computational
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
L EED & G r e e n B u i ldi ngs
L EED & G r e e n B u i ldi ngs A P P L I C AT I O N G U I D E contents 3 - General 3 - Introduction 3 - Leadership in Energy & Environment 3 - Purpose 3 - LEED Rating System 4 - Energy & Atmosphere 4
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
RESNET National Rater Test Study Guide Outline
RESNET National Rater Test Study Guide Outline The RESNET national home energy rating standard spells out a listing of the knowledge base and skills set for Home Energy Ratings. Trainers and Rating Quality
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
underfloor air distribution
hospitals fire rated woodgrains energy solutions Redefine your comfort zone. www.titus-hvac.com Table of Contents products UnderFloor Air Distribution Products... 4 overview Application Guide... 8 Introduction
Whole House Dehumidification for Occupant Comfort and Energy Savings
Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009
Integrated Solar Radiant Systems
Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant
Radiant Floor Heating In Theory and Practice
The following article was published in ASHRAE Journal, July 02. Copyright 02 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes only.
Basics of HVAC Cleaning
Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project
Application Guide. www.titus-hvac.com www.titus-energysolutions.com
Application Guide leed AND GREEN BUILDINGS www.titus-hvac.com www.titus-energysolutions.com table of contents General 3 Introduction 3 Leadership in Energy & Environment 3 Purpose 3 LEED Rating System
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Displacement Ventilation in Schools
Displacement Ventilation in Schools Price Displacement Ventilation in Schools Introduction Displacement Ventilation (DV) originated in industrial facilities in Europe as an effective way to remove contaminants
Dual Maximum VAV Box Controls
ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
Air Conditioning Contractors of America
Air Conditioning Contractors of America WHO IS ACCA???? Industry Manuals Residential D, J, S, H, RS, T, P A manual J load calculation is a measurement of how much heating and cooling capacity a home will
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
BUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program
BUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program Use of Moisture Measuring Devices in Evaluating Water Damage in Buildings July 2007 The evaluation of mold colonization of building
Essam E. Khalil [email protected]
AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil [email protected] PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract
FEDERAL LEADERSHIP IN HIGH PERFORMANCE and SUSTAINABLE BUILDINGS MEMORANDUM OF UNDERSTANDING
FEDERAL LEADERSHIP IN HIGH PERFORMANCE and SUSTAINABLE BUILDINGS MEMORANDUM OF UNDERSTANDING PURPOSE: With this Memorandum of Understanding (MOU), signatory agencies commit to federal leadership in the
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Air distribution effectiveness with stratified air distribution systems
Lee, K.S., Jiang, Z., and Chen, Q. 2009 Air distribution effectiveness with stratified air distribution systems, ASHRAE Transactions, 115(2). Air distribution effectiveness with stratified air distribution
Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
Acoustic Design Practices for Sustainable Buildings
Acoustics 2008 Geelong, Victoria, Australia 24 to 26 November 2008 Acoustics and Sustainability: How should acoustics adapt to meet future demands? Acoustic Design Practices for Sustainable Buildings Danny
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
Haworth s Product to LEED Points. LEED - Commercial Interiors
Haworth s Product to LEED Points LEED - Commercial Interiors Chicago Showroom Haworth products may contribute to the individual prerequisites and credits of LEED. LEED is a holistic building rating system
Active & Passive Beams
Active & Passive Beams Active & Passive Beams Introduction Beam systems are an alternative to traditional all-air conditioning systems. Beams use water to move energy through a building and service the
AIRCONDITIONING Cooling Loads Calculations
Calculations -1- AIRCONDITIONING Cooling s Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example (p. 18.37)
DUCT SYSTEM DESIGN CONSIDERATIONS Part 1
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 by Roger M Hensley, CMS TYPES OF SUPPLY DUCT SYSTEMS There are several basic
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
IEQ-15 Air Distribution System
AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA
Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes
Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes Jonathan Coulter, Bruce Davis, Cyrus Dastur, Melissa Malkin-Weber and Tracy Dixon Advanced Energy,
Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP
Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s
THERMAL LOSSES Thermal Losses Calculations
Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak
IPACK2005-73273 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS
Proceedings of IPACK5 ASME InterPACK '5 July 17-, San Francisco, California, USA IPACK5-7373 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS Amir Radmehr Innovative Research, Inc. Plymouth, MN, USA
Mold Response and Remediation Plan
1.0 Policy Statement The University of New Haven has developed a mold response and remediation plan in accordance with best practices set forth by the Environmental Protection Agency (EPA), Occupational
MOLD RESPONSE AND REMEDIATION PLAN
MOLD RESPONSE AND REMEDIATION PLAN Prepared By: Triumvirate Environmental Developed: April 2011 Last Revised: March 2015 Program Approval Associate Vice President of Public Safety & Administrative Services
Radiant Panels and Chilled Sails. www.price-hvac.com
Radiant Panels and Chilled Sails www.price-hvac.com Radiant Panels and Chilled Sails Introduction Radiant panels use thermal radiation to modify surface temperatures in order to provide sensible cooling
Mechanical and Natural Ventilation
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy
Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy Jonathan Coulter 1 ABSTRACT This paper documents the influences vented crawl
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
IEQ Management Plan. Denver Museum of Nature and Science ECF Addition
IEQ Management Plan GH Phipps Construction Companies 5995 Greenwood Plaza Blvd., Suite 100 Greenwood Village, Colorado 80111-4710 303.571.5377 PHONE www.ghphipps.com Denver Museum of Nature and Science
Flexibility, Efficiency In San Antonio Arena
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not
WATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts
WATER DAMAGE INVESTIGATION Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor
Galina Stankevica. Master of Science in Engineering and ICT
Commissioning of the HVAC-plant in a large office building designed with an underfloor ventilation system including input into what should be emphasized when evaluating the total system is to be done.
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Residential HVAC System Sizing
Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: [email protected] SUMMARY Heating, ventilating and air-conditioning (HVAC)
Dedicated Outdoor Air Systems (D.O.A.S.)
Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS
COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International
Dehumidification Design
Dehumidification Design Using Data-Center Heat Utilizing free heat from a server room was the concept behind an air-handling system in a college-campus building Considerable energy savings are possible
Using BIM In HVAC Design
This article was published in ASHRAE Journal, June 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
GUIDELINES ON AIRFLOW AND REFRIGERANT CHARGE VERIFICATION AND DIAGNOSTICS
GUIDELINES ON AIRFLOW AND REFRIGERANT CHARGE VERIFICATION AND DIAGNOSTICS Alliance for Residential Building Innovation David Springer, Davis Energy Group Context Airflow and refrigerant charge defects
250 St Georges Tce, Perth, WA (QV1)
250 St Georges Tce, Perth, WA (QV1) Building Profile Building Construction date 1991 Refurbishment date Owner Building Size Refurbishment Team Building Management Awards Ratings QV.1, 250 St Georges Terrace,
Center for the Built Environment UC Berkeley
Center for the Built Environment UC Berkeley Peer Reviewed Title: Analysis of a hybrid UFAD and radiant hydronic slab HVAC system Author: Raftery, Paul, National University of Ireland Galway Lee, Kwang
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
AMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL
AMCA International Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on Air
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE
TECHNICAL FEATURE Fundamentals at Work This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
Implications IN THIS ISSUE. A Newsletter by InformeDesign. A Web site for design and human behavior research.
VOL. 08 ISSUE 01 A Newsletter by InformeDesign. A Web site for design and human behavior research. IN THIS ISSUE Acoustics of Green Buildings Related Research Summaries Acoustics of Green Buildings Ralph
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects
4.02.08 updated Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects Moisture Removal Systems www.groundheaters.com www.wackerneuson.com Controlling moisture
Air Conditioning in Green Office Buildings?
Air Conditioning in Green Office Buildings? How to implement Demand Controlled Ventilation Stuttgart Rechte allein bei ICEBO 08 10.10.2008 CI / DrRo 1 Air Conditioning in Green Office Buildings ventilation
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of
Controlling Condensation On CWP Insulation BY ED LIGHT, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; AND ROGER GAY
This article was published in ASHRAE Journal, Decemeber 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without
CENTER FOR ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program
CENTER FOR ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program Guidance Concerning Remediation and Prevention of Mold Growth and Water Damage in Public Schools/Buildings to Maintain Air
How To Get An Energy Star For A Small Duct High Velocity (Sdhv)
May 12, 2014 Ms. Abigail Daken U.S. Department of Environmental Protection (EPA) ENERGY STAR Program 7401 Alabama Avenue St. Louis, MO 63111 314-481-9000 www.unicosystem.com Delivered via email to: [email protected]
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Greening Commercial Data Centres
Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling
Tate s Wire & Cable Solution
Access Floors Tate s Wire & Cable Solution A Flexible & Sustainable Management System Access Flooring to the Power of Your company will discover complete flexibility and reconfiguration capability 2 Creating
Prestige Home Inspection LLC
Cover Page Prestige Home Inspection LLC IAC2/ESA - Mold Assessment and Water Damage Report 555 W. Brook ave., Client's town MI, 48059 Inspection prepared for: Client's name Inspection Date: 10/15/2012
University of Nevada, Reno Facilities Services Department STANDARD OPERATING PROCEDURE. Facilities Maintenance Services
University of Nevada, Reno Facilities Services Department STANDARD OPERATING PROCEDURE Facilities Maintenance Services Indoor Flood Cleanup and Mold Prevention DATE: 6/24/15 REVISED: PURPOSE This University
CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?
Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
SECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution.
SECTION EG Air Distribution Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. Space Air Diffusion AIR DISTRIBUTION ENGINEERING GUIDE Proper selection of air diffusion
Halton - Achieving Energy Efficiency in School Design
Halton - Achieving Energy Efficiency in School Design Enabling Wellbeing Halton Design Tools Drive Energy Efficient Kitchen Ventilation and Comfort Today, nutritional guidelines for school foodservice
CRAWLSPACE ISSUES IN THE NORTHWEST
CRAWLSPACE ISSUES IN THE NORTHWEST Ken Baker, K energy, Association of Idaho Cities Chuck Murray, Washington State University Extension Energy Program Issue Statement With respect to crawl space design
Impact of Infiltration on Heating and Cooling Loads in U.S. Office Buildings
Impact of Infiltration on Heating and Cooling Loads in U.S. Office Buildings 1 Steven J. Emmerich, 1 Andrew K. Persily, and 2 Timothy P. McDowell 1 Building and Fire Research Laboratory, National Institute
CLOSED CRAWLSPACES. Have you ever been in your crawlspace? If not, have you ever even
CLOSED CRAWLSPACES What s In the Crawlspace? Wet Sagging Fiberglass Improper Drainage Have you ever been in your crawlspace? If not, have you ever even opened the door to look inside and see what it looked
BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES
Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE