TRNSYS Modelling of a Hybrid Membrane Liquid Desiccant Air Conditioning System
|
|
|
- Benjamin Clark
- 10 years ago
- Views:
Transcription
1 TRNSYS Modelling of a Hybrid Membrane Liquid Desiccant Air Conditioning System Ahmed Abdel-Salam a, Gaoming Ge b, Carey Simonson c a,b,c Department of Mechanical Engineering, University of Saskatchewan, 57 Campus Drive, Saskatoon, SK, Canada S7N 5A9 a [email protected], b [email protected], c [email protected] Abstract The attention to liquid desiccant air itioning (LDAC) systems is increasing worldwide. This is mainly due to the ability of these systems to efficiently maintain indoor air humidity within acceptable ranges in energy efficient way compared to conventional air itioning systems. LDAC systems still under R&D in order to reduce/eliminate common drawbacks, such as the carryover of desiccant droplets in air streams, and to develop novel configurations which aim to achieve higher energy efficiency. To address these, two improvements are implemented on a LDAC system in this study. First, liquid-to-air membrane energy exchangers (LAMEEs) are used as the dehumidifier and regenerator, in order to avoid the carryover of desiccant droplets in air streams. Se, the desiccant solution heating and cooling energy requirements are simultaneously provided using a hybrid liquid desiccant heat pump (LDHP). The proposed hybrid membrane LDAC (H-M-LDAC) system is annually simulated using TRNSYS for a small office building located in Miami, FL. Results show that the COPs of the return air heat pump (RAHP), LDHP and H-M-LDAC system vary under different operating itions with an approximate average annual values of 4.5, 7.8 and 1, respectively. 1 Introduction The last few decades have witnessed the development of several novel air itioning technologies. With the increasing concerns regarding humidity control, liquid desiccant air itioning (LDAC) technologies have become promising competitors with the widely used conventional air itioning systems. The main components of a LDAC system are dehumidifier, regenerator, cooling coil and heating coil. Although liquid desiccant systems may still include one heat pump or more, in order to provide the heating and cooling requirements of the desiccant solution streams, the operating temperatures of desiccant solution in LDAC systems enable the used heat pumps to be operated in energy efficient manner. For instance, the humid air is dehumidified in a conventional air itioning system by overcooling the humid air stream below its dew point temperature in order to ense the moisture required to be removed, which requires low orating temperatures. While, in LDAC systems, the air dehumidification is achieved using a concentrated and cool liquid desiccant solution stream, which has a lower surface vapor pressure than the humid air stream required to be dehumidified. In LDAC systems, the desiccant solution should be regenerated, after it absorbs the moisture from humid air. Liquid desiccant regeneration is achieved by heating the desiccant solution up to 45 o C-65 o C in order to increase its surface vapor pressure, and then transferring the 1
2 moisture from the desiccant solution to the regeneration air, which could be either exhaust air from the building or ambient air. Since considerable amount of heating is consumed in the regeneration of dilute desiccant solution, many studies have investigated the potential of integrating LDAC system with solar thermal system (Abdel-Salam et al. 2014; Crofoot and Harrison 2012; Li et al. 2010; Gommed and Grossman 2007; Davies 2005). The results of solar LDAC systems were promising from energy consumption point of view. However, the achieved energy savings using solar LDAC systems are accompanied with higher initial costs (Abdel- Salam et al. 2014). Although they seemed to be promising several years ago, solar LDAC systems do not seem to be the most energy efficient configuration any more, especially considering the fact that a heat pump may be still needed in a solar LDAC system in order to cool the desiccant solution before it removes the moisture from the humid air. Some researchers have investigated the potentiality of using the heat rejected from the solution cooling heat pump in order to cover the heating requirements of dilute desiccant solution, and this was found to improve the coefficient of performance (COP) of the system. Thus, a hybrid liquid desiccant heat pump (LDHP) will be used in the current study in order to simultaneously provide the solution heating and cooling requirements. Another issue with majority of LDAC systems is that direct contact itioners are used as dehumidifier and regenerator. This may cause the carryover of desiccant droplets in supply and exhaust air streams, which might lead to several undesirable consequences such as the degradation of indoor air quality (IA) and corrosion of downstream ducting and equipment. Previous studies have showed that there are two ways to eliminate the desiccant droplets carryover problem. Internally cooled/heated low solution flow rate itioner is one promising design (Lowenstein 1994; Lowenstein et al. 2006), where it is characterized by its low solution flow rate which may be up to 20 times lower than conventional itioners. This leads to a rapid change in its temperature, and thus this design should be internally cooled/heated, and cannot be operated in adiabatic mode. This design was investigated in several previous studies by the Solar Calorimetry Laboratory at ueen s University (Mesquita 2007; Jones 2008; Crofoot 2012). Another design, which is able to eliminate the desiccant droplets carryover problem, is the liquidto-air membrane energy exchanger (LAMEE). In a LAMEE, the air and solution streams are separated using semi-permeable membranes, which allow the transfer of water vapor but do not permit any liquid droplets to be transferred. Several experimental and theoretical studies have been performed on the LAMEE by the Thermal Laboratory at University of Saskatchewan (Abdel-Salam et al. 2013a; Ge et al. 2013a). The authors have performed several studies on different configurations of membrane LDAC (M-LDAC) systems, which use LAMEEs as itioners (Abdel-Salam and Simonson 2014; Abdel-Salam et al. 2014; Abdel-Salam et al. 2013b-2013d). The performances of the studied M-LDAC systems were found to be promising, and thus LAMEEs are used in the current study. A schematic diagram which shows the specifications of the used LAMEEs is presented in Fig.1. More information about the properties of the semi-permeable membranes, which are used in the LAMEEs, is presented in a previous study by the authors (Abdel-Salam and Simonson 2014). In the current study, a hybrid M-LDAC (H-M-LDAC) system will be annually simulated, for the first time in the scientific literature, using the TRNSYS building energy simulation software. The proposed H-M-LDAC system is characterized by two advanced modifications, compared to basic LDAC systems as follows. (1) LAMEEs are used in the H-M-LDAC systems as dehumidifier and regenerator, which eliminate the desiccant droplets carry over problem. (2) Only one liquid desiccant heat pump (LDHP) is used in the H-M-LDAC system to 2
3 simultaneously cover the heating and cooling requirements of the dilute and concentrated solution streams, respectively. The annual performance of the H-M-LDAC system is investigated in the current study for a small office building located in Miami, FL. Fig. 1. A schematic diagram of the (a) LAMEE, and (b) heat and mass transfer directions in the LAMEE when it operates as a dehumidifier and regenerator. (Abdel-Salam et al. 2014) 2 System Description A schematic diagram for the proposed H-M-LDAC system is presented in Fig. 2. The hot-humid outdoor air passes through the dehumidifier, where the entire latent load and a portion of the sensible load are covered. The return air is sensibly cooled as it passes through the orator of the return air heat pump (RAHP), in order to cover any additional sensible load not covered by the dehumidifier. The dehumidified fresh air is mixed with the sensibly cooled return air, and then the mix is supplied to the itioned space. As the hot and humid fresh air passes through the dehumidifier, it transfers heat and moisture to the desiccant solution stream, and thus the solution leaves the dehumidifier warm and dilute. The desiccant solution should be regenerated before being reused in the dehumidifier, in order to increase its ability to efficiently dehumidify the humid fresh air. Thus, it has to be heated to a high temperature (i.e. 50 o C in the current study), in order to increase its surface vapor pressure to a level which leads to the transfer of moisture from it to the regeneration air stream (i.e. ambient air in this study). The warm and dilute solution leaving the dehumidifier is preheated in a solution-to-solution sensible heat exchanger; then, it is heated up to 50 o C as it passes through the enser of the liquid desiccant heat pump (LDHP). As the hot and dilute desiccant solution passes through the regenerator, it transfers heat and moisture to the regeneration air, and consequently it leaves the regenerator at higher concentration. The hot and concentrated desiccant solution has to be cooled before entering the dehumidifier, in order to decrease its surface vapor pressure to a level which makes it capable of absorbing moisture from the humid fresh air. Thus, it is precooled in the solution-to-solution sensible heat exchanger, and then it is cooled down to 20 o C in the orator of the LDHP. The cool and concentrated desiccant solution enters the dehumidifier in order to dehumidify and precool the hot and humid fresh air. It is worth mentioning that the desiccant solution used in the current study is Lithium Chloride (LiCl). 3
4 As can be seen from Fig. 2, the LDHP can be operated in two modes, as it is operated so that either the enser typically matches with the solution heating requirements (Case A), or the orator load typically matches with the solution cooling requirements (Case B). In Case A, the orator load is higher than the solution cooling requirements, and thus an auxiliary orator is used to cover the orator load. In Case B, the enser load is higher than the solution heating requirements, and thus an auxiliary enser is used to cover the enser load. More details about each operating ition are presented in Section 3.3. Fig. 2. Schematic diagram for the H-M-LDAC system The H-M-LDAC system is controlled in the current study using an ON/OFF control methodology, and it operates at one of three operating modes as follows. Sensible Mode (Modesensible): This operating mode occurs when the indoor humidity ratio is 9.3 g/kg and the indoor air temperature is > 24 o C. In this case, only the RAHP is in operation in order to cool the indoor air down to the set point temperature. 4
5 Latent Mode (Modelatent): This operating mode occurs when the indoor air temperature is 24 o C and the indoor air humidity ratio is > 9.3 g/kg. In this case, only the LDHP is in operation in order to dehumidify the indoor air down to the set point humidity ratio. Total Mode (Modetotal): This operating mode occurs when the indoor air temperature is > 24 o C and the indoor air humidity ratio is > 9.3 g/kg. In this case, both the LDHP and RAHP are in operation in order to cool and dehumidify the indoor air down to the set point temperature and humidity ratio. 3 Modeling Approach The H-M-LDAC system proposed in the current study is annually simulated using the TRNSYS building energy software. The H-M-LDAC system is modelled for a small office building located in Miami, FL. The building model was developed in accordance with the ASHRAE Standards and , and a typical meteorological weather data (TMY) file was used to describe the climate in Miami, FL. A detailed description for the building and weather data can be found in a previous study by the authors (Abdel-Salam and Simonson 2014). The modelling approach followed in this study to evaluate the performance of the H-M-LADC system is presented in the following three Sections. 3.1 Liquid-to-Air Membrane Energy Exchanger (LAMEE) The performance of the LAMEE is evaluated in the current study using an analytical model that was developed by Zhang (2011) for a hollow-fiber LAMEE, and modified by Ge et al. (2013b) in order to be used for a counter-flow flat-plate LAMEE. The analytical model for the counter-flow flat-plate LAMEE was experimentally validated in a previous study by Ge et al. (2014), and its performance was found to be reliable in predicting the performance of the LAMEE. The analytical model is not presented in detail in the current study, and only a flow chart which shows how the performance of the LAMEE is evaluated using the model is presented in Fig. 3. A detailed description for the analytical model is presented in previous studies by the authors (Abdel-Salam and Simonson 2014; Abdel-Salam et al 2013b, 2014; Ge et al. 2014). 3.2 Return Air Heat Pump (RAHP) The effectiveness of the orator/enser (Ɛ/) is calculated using the Ɛ-NTU method, Eq. (1), where the NTU/ is assumed to be 2 (Tu et al., 2014). The orating temperature (T) is calculated as shown in Eq. (3) after determining the operating itions of the return air stream (ṁair, T,in, T,out). The enser used in the RAHP is air cooled, and the ensing temperature (T) is assumed to be 10 o C higher than the ambient air temperature (i.e. ΔT=10 o C). After calculating the orating and ensing temperatures, the compressor power (Wcomp) is calculated, Eq. (5), where the theoretical efficiency (ηth) of the RAHP is assumed to be 55% (Tu et al., 2014). In order to present a complete evaluation for the performance of the RAHP, the fan power (Wfan,) required to circulate the ambient air in the air-cooled enser is calculated, Eq. (6), where the pressure drop in the enser (ΔP) is assumed to be 375 Pa and the efficiency of the fan is assumed to be 60%. The COP of the RAHP (COPRAHP) is then calculated, Eq. (7), where the power of both the compressor and enser s fan are included. NTU / / 1 e (1) air, p,air air,,in air,,out m c T T (2) 5
6 T T W W comp T air,,in m air, c p,air Tamb 10 (4) (5) T th T T P air, fan, (6) c p,air T Tair,,in fan air COP RAHP (7) W W fan, comp (3) Fig. 3. Flow chart for the analytical model used to evaluate the LAMEE s performance. (Abdel- Salam et al. 2014) 3.3 Liquid Desiccant Heat Pump (LDHP) Unlike the RAHP which only provides cooling for the return air stream, the LDHP provides simultaneous heating and cooling for the dilute and concentrated solution streams, respectively. 6
7 The loads of the enser and orator of the LDHP have to be efficiently matched with the cooling and heating solution loads, respectively, in order to avoid either the overheating of dilute solution stream or the overcooling of concentrated solution stream. For this reason, a matching index is defined in the current study in order to show the relation between the thermal loads of the enser and orator of the LDHP, and the heating and cooling energy required by solution streams. The matching index is defined as follows. sol,cool sol,heat HR LDHP (8) where, sol,cool and sol,heat are the cooling and heating energy requirements of the desiccant solution, respectively, is the orator load, and is the enser load. In order to assure that the LDHP is operating at the proper operating mode, the HRLDHP is checked at every time step. A flow chart which shows how the operating mode of the LDHP is determined at every time step is presented in Fig. 4. The next two Sections show how the COPLDHP is evaluated at each operating mode (i.e. Case A or Case B) for the LDHP. = sol,heat Case A Yes HR LDHP 1 No Case B = sol,cool Finish HR LDHP Fig. 4. Flow chart of the operating modes of the LDHP. Case A: If HRLDHP 1, the enser load matches the solution heating requirements and the orator provides larger cooling energy than that required for the concentrated solution cooling. Thus, an auxiliary orator is used in order to reject the additional cooling energy. The required orator and enser loads are calculated using the operating itions of the concentrated and dilute solution streams, Eqs. (9) and (10). The orating temperature is then calculated using Eq. (11), in order to assure that the orating temperature does not exceed the ambient air temperature at any operating ition when the air-cooled auxiliary orator is used. The ensing temperature is then calculated, Eq. (12), followed by the power of the compressor, Eq. (13). The amount of cooling energy which should be rejected from the auxiliary orator is calculated as shown in Eq. (14), and the fan power required to circulate the ambient air through the auxiliary orator is calculated using Eq. (15). m c T T (9),sol sol, sol, p,sol p,sol sol,,in sol,,in sol,,out m c T T (10) sol,,out T,sol Min Tsol,,in,Tamb 10 m sol, cp,sol (11) 7
8 T W comp T sol,,in T th T T m sol, c p,sol (12) (13) W,aux W (14) comp,sol P,aux air,,aux fan,,aux (15),aux cp,air T amb T fan air Case B: If HRLDHP > 1, the heat pump loads will not be matched with the solution heating and cooling requirements under the aforementioned operating ition (i.e. enser meets the solution heating load). Thus, the LDHP is operated so that the orator load matches with the solution cooling requirements and an additional enser will be used in order to meet the ensation requirements in the LDHP. The ensing and orating temperatures are calculated using Eqs. (12) and (16), respectively. The power of the compressor is then calculated, Eq. (17), and the fan power required to circulate the ambient air in the seary enser is evaluated, Eq. (19). T (16) W W comp T,aux sol,,in m T th T T comp sol, c,sol p,sol W (18) P,aux air,,aux fan,,aux (19),auxcp,air T Tamb fan air Eventually, the COP of the LDHP (COPLDHP) is calculated as follows. (17) COP LDHP sol,cool sol,heat (20) W fan,aux, / W comp,ldhp 4 Performance Indices The performance of the H-M-LDAC system is evaluated using the following indices. (1) The annual COPRAHP, which is calculated as shown in Eq. 7, Section 3.2. (2) The annual HRLDHP and COPLDHP which are calculated as shown in Eqs. 8 and 20, respectively, Section 3.3. (3) The annual COP of the H-M-LDAC system (COPH-M-LDAC), which is calculated as follows. 8
9 T lift ( o C) air COPH M LDAC (21) Wcomp,LDHP Wcomp,RAHP Wfans 0.33 where, air is the total (sensible and latent) cooling load of the supply air stream, and Wfans includes the fans power for the supply and exhaust ducts, the air-cooled enser of the RAHP, the auxiliary enser/orator of the LDHP. It is worth mentioning that the electrical-thermal conversion coefficient is assumed to be 0.33 in the current study (Abdel-Salam and Simonson, 2014). 5 Results and Discussions 5.1 Annual Performance of LDHP and RAHP The annual hourly temperature lifts for the RAHP and LDHP are shown in Fig. 5. The temperature lift for the LDHP (Tlift,LDHP) is found to be higher than that for the RAHP (Tlift,RAHP) year round. This is because although the orating temperature for the LDHP (~17 o C) is higher than that for the RAHP (~13 o C), the ensing temperature for the LDHP is significantly higher than the RAHP. This is because the LDHP simultaneously covers the heating and cooling requirements of the desiccant solution, which means that the LDHP is operated at high ensing temperatures in order to heat the diluted desiccant up to 50 o C before being supplied to the regenerator. In addition, it can be seen from Fig. 5 that unlike the Tlift,RAHP which fluctuates depending on the ambient itions, the Tlift,LDHP is almost constant during all operating itions. The fluctuation of the Tlift,RAHP is because the enser of the RAHP is air cooled, which means that the ensing temperature depends on the ambient air temperature. On the other hand, the orating and ensing temperatures of the LDHP are mainly determined based on the desiccant solution set points which are maintained constant, as previously mentioned, except for the startup of the system and the few cool operating hours where the orating temperature is determined based on the ambient temperature as shown in Eq Time (hr) Fig. 5. The annual hourly temperature lifts for the RAHP and LDHP. Fig. 6 shows the annual hourly values and the frequency of occurrence for the COPLDHP and COPRAHP. Although Tlift,RAHP is lower than Tlift,LDHP, it is found that the COPLDHP is higher than the COPRAHP. The COPRAHP lies between in the range of , while the COPLDHP lies in the range of This is expected due to the fact that the LDHP provides simultaneous heating and 9 LDHP RAHP
10 COP COP cooling for the desiccant solution, which means that the LDHP is operated in a more energy efficient manner compared to the RAHP which provides only cooling for the return air. It is found that the ambient air itions have an opposite influence on the COPLDHP compared with the COPRAHP, as can be seen from Fig. 6a. The COPRAHP is found to decrease during the hot summer months, and improves during the mild winter months. This is expected for the RAHP, as the higher the ambient air temperature the higher the ensing temperature, which decreases the COPRAHP. On the other hand, the COPLDHP is found to have an opposite trend, where it improves during the hot summer months and decreases during the mild winter months. a 11 LDHP RAHP b Time (hr) LDHP RAHP Percentage of occupied hours (%) Fig. 6. The (a) annual hourly values and (b) frequency of occurrence for the COPLDHP and COPRAHP. As previously discussed, there are two operating modes for the LDHP (Case A and Case B). It is necessary to track the operating mode of the LDHP in order to assure that the heating and cooling requirements of the desiccant solution are efficiently matched with the enser and orator loads of the LDHP at different operating ition. As can be seen from Fig. 7, it is found that the LDHP operates at Case A operating mode for 95% of the operating hours, and operates at Case B for 5% of the operating hours. In Case A, the solution cooling requirements range from 30% to 100% of the orator load, depending on the operating itions, with an average value of 77%. While in Case B, the enser load ranges from 100% to 130% of the solution heating requirements, depending on the operating itions, with an average value of 106%. It is worth mentioning that this shows a potential for improving the COPLDHP by using the available 10
11 cooling energy when the LDHP operates at Case A to provide a portion of the sensible cooling required for the return air. This is expected to cause an observable improvement in the energy efficiency of the LDHP, and consequently in the energy efficiency of the H-M-LDAC system. This point will be investigated in detail in future work by the authors. 1.4 Case A { sol,cool = 0.3 ~ } Case B { = sol,heat ~ 1.3 sol,heat } HR LDHP Time (hr) Fig. 7. The hourly annual heat ratio between the solution heating and cooling requirements, and the orator and enser loads of the LDHP (HRLDHP). 5.2 Annual Performance of H-M-LDAC System After evaluating the performance of the LDHP and RAHP, the performance of the whole system is analyzed in the current Section. Fig. 8 shows the annual hourly values and frequency of occurrence for the COP of the H-M-LDAC system (COPH-M-LDAC). It is found that the COPH-M- LDAC is not maintained within specific range year around. The H-M-LDAC system operates for approximately 15%, 21% and 63% of the operating hours at Modesensible, Modelatent and Modetotal, respectively (i.e. the three operating modes are defined in Section 2). It is clear from Fig. 8 that the operating mode has a significant impact on the COPH-M-LDAC, where the COPH-M-LDAC is the lowest during Modelatent and the highest during Modesensible. Since the COPH-M-LDAC is dependent on both the outdoor air itions, and the cooling and dehumidification requirements of the itioned space, the COPH-M-LDAC is plotted versus the cooling load in order to have a better understanding of the performance of the H-M-LDAC system, see Fig. 9. It can be seen that the COPH-M-LDAC is strongly correlated with the cooling load when the H-M-LDAC system operates at either Modelatent or Modetotal, with larger slope during Modelatent compared with Modetotal. It can be seen that the COPH-M-LDAC is high during Modesensible which is believed to be due to the following. The H-M-LDAC system is controlled using an ON/OFF control methodology, as previously mentioned. During Modesensible, the LDHP is turned off; however, the desiccant solution stream might still cool and dehumidify the fresh air stream for a few time steps, depending on the operating itions, but at lower capacity due to the quick variations that would occur in the dilute and concentrated desiccant solution streams when the LDHP is turned off. Thus, although there is no energy consumed by the LDHP during Modesensible, the desiccant cycle causes a cooling effect for the fresh air stream, which when added to the sensible cooling caused by the RAHP will result in high COPH-M-LDAC. 11
12 COP COP COP a b Time (hr) Sen Mode sensible Lat Mode latent Percentage of operating hours (%) Fig. 8. The (a) annual hourly values and (b) frequency of occurrence for the COPH-M-LDAC. Tot Mode total Lat Mode latent Sen Mode sensible Tot Mode total Cooling load (MJ/hr) Fig. 9. The annual hourly COPH-M-LDAC versus the annual hourly cooling loads. 5.3 Sensitivity Analysis of LDHP and RAHP Parameters In this Section, the influences of the NTU/, ΔP/, ηth and ΔT on the COPH-M-LDAC are evaluated. Each of the investigated parameters is varied by up to ±20% of its base value in ±5% intervals, and the equivalent percent change in the COPH-M-LDAC is evaluated. Fig. 10 shows 12
13 Percent change in COP (%) the variation of the COPH-M-LDAC due to the different variations performed in the NTU/, ΔP/, ηth and ΔT. It is found that ΔT has the lowest influence on the COPH-M-LDAC, while ηth has the largest influence. It is clear that the assumptions used to evaluate the performance of the heat pumps have considerable influences on the results. Thus, future work will include developing more advanced heat pump model Percent change (%) Fig. 10. The influence of the NTU/, ΔP/, ηth and ΔT on the COPH-M-LDAC. 6 Conclusions The annual COP of a hybrid membrane liquid desiccant air itioning (H-M-LDAC) system was evaluated in this study using the TRNSYS building energy simulation software for a small office building located in Miami, FL. The main advantages of the proposed H-M-LDAC system are: (1) the elimination of the desiccant droplets carryover problem through the use of liquid-toair membrane energy exchangers (LAMEEs) as the dehumidifier and regenerator, and (2) the simultaneous heating and cooling of the desiccant solution using a hybrid liquid desiccant heat pump (LDHP). It is found that the annual hourly COP of the LDHP ranges between 4.2 and 10.6, with an annual average value of 7.8. The annual hourly COP of the return air heat pump (RAHP) ranges between 3.8 and 6.8, with an annual average value of 4.5. A new matching index was defined for the hybrid LDHP in this study, where it was found that there is auxiliary cooling energy which is provided by the LDHP for 95% of the operating hours. This is promising, because considerable reductions is expected to be achieved in the return air cooling requirements if the auxiliary cooling energy provided by the LDHP is used to precool the return air before it enters the RAHP. Based on the evaluated COPs for the RAHP and LDHP, the average annual COP of the H-M- LDAC system is found to be 1. The COP of the H-M-LDAC system is found to be strongly influenced by the cooling loads and the mode of operation of the system. The influence of four heat pump parameters was investigated on the COP of the H-M-LDAC system, where the theoretical efficiency of the heat pump is found to be the most influential parameter. The authors strongly recommend that future research on LDAC systems focus on two main points. First, the development of novel itioners (dehumidifier/regenerator), in order to 13 ΔP / dp NTU dt Eff NTU / ΔT η th
14 improve the performance of LDAC systems, and eliminate the problems associated with the use of available itioners. Se, since LDAC system includes several components, it is important to keep investigating the performance of novel energy efficient LDAC systems configurations, which improves the energy efficiency for these systems. Acknowledgement The authors acknowledge the financial support of the Natural Sciences and Engineering Research Council of Canada (NSERC) and the Smart Net-Zero Energy Buildings strategic Research Network (SNEBRN). Nomenclature P pressure drop (Pa) COP coefficient of performance cp specific heat capacity(j/(kg.k) ) HR matching index ṁ mass flow rate (kg/s) NTU number of heat transfer units rate of energy consumption (J/s) T temperature ( o C) Greek letters ηth ε ρ Subscripts amb aux cool heat in out sol Abbreviations H-M-LDAC LAMEE LDAC LDHP RAHP thermal efficiency of heat pump effectiveness density ambient air auxiliary enser cooling orator heating inlet outlet desiccant solution hybrid membrane liquid desiccant air itioning liquid liquid desiccant air itioning liquid desiccant heat pump return air heat pump References Abdel-Salam, A.H. & Simonson, C.J., Annual evaluation of technical, environmental and economic performance of a membrane liquid desiccant air itioning system with/without ERV, Applied Energy 116:
15 Abdel-Salam, A.H., Ge, G. & Simonson, C.J., Thermo-economic performance of a solar membrane liquid desiccant air itioning, Solar Energy, 102: Abdel-Salam, M.R.H., Ge, G., Fauchoux, M., Simonson, C.J. & Besant R.W., 2013a. State-ofthe-art in liquid-to-air membrane energy exchangers (LAMEEs): A comprehensive review, submitted to Renewable and Sustainable Energy Reviews. Abdel-Salam, A.H., Ge, G. & Simonson, C.J., 2013b. Performance analysis of a membrane liquid desiccant air-itioning system, Energy and Buildings 62: Abdel-Salam, A.H., Ge, G., Fauchoux, M.T. & Simonson, C.J., 2013c. Annual energy simulation of a novel membrane liquid desiccant air itioning system in an office building located in a hot humid climate, Proceedings of the 5th International Conference on Solar Air-Conditioning, Bad Krozingen, Black Forest, Germany. Abdel-Salam, A.H., Ge, G., Fauchoux, M.T., Ghadiri Moghaddam, D. & Simonson, C.J., 2013d. Effectiveness evaluation of a liquid-to-air membrane energy exchangers as dehumidifier/regenerator in a liquid desiccant air-itioning system, Proceedings of the 24th Canadian Conference of Applied Mechanics (CANCAM 2013), Saskatoon, SK, Canada. Crofoot, L., Experimental evaluation and modeling of a solar liquid desiccant air itioner, MSc Thesis, ueen's University, Kingston, ON. Crofoot, L. & Harrison, S., Performance evaluation of a liquid desiccant solar air itioning system. Energy Procedia 30, Davies, P.A., A solar cooling system for greenhouse food production in hot climates. Solar Energy 79, Ge, G., Abdel-Salam, M.R.H., Besant, R.W. & Simonson, C.J., 2013a. Research and applications of liquid-to-air membrane energy exchangers in building HVAC systems at University of Saskatchewan: A review. Renewable and Sustainable Energy Reviews 26, Ge, G., Ghadiri Moghaddam, D., Namvar, R., Simonson, C. & Besant, R., 2013b. Analytical model based performance evaluation, sizing and coupling flow optimization of liquid desiccant run-around membrane energy exchanger system. Energy and Buildings 62, Ge, G., Ghadiri Moghaddam, D., Abdel-Salam, A.H., Simonson, C.J. & Besant, R.W., Experimental and analytical study of liquid-to-air membrane energy exchangers (LAMEEs) as active dehumidifier and regenerator, International Journal of Heat and Mass Transfer 68: Gommed, K. & Grossman, G., Experimental investigation of a liquid desiccant system for solar cooling and dehumidification. Solar Energy 81, Jones, B.M., Field evaluation and analysis of a liquid desiccant air handling system, MSc Thesis, ueen's University, Kingston, ON. Li, Y., Lu, L. & Yang, H., Energy and economic performance analysis of an open cycle solar desiccant dehumidification air-itioning system for application in Hong Kong, Solar Energy 84, Lowenstein, A., Slayzak, S. & Kozubal, E., A zero carryover liquid-desiccant air itioner for solar applications, Proceedings of ISEC 2006 ASME international solar energy conference, Denver, USA. Lowenstein, A., Low-flow internally-cooled liquid-desiccant absorber. US patent # , US patent and trademark office. 15
16 Mesquita, L.C Analysis of a flat-plate liquid-desiccant dehumidifier and regenerator. PhD Thesis, ueen's University, Kingston, ON. Tu, R., Liu, X.-H. & Jiang, Y., Performance analysis of a two-stage desiccant cooling system, Applied Energy 113, Zhang, L.-Z., An analytical solution to heat and mass transfer in hollow fiber membrane contactors for liquid desiccant air dehumidification. ASME Journal of Heat Transfer 133,
Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems
Abstract Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems M. Jaradat, R. Heinzen, U. Jordan, K. Vajen Kassel University (Germany), Institute
Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning
A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications
A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications Mustafa Jaradat, Klaus Vajen, Ulrike Jordan Institut für Thermische Energietechnik, Universität Kassel, 34125 Kassel,
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
Energy and Buildings
Energy and Buildings 42 (2010) 1833 1840 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild Membrane heat exchanger in HVAC energy recovery
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *
Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
Performance Test of Solar Assisted Solid Desiccant Dryer
Performance Test of Solar Assisted Solid Desiccant Dryer S. MISHA 1,2,*, S. MAT 1, M. H. RUSLAN 1, K. SOPIAN 1, E. SALLEH 1, M. A. M. ROSLI 1 1 Solar Energy Research Institute, Universiti Kebangsaan Malaysia,
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS by Dr. Bing Chen and Prof. John Bonsell Passive Solar Research Group University of Nebraska-Lincoln Omaha campus and Richard
EXPERIMENTAL EVALUATION AND MODELING OF A SOLAR LIQUID DESICCANT AIR CONDITIONER
EXPERIMENTAL EVALUATION AND MODELING OF A SOLAR LIQUID DESICCANT AIR CONDITIONER by Lisa Crofoot A thesis submitted to the Department of Mechanical and Materials Engineering In conformity with the requirements
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air 0 Optimal Air Quality: Critical to Hotels Provides comfortable environment for guests no overcooling Protects building, carpets
Research on the Air Conditioning Water Heater System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric
A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING
A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING John Archibald American Solar Roofing Company 8703 Chippendale Court Annandale, Va. 22003 e-mail: [email protected]
Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the
Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture
Thermochemical Storage for Air-Conditioning using Open Cycle Liquid Desiccant Technology
Thermochemical Storage for Air-Conditioning using Open Cycle Liquid Desiccant Technology E. Laevemann, M. Peltzer, A. Hublitz, A. Kroenauer, U. Raab, A. Hauer Bavarian Center for Applied Energy Research
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Low-Flow Liquid Desiccant Air-Conditioning: Demonstrated Performance and Cost Implications
Low-Flow Liquid Desiccant Air-Conditioning: Demonstrated Performance and Cost Implications Eric Kozubal, Lesley Herrmann, and Michael Deru National Renewable Energy Laboratory Jordan Clark University of
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Building Re-Tuning Training Guide: AHU Heating and Cooling Control
Building Re-Tuning Training Guide: AHU Heating and Cooling Control Summary The purpose of the air-handling unit (AHU) heating and cooling control guide is to show, through examples of good and bad operations,
saving energy in comfort Factsheet Recair Enthalpy
saving energy in comfort Factsheet Recair Enthalpy Introduction Enthalpy Exchanger The enthalpy exchanger is able to transfer both sensible heat and latent heat (moisture) from the cooled to the heated
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
Whole House Dehumidification for Occupant Comfort and Energy Savings
Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009
How To Control Humidity With A Humidifier
Control of ventilation and air conditioning plants Building Technologies s Contents.Temperature control in air treatment systems 2. Humidity controls 3. Recirculated air mixing. Internal heat sources 6.2
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
Absolute and relative humidity Precise and comfort air-conditioning
Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No
THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University
THE PSYCHROMETRIC CHART: Theory and Application Perry Peralta NC State University PSYCHROMETRIC CHART Identify parts of the chart Determine moist air properties Use chart to analyze processes involving
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015
Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed
Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle
INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication
Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov. 2003 to Mar. 15, 2004.
Proceedings World Geothermal Congress 2005 Antalya, Turkey, 24-29 April 2005 A Case Study of Ground Source Heat Pump System in China Jun Zhao, Chuanshan Dai, Xinguo Li, Qiang Zhu and Lixin Li College of
PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING
PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING LI CHUNYING DOCTOR OF PHILOSOPHY CITY UNIVERSITY OF HONG KONG FEBRUARY 2012 CITY UNIVERSITY OF HONG KONG 香 港 城 市 大 學 Performance Evaluation of Water-flow
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
How To Get A Passive House
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product
Testing methods applicable to refrigeration components and systems
Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"
Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A" Takahiro OUE *1, Kazuto OKADA *1 *1 Refrigeration System & Energy Dept., Compressor Div., Machinery Business Kobe Steel has developed an air-sourced
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine
A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine G Vicatos J Gryzagoridis S Wang Department of Mechanical Engineering,
SOLAR DESSICANT COOLING EXAMPLE OF APPLICATION TO A LOW ENERGY BUILDING
SOLAR DESSICANT COOLING EXAMPLE OF APPLICATION TO A LOW ENERGY BUILDING Thibaut Vitte, Monika Woloszyn, Jean Brau CETHIL, CNRS UMR 5008, UCBL, INSA, Lyon, France ABSTRACT This article presents the study
SIMULATION OF RADIANT COOLING PERFORMANCE WITH
SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE
newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer
engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
How Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
Energy savings in commercial refrigeration. Low pressure control
Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
White Paper: Free Cooling and the Efficiency of your Data Centre
AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...
10% 50% 20% Air-conditioning
AIR-CON SYSTEM EFFICIENCY PRIMER: A SUMMARY Background Air conditioning is widely used in Singapore with its hot and humid conditions. In our hot and humid climate, the energy consumed by Heating, Ventilation
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
Air-Conditioning Buying Guide
Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Solar chilled drinking water sourced from thin air: modelling and simulation of a solar powered atmospheric water generator
20th International Congress on Modelling and Simulation, Adelaide, Australia, 1 6 December 2013 www.mssanz.org.au/modsim2013 Solar chilled drinking water sourced from thin air: modelling and simulation
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!
Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST
FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation
A heat pump system with a latent heat storage utilizing seawater installed in an aquarium
Energy and Buildings xxx (2005) xxx xxx www.elsevier.com/locate/enbuild A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Satoru Okamoto * Department of Mathematics
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012
Air Side Economizers and Energy Recovery - Improvements and New Regulations Richard Lord 09-20-2012 Introduction For commercial buildings the use of outside air for cooling and ventilation is an important
Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling
Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle
Hospital Application Guide. Cost-effective climate control for hospitals
Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing
ALONE. small scale solar cooling device Project No TREN FP7EN 218952. Project No TREN/FP7EN/218952 ALONE. small scale solar cooling device
Project No TREN/FP7EN/218952 ALONE small scale solar cooling device Collaborative Project Small or Medium-scale Focused Research Project DELIVERABLE D5.2 Start date of the project: October 2008, Duration:
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA
Optimization of combined heating and cooling in Supermarkets
Optimization of combined heating and cooling in Supermarkets Funder-Kristensen T. 1 ; Fösel G. 2 and Bjerg P. 3 1 Ph.d. Head of Public & Industry Affairs, Danfoss, Nordborg, 6430, Denmark. 2 Dipl.-Ing.
Condensing Economizers Workshop Enbridge Gas, Toronto. MENEX Boiler Plant Heat Recovery Technologies. Prepared by: Jozo Martinovic, M A Sc, P Eng
Condensing Economizers Workshop Enbridge Gas, Toronto MENEX Boiler Plant Heat Recovery Technologies Prepared by: Jozo Martinovic, M A Sc, P Eng MENEX Innovative Solutions May 15, 2008 MENEX INC. 683 Louis
SustainE(Sustainable Energy)
SustainE(Sustainable Energy) Air Source Heat Pump Water to water Heat Pump Total Energy Heat Pump/Chiller Integrated Heat Pump AHU Swimming Pool Heat Pump Remote Condenser / Radiator H e n n e x S u s
New Trends in the Field of Automobile Air Conditioning
New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic
Building HVAC Load Profiling Using EnergyPlus
Building HVAC Load Profiling Using EnergyPlus Dong Wang School of EEE Nanyang Technological University Singapore Email: [email protected] Abhisek Ukil, Senior Member, IEEE School of EEE Nanyang Technological
Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling
Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling Yefu Wang1, Xiaorui Wang1,2, and Yanwei Zhang1 ABSTRACT The Ohio State University 14 1 1 8 6 4 9 8 Time (1 minuts) 7 6 4 3
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Rittal White Paper 305: Selecting Air Conditioners for Industrial Enclosures By: Judith Koetzsch Mark Corcoran, Editor
Rittal White Paper 305: Selecting Air Conditioners for Industrial Enclosures By: Judith Koetzsch Mark Corcoran, Editor Executive Summary Choosing the right air conditioners for enclosures can have a tremendous
Dedicated Outdoor Air-Dual Wheel System Control Requirements
4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
Transient Analysis of Integrated Shiraz Hybrid Solar Thermal Power Plant Iman Niknia 1, Mahmood Yaghoubi 1, 2
Transient Analysis of Integrated Shiraz Hybrid Solar Thermal Power Plant Iman Niknia 1, Mahmood Yaghoubi 1, 2 1 School of Mechanical Engineering, Shiraz University, Shiraz, Iran 1, 2 Shiraz University,