ekorrp PROTECTION, METERING AND CONTROL UNITS

Size: px
Start display at page:

Download "ekorrp PROTECTION, METERING AND CONTROL UNITS"

Transcription

1 General Instructions PROTECTION, METERING AND CONTROL UNITS LIB Transformer Substations Secondary Distribution Switchgear Primary Distribution Switchgear Protection and Automation Low Voltage Boards Distribution Transformers

2 Legal Deposit: 1457/2012 CAUTION! When MV equipment is operating, certain components are live, other parts may be in movement and some may reach high temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks. In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on the following criteria: Elimination of hazards wherever possible. Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are incorporated in the equipment. Communication about remaining risks to facilitate the design of operating procedures which prevent such risks, training for the personnel in charge of the equipment, and the use of suitable personal protection equipment. Use of recyclable materials and establishment of procedures for the disposal of equipment and components so that once the end of their service lives is reached, they are duly processed in accordance, as far as possible, with the environmental restrictions established by the competent authorities. Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of the forthcoming IEC standard It must therefore only be operated by appropriately qualified and supervised personnel, in accordance with the requirements of standard EN on the safety of electrical installations and standard EN on activities in or near electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this manual and in other recommendations of a more general nature which are applicable to the situation according to current legislation. The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but also on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically: The equipment must be handled and transported appropriately from the factory to the place of installation. All intermediate storage should occur in conditions which do not alter or damage the characteristics of the equipment or its essential components. Service conditions must be compatible with the equipment rating. The equipment must be operated strictly in accordance with the instructions given in the manual, and the applicable operating and safety principles must be clearly understood. Maintenance should be performed properly, taking into account the actual service and environmental conditions in the place of installation. The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts. Guarantee The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this equipment and its repair by the user shall constitute a violation of the guarantee. Registered Trademarks and Copyrights All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this manual belongs to the manufacturer. In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are subject to change without prior notification. The validity of these characteristics, as well as the availability of components, are subject to confirmation by Ormazabal s Technical - Commercial Department.

3 GENERAL INSTRUCTIONS FOR CONTENTS 1. GENERAL DESCRIPTION GENERAL FUNCTIONAL CHARACTERISTICS PARTS OF THE UNIT COMMUNICATIONS AND PROGRAMMING SOFTWARE APPLICATIONS TRANSFORMER PROTECTION GENERAL PROTECTION LINE PROTECTION PROTECTION FUNCTIONS OVERCURRENT THERMOMETER (EXTERNAL TRIP) EARTH ULTRASENSITIVE DEVICE METERING FUNCTIONS CURRENT SENSORS CURRENT SENSORS TECHNICAL CHARACTERISTICS RATED VALUES MECHANICAL DESIGN INSULATION TESTS ELECTROMAGNETIC COMPATIBILITY CLIMATIC TESTS MECHANICAL TESTS POWER TESTS CE CONFORMITY PROTECTION, METERING AND CONTROL MODELS DESCRIPTION OF MODELS vs. FUNCTIONS RELAY CONFIGURATOR T UNITS G UNITS Page 3 of 84

4 GENERAL INSTRUCTIONS FOR IG-159-GB SETTING AND HANDLING MENUS KEYPAD AND ALPHANUMERIC DISPLAY DISPLAY PARAMETER SETTING TRIP RECOGNITION ERROR CODES MENU MAP (QUICK ACCESS) MODBUS PROTOCOL FOR RANGE UNITS READ / WRITE FUNCTIONS PASSWORD-PROTECTED REGISTER WRITING CRC GENERATION REGISTER MAP ANNEX A ANNEX B Page 4 of 84

5 GENERAL INSTRUCTIONS FOR 1. GENERAL DESCRIPTION The range of protection, metering and control units brings together an entire family of different equipment, which depending on the model, may incorporate protection functions as well as other functions such as local control, remote control, electrical parameter metering, automation, etc., related to the current and future automation, control and protection needs of Transformer and Switching Substations. Its use in Ormazabal s CGMCOSMOS, CGM-CGC and CGM.3 cubicle systems allows the configuration of customised products for meeting the diverse needs of the different installations. The protection, metering and control units have been designed to meet the national and international standard requirements and recommendations that are applied to each of the parts that make up the unit: EN 60255, EN 61000, EN , EN 60068, EN 60044, IEC 60255, IEC 61000, IEC , IEC 60068, IEC Page 5 of 84

6 GENERAL INSTRUCTIONS FOR IG-159-GB Designed to be integrated in a cubicle, the units also provide the following advantages over conventional devices: Reduction in handling of interconnections when installing the cubicle. The only connection required is limited to MV cables. Minimisation of the need to install control boxes on the cubicles. Avoidance of wiring and installation errors; minimisation of commissioning time. All the units are factory installed, adjusted and checked; each piece of equipment (relay + control + sensors) also undergoes a comprehensive check before being installed. The final unit tests are carried out once the unit is incorporated in the cubicle before delivery. They protect a broad power range with the same model (e.g.: G from 160 kva up to 15 MVA, in CGMCOSMOS system cubicles) GENERAL FUNCTIONAL CHARACTERISTICS All the relays of the units include a microprocessor for processing the signals from the metering sensors. They process current metering by eradicating the influence of transient phenomena and calculate the magnitudes needed for to carry out protection functions. In addition, the efficient electrical metering values, which provide the instantaneous value of these installation parameters, are determined. They are equipped with keypad for local display, setup and operation of the unit, as well as communication ports to handle these functions from a computer, whether locally or remotely. A user-friendly design has been employed, so that the use of the various menus is intuitive. The current is measured by means of several current sensors with a high transformation ratio, making it possible for the same equipment to detect a wide range of power levels. These transformers or current sensors maintain the accuracy class in all of their rated range. Page 6 of 84

7 GENERAL INSTRUCTIONS FOR The unit contains an events log where all of the latest trips made by the protection functions are registered. In addition, the total number of operations is saved as well as the unit's settings parameters. The local interface uses menus to provide the instantaneous values of the current metering for each phase and zero-sequence current, as well as the setting parameters, trip motives, etc. They can also be accessed via the communication ports. From a maintenance perspective, the units have a series of features that reduce the time and the possibility of errors in the test and service restoration tasks. The main features include some toroidal-core current transformers with larger diameters and test connections; accessible and disconnectable terminal blocks for tests using current injection; and built-in test contacts, even in the basic models PARTS OF THE UNIT The parts that form the protection, metering and control unit include the electronic relay, current sensors, power supply and test board, selfpowered toruses (only for selfpowered models) and the bistable trigger. Page 7 of 84

8 GENERAL INSTRUCTIONS FOR IG-159-GB Figure 1.2: Example of T unit installation in fused protection cubicles Page 8 of 84

9 GENERAL INSTRUCTIONS FOR Electronic Relay The electronic relay has keys and a display to set and view the protection, metering and control parameters. It includes a seal on the SET key to ensure that once the settings have been made they cannot be changed unless the seal is broken. The protection trips are registered on the display with the following parameters: reason for tripping, fault current value, tripping time and the time and date the event occurred. Errors in the unit, such as a switch failure, incorrect thermometer connection, low battery, etc., are also shown permanently. The 'On' LED is activated when the equipment receives power from an external source or the self-powered transformers. In this situation, the unit is operational to perform the protection functions. If the 'On' LED is not activated, only the unit's parameters can be viewed and/or adjusted (function exclusively assigned to the relay's internal battery). The current analog signals are conditioned internally by small and very accurate transformers that isolate the electronic circuits from the rest of the installation. The equipment has two communication ports, one on the front used for local configuration (RS232), and another one on the rear used for remote control (RS485). The standard communication protocol for all models is MODBUS. Others may be used depending on the application Current Sensors The current sensors are toroidal-core current transformers with a 300/1 A or 1000/1 A ratio, depending on the models. Their range of action is the same as the switchgear where they are installed. They are factory-installed in the cubicle bushings, which significantly simplifies the on-site assembly and connection. This way, once the MV cables are connected to the cubicle, the installation protection is operational. There are no sensor installation errors, due to earthing grids, polarities, etc. since they are previously installed and tested at the factory. Bushing Current sensors The inner diameter of the toroidal-core current transformers is 82 mm, which means they can be used in cables of up to 400 mm 2 without any problems for performing maintenance testing afterwards. If the equipment is selfpowered, the toroidal transformers are equipped with some anchorage points to place them in the same area as the metering transformers, thus forming a single, Page 9 of 84

10 GENERAL INSTRUCTIONS FOR IG-159-GB compact block. These transformers supply 1 W when the primary current is 5 A. This power is enough to allow the units to function correctly. All the current sensors have an integrated protection against the opening of secondary circuits, which prevents overvoltages Power Supply and Test Board The selfpowered equipment's power supply board prepares the selfpowered transformers' signal and converts it into a DC signal to safely power the equipment. The transformers permanently feed power from 5 to 630 primary amps to the board. It also has a 230 V ac input with 10 kv level of insulation. This input is for direct connection to the Transformer Substation's LVB. The power supply board of models with auxiliary power supply has an input for connecting both the AC (24 to 110 V ac ) and DC (24 to 125 V dc ) power supply. The board prepares the signal, converting it into a DC signal suitable for safely powering the equipment. Furthermore, both types of board have a built-in protection trip test circuit as well as connectors for carrying out current injection functional tests during maintenance and checking operations. The units also have a protection device for absorbing the excess energy produced by the transformers when there are short-circuits up to 20 ka Bistable trigger The bistable trigger is an electromechanical actuator that is integrated into the switch driving mechanism. This trigger acts upon the switch when there is a protection trip. It is characterised by the low actuation power it requires for tripping. This energy is received in the form of pulses lasting 50 ms and with an amplitude of 12 V. When there is a fault, these pulses are repeated every 400 ms to ensure that the switch opens. Page 10 of 84

11 GENERAL INSTRUCTIONS FOR 1.3. COMMUNICATIONS AND PROGRAMMING SOFTWARE All the units have two serial communication ports. The standard RS232 front port is used to set the local parameters with the ekorsoft program [1]. At the rear, there is an RS485 port which is used for remote control. The standard communication protocol implemented in all equipment is MODBUS-RTU (binary) transmission mode, although other specific protocols can be implemented depending on the application. This protocol has the advantage of greater information density than other modes, resulting in a higher transmission rate for the same communication speed. Each message must be transmitted as a continuous string and the silences are used to detect the end of the message. [1] For more information about the ekorsoft program, consult Ormazabal s IG-155 document. Page 11 of 84

12 GENERAL INSTRUCTIONS FOR IG-159-GB The ekorsoft setup program has three main operating modes: Display: indicates the unit status, including electrical measurements, current settings, date and time. User Settings: protection parameter change is enabled. Event Log: the parameters of the final and penultimate trip are shown as well as the total number of trips made by the protection unit. Minimum system requirements for installing and using the ekorsoft software: Processor: Pentium II RAM: 32 Mb Operating System: MS WINDOWS CD-ROM / DVD RS-232 serial port Page 12 of 84

13 GENERAL INSTRUCTIONS FOR 2. APPLICATIONS 2.1. TRANSFORMER PROTECTION The distribution transformers require various protection functions. Their selection depends primarily on the power and level of responsibility they have in the installation. As an example, the protection functions that must be implemented to protect distribution transformers with a power rating between 160 kva and 2 MVA are the following: 50 Instantaneous phase overcurrent. Protects against shortcircuits between phases in the primary circuit, or high value short-circuit currents between phases on the secondary side. This function is performed by the fuses when the protection cubicle does not include a circuit-breaker. 51 Phase overload. Protects against excessive overloads, which can deteriorate the transformer, or against short-circuits in several turns of the primary windings. 50N Instantaneous earth fault. Protects against phase to earth short-circuits or secondary winding short-circuits, from the primary interconnections and windings. 51N Earth Leakage. Protects against highly resistive faults from the primary to earth or to the secondary. 49T Thermometer. Protects against excessive transformer temperature. Protection units that include the above mentioned functions: System CGMCOSMOS Systems CGM-CGC / CGM.3 Unit Type of cubicle Power ranges to protect Power ranges to protect T Fuse-combination switch 50 kva kva 50 kva kva G Circuit-breaker 50 kva...15 MVA 50 kva...25 MVA See tables and Page 13 of 84

14 GENERAL INSTRUCTIONS FOR IG-159-GB GENERAL PROTECTION The client supply installations require general protection to ensure that an installation is disconnected from the rest of the network in the event of a fault. In this way, the Utility's supply line will remain energised and other clients will remain unaffected. It also protects the client's installation by disconnecting it from the power source in the event of a fault. In this type of protection, all the faults detected in the substation's main circuit breaker should be simultaneously detected in the transformer substations so that they can be cleared before the line trips (protection selectivity). 50 Instantaneous phase overcurrent. Protects against short-circuits between phases. 51 Phase overload. Protects against excessive overloads, which can deteriorate the installation. It is also used as a limiting device to control the supply's maximum power. 50N Instantaneous earth fault. Protects against phase-to-earth short-circuits. 51N Earth leakage. Protects against highly resistive faults between phase and earth. The following protection units provide the above-mentioned functions: System CGMCOSMOS Systems CGM-CGC / CGM.3 Unit Type of cubicle Power ranges to protect Power ranges to protect T Fuse-combination switch 50 kva kva 50 kva kva G Circuit-breaker 50 kva...15 MVA 50 kva...25 MVA See tables and Page 14 of 84

15 GENERAL INSTRUCTIONS FOR 2.3. LINE PROTECTION The purpose of the line protection is to isolate this part of the network in case of fault, without it affecting the rest of the lines. Generally, it covers any fault that originates between the Substation, or Switching Substation, and the consumption points. The types of fault that occur in these areas of the network primarily depend on the nature of the line, overhead line or cable and the neutral used. In networks with overhead lines, most faults are transitory. Hence, many line reclosings are effective. On the other hand, in case of phase-to-earth faults in overhead lines, when the ground resistance is very high, the zero-sequence fault currents have a very low value In these cases, an ultrasensitive neutral current detection is required. The underground cables have earth coupling capacities, which causes the single phase faults to include capacitive currents. This phenomenon makes detection difficult in isolated or resonant earthed neutral networks and thus requires the use of the directional function. Line protection is mainly accomplished by the following functions: 50 Instantaneous phase overcurrent. Protects against short-circuits between phases. 51 Phase overload. Protects against excessive overloads, which can deteriorate the installation. 50N Instantaneous earth fault. Protects against phase-to-earth short-circuits. 51N Earth leakage. Protects against highly resistive faults between phase and earth. 50Ns Ultrasensitive earth instantaneous overcurrent. Protects against phase to earth short-circuits of very low value. 51Ns Ultrasensitive earth leakage protection. Protects against highly resistive faults between phase and earth of very low value. Unit that includes the above mentioned functions: CGMCOSMOS / CGM-CGC / CGM.3 systems Unit Type of cubicle Maximum rated current G Circuit-breaker 630 A Page 15 of 84

16 GENERAL INSTRUCTIONS FOR IG-159-GB PROTECTION FUNCTIONS 3.1. OVERCURRENT The units have an overcurrent function for each one of the phases (3 x 50-51) and, depending on the model, they may have another one for earth (50N-51N). The implemented protection curves are the ones listed in standard IEC Overcurrent functions that can be performed depending on the model: Overload multicurve protection for phases (51). Protection of phase-to-earth multicurve faults (51N). Short-circuit protection (instantaneous) at a defined time between phases (50). Short-circuit protection (instantaneous) at a defined time between phase and earth (50N). Meaning of the curve parameters for phase settings: t(s) Theoretical tripping time for a fault which evolves with a constant current value. I Actual current flowing through the phase with the largest amplitude. I n Rated setting current. I> Withstand overload increment. K Curve factor. I>> Short-circuit current factor (instantaneous). T>> Short-circuit delay time (instantaneous). Pick-up current value of NI, VI, and EI curves = 1.1 x I n x I> Pick-up current value of DT curve = 1.0 x I n x I> Instantaneous pick-up current value = I n x I> x I>> In the case of earth settings, the parameters are similar to the phase settings. Each of them is described below. t o (s) Theoretical tripping time for an earth fault which evolves with a constant current value I 0. I o Actual current flowing to earth. I n Rated phase setting current. I o > Withstand earth leakage factor (phase). K o Curve factor. I o >> Short-circuit current factor (instantaneous). T o >> Short-circuit delay time (instantaneous). Pick-up current value of NI, VI, and EI curves = 1,1 x I n x I o > Pick-up current value of DT curve = 1,0 x I n x I o > Instantaneous pick-up current value = I n x I o > x I o >> Page 16 of 84

17 GENERAL INSTRUCTIONS FOR Page 17 of 84

18 GENERAL INSTRUCTIONS FOR IG-159-GB Page 18 of 84

19 84 GENERAL INSTRUCTIONS FOR 3.2. THERMOMETER (EXTERNAL TRIP) The equipment has an input for connecting volt-free contacts and tripping the switch. This input is protected against erroneous connections (e.g. 230 V ac ) showing an error code on the display when this anomaly occurs. The switch trips when the volt-free contact is closed for at least 200 ms. This prevents untimely tripping due to external disturbances. External tripping protection is disabled when all of the overcurrent protection functions are disabled (for firmware version 18 or later). In this situation, the relay will not trip the switch but a flashing arrow will appear at the top of the display screen to show that the external trip contact is closed (see section 8.4). The purpose of this function is to protect the transformers' maximum temperature. The trip input is associated to contact of the thermometer which measures the oil's temperature and when the maximum set value is reached, its associated contact closes and the switch trips. Unlike conventional coils, it has the advantage of not having low-voltage network connections with the consequent overvoltages generated in the control circuits. This trip input can also be associated to output contacts of remote control terminals, alarms and auxiliary relays responsible for opening the switch EARTH ULTRASENSITIVE DEVICE This protection corresponds to a particular type of overcurrent protections. It is primarily used in networks with isolated or resonant earthed neutral, where the phase-to-earth fault current value depends on the system cable capacity value and on the point in which the fault occurs. Generally, in Medium Voltage private installations with short cable stretches, simply determine a minimum zerosequence current threshold at which the protection must trip. 0-sequence toroidal transformer Page 19 of 84

20 GENERAL INSTRUCTIONS FOR IG-159-GB The current flowing to earth is detected using a toroidal-core current transformer which covers the three phases. In this way, the metering is independent from the phase current, thus avoiding errors in the phase metering transformers. In general, this type of protection must be used when the set earth current is less than 10% of the rated phase current (for example: for a rated phase current of 400 A with earth faults below 40 A). On the other hand, in the lines, whose cable stretches are usually long, it is necessary to identify the fault direction. Otherwise, trips can occur due to capacitive currents from other lines, when there is not any fault in the line. The available curves are: normally inverse (NI), very inverse (VI), extremely inverse (EI) and defined time (DT). The setting parameters are the same as in the earth faults of the overcurrent functions (section 3.1 Overcurrent), with the exception that factor I o > is replaced with the value directly in amps I g. This way, this parameter can be set to very low earth current values, regardless of the phase setting current. Pick-up current value of NI, VI, and EI curves = 1.1x I g Pick-up current value of DT curve = I g Instantaneous pick-up current value = I g x I o >> Page 20 of 84

21 84 GENERAL INSTRUCTIONS FOR 4. METERING FUNCTIONS 4.1. CURRENT The current values measured by the units correspond to the efficient values of each of the phases I 1, I 2 and I 3. Eight samples from a halfperiod are used and the mean of five consecutive values is calculated. This measurement is updated every second. It offers Class 1 meter accuracy, from 5 A up to 120% of the current sensor s maximum rated range. The zero-sequence current measurement I o is performed in the same way as the phase currents. Current meters: I 1, I 2, I 3 and I o 5. SENSORS 5.1. CURRENT SENSORS The electronic current transformers are designed for optimal adaptation to digital equipment technology, with a slight modification of the secondary interface. Therefore, the protection, metering and control equipment for these sensors operate with the same algorithms and with the same consistency as conventional devices. The low power outputs from the sensors can be adapted to standard values using external amplifiers. In this way, you can use conventional equipment or electronic relays. Page 21 of 84

22 GENERAL INSTRUCTIONS FOR IG-159-GB Main advantages derived from the use of sensor based systems: Small volume.the decreased power consumption of these transformers allows their volume to be drastically reduced. Improved accuracy. Signal acquisition is much more accurate due to high transformation ratios. Wide range. When there are power increases in the installation, the sensors do not have to be replaced with ones having a greater ratio. Greater safety. The open-air live parts disappear, increasing personnel safety. Greater reliability. The full insulation of the whole installation provides greater levels of protection against external agents. Easy maintenance. The sensors do not need to be disconnected when the cable or cubicle is being tested Functional Characteristics of Current Sensors The current sensors are toroidal-core current transformers with a high transformation ratio and low rated burden. These sensors are encapsulated in self-extinguishing polyurethane resin. Phase toroidal current transformers Range A Range A Ratio 300 / 1 A 1000 / 1 A Metering range 5 A to 100 A Extd. 130% 15 A to 630 A Extd. 130% Protection 5P20 5P20 Metering Class 1 Class 1 Burden 0,18 VA 0.2 VA Thermal current 20 ka 20 ka Dynamic current 50 ka 50 ka Saturation current 7,800 A 26,000 A Frequency Hz Hz Insulation 0,72 / 3 kv 0,72 / 3 kv Outer diameter 139 mm 139 mm Inner diameter 82 mm 82 mm Height 38 mm 38 mm Weight kg kg Polarity S1 blue, S2 brown S1 blue, S2 brown Encapsulation Self-extinguishing polyurethane Self-extinguishing polyurethane Thermal class B (130 ºC) B (130 ºC) Reference standard IEC IEC Page 22 of 84

23 84 GENERAL INSTRUCTIONS FOR Toroidal power transformers T / G Ratio 200/1 A with centre tap ( A) Power supply range 5 A to 630 A Thermal current 20 ka Dynamic current 50 ka Power 0.4 VA to 5 A Frequency Hz Insulation 0,72 / 3 kv Outer dimensions 139 mm Inner dimensions 82 mm Height 38 mm Weight kg Polarity S1 blue, S2 brown Encapsulation Self-extinguishing polyurethane Thermal class B (130ºC) Phase toroidal transformer 0-sequence toroidal transformer Page 23 of 84

24 GENERAL INSTRUCTIONS FOR IG-159-GB Vector Sum/Zero-SequenceWiring The wiring of the aforementioned transformers is performed in two different ways, depending on whether they have a zero-sequence toroidal current transformer installed or not. As a general rule, the zero-sequence toroidal transformer is used when the earth fault current is a below 10% of the phase current rating. R S T DETECTION OF EARTH CURRENT BY VECTOR SUM Page 24 of 84

25 84 GENERAL INSTRUCTIONS FOR Zero-sequence Toroidal Current Transformers Range A Range A Ratio 300 / 1 A 1000 / 1 A Metering range 0.5 A to 50 A Extd. 130% 0.5 A to 50 A Extd. 130% Protection 5P10 5P10 Metering Class 3 Class 3 Burden 0.2 VA 0.2 VA Thermal current 20 ka 20 ka Dynamic current 50 ka 50 ka Saturation current 780 A 780 A Frequency Hz Hz Insulation 0,72 / 3 kv 0,72 / 3 kv Outer dimensions 330 x 105 mm 330 x 105 mm Inner dimensions 272 x 50 mm 272 x 50 mm Height 41 mm 41 mm Weight 0.98 kg 0.98 kg Polarity S1 blue, S2 brown S1 blue, S2 brown Encapsulation Self-extinguishing polyurethane Self-extinguishing polyurethane Thermal class B (130 ºC) B (130 ºC) Reference standard IEC IEC Page 25 of 84

26 GENERAL INSTRUCTIONS FOR IG-159-GB 6. TECHNICAL CHARACTERISTICS 6.1. RATED VALUES Power supply AC 24 V ac V ac +/-30% DC 24 V dc V dc +/-30% Selfpowered >5 A, 230 V ac +/-30% Consumption < 1 VA Current inputs Primary phase 5 A A (depending on model) Earth 0.5 A A (depending on model) I thermal/dynamic 20 ka / 50 ka Impedance 0.1 Ω Accuracy Time delay 5% (minimum 20 ms) Metering / Protection Class 1 / 5P20 Frequency 50 Hz; 60 Hz +/-1% Output contacts Voltage 250 V ac Current 10 A (AC) Switching power 500 VA (resistive load) Temperature Operating - 40 ºC to + 70 ºC Storage - 40 ºC to + 70 ºC Communications Front port DB9 RS232 Rear port RS485 (5 kv) RJ45 Protocol MODBUS (RTU) 6.2. MECHANICAL DESIGN IP rating Terminals IP2X In cubicle IP3X IP4X (according to IEC ) IK06 (according to EN 50102) Dimensions (h x w x d): 146 x 47 x 165 mm Weight 0.3 kg Wiring Cable/Termination mm INSULATION TESTS IEC Insulation resistance 500 V DC : > 10 G Electric strength 2 kv ac ; 50 Hz; 1 min Voltage impulses: standard 5 kv; 1.2/50 s; 0.5 J differential 1 kv; 1.2/50 s; 0.5 J 6.4. ELECTROMAGNETIC COMPATIBILITY IEC Voltage dips 200 ms Ripple 12 % IEC Damped wave 1 MHz 2.5 kv; 1 kv IEC Electrostatic discharges 8 kv air (IEC , class IV) 6 kv contact IEC Radiated fields 10 V/m (IEC , class III) IEC Bursts - Fast transients ± 4 kv (IEC ) IEC Overvoltage pulses (IEC ) 4 kv; 2 kv Page 26 of 84

27 84 GENERAL INSTRUCTIONS FOR IEC Induced radio frequency 150 khz MHz signals (IEC ) IEC Magnetic fields 100 A/m; 50 Hz constant 1000 A/m; 50 Hz short- time (2 s) IEC Sinusoidal damped wave 2.5 kv; 1 kv IEC Electromagnetic emissions (EN ) 150 khz to 30 MHz (conducted) 30 MHz to 1 GHz (radiated) 6.5. CLIMATIC TESTS IEC Slow changes. Cold - 40 ºC; 16 hrs ºC; 16 hrs. IEC Slow changes. Heat + 60 ºC; 16 hrs ºC; 16 hrs. IEC Damp heat, continuous test + 40 ºC; 93%; 10 days IEC Damp heat cycles + 55 ºC; 6 cycles 6.6. MECHANICAL TESTS IEC Sinusoidal vibration. Response Hz; 1 g Sinusoidal vibration. Endurance Hz; 2 g IEC Impacts. Response 11 ms; 5 g Impact. Endurance 11 ms; 15 g Shock. Endurance 16 ms; 10 g IEC Seismic tests 1-38 MHz, 1g vertical, 0.5 g horizontal 6.7. POWER TESTS IEC No-load cable making and 24 kv/50 A/ cosφ = 0.1 breaking IEC Mainly active load making and 24 kv/630 A/ cosφ = 0,7 breaking IEC Earth faults 24 kv/200 A/50 A No-load transformer making and 13.2 kv /250 A/1250 kva breaking IEC Short-circuit making and breaking 20 ka / 1s 6.8. CE CONFORMITY This product complies with the European Union directive 2004/108/EC on electromagnetic compatibility, and with the IEC international regulations. The unit has been designed and manufactured for use in industrial areas, in accordance with EMC standards. This compliance results from a test performed according to article 10 of the directive, and included in protocol CE- 26/08-43-EE-1. Page 27 of 84

28 GENERAL INSTRUCTIONS FOR IG-159-GB 7. PROTECTION, METERING AND CONTROL MODELS 7.1. DESCRIPTION OF MODELS vs. FUNCTIONS T Distribution transformer protection unit installed in fuse-combination switch cubicles. The electronic unit performs all the protection functions except for the high value polyphase short-circuits that occur in the transformer s primary. It has inputs and outputs for switch monitoring and control. The unit can protect a power range from 50 kva up to 2000 kva in CGMCOSMOS system cubicles and from 50 kva up to 1250 kva in CGM-CGC and CGM.3 system cubicles. G Distribution general protection unit installed in circuit-breaker cubicles. The main usage applications are: general protection of lines, private installations, transformers, capacitor stacks, etc. They can protect a power range from 50 kva up to 400 kva (630 kva for CGM-CGC and CGM.3 system cubicles), when they include toroidal-core current transformers from 5 A to 100 A. With 15 A to 630 A toroidal-core current transformers, they offer a power range between 160 kva and 15 MVA (25 MVA for CGM-CGC and CGM.3 system cubicles). Page 28 of 84

29 84 GENERAL INSTRUCTIONS FOR Protection, Metering and Control Units T G General Phase current sensors 3 3 Earth (zero-sequence) current sensor Op Op Voltage sensors No No Digital Inputs 2 2 Digital outputs 2 2 Power supply 24 V dc to 125 V dc / 24 V ac to 110 V ac Op Op Self powered (> 5 A, V ac +/- 30%) Op Op Protection Phase overcurrent (50-51) Yes Yes Earth leakage overcurrent (50N-51N) Op Op Ultrasensitive earth leakage protection (50Ns-51Ns) Op Op Thermometer (49T) Yes Yes Communications MODBUS-RTU Yes Yes PROCOME No No RS-232 configuration port Yes Yes RS-485 port for remote control Yes Yes ekorsoft setup and monitoring program Op Op Indications Tripping cause indication Yes Yes Error display Yes Yes Test Test blocks for current injection Yes Yes Output contact for test Yes Yes Measurements Current Yes Yes Presence / Absence of voltage No No Op - Optional Page 29 of 84

30 GENERAL INSTRUCTIONS FOR IG-159-GB 7.2. RELAY CONFIGURATOR NOTE Not all combinations resulting from this configurator are possible. For the availability of other models, please consult Ormazabal's Technical - Commercial Department. To select the unit on the basis of the installation characteristics, the following configurator will be used: Type: G For protection cubicle with circuit-breaker T For fuse protection cubicle Protection functions: 10 Three phases (3 x 50/51) 20 Three phases and neutral (3 x 50/ N/51N) 30 Three phases and sensitive neutral (3 x 50/ Ns/51Ns) Toroidal-core current transformers: 0 Without toruses 1 Range A 2 Range A Power supply: A Self powered B Auxiliary power supply (Battery, UPS, etc.) Example: In the case of a selfpowered relay for a protection cubicle with a circuit-breaker, with functions 3 x 50/ Ns/51Ns and toroidal-core current transformers with a range of A, the corresponding configurator would be G-301A. Page 30 of 84

31 84 GENERAL INSTRUCTIONS FOR 7.3. T UNITS Functional description The T protection, metering and control unit is used for the protection of distribution transformers. It is installed in fuse-combination switch cubicles so the electronic system performs all the protection functions, except high polyphase short-circuit values, which are cleared by the fuses. When an overcurrent that is within the values that the load break switch can open is detected, the relay acts upon a low power bistable trigger that opens the switch. If the fault current is greater than the breaking capacity of the load break switch [2], the switch trip is blocked so that the fuses will blow. On the other hand, the equipment is disconnected and the fuses do not remain energised. TRANSFORMER PROTECTION GENERAL PROTECTION (MV client supply) [2 ] 1200 A for CGMCOSMOS-P, 480 A for CGM-CMP-F, 36 kv range, and CGM.3 and 300 A for CGM-CMP-F, 24 kv range. Page 31 of 84

32 GENERAL INSTRUCTIONS FOR IG-159-GB Technical Characteristics The T unit is used to protect the following transformer power ratings. Line voltage Fuse Rated Voltage [kv] CGMCOSMOS System MINIMUM Transformer Power Fuse Rating [A] [kva] MAXIMUM Transformer Power Fuse Rating [A] [kva] [kv] 6,6 3/7, ( ¹ ) / ( ¹ ) ,8 10/ / ( ² ) / ( ¹ ) 442 mm cartridge, ( ² ) 125 A SIBA SSK Fuse Line voltage Fuse Rated Voltage [kv] CGM-CGC / CGM.3 System MINIMUM Transformer Power MAXIMUM Transformer Power Fuse Rating [A] [kva] Fuse Rating [A] [kva] [kv] 6,6 3/7, ( ¹ ) / ,8 10/ / / / (2) / (2) 2500 ( ¹ ) 442 mm cartridge (2) SIBA SSK fuse (check) Selection process for the T unit protection parameters in CGMCOSMOS-P cubicles: 1. Determine the required fuse rating to protect the transformer in accordance with the fuse table in Ormazabal s document IG-078. The maximum ratings that can be used are 160 A for voltages up to and including 12 kv, and 125 A for voltages up to and including 24 kv. 2. Calculate the transformer rated current I n = S/ 3xU n. 3. Define the continuous overload level I>. Normal values in transformers of up to 2000 kva are 20% for distribution installations and 5% for power generation installations. 4. Select the transitory overload curve. Coordination between relay curves and LV fuses is performed with the EI type curve. 5. Define the delay time in transitory overload K. This parameter is defined by the transformer s thermal constant. This way, the greater the constant, the longer it takes for the transformer s temperature to increase under an overload condition; and therefore, the protection trigger can be delayed longer. The usual value for distribution transformers is K = 0.2, which means that it trips in 2 s if the overload is 300% in the EI curve. 6. Short-circuit level I>>. The maximum value of the transformer s magnetisation current must be determined. The current peak produced when a no-load transformer is connected, due to the effect of a magnetised nucleus, is several times greater than the rated current. This peak value, up to 12 times the rated value (10 times for more than Page 32 of 84

33 84 GENERAL INSTRUCTIONS FOR 1000 kva) has a very high harmonic content, so its fundamental 50 Hz component is much less. Therefore, a usual setting value for this parameter is between 7 and Instantaneous time delay T>>. This value corresponds with the protection trip time in the event a short-circuit occurs. It depends on the coordination with other protections and the usual values are between 0.1 and 0.5 s. If the short-circuit value is high, the fuses will act in the time determined by their characteristic curve. 8. Determine the current value in case of secondary three-phase short-circuit. This fault must be cleared by the fuses, and it corresponds with the intersection point s maximum value between the relay and the fuse curves. If the intersection point is greater than the secondary short-circuit value, the settings must be adjusted to meet this requirement. To select the T unit protection parameters in CGM-CMP-F and CGM.3-P cubicles, the steps to follow are similar to those proposed in the paragraphs above, except for the first step. The fuse rating required to protect the transformer is determined according to the fuse table of Ormazabal s documents IG-034 and IG-136 respectively. Please take into consideration that the minimum protection powers are listed in the table above. In case of protecting a transformer with following characteristics in CGMCOSMOS cubicle system: S = 1250 kva, U n =15 kv and U k = 5% Follow the procedure below for proper coordination between the fuses and the protection relay: Fuse selection according to IG /24 kv 125 A fuse Rated current. In = S/ 3 x U n = 1250 kva/ 3 x 15 kv 48 A Continuous withstand overload 20%. I n x I> = 48 A x A Extremely Inverse Curve type. E.I. Transitory overload factor. K =0.2 Short-circuit level. I n x I> x I>> = 48 A x 1.2 x A Instantaneous time delay T>> = 0,4 s Secondary short-circuit. I cs = I n x 100/ U k = 48 A x 100 / A Page 33 of 84

34 GENERAL INSTRUCTIONS FOR IG-159-GB Figure 7.1: Example for SIBA SSK fuse The earth unit setting depends on the characteristics of the line where the unit is installed. In general, the earth fault values are high enough to be detected as overcurrent. Even in isolated or resonant earthed neutral networks, the fault value in transformer protection installations is clearly different from the capacitive currents of the lines. This way, the transformer protection T units are used in isolated neutral networks that do not require the directional function. The values of the setting parameters must guarantee selectivity with the main switch protections. Given the variety of protection criteria and types of neutral used in the networks, it does not exist a single parameterisation; each case requires a specific parameterisation. For transformers up to 2000 kva, the settings below are given as a general example. It must be ensured that they properly apply to the protections upstream (general, line or main switch protections, among others.) Page 34 of 84

35 84 GENERAL INSTRUCTIONS FOR Phase setting Setting of Earth Rated Current Time delayed Instantaneou s I> K I>> T>> In=S/ 3xU n = 48 A EI DT 1,2 0,2 7 0,4 Type of Neutral Time delayed Instantaneou s I o > K o I o >> T o >> Solid or impedant NI DT 0,2 0,2 5 0,4 Isolated or resonant NI DT 0.1/Ig=2 A(*) 0,2 5 0,4 ( * ) In case a zero-sequence toroidal transformer is used Page 35 of 84

36 GENERAL INSTRUCTIONS FOR IG-159-GB Installation in a Cubicle The integral parts of the T units are the electronic relay, the power supply and test board, the bistable trigger and the current sensors. The electronic relay is fixed to the cubicle driving mechanism using anchors. The front of the equipment, which contains the components of the user interface, display, keys, communication ports, etc., is accessible from the outside without the need to remove the mechanism enclosure. The rear contains the X1 and X2 connectors, as well as the wiring that connects it to the power supply board.. CGM.3-F Page 36 of 84

37 84 GENERAL INSTRUCTIONS FOR All of the signals that come from the relay go through the board. Hence, the board enables the unit to be checked. Furthermore, there is a volt-free contact (J3) which is activated simultaneously with the relay trip. This enables to use conventional current injection equipment for testing the protection relays. The selfpowered transformers are also connected to the power supply board using the J7 connector in the selfpowered relays. The signal transformers are connected to the board's J8 connector, the function being to inject current into the secondary in order to test the relay. The T protection, metering and control unit has three connectors (J1, J3 and J4) to which the user can connect. They are situated on the upper part of the power supply and test board and their functions are as follows: Connector Name Functions Normal use It must be connected to an NO, volt-free J1 EXT. TRIP contact. When it is activated, the protection Transformer THERMOMETER. device trips if an overcurrent protection function is activated. J3 TRIP This is an NO, volt-free contact which is Protection unit TEST. activated when the protection device is Trip SIGNAL for remotelycontrolled tripped. It also works in self powered mode. installations J4 V. AUX Auxiliary power supply input: 230 V ac for selfpowered units and 24 to 125 V dc or 24 to 110 V ac for those with auxiliary power supply (10 kv insulated in relation to the rest of the equipment, in self powered models). Relay power supply (LVB of the transformer to protect, battery, etc.). Page 37 of 84

38 GENERAL INSTRUCTIONS FOR IG-159-GB T Electrical Diagram NOTE For more details, please see electrical diagram No , which shows the electrical connections between the different parts of the G unit and the cubicle. Page 38 of 84

39 84 GENERAL INSTRUCTIONS FOR Installation of Toroidal-core current transformers The installation of toroidal-core current transformers requires special attention. It is the main cause of untimely tripping problems, and its improper operation can cause trips that go undetected during commissioning. Aspects that must be considered in the installation: The toroidal-core current transformers are installed on the outgoing cables of the cubicle. The inner diameter is 82 mm, which means that MV cables can easily pass through the inside. The earthing screen MUST go through the toroidal-core current transformer when it comes out of the part of cable remaining above the toroidal-core current transformer. In this case, the braided pair goes through the inside of the toroidal-core current transformer before it is connected to the earthing of the cubicle. The braided pair must not touch any metal part, such as the cable support or other areas of the cable compartment, before it is connected to the cubicle's earth. Earth screen: it must pass through the inside of the toroidal-core The earthing screen must NOT go through the toroidal-core current transformer when it comes out of the part of cable remaining under the toroidal-core current transformer. In this case, the braided pair is connected directly to the earthing collector of the cubicle. If there is no braided pair for the earthing screen because it is connected at the other end (as in metering cubicles), the twisted pair should also not go through the toroidal-core current transformer Checking and Maintenance The T protection, metering and control unit is designed to perform the operating test necessary for both commissioning and regular maintenance checks. Several levels of checks are available depending on the possibility of interrupting service and accessing the MV cubicle cable compartment. Check through the primary: This case corresponds to the tests that are performed on the equipment when it is completely shut down, since it involves actuating the switchdisconnector and earthing the cubicle outgoing cables. When current is injected through the toroidal-core current transformers, you must check that the protection opens the switch within the selected time. In addition, you must make sure that the tripping indications are correct and that all the events are being recorded in the history log. CAUTION To perform this check, the unit must be powered up. Hence more than 5 A must be injected, or it must be connected to 230 Vac for self powered relays. As regards those which have auxiliary power supply, feed the voltage through the board's J4 connector. Page 39 of 84

40 GENERAL INSTRUCTIONS FOR IG-159-GB To perform this check, follow the steps indicated below: - Open the cubicle s switch-disconnector and then earth the output. - Access the cable compartment and pass a test cable through the toroidal-core current transformers. - Connect the test cable to the current circuit of the tester. - Connect the power supply board's J3 connector to the tester's timer stopper input. - Open the earthing switch and close the switch. Reset the latch and remove the actuating lever in order to leave the cubicle ready for tripping. - Inject the test currents and verify the tripping times are correct. Check that the trips are correctly displayed. For phase trips, the test cable must pass through two toroidal-core current transformers. The cable must pass through each of them in opposite direction; in other words, if in the first one current flows up bottom, in the other it must flow bottom up so that the sum of the two currents equals zero and no earth trip occur. For earth trips, the test cable is passed through a single toroidal-core current transformer (zero-sequence or phase toroidal, depending on whether a zero-sequence toroidal is available or not). Trip tests must be performed for all toroidal-core current transformers to check the proper operation of the complete unit. Check through the secondary. In this case, the tests are performed on the equipment when the cable compartment is not accessible. This occurs because the cubicle outgoing cables are energised and cannot be connected to earth. In this case, it is not possible to feed a test cable through the toroidal transformers and current must be injected from the power supply board. This testing method is much better than using testing equipment (normally more than 100 A). To perform this check, follow the steps indicated below: - Access the control's upper compartment where the power supply board is located. - Disconnect the bistable trigger. - Disconnect the blue, brown, black and earth cables of the J8 connector, corresponding to points J8-6, J8-8, J8-10 and J8-1 respectively. - Connect the previously disconnected cables to the earth points N of connector J8-3. This operation will short-circuit the current transformers' secondary circuitry. Page 40 of 84

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,

More information

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1.... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800 Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Trip circuit supervision relay. Type RXTCS

Trip circuit supervision relay. Type RXTCS Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS (PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS IS 12729:2004 IEC 60694(2002) 1.1 Scope This International Standard applies to a.c. switchgear and controlgear,

More information

Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W

Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 14713221 001 Seite 2 von 37 Page 2 of 37 Model List: No Model Rated Voltage(V) 1. EG-LED0827-01 Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 4. EG-LED1040-01 AC 100-240V, 10W 5. EG-LED1027-02

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

MOUNTING AND OPERATING INSTRUCTIONS

MOUNTING AND OPERATING INSTRUCTIONS MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

Energy Management Energy Meter Type EM23 DIN

Energy Management Energy Meter Type EM23 DIN Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

Earth Fault Detection Basics in Theory

Earth Fault Detection Basics in Theory Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star

More information

15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE

15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

MODEL 2202IQ (1991-MSRP $549.00)

MODEL 2202IQ (1991-MSRP $549.00) F O R T H E L O V E O F M U S I C F O R T H E L O V E O F M U S I C MODEL 2202IQ (1991-MSRP $549.00) OWNER'S MANUAL AND INSTALLATION GUIDE INTRODUCTION Congratulations on your decision to purchase a LINEAR

More information

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

Relion 605 series. Feeder protection and control / Feeder protection REF601 / REJ601 Product Guide

Relion 605 series. Feeder protection and control / Feeder protection REF601 / REJ601 Product Guide Relion 605 series Feeder protection and control / Feeder protection Product Guide Product version: 2.2FP1 Contents 1. Description... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

Remote Monitoring and REC 501 Control Unit Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the

More information

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Capacitor Protection Relay SPAJ 160 C. Product Guide

Capacitor Protection Relay SPAJ 160 C. Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase

More information

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter FEATURES: Click on Series name for product info on aimtec.com Models Single output Model Max Output Power (W) 1 AC-DC Constant Current or Constant Over temperature protection Voltage LED Driver Over current

More information

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

Gain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server

Gain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server Gain energy insight and control with PowerLogic PowerLogic EGX300 integrated gateway-server Plug into your energy usage with a simple mouse click The PowerLogic EGX300 is an integrated gateway-server that

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic

More information

Type: DILM32 10(24V50HZ) Article No.: 277247

Type: DILM32 10(24V50HZ) Article No.: 277247 Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,

More information

Circulating Current Relay. Type IRXm

Circulating Current Relay. Type IRXm Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

Catalog. Arc Guard System TM TVOC-2

Catalog. Arc Guard System TM TVOC-2 Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already

More information

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used

More information

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

Current Probes. User Manual

Current Probes. User Manual Current Probes User Manual ETS-Lindgren L.P. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall

More information

Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification

Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification Feeder protection for overhead lines and cables in isolated neutral or compensated networks Specification Feeder protection for overhead lines and cables in isolated neutral or compensated networks Version

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

EPL225 Series. 225 Watts. www.xppower.com. AC-DC Power Supplies. Models & Ratings. Summary

EPL225 Series. 225 Watts. www.xppower.com. AC-DC Power Supplies. Models & Ratings. Summary 225 Watts 50 W Convection/ 225 W Forced-cooled Ratings 2 by 4 Footprint Low.26 Profile 2 V Fan Output High Efficiency, up to 95% ITE & Medical pprovals High Power Density Less than 0.5 W No Load Input

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Communicate and view data from meters with one simple device

Communicate and view data from meters with one simple device Communicate and view data from meters with one simple device PowerLogic EGX300 integrated gateway-server Web Monitoring Communications Plug and Play Plug into your energy usage with a simple mouse click

More information

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable

More information

NMI M 6-2 Electricity Meters. Part 2: Test Report Format

NMI M 6-2 Electricity Meters. Part 2: Test Report Format NMI M 6-2 Electricity Meters Part 2: Test Report Format Commonwealth of Australia 2010 First edition September 2010 National Measurement Institute Bradfield Road, Lindfield, NSW 2070 PO Box 264, Lindfield,

More information

Analog signal converters CC-E I/I Current / current isolators

Analog signal converters CC-E I/I Current / current isolators ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module! Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8

More information

GE Protection and Control Business Department. Page 1 Date 5/11/99

GE Protection and Control Business Department. Page 1 Date 5/11/99 GE Protection and Control Business Department Page 1 GE Protection and Control Business Department Proven Overcurrent Protection with Power Management Communication The The Advantages of Microprocessor

More information

Table of Contents. TransformerIQ FAQs 1

Table of Contents. TransformerIQ FAQs 1 [12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Cable Solutions for Servo and Variable Frequency Drives (VFD) Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence

More information

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World Catalogue 2002 Automatic capacitor banks Building a New Electric World 0Contents Power factor correction 2 Power factor equipment selection guide 3 General technical data 4 Capacitors and banks 50 z 6

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D

DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D ELECTRONICS AB DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D & HIGH&VOLTAGE& FIXED&GAIN& BROADBAND & 800Vpp&60mA& 100x& DC&to&ca&200&kHz & LOW&OUTPUT&IMPEDANCE& HIGH&SLEW&RATE &

More information

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual. i800 AC Current Clamp Instruction Sheet Introduction The i800 AC Current Clamp, the Clamp, has been designed for use with multimeters, recorders, power analyzers, safety testers, etc., for accurate non-intrusive

More information

Type: DILM9 10(24VDC) Article No.: 276705

Type: DILM9 10(24VDC) Article No.: 276705 Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50

More information

Eaton s E-Series protective relay family

Eaton s E-Series protective relay family E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family

More information

Disturbance Recoder SPCR 8C27. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power

More information

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

For a complete explanation of all the functions and configurations available please refer to the SC6006: Manual of operation.

For a complete explanation of all the functions and configurations available please refer to the SC6006: Manual of operation. PRELIMINARY TECHNICAL INFORMATION Three-phase Digital SCR Firing Board HIGHLIGHTS - Up to 480 V AC input supply voltage - Up to 700 V AC sync input - DSP controlled - Digital or analog input signaling

More information

Silvertel. Ag5200. 1 Features. 2 Description. Power-over-Ethernet Plus Module. IEEE802.3at and IEEE802.3af compliant. Maximum 30W output power

Silvertel. Ag5200. 1 Features. 2 Description. Power-over-Ethernet Plus Module. IEEE802.3at and IEEE802.3af compliant. Maximum 30W output power Silvertel V1.1 November 2012 Datasheet Pb 1 Features IEEE802.3at and IEEE802.3af compliant Maximum 30W output power Dual In-Line (DIL) package size 50.6mm (L) x 30mm (W) Overload, short-circuit and thermal

More information

Current Monitoring Kit QUICK START GUIDE

Current Monitoring Kit QUICK START GUIDE Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information