BUILDING DESIGN FOR HOMELAND SECURITY. Unit IV Vulnerability Assessment
|
|
|
- Morgan Phelps
- 10 years ago
- Views:
Transcription
1 Unit IV Vulnerability Assessment
2 Vulnerability Any weakness that can be exploited by an aggressor or, in a non-terrorist threat environment, make an asset susceptible to hazard damage Unit IV-2
3 Unit Objectives Explain what constitutes a vulnerability. Identify vulnerabilities using the Building Vulnerability Assessment Checklist. Understand that an identified vulnerability may indicate that an asset: is vulnerable to more than one threat or hazard; and that mitigation measures may reduce vulnerability to one or more threats or hazards. Provide a numerical rating for the vulnerability and justify the basis for the rating. Unit IV-3
4 Vulnerability Assessment Identify site and building systems design issues Evaluate design issues against type and level of threat Determine level of protection sought for each mitigation measure against each threat Unit IV-4
5 Assessment Flow Chart AssetValue Assessment (Section 1.1) Cost Analysis Analyze how mitigation options affect asset criticality and ultimately risk Vulnerability Assessment (Section 1.3) Risk Assessment (Section 1.4) Identify Mitigation Options (Chapters 2 and 3) Decision (Risk Management) (Section 1.5) Threat/Hazard Assessment (Section 1.2) Analyze how mitigation options change vulnerability and ultimately risk Unit IV-5
6 Identifying Vulnerabilities Multidisciplinary Team Engineers Architects Security specialists Subject matter experts Outside experts if necessary Unit IV-6
7 Vulnerability Assessment Preparation Coordinate with the building stakeholders: Site and Building Plans Utilities Emergency Plans (shelter, evacuation) Interview schedules Escorts for building access Unit IV-7
8 Assessment GIS Portfolio Unit IV-8
9 10-Mile Radius Unit IV-9
10 Regional Transportation Unit IV-10
11 Metro Center Imagery Unit IV-11
12 Site Emergency Response Unit IV-12
13 Site Public and Government Buildings Unit IV-13
14 Site HazMat Unit IV-14
15 Site Local Transportation Network Unit IV-15
16 Site Principal Buildings by Use Unit IV-16
17 Site Perimeter Imagery Unit IV-17
18 Site Truck Bomb Unit IV-18
19 Site Car Bomb Unit IV-19
20 Options to Reduce Vulnerability 1) Define Site Functions 2) Identify Critical Systems Interviews with Site Personnel 3) Evaluate Facility System Interactions 4) Determine Common System Vulnerabilities 5) Physically Locate Components and Lines 6) Identify Critical Components and Nodes Review Prints and Specs; Check with Systems Experts On-site Inspections Apply Vulnerability Checklist 7) Assess Critical Nodes vs. Threats Threat Spectrum Evaluation 8) Determine Survivability Enhancements Survivability Options 9) Document Entire Analysis Process Records Unit IV-20
21 Facility System Interactions Figure 1-8: Facility System Interactions, page 1-23 Unit IV-21
22 Single-Point Vulnerabilities Unit IV-22
23 Functional Analysis SPVs Standard 11 Standard 13 and 17 Standard 1 Standard 1 The loading dock and warehouse provide single point of entry to the interior The mailroom is located within the interior and not on exterior wall or separate HVAC system The telecom switch and computer data center are adjacent to the warehouse The trash dumpster and emergency generator are located adjacent to the loading dock Figure 1-10: Non-Redundant Critical Functions Collocated Near Loading Dock, p Unit IV-23
24 Infrastructure SPVs Electrical Service Air Intakes Drive Through Telecom Service Unit IV-24
25 Building Vulnerability Assessment Checklist Compiles best practices from many sources Includes questions that determine if critical systems will continue to function during an emergency or threat event Organized into 13 sections Each section should be assigned to a knowledgeable individual Results of all sections should be integrated into a master vulnerability assessment Compatible with CSI Master Format standard to facilitate cost estimates Unit IV-25
26 Building Vulnerability Assessment Checklist Site Architectural Structural Systems Building Envelope Utility Systems Mechanical Systems (HVAC and CBR) Plumbing and Gas Systems Electrical Systems Fire Alarm Systems Communications and IT Systems Equipment Operations and Maintenance Security Systems Security Master Plan Unit IV-26
27 Building Vulnerability Assessment Checklist Vulnerability Question Guidance Observations 6 Mechanical Systems (HVAC and CBR) 6.1 Where are the air intakes and exhaust louvers for the building? (low, high, or midpoint of the building structure) Are the intakes and exhausts accessible to the public? Air intakes should be located on the roof or as high as possible. Otherwise secure within CPTED-compliant fencing or enclosure. The fencing or enclosure should have a sloped roof to prevent throwing anything into the enclosure near the intakes. Ref: CDC/NIOSH Pub Is roof access limited to authorized personnel by 6.2 means of locking mechanisms? Is access to mechanical areas similarly controlled? Roofs are like entrances to the building and are like mechanical rooms when HVAC is installed. Adjacent structures or landscaping should not allow access to the roof. Ref: GSA PBS P100, CDC/NIOSH Pub , and LBNL Pub Extracted from Table 1-22: Building Vulnerability Assessment Checklist, pages 1-46 to Unit IV-27
28 Building Vulnerability Assessment Checklist By what means does the main telephone and data communications interface the site or building? Are there multiple or redundant locations for the telephone and communication service? Does the fire alarm system require communication with external sources? 5.21 By what method is the alarm signal sent to the responding agency: telephone, radio, etc.? Is there an intermediary alarm monitoring center? Extracted from Table 1-22: Building Vulnerability Assessment Checklist, pages 1-46 to Unit IV-28
29 Building Vulnerability Assessment Checklist 1.15 Is there minimum setback distance between the building and parked cars? 4.1 What is the designed or estimated protection level of the exterior walls against the postulated explosive threat? 4.2 Is the window system design on the exterior façade balanced to mitigate the hazardous effects of flying glazing following an explosive event? (glazing, frames, anchorage to supporting walls, etc.)? Extracted from Table 1-22: Building Vulnerability Assessment Checklist, pages 1-46 to Unit IV-29
30 Building Vulnerability Assessment Checklist 6.1 Where are the air intakes and exhaust louvers for the building? (low, high, or midpoint of the building structure) Are the intakes and exhausts accessible to the public? 1.9 Is there any potential access to the site or building through utility paths or water runoff? (Eliminate potential site access through utility tunnels, corridors, manholes, storm water runoff culverts, etc. Ensure covers to these access points are secured.) What type of construction? 3.1 What type of concrete and reinforcing steel? What type of steel? What type of foundation? Extracted from Table 1-22: Building Vulnerability Assessment Checklist, pages 1-46 to Unit IV-30
31 Building Vulnerability Assessment Checklist 2.19 Are loading docks and receiving and shipping areas separated in any direction from utility rooms, utility mains, and service entrances, including electrical, telephone/data, fire detection/alarm systems, fire suppression water mains, cooling and heating mains, etc.? 1.16 Does adjacent surface parking on site maintain a minimum standoff distance? For initial screening consider using 25 meters (82 feet) as a minimum with more distance needed for unreinforced masonry or wooden walls. Reference: GSA PBS-P100 Extracted from Table 1-22: Building Vulnerability Assessment Checklist, pages 1-46 to Unit IV-31
32 Vulnerability Rating Very High One or more major weaknesses have been identified that make the asset extremely susceptible to an aggressor or hazard. High - One or more significant weaknesses have been identified that make the asset highly susceptible to an aggressor or hazard. Medium High An important weakness has been identified that makes the asset very susceptible to an aggressor or hazard. Medium A weakness has been identified that makes the asset fairly susceptible to an aggressor or hazard. Medium Low A weakness has been identified that makes the asset somewhat susceptible to an aggressor or hazard. Low A minor weakness has been identified that slightly increases the susceptibility of the asset to an aggressor or hazard. Very Low No weaknesses exist. Unit IV-32
33 Critical Functions Function Cyber attack Armed attack (single gunman) Vehicle bomb CBR attack Administration Asset Value Threat Rating Vulnerability Rating Engineering Asset Value Threat Rating Vulnerability Rating Extracted from Table 1-20, page 1-38 Unit IV-33
34 Critical Infrastructure Function Cyber attack Armed attack (single gunman) Vehicle bomb CBR attack Site Asset Value Threat Rating Vulnerability Rating Structural Systems Asset Value Threat Rating Vulnerability Rating Extracted from Table 1-21, page 1-39 Unit IV-34
35 Summary Step-by-Step Analysis Process: Expertly performed by experienced personnel Determines critical systems Identifies vulnerabilities Focuses survivability mitigation measures on critical areas Essential component of Critical Infrastructure and Critical Function Matrices Unit IV-35
36 Unit IV Case Study Activity Vulnerability Rating Background Vulnerability: any weakness that can be exploited by an aggressor or, in a non-terrorist threat environment, make an asset susceptible to hazard damage Requirements: Vulnerability Rating Approach Use rating scale of 1 (very low or no weakness) to 10 (one or major weaknesses) Refer to HIC case study and rate the vulnerability of asset-threat/hazard pairs: HIC Critical Functions HIC Infrastructure Unit IV-36
BUILDING DESIGN FOR HOMELAND SECURITY. Unit I Building Design for Homeland Security
BUILDING DESIGN FOR HOMELAND SECURITY Unit I Building Design for Homeland Security Participant Introductions Name Affiliation Area of Concentration BUILDING DESIGN FOR HOMELAND SECURITY Unit I-2 Course
Risk Management Series Building Design for Homeland Security. Student Manual January 2004 FEMA E 155
Risk Management Series Building Design for Homeland Security Student Manual January 2004 FEMA E 155 E155/ January 2004 RISK MANAGEMENT SERIES Building Design for Homeland Security PROVIDING PROTECTION
Current as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
Chapter 8. EOC Security Concepts and Requirements:
: One of the primary objectives in the design and construction (or retrofit) of an Emergency Operations Center (EOC) is to provide a safe and secure environment that will enable the emergency management
File 6: Appendix A, 36 CFR 1234 (formally numbered as 36 CFR 1228 subpart K) Federal Facility Security Standards (version 2.0 issued May 15, 2014)
File 6: Appendix A, 36 CFR 1234 (formally numbered as 36 CFR 1228 subpart K) Federal Facility Security Standards (version 2.0 issued May 15, 2014) Appendix A -- Minimum Security Standards for Level Federal
Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria
Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards
Security Tools. Forms. Physical Security Assessment Security Plan Template Traffic Control Plan Template
Security Tools Forms Physical Security Assessment Security Plan Template Traffic Control Plan Template 1 Physical Security Assessment (PSA) Date: I. PHYSICAL SECURITY ASSESSMENT (PSA): EXTERIOR OF THE
Does a fence or other type physical barrier define the perimeter of the facility?
PHYSCIAL SECURITY SURVEY CHECKLIST PERIMETER BARRIERS TRANSIT FACILITIES Does a fence or other type physical barrier define the perimeter of the facility? (1) Specify type and height of physical barrier
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
Industrial Suburban District Regulations City of St. Petersburg City Code Chapter 16, Land Development Regulations
16.20.110 - Industrial Suburban District ( IS ) Figure REFERENCE Typical Buildings in the IS District Figure REFERENCE Site Plan of a typical development in the IS District Sections: 16.20.110.1 Composition
All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.
2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other
CRITICAL INFRASTRUCTURE PROTECTION BUILDING ORGANIZATIONAL RESILIENCE
1 CRITICAL INFRASTRUCTURE PROTECTION BUILDING ORGANIZATIONAL RESILIENCE Gavin McLintock P.Eng. CISSP PCIP 2 METCALFE POWER STATION 16 April 2013 Sophisticated physical attack 27 Days outage $15.4 million
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
EVACUATION Fire / Explosion / Smell of Smoke / Gas Odor / Fire Alarm / Bomb Threat
Emergency Procedures Quick Reference Guide Faculty Edition EVACUATION Fire / Explosion / Smell of Smoke / Gas Odor / Fire Alarm / Bomb Threat LOCKDOWN Intruder / Weapon / Hostage /Active Shooter / Hostile
Data Center Due Diligence List
Data Center Due Diligence List Name and address of site facility Date constructed Building owner/date purchased by current owner Name of previous owner Adjacent Property Descriptions North South East West
9770 CULVER BOULEVARD CULVER CITY, CA 90232-0507 www.culvercity.org. Incidental improvements: improvements that do not qualify as minor or
9770 CULVER BOULEVARD CULVER CITY, CA 90232-0507 www.culvercity.org Construction Permitting Guidelines for Businesses Moving into Existing Buildings in Culver City If your business is moving into an existing
CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.
Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M
ORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT
1. SAFETY, HEALTH, CODE 1.1 Structural Requirements, Seismic Stability 1.1.1 Primary Structure 1.1.2 Ceilings 1.1.3 Cabinets, Equipment 1.1.4 Portables 1.2 Fire / Life Safety 1.2.1 Corridor, Separation
Civil Engineering and Architecture (CEA) Detailed Outline
Civil Engineering and Architecture (CEA) Detailed Outline Unit 1: Overview of Civil Engineering and Architecture (23 days) Lesson 1.1: History of Civil Engineering and Architecture 1. Many features of
May 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client,
PROPERTY INSPECTION PROFESSIONALS May 5, 2010 Client Client Address Re: Inspection Address, Chicago, Illinois Dear Mr. Client, On May 4, 2010, Tomacor completed a property inspection of the above referenced
REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
Disaster Ready. By: Katie Tucker, Sales Representative, Rolyn Companies, Inc
By: Katie Tucker, Sales Representative, Rolyn Companies, Inc Are you and your facility disaster ready? As reported by the Red Cross, as many as 40 percent of small businesses do not reopen after a major
DESIGN REVIEW CHECKLIST Chapter 6 Special Consideration Design Guidelines
DESIGN REVIEW CHECKLIST Chapter 6 Special Consideration Design Guidelines A. Offices a. Office buildings should be built to the minimum required setback. b. Surface parking should be located towards the
2.4 Hardcopy submittals shall be provided at adequate size so that all notes are readable.
DESIGN EQUIEMENTS POJECT DELIVEABLES CHECKLISTS GENEAL INFOMATION 1.1 The following is a checklist to be used as a guide for the required deliverables for the Schematic Design phase. 1.2 Schematic Design
FRONTIER PITTS Datacentre Protection
FRONTIER PITTS Introduction Bespoke protection for Data and Cash Centres Frontier Pitts secure various Data Centres and Cash Centres in the UK and around the World, with a variety of equipment from both
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS Permit applicants shall submit three (3) COMPLETE SETS of plans and specifications with each application for a permit. Plans and specifications
Todd & Cue Ltd Your Business Continuity Partner
Todd & Cue Ltd Your Business Continuity Partner Preparation and Planning We provide strategies, tools and resources to help you prepare for a business interruption whether it is caused by fire, water,
FACILITY SECURITY CERTIFICATION FORM DOJ SECURITY LEVEL II
FACILITY SECURITY CERTIFICATION FORM DOJ SECURITY LEVEL II AGENCY: FACILITY: ADDRESS: LEASED/OWNED: UPGRADE COSTS: REVIEW TEAM: REVIEW DATE: FACILITY POC: CERTIFIED Y/N: I. PERIMETER SECURITY A.. PARKING
Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA
Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA Boggarm S. Setty, P.E., Fellow ASHRAE Setty & Associates, Ltd. 3040 Williams Drive, Suite 600, Fairfax,
AT&T Internet Data Center Site Specification New York III (Secaucus, NJ)
AT&T Internet Data Center Site Specification New York III (Secaucus, NJ) Site Biography Market Area: New York City, New Jersey, Upstate NY and Lower Connecticut Location: Secaucus, NJ 07094 Address: 15
Lease Security Standards: Instructions for Lease Acquisitions
Addendum 1 Lease Security Standards: Instructions for Lease Acquisitions 1. Summary. a. The Interagency Security Committee (ISC) Standards will provide a consistent level of security to federal tenants
Post Occupancy Evaluation (POE) Technical Instructions
1.0 Purpose These technical instructions define the typical steps required by HHS personnel in the use of the. The POE consists of a detailed and systematic assessment of a facility that is operational
New York State Unified Court System. Workplace Safety Assessment
New York State Unified Court System Workplace Safety Assessment WORKPLACE SAFETY ASSESSMENT COURTHOUSE/FACILITY INFORMATION... 2 WORKPLACE SAFETY TRAINING PROTOCOLS... 3 Workplace Violence Policy, Exposure
APPENDIX A: BUILDING VULNERABILITY ASSESSMENT CHECKLIST
APPENDIX A: BUILDING VULNERABILITY ASSESSMENT CHECKLIST The Building Vulnerability Assessment Checklist is based on the checklist developed by the Department of Veterans Affairs (VA) and is part of FEMA
BUILDING DATA. Facility Assessment Report, Garland Independent School District 3. Williams Stadium (Facility #913)
WILLIAMS STADIUM BUILDING DATA WILLIAMS STADIUM 510 Stadium Dr., Garland, TX 75040 Facility # 913 Year Built No. of Buildings No. of Portables 0 Approx. Total Square Footage Approx. Capacity Building
Disaster Prevention and Protection Checklist
Preservation Services Leaflet 1438 West Peachtree Street, Suite 200/Atlanta, GA 30309 Phone: 404-892-0943/Fax: 404-892-7879 Website: Disaster Prevention and Protection Checklist The inspection
LogisticsCentre IV Distribution Center
KCI Intermodal BusinessCentre LogisticsCentre IV LogisticsCentre IV Distribution Center Modern Warehouse/Distribution Space Ranging From 108,000± SF to 432,000± SF 10221 NW Transcon Drive 112th Street
Risk Management Report
Risk Management Report Main Street, White Plains, NY 060 Member: Joan Smith Policy No.: 45678 Agency: ABC Insurance Brokers, Inc. Date of Visit: January, 0 Prepared By: Tim Arone Summary of Scheduled Changes
City of La Vernia 102 E. Chihuahua Street, La Vernia, Texas 78121 Phone: (830)779-4541 Fax: (830) 253-1198 cityoflavernia@lavernia-tx.
[email protected] Commercial New/Remodel Building Requirements This document is not meant to modify any Federal or State laws or City Ordinances. It is intended to be informative and to be
How To Visit An Internet Data Center
AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina
DRAPER ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1953 BUILDING AREA 54,000 SF CURRENT PROGRAM CAPACITY 250 ENROLLMENT 2008 84 WARD 8 PROPOSED PROGRAM CAPACITY 325 Site Plan DRAPER - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
Prepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103. Prepared By
Project Structural Conditions Survey and Seismic Vulnerability Assessment For SFCC Civic Center Campus 750 Eddy Street San Francisco, California 94109 Prepared For San Francisco Community College District
SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
Sample Outline (courtesy of City of Guelph Museums) Building Conservation Plan
Sample Outline (courtesy of City of Guelph Museums) Building Conservation Plan 1. Introduction 2. Commemorative Integrity Statement/Statement of Purpose 3. Contacts Staff City Contacts Ambulance Cold Storage
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.
ST. MONICA FOOD PANTRY HOUSTON, TEXAS
PROJECT MANUAL FOR ST. MONICA FOOD PANTRY HOUSTON, TEXAS OWNER: ST. MONICA CATHOLIC CHURCH 8421 W. MONTGOMERY ROAD HOUSTON, TEXAS 77088 ARCHITECT: C SIX ARCHITECTURE, LLC 4606 F.M. 1960 WEST, STE 400 HOUSTON,
Hurricane Checklist. It is in the best interest to ensure that our employees are safe and that our properties are secure prior to a hurricane event.
Hurricane Checklist Although most hurricane warnings refer to the time a hurricane will make landfall, the impact from a hurricane can begin to be felt several hours prior to landfall. Landfall is defined
SUBSTANTIAL IMPROVEMENT OR SUBSTANTIAL DAMAGE NOTICE TO PROPERTY OWNER
NOTICE TO PROPERTY OWNER Rebuilding your Home after the storm? Adding on, renovating, or remodeling your home? Here's information YOU need to know about the 50% Rule. If your home or business is below
Lindsay Thurber Comprehensive High School Red Deer School District No. 104 School Facilities Evaluation Project Page 1
School Facilities Evaluation Project Page 1 Executive Summary In November 1999, Alberta Infrastructure, School Facilities Branch engaged Stephens Kozak Carr and Brown Architects to conduct evaluations
Suffolk County Department of Health Services. Division of Environmental Quality
Suffolk County Department of Health Services Division of Environmental Quality Guidelines For the Construction of Storage Areas for Portable Containers ~~~~ Clare B. Bradley, M.D., M.P.H. Suffolk County
Commercial Building Valuation Report
INSURED University of Houston - Victoria Effective Date: Expiration Date: Cost as of: 09/2010 BUILDING 1 217 - University Center 77901 Location Adjustments Climatic Region: High Wind Region: Seismic Zone:
When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:
When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory
AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx)
AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx) Site Biography Market Area: Dallas and Fort Worth Areas of Texas Location: Allen, Tx 75013 Address: 900 Ventura Drive CLLI, POP, NPA/NXX
Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]
Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration
Protection of unoccupied or void properties
Real Estate Issue one Protection of unoccupied or void properties Introduction The current economic downturn has lead to a greatly increased number of vacant properties. In some countries rates of unoccupancy
HATFIELD TOWNSHIP DEMOLITION PERMIT APPLICATION PROCEDURES
HATFIELD TOWNSHIP DEMOLITION PERMIT APPLICATION PROCEDURES A demolition permit is required for complete demolition of residential or non-residential structures. PART I Location of Property Complete address
Security Risk Assessment and Mitigation Prioritization
Security Risk Assessment and Mitigation Prioritization Stephanie King, PhD, PE Weidlinger Associates, Inc. FFC Committee on Physical Security and Hazard Mitigation July 15, 2008 www.wai.com New York Massachusetts
Emergency Preparedness
Policy Number: J104 Title: Emergency Preparedness Section: Operations Emergency Preparedness It is the responsibility of EASTERN to safeguard the health and welfare of School students and employees by
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA
ORANGE UNIFIED SCHOOL DISTRICT SCHOOL FACILITIES MASTER PLAN NEEDS ASSESSMENT
1. SAFETY, HEALTH, CODE 1.1 Structural Requirements, Seismic Stability 1.1.1 Primary Structure 1.1.2 Ceilings 1.1.2 Water damage in many classrooms. Replace tiles. 1.1.3 Cabinets, Equipment 1.1.4 Portables
NON-RESIDENTIAL BUILDING PERMIT PROCEDURES
TOWAMENCIN TOWNSHIP NON-RESIDENTIAL BUILDING PERMIT PROCEDURES PART I Location of Property Address, Zoning District, Parcel Number and Lot & Block must be provided on all applications. PARTS II thru VIII
NATIONAL INSTITUTE OF GOVERNMENT PURCHASING (NIGP) DESIGN AND CONSTRUCTION CODES
NATIONAL INSTITUTE OF GOVERNMENT PURCHASING (NIGP) DESIGN AND CONSTRUCTION CODES All searches and notifications on Bid4Michigan are based on National Institute of Government Purchasing (NIGP) codes. It
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
East Mississippi Community College. Scooba Campus * Mayhew Campus Department of Public Safety. Campus Emergency Action Plan.
1 East Mississippi Community College Scooba Campus * Mayhew Campus Department of Public Safety Campus Emergency Action Plan Revised 2013 TABLE OF CONTENTS 2 Foreword & Emergency Numbers Page 3 Active Shooter
Building Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER
CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST
CITY OF BERKELEY DETAILED CHECKLIST This checklist will assist you in preparing plans for submittal with a building permit application. Alterations, additions and remodeling projects may not require all
MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS
Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT
Lot Number. City. Architect Name SUBCONTRACTORS - COMPLETE AND ATTACH LIST ON PAGE 4
New Construction Permit Application Village of Shorewood Building Division One Towne Center Blvd Shorewood, IL 60404 (815)553-2310 Fax (815)744-6766 SUBMISSION CHECKLIST - Complete this application and
Accela Automation User Manual for Gwinnett County Automated Inspection Request System (IVR)
Accela Automation User Manual for Gwinnett County Automated Inspection Request System (IVR) Version 1.2 9/30/2010 Table of Contents IVR Instructions...3 Initial Entry Instructions...3 Permit Access Instructions
Bureau Veritas Contact Information
Bureau Veritas Contact Information Permit Submittal The permit documents and fees will be submitted to the city. Submittal documents should be complete to expedite plan review and permit issuance. Please
Date: Business Name: Business Contact Person: Business Address: Business Telephone Number: Alternate Contact Number/Email: Officer: Case No:
ISLE OF PALMS POLICE DEPARTMENT Thomas E. Buckhannon, III, Chief of Police 30 J. C. Long Boulevard Isle of Palms, South Carolina 29451 (843) 886-6522 BUSINESS SECURITY SURVEY Date: Business Name: Business
Physical Security Assessment Form
Physical Security Assessment Form Security Self-Assessment T Wake 10 February 2012 Security Assessment Contents Facility / Site Security Assessment Form... 3 Identification Details... 3 Facility Details...
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) Site Biography Market Area: Washington, DC Area Location: Ashburn, VA 20147-6011 Address: All deliveries should be sent to
Walkthrough Inspection Checklist
Walkthrough Inspection Checklist This checklist is to aid during an IAQ Walkthrough of the school. The checklist includes considerations both inside and outside the school building: Instructions: 1. Read
Factors to Consider When Developing an Evacuation Plan
The following should be viewed only as suggestions: Factors to Consider When Developing an Evacuation Plan 1. You must identify your document with a specific title and explanation. Example: Evacuation
Commercial or Business Security Survey
Exterior Grounds Commercial or Business Security Survey Is there a fence around the property or a clear definition of Territoriality? If there is a fence, is it tall enough and maintained in good repair?
Aurora Mall. Aurora (Denver), Colorado
is the largest superregional mall in the city of Aurora, and it s only getting bigger and better. The mall is currently undergoing a significant interior and exterior renovation, scheduled for completion
PARKVILLE HIGH SCHOOL LIMITED RENOVATION
PARKVILLE HIGH SCHOOL LIMITED RENOVATION DESIGN BRIEFING For Dr. Joe A. Hairston BALTIMORE COUNTY PUBLIC SCHOOLS August 11, 2009 Smolen 3 Emr + Associates Architects 1355 Piccard Drive, Suite 200 Rockville,
Vulnerability Assessment. U.S. Food Defense Team
Vulnerability Assessment U.S. Food Defense Team Vulnerability A weakness in a processing, handling or storage facility or operation that would allow for intentional contamination of a food product Vulnerability
29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York
Due Diligence Report New York, New York Prepared for Mr. On February 8, 2010 P a g e 1 Table of Contents PAGE 3.. GENERAL INFORMATION PAGE 4 FILINGS PERMITS AND ENCUMBRANCES PAGE 6. CORE AND SHELL PAGE
Commercial Building Valuation Report
INSURED State Office of Risk Management Effective Date: 300 W 15th Street Expiration Date: Austin, TX 78701 Cost as of: 12/2013 BUILDING 1 Athletics/PCI - 206 3302 N. Ben Wilson Victoria, TX 77901 Location
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
SECURITY VULNERABILITY CHECKLIST FOR ACADEMIC AND SMALL CHEMICAL LABORATORY FACILITIES
SECURITY VULNERABILITY CHECKLIST FOR ACADEMIC AND SMALL CHEMICAL LABORATORY FACILITIES by the American Chemical Society, Committee on Chemical Safety, Safe Practices Subcommittee Introduction Terrorism
Assessment of Existing Data Centers for Critical Facilities Round Table Group
Assessment of Existing Data Centers for Critical Facilities Round Table Group Chuck Shalley, P.E. Consulting Electrical Engineers BACKGROUND INFORMATION ASSIGNMENT Data Center Criteria Type Raised Floor
Preventative Maintenance
Preventative Maintenance Safety Committee To have a preventative maintenance plan, you should have a Safety Committee. Designate persons involved with day to day operations and grounds control. Use your
SYSTRUST CERTIFICATION REPORT FOR COLLOCATION AND DATA CENTER HOSTING SERVICES FOR THE PERIOD FROM JANUARY 1, 2013 TO DECEMBER 31, 2013
SYSTRUST CERTIFICATION REPORT FOR COLLOCATION AND DATA CENTER HOSTING SERVICES FOR THE PERIOD FROM JANUARY 1, 2013 TO DECEMBER 31, 2013 TABLE OF CONTENTS SECTION I: INDEPENDENT PRACTITIONERS TRUST SERVICES
Facility Assessment for. 11801 East Main Street, Huntley, IL
Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested
BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES
Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE
