O & M Manual for ATC-800, Open/Closed Transition Contactor Based Transfer Switch

Size: px
Start display at page:

Download "O & M Manual for ATC-800, Open/Closed Transition Contactor Based Transfer Switch"

Transcription

1 O & M Manual for ATC-800, Open/Closed Transition Contactor Based Transfer Switch Description Page Introduction Receiving, Handling, and Storage Equipment Description Installation and Wiring Operation Testing and Problem Solving Adjustments Maintenance Renewal Parts Guide ATC-800 Contactor Based ATS Quick Start Instructions...27 Appendix A: Pickup / Dropout Tables

2 Page 2 Effective: August 2010 WARNING READ AND UNDERSTAND THE INSTRUCTIONS CONTAINED HEREIN- AFTER BEFORE ATTEMPTING TO UNPACK, ASSEMBLE, OPERATE, OR MAINTAIN THIS EQUIPMENT. HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH ENCLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. FOLLOW PROPER INSTALLATION, OPERATION, AND MAIN- TENANCE PROCEDURES TO AVOID THESE VOLTAGES. TRANSFER SWITCH EQUIPMENT COVERED BY THIS INSTRUCTION BOOK IS DESIGNED AND TESTED TO OPERATE WITHIN ITS NAME- PLATE RATINGS. OPERATION OUTSIDE OF THESE RATINGS MAY CAUSE THE EQUIPMENT TO FAIL RESULTING IN DEATH, SERIOUS BODILY INJURY, AND/OR PROPERTY DAMAGE. ALL RESPONSIBLE PERSONNEL SHOULD LOCATE THE DOOR MOUNTED EQUIPMENT NAMEPLATE AND BE FAMILIAR WITH THE INFORMATION PROVIDED ON THE NAMEPLATE. A TYPICAL EQUIPMENT NAMEPLATE IS SHOWN IN FIGURE 1. CS#: Cat No: ATC8C2X20400WRU ITEM: 001 Style No: PIECE: 001 GO No: ABC0123 OF: 001 Volts: 240 Poles: 2 Amps: 400 Phase: 1 Hertz: 60 Wire: 3 J ASSEMBLED IN MEXICO WITH U.S. COMPONENTS Figure 1. Typical Automatic Transfer Switch (ATS) Equipment Nameplate. All possible contingencies that may arise during installation, operation, or maintenance, and all details and variations of this equipment do no purport to be covered by these instructions. If further information is desired by the purchaser regarding a particular installation, operation, or maintenance of particular equipment, please contact an authorized Eaton Sales Representative or the installing contractor. Section 1: Introduction 1.1 Preliminary Comments and Safety Precautions This technical document is intended to cover most aspects associated with the installation, application, operation, and maintenance of the Automatic Transfer Controller (ATC-800) controlled contactor based ATS with ratings from 40 through 400 amperes (A). It is provided as a guide for authorized and qualified personnel only. Please refer to the specific WARNING and CAUTION in Section before proceeding. If further information is required by the purchaser regarding a particular installation, application, or maintenance activity, please contact an authorized Eaton sales representative or the installing contractor Warranty and Liability Information No warranties, expressed or implied, including warranties of fitness for a particular purpose of merchantability, or warranties arising from course of dealing or usage of trade, are made regarding the information, recommendations and descriptions contained herein. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information and descriptions contained herein Safety Precautions All safety codes, safety standards, and/or regulations must be strictly observed in the installation, operation, and maintenance of this device. WARNING THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PRO- CEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONAL SAFETY AND PROTECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE OF A TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE TO FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION. THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO WARNINGS, WHICH APPEAR THROUGHOUT THE DOCUMENT. IN ADDITION, WARNINGS AND CAUTIONS ARE ALL UPPER CASE AND BOLDFACE. CAUTION COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERA- TION, OR APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY QUALIFIED PERSONS SHOULD BE PERMITTED TO PERFORM ANY WORK ASSOCIATED WITH THIS EQUIPMENT. ANY WIRING INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOL- LOWED PRECISELY. FAILURE TO DO SO COULD CAUSE PERMANENT EQUIPMENT DAMAGE.

3 Effective: August 2010 Page General Information Transfer switches are used to protect critical electrical loads against loss of power. The load s Source 1 power source is backed up by a Source 2 power source. A transfer switch is connected to both the Source 1 and Source 2 power sources and supplies the load with power from one of the two sources. In the event that power is lost from Source 1, the transfer switch transfers the load to the Source 2 power source. This transfer is automatic. Once Source 1 power is restored, the load is automatically transferred back to the Source 1 power source (Figure 2). Source 1 Source 2 and the Source 2 power source fails while the Source 1 power source is still unavailable, the ATS remains connected to the Source 2 power source. ATSs automatically perform the transfer function and include three basic elements: 1. A power contactor to connect and disconnect the load to and from either power source. 2. Solenoids to make the transfer of the main contacts from source to source. 3. Intelligence/supervisory circuits to constantly monitor the condition of the power sources and thus provide the intelligence necessary for the switch and related circuit operation Design Configuration The Eaton contactor based ATS is a compact design that uses a power contactor to transfer essential loads from one power source to another (Figure 3 [100A]). Load Figure 2. Typical Load Transfer Switch Schematic (Contactor Type). In ATS equipment, the switch s intelligence system initiates the transfer when the Source 1 power fails, falls below, or rises above a preset voltage. If the Source 2 power source is a standby generator, the ATS initiates generator startup and transfers to the Source 2 power source when sufficient generator voltage is available. When Source 1 power is restored, the ATS automatically transfers back and initiates generator shutdown. In the event the Source 1 power source fails and the Source 2 power source does not appear, the ATS remains connected to the Source 1 power source until the Source 2 power source does appear. Conversely, if connected to the Source 2 power source Figure 3. Typical Power Panel for a 100A Open Transition ATS. The Eaton contactor based ATS was designed with easy installation and simplified maintenance in mind. Three main panels comprise the contactor based ATS design: 1. Power panel; 2. Voltage selection and transformer panel (if required); and 3. Microprocessor-based logic panel.

4 Page 4 Effective: August 2010 Figure 4. Open Transition Contactor Based ATS (100A). Each panel is independently mounted with interconnecting wiring terminated at the connector receptacles on the ATC-800 Controller. Door or individual panel removal is achieved without disturbing critical connections by removing the connectors from the receptacles and cutting the wire ties that secure the wires to the door. Mounting the enclosure is simple using top and bottom mounting flanges with elongated (teardrop) mounting holes. These mounting holes, along with power panel positioning bolts and pretapped inserts, insure proper power panel mounting after the initial enclosure installation. Refer to Section 4 for specific mounting and modification details. Figure 5. Closed Transition Contactor Based ATS (100A). Table 1. Withstand Ratings. UL 1008 WITHSTAND AND CLOSE-ON RATINGS (ka) 480 Vac 600 Vac Switch Rating (Amps) Any Specific Any Specific Breaker Breaker Breaker Breaker (Amps) Amps) Amps) Amps) 100A 10,000 30,000 10,000 22, A 10,000 30,000 22,000 35, A 30,000 50, A 30,000 50, A 30,000 50, A (Close Transition) 10,000 30,000 10,000 22, A (Close Transition) 10,000 30,000 22,000 35, ATS Catalog Number Identification Transfer switch equipment catalog numbers provide a significant amount of relevant information that pertains to a particular piece of equipment. The Catalog Number Identification Table (Table 2) provides the required interpretation information. An example is offered here to initially simplify the process. Example: Catalog Number (circled numbers correspond to position headings in Table 2). 1to to to AT C 8 C2 X W R U The catalog number ATC8C2X20400WRU describes an ATS with a 2 pole, 2 position Power Contactor mounted on a baseplate within the enclosure. The intelligence represented by the logic panel is ATC-800 controller. The continuous current rating of this equipment is 400A and applicable at 240 Vac, 60 Hz. The transfer switch equipment is enclosed in a NEMA 3R enclosure and is listed for UL applications.

5 Effective: August 2010 Page 5 Table 2. Transfer Switch Catalog Number Explanation POSITIONS 1 TO 2 POSITION 3 POSITION 4 POSITIONS 5 TO 6 BASIC DEVICE SWITCHING DEVICE CONTROL PANEL SWITCHING DEVICE Automatic Transfer Switch (Open Transition) AT Automatic Transfer Switch (Closed Transition) CT Contactor C ATC-800 Controller 8 2 Position Power Contactor C2 POSITION 7 POSITION 8 POSITIONS 9 TO 12 POSITION 13 POSITION 14 POSITION 15 SWITCHING DEVICE ARRANGEMENT NUMBER OF POLES AMPERE RATING VOLTAGE/ FREQUENCY ENCLOSURE LISTING Fixed Mount X Two (2) 40A Vac/60 Hz B Type 1 S UL/CSA Listing U Three (3) 80A Vac/50 Hz G Type 12 J No Listing X Four (4) 100A Vac/60 Hz W Type 3R R 150A Vac/50 Hz H Open K 200A Vac/50 Hz O *225A Vac/60 Hz X *260A Vac/60 Hz E *400A 0400 *For 225A to 400A, 600 Vac application, please refer to IB E. 1.4 Environmental Conditions Operational Conditions Normally, an ATS is applied indoors in an electrical equipment room. In the appropriate enclosure, it can be used for outdoor applications where the equipment is subject to falling rain, freezing temperatures, and no greater than 90% humidity (non-condensing). The ambient temperature range for operation is between -20 and 70 C (-4 to 158 F). 1.5 Glossary With respect to their use within this document and as they relate to transfer switch and controller operation, the following terminology is defined. Available A source is defined as available when it is within its undervoltage/overvoltage/ underfrequency/overfrequency (if applicable) setpoint ranges for the nominal voltage and frequency setting. Connected Connected is defined as when the input is shorted by an external contact or connection. Failed or Fails A source is defined as failed when it is outside of the applicable voltage and frequency setpoint ranges for the nominal voltage and frequency setting for a time exceeding 0.5 seconds after the time delay emergency fail (TDEF) time delays expires. Source 1 Source 1 is the primary source (normal source, normal power source, or normal). Source 2 Source 2 is the secondary source (emergency source, emergency power source, emergency, standby, or backup source). Source 1: Failed or Fails Source 1 is defined as failed when it is outside of its undervoltage/overvoltage/ underfrequency/overfrequency (if applicable) setpoint ranges for the nominal voltage and frequency setting. Source 2: Failed or Fails Source 2 is defined as failed when it is outside of its undervoltage/overvoltage/ underfrequency/overfrequency (if applicable) setpoint ranges for the nominal voltage and frequency setting for a time exceeding 0.5 seconds after the Time Delay Emergency Fail (TDEF) time delay expires. Transfer Transfer is defined as a change of the load connection from the Source 1 to the Source 2 power source. Unconnected Unconnected is defined as when the input is not shorted by an external contact or connection. Failsafe Failsafe is a feature that prevents disconnection from the only available power source and also forces a transfer or re-transfer operation to the only available power source. Re-Transfer Re-transfer is defined as a change of the load connection from the Source 2 to the Source 1.

6 Page 6 Effective: August 2010 Section 2: Storage 2.1 Receiving Receiving, Handling, and Every effort is made to ensure that the ATS equipment arrives at its destination undamaged and ready for installation. Packing is designed to protect internal components as well as the enclosure. Care should be exercised, however, to protect the equipment from impact at all times. Do not remove the protective packaging until the equipment is ready for installation. When the ATS equipment reaches its destination, the customer should inspect the shipping container for any obvious signs of rough handling and/or external damage that occurred during transportation. Record any external and internal damage for reporting to the transportation carrier and Eaton, once a thorough inspection is complete. All claims should be as specific as possible and include the catalog and General Order numbers. A shipping label affixed to the shipping container includes a variety of equipment and customer information, such as General Order Number and catalog numbers. Make certain that this information matches other shipping paper information. Each transfer switch is packed securely with appropriate shipping materials to prevent damage during shipment. Do not remove or discard the packing material until the equipment is ready for installation. Once the top packaging is removed from the shipment, the enclosure door can be opened. A plastic bag of documents will be found in the enclosure, usually attached to the inside of the enclosure. Important documents, such as test reports, wiring diagrams, and appropriate instruction leaflets, are enclosed within the bag and should be filed in a safe place. 2.2 Handling As previously mentioned, ATS equipment is packaged for forklift movement. Protect the equipment from impact at all times and DO NOT double stack. Once the equipment is at the installation location and ready to be installed, packaging material can be removed and discarded. Once the enclosure is unbolted from the wooden pallet, it can be hand moved to its installation position. Be careful not to damage the top or bottom enclosure mounting flanges. Refer to Section 4 of this manual for specific installation instructions. 2.3 Storage Although well packaged, this equipment is not suitable for outdoor storage. The equipment warranty will not be applicable if there is evidence of outdoor storage. If the equipment is to be stored indoors for any period of time, it should be stored with its protective packaging material in place. Protect the equipment at all times from excessive moisture, construction dirt, corrosive conditions, and other contaminants. It is strongly suggested that the package-protected equipment be stored in a climate-controlled environment with temperatures from -30 to 85 C (-22 to 185 F) and with a relative humidity of 80% or less. DO NOT, under any circumstance, stack other equipment on top of a transfer switch equipment enclosure, whether packaged or not.

7 Section 3: 3.1 General Equipment Description The ATS consists of three basic panels: 1. The power panel; 2. The voltage selection and transformer panel (if required); and 3. The microprocessor-based logic panel. These panels are interconnected via connector plugs and mounted in an enclosure (see Figures 6 and 7). VOLTAGE SELECTION PANEL Effective: August 2010 Page 7 LOGIC PANEL POWER PANEL LOGIC PANEL POWER PANEL VOLTAGE SELECTION PANEL Figure 7. Three Basic Panels of the Closed Transition ATS (40-400A). 3.2 Power Panel Figure 6. Three Basic Panels of the Open Transition ATS (40-400A). The power panel is used for making load, power, and neutral connections. The power contactor is mounted on a steel baseplate (Figure 8) Main Contacts This ATS incorporates a power contactor. The main contacts connect and disconnect the load to and from the different power sources. The power contactor is mechanically and electrically interlocked to prevent the two sets of main contacts from being closed simultaneously.

8 Page 8 Effective: August 2010 Figure 8. Typical Power Panel for A Open Transition ATS. 3.3 Voltage Selection Standard Voltage Selection (208, 240, 480, 600 V, - 60 Hz & 220, 380, 415 V, - 50 Hz) The standard voltage selection panel consists of multi-tap transformers, contained in a steel case mounted in the enclosure (Figure 9). The voltage is selected by simply removing the wires from the default primary taps of both transformers and installing them on the primary taps for the desired voltage. Taps are provided for 208 to 600 Vac to satisfy application voltage. The factory default position is 600 Vac. CAUTION WHEN CHANGING THE SELECTED VOLTAGE, THE POWER MUST BE REMOVED FROM THE ATS AND THE WIRES MUST BE MOVED ON THE TAPS OF BOTH TRANSFORMERS. Figure 9. Standard Voltage Selection Terminals (Shown Connected to the 480 Vac Taps). 3.4 ATC-800 Logic Panel The ATC-800 is a microprocessor-based transfer switch logic control package. The hardware and software of the controller contain the intelligence/supervisory circuits that constantly monitor the condition of the power sources. It provides the intelligence necessary for the operation of the ATS (Figure 10). Figure 10. ATC-800 Logic Control Panel.

9 Effective: August 2010 Page 9 The ATC-800 controller has an operating temperature of -20 to 70 C (-4 to 158 F). The controller circuit board is protected by an insulating conformal coating. The specifications, under normal operating conditions, are as follows: Tolerance for voltage sensing function: ±1% of full scale. Tolerance for frequency sensing function: ±0.3 Hz of setting. 3.5 Features A variety of standard and optional features are available for Eaton ATSs. All features or combinations of features may not be available on specific ATSs. All features and/or accessories are Underwriters Laboratories (UL) listed unless noted Operational Simplicity From installation to programming to usage, the ATC-800 was designed with operational simplicity in mind. Only one style needs to be considered, regardless of input/output requirements or system voltages and frequencies. The ATC-800 provides the functionality of numerous other devices combined in one package that mounts in less than 7 x 11 in. (177.8 x mm) of panel space. The user friendly front panel interface simplifies routine operation, programming, data presentation and setting adjustments. An LED based display provides the flexibility of large character displays for enhanced visibility. The operation of front panel membrane pushbuttons moves the ATC-800 display from function to function or step to step within a function. Three LEDs at the top of the faceplate provide an immediate indication as to the device s operational mode. An integral Help Mode provides immediate user assistance in the form of English language message displays through the use of a front panel Help pushbutton. With a Product Operated Network Interface (PONI), the ATC-800 is communications ready and compatible with other devices in the IQ Family of products. The Communication Module (PONI) is available in three versions, the INCOM PONI, RS-232 PONI and PONI Modem. Reliable two-way communications can be provided over a twisted pair communications network. With the INCOM PONI, ATC-800 is compatible with the Eaton IMPACC system Standard and Optional Features A variety of programmable features are available to meet a wide variety of application requirements. Individual features or feature combinations provide the intelligence required to tailor switches to individual needs. The features are factory activated, depending upon customer requirements. The specific variable setpoints associated with standard and factory activated features are stored in a nonvolatile memory. Activated feature setpoints are available for customer adjustment. Any feature not selected and factory activated cannot be viewed or adjusted. NOTICE WITH RESPECT TO THEIR USE IN THIS DOCUMENT AND AS THEY RELATE TO AUTOMATIC TRANSFER SWITCH OPERATION, THE FOL- LOWING WORDS OR PHRASES ARE DEFINED: Available A source is defined as available when it is within its undervoltage/overvoltage/underfrequency/overfrequency (if applicable) setpoint ranges for the nominal voltage and frequency setting. Fails A source is defined as failed when it is outside of its undervoltage/overvoltage/underfrequency/overfrequency (if applicable) setpoint ranges for the nominal voltage and frequency setting. Normal Source The Normal Source is defined as the source that is preferred. The Preferred Source setting allows the operator to select Source 1, Source 2 or NONE as the Preferred Source. If NONE is chosen, the Preferred Source or the Normal Source will be the source that is presently attached to the load. If the Preferred Source feature is not available from the factory, the default is set as being Source 1 as the Preferred and Normal Source. Emergency Source The Emergency Source is defined as the source that is not preferred. If NONE is chosen for the Preferred Source setting, the Emergency Source will be the source that is presently not attached to the load. Therefore, in this condition after a transfer, what was the Normal and Emergency Sources will switch between Source 1 and 2. If the Preferred Source feature is not available from the factory, the default is set with Source 2 as the Emergency Source. Option # For personnel who are familiar with previous transfer switch controller option specifications, an attempt at equivalence to some of the features is made. ATC-800 features with a brief description follow. The actual programmable setpoints for each feature are covered in Section 10, Table 6. Standard Feature 1: Time Delay Normal to Emergency (TDNE) TDNE delays the transfer to the Emergency Source to permit stabilization of the Emergency power source before the transfer is made. This timer will begin the countdown from its setting value when the Emergency Source becomes available. If the Normal Source should become available during the countdown of this timer, the timer will be aborted. Standard Feature 2: Time Delay Engine Start (TDES) TDES is used where the source is an engine generator. It delays initiation of the engine start circuit in order to override momentary power outages and/or fluctuations. This timer and the associated engine start circuit will operate with or without control power. There are two separate start circuits, one for each source when applications of two generators are selected, although the same TDES timer value is used for both. When one generator is selected, this timer s engine start circuit will operate on generator 2 for source 2. If the source that is being transferred to has a generator and that source is already available, the TDES timer is bypassed. Standard Feature 3: Time Delay Emergency to Normal (TDEN) TDEN delays the transfer to the Normal Source to permit stabilization of the Normal power source before the transfer is made. This timer will begin the countdown from its setting value when the Normal Source becomes available. During the countdown of this timer, if the Normal Source should become unavailable, the timer will be aborted. If the Preferred Source is available and the Emergency Source fails while the TDEN timer is counting down, the TDEN timer will be bypassed. Standard Feature 4: Time Delay for Engine Cool-Off (TDEC) TDEC permits the generator to run under a no-load condition after a transfer from the generator source has been made. Countdown timing begins when the transfer is completed. In applications where two generators are selected, the same cool-off timer setting value is used for both.

10 Page 10 Effective: August 2010 Standard Feature 7: Time Delay Emergency Failure (TDEF) TDEF is used where at least one source is an engine generator. TDEF will delay an available source from being declared unavailable in order to override momentary generator fluctuations. This time delay is only implemented when the load is connected to a generator source. TDEF is not displayed when the number of generators is zero. Standard Feature 12: Power Source Annunciation LEDs are used to indicate the device s mode of operation, the status of the system, and the operations and/or conditions of displayed functions. Three LEDs at the top of the ATC-800 provide a quick snapshot of the unit s status (Mode). Seven LEDs, just above the display window, indicate which portions of the mimic bus are active, and the actual status of both sources and load. The remaining seven LEDs, just below the display window, are lit to indicate the identity of information being displayed. Unit Status LED This LED blinks green indicating that the ATC-800 is operating and providing the transfer switch control function in keeping with programmed setpoints. If the LED is not lit or is on continuously, a problem may be indicated. Test Mode LED This LED is lit red upon entering the Test Mode. The Test Mode can only be entered with the LEDs below the display window not lit. When a test is initiated, the Status LED lights. Both LEDs will turn off upon the successful completion of a test cycle. Program Mode LED This LED is lit red when the Run/Program switch on the rear of the chassis is in the Program position. This condition permits programming of control setpoints. When the setpoints LED is lit indicating that existing setpoints can be changed, the Program Mode LED blinks. 12C: Source 1 Connected - Status LED This LED is lit green if Source 1 is connected. This is accomplished by sensing the Source 1 breaker via the S1 closed auxiliary contact. 12D: Source 2 Connected - Status LED This LED is lit red if Source 2 is connected. This is accomplished by sensing the Source 2 breaker via the S2 closed auxiliary contact. 12G: Source 1 Available - Status LED This LED is lit amber if Source 1 meets the criteria for programmed Source 1 setpoints. 12H: Source 2 Available - Status LED This LED is lit amber if Source 2 meets the criteria for programmed Source 2 setpoints. Source 1 Preferred - Status LED This LED is lit red if Source 1 is the preferred source choice. Source 2 Preferred - Status LED This LED is lit red if Source 2 is the preferred source choice. Load Energized - Status LED This LED is lit red if the load is connected to a source that is available. CAUTION LOAD ENERGIZE LED IS NOT A POSITIVE INDICATION THAT VOLT- AGE IS NOT PRESENT ON THE LOAD TERMINALS. Status - Display LED This LED is lit red when action is occurring, such as a timer timing down, and one of the other display categories has not been selected. When the action is completed, the display goes blank and the LED turns off. The Status position is the default position of the display. Source 1 - Display LED This LED is lit green when displaying Source 1 voltage, frequency, and status information. The LED also lights when displaying specific Source 1 setpoint information. Source 2 - Display LED This LED is lit red when displaying Source 2 voltage, frequency, and status information. The LED also lights when displaying specific Source 2 setpoint information. Load - Display LED This LED is lit red when load voltage is being displayed. History - Display LED This LED is lit red when displaying historical information. Time/Date - Display LED This LED is lit red when displaying the time or date. Setpoints - Display LED This LED is lit red when displaying the programmed setpoints of the ATC-800. When a specific displayed setpoint is associated with one of the sources, the specific source LED will also be lit. CAUTION CHANGING THE SYSTEM NOMINAL VOLTAGE OR FREQUENCY SET- POINTS WILL CAUSE PICKUP AND DROPOUT SETPOINTS TO CHANGE AUTOMATICALLY TO NEW DEFAULT VALUES. Standard Feature: System Nominal Frequency (NOMF) There are only two choices for system nominal frequency of the distribution system, 50 or 60 Hertz. The dropout/pickup, underfrequency and overfrequency upper and lower setting limits are based on the nominal frequency value. Standard Feature: System Nominal Voltage (NOMV) This refers to the standard system nominal RMS line to line voltage. A wide range (120 to 600) of sensing voltage is available to be programmed. The dropout/pickup, undervoltage and overvoltage upper and lower setting limits are based upon the nominal voltage value. Standard Feature: Commit to Transfer During TDNE Timing (CTDNE) This feature provides for selection as to whether or not commitment to transfer is desired when Time Delay Normal to Emergency countdown has begun. If no commitment is chosen and the Normal Source returns to availability when the TDNE timer is counting down, the transfer is aborted and the engine generator (if applicable) is cooled down. Standard Feature: Engine Test Mode (TMODE) This feature provides selection of the type of test that can be initiated by the front panel Engine Test pushbutton. An engine test without transferring the load to it, or an engine test with a full transfer of the load to the engine can be chosen. Load testing is fail-safe. If the generator fails during testing for any reason, the ATC-800 will signal the transfer switch to return to normal. If disable test mode is chosen, the front panel pushbutton cannot be used to initiate a test.

11 Effective: August 2010 Page 11 Standard Feature: Test Engine Run (TER) This feature provides selection of the length of time in hours and minutes that the ATC-800 will enable the generator contacts during an Engine Test that was initiated from the front panel pushbutton or for the plant exerciser feature, if applicable. Standard Feature 5J: Undervoltage Monitoring for Source 2 (2UVD, 2UVP) This feature constantly monitors Source 2 for an undervoltage condition. When the Source 2 voltage drops to a value equal to or below the undervoltage dropout setting, the source will become unavailable. The source s voltage will then have to rise to a value that is equal to or above the pickup setting to become available again. Underfrequency Monitoring for Source 2 (2UFD, 2UFP) This feature constantly monitors Source 2 for an underfrequency condition. When the Source 2 frequency drops to a value equal to or below the underfrequency dropout setting, the source will become unavailable. The source s frequency will then have to rise to a value that is equal to or above the pickup setting to become available again. Standard Feature 5K: Overvoltage Monitoring for Source 2 (2OVD, 2OVP) This feature constantly monitors Source 2 for an overvoltage condition. When the Source 2 voltage rises to a value equal to or above the overvoltage dropout setting, the source will become unavailable. The source s voltage will then have to drop to a value that is equal to or below the pickup setting to become available again. Overfrequency Monitoring for Source 2 (2OFD, 2OFP) This feature constantly monitors Source 2 for an overfrequency condition. When the Source 2 frequency rises to a value equal to or above the overfrequency dropout setting, the source will become unavailable. The source s frequency will then have to drop to a value that is equal to or below the pickup setting to become available again. Standard Feature 6B: Test Pushbutton Programmable setpoints include: 1. Load or No Load Testing, or Disabled 2. Engine run time equal to the plant exerciser (Feature 23) setting Standard Feature 8C/8D: Transfer Time Delay Bypass This feature allows an external pushbutton input to be used to bypass the timer for Standard Feature (TDNE) or Standard Feature (TDEN) individually, or both simultaneously. This feature is usually used in testing when it is not desirable to wait for completion of the timing sequence. Standard Feature 14: Relay Auxiliary Contacts This feature provides form C relay auxiliary contacts. Standard Feature 14E: Source 1 Present Provides one (1) normally open and one (1) normally closed contacts. The relay is energized when Source 1 is available. Standard Feature 14F: Source 2 Present Provides one (1) normally open and one (1) normally closed contacts. The relay is energized when Source 2 is available. Standard Feature 15: Switch Position Indication Contact This feature provides a contact that indicates if the powerswitching device is in the Open or Closed position. Standard Feature 15E: Source 1 Position Indication Contact This feature provides one (1) Dry Form C contact that indicates the position of the Source 1 power-switching device. Standard Feature 15F: Source 2 Position Indication Contact This feature provides one (1) Dry Form C contact that indicates the position of the Source 2 power-switching device. Standard Feature 23J: Plant Exerciser (EXER) This feature provides for the automatic test operation of the generator for a pre-selected weekly interval. When the test is running, pressing and releasing the Engine Test pushbutton will cancel the test. The day of the week, hour, and minute that exercising is desired can be programmed into the ATC-800. The type of test, whether a load transfer or just an engine test, can also be selected. Load testing is fail-safe. If the generator fails during testing for any reason, the ATC-800 will signal the transfer switch to return to normal. Standard Feature 26D: Go To Emergency This feature enables an external contact closure to initiate a transfer from the Normal Source to the Emergency Source. If the external contact is closed and the Emergency Source fails, the ATC-800 will transfer the load back to the Normal Source. Standard Feature 26J: Undervoltage Monitoring for Source 1 (1UVD, 1UVP) This feature constantly monitors Source 1 for an undervoltage condition. When the Source 1 voltage drops to a value equal to or below the undervoltage dropout setting, the source will become unavailable. The source s voltage will then have to rise to a value that is equal to or above the pickup setting to become available again. Underfrequency Monitoring for Source 1 (1UFD, 1UFP) This feature constantly monitors Source 1 for an underfrequency condition. When the Source 1 frequency drops to a value equal to or below the underfrequency dropout setting, the source will become unavailable. The source s frequency will then have to rise to a value that is equal to or above the pickup setting to become available again. Standard Feature 26K: Overvoltage Monitoring for Source 1 (1OVD, 1OVP) This feature constantly monitors Source 1 for an overvoltage condition. When the Source 1 voltage rises to a value equal to or above the overvoltage dropout setting, the source will become unavailable. The source s voltage will then have to drop to a value that is equal to or below the pickup setting to become available again. Overfrequency Monitoring for Source 1 (1OFD, 1OFP) This feature constantly monitors Source 1 for an overfrequency condition. When the Source 1 frequency rises to a value equal to or above the overfrequency dropout setting, the source will become unavailable. The source s frequency will then have to drop to a value that is equal to or below the pickup setting to become available again. Standard Feature 36: Emergency Inhibit This feature enables the Emergency Inhibit control input to inhibit transfers to the Emergency Source. See Control Inputs section for more information. Standard Feature 42: Seismic Withstand Capability Provides transfer switch with seismic capability exceeding the worst case Zone 4 required per both the Uniform Building Code and the California Building Code.

12 Page 12 Effective: August 2010 Optional Feature 5H: Phase Reversal Protection (Source 2) For a 3-phase wye or delta source, this feature monitors the phase sequence of the sources using an external reverse phase sensing relay. If a source does not have the same ABC or CBA sequence as the phase reversal setpoint, that source will be considered Unavailable. Optional Feature 5L: Source 2 All Phase Voltage Unbalance / Phase Loss Phase unbalance relay has two external user adjustable controls marked UNBAL & DELAY. The UNBAL control adjusts the relay trip point. The relay will trip when voltage becomes unbalanced by the percentage set by UNBAL control. The trip point is adjustable from 5% to 15% of nominal input. The delay control adjusts the time from when a fault is detected until the output contact changes state. The delay is adjusted from 0 to 10 seconds. Optional Feature 9B: Maintenance Selector Switch (MSS) Marked OFF, ON. This feature provides selector switch disconnection of control to transfer thus allowing testing of the transfer switch control logic circuitry without initiating load transfer. Positioning the MSS in the OFF position isolates the control circuit, permitting manual operation of the transfer switch or testing of logic circuitry without load transfer. Optional Feature 10: Preferred Source Selection (PRF SRC) This feature permits the selection of either source (1 or 2) as the Preferred or Normal Source. The Normal Source is the source that the switch always looks to for availability so that it can transfer to it. When two generators are selected and the switch has transferred to the Emergency Source, the ATC-800 will constantly be waiting and attempting to start the generator on the Preferred Source so that it may return to it. IF NONE is chosen, the Preferred Source or the Normal Source will be the source that is presently attached to the load. Optional Feature 14: Relay Auxiliary Contact This feature provides form C relay auxiliary contacts. Optional Feature 14C: Source 1 Present Provides four (4) normally open and four (4) normally closed contacts. The relay is energized when Source 1 is available. Optional Feature 14D: Source 2 Present: Provides four (4) normally open and four (4) normally closed contacts. The relay is energized when Source 2 is available. Optional Feature 14G: Source 1 Present: Provides two (2) normally open and two (2) normally closed contacts. The relay is energized when Source 1 is available. Optional Feature 14H: Source 2 Present: Provides two (2) normally open and two (2) normally closed contacts. The relay is energized when Source 2 is available. Optional Feature 15: Switch Position Indication Contact This feature provides a contact that indicates if the power switching device is in the Open or Closed position. Optional Feature 15G: Source 1 Position Indication Contact This feature provides 3 Dry Form C contacts that indicate the position of the Source 1 power-switching device. Optional Feature 15H: Source 2 Position Indication Contact This feature provides 3 Dry Form C contacts that indicate the position of the Source 2 power-switching device. Option-18 Metering This feature includes all required external devices (CTs, shorting blocks, fuses, etc.) for a fully functional metering system. Option-18O IQ Analyzer Normal (S1) Only Option-18P IQ Analyzer Emergency (S2) Only Option-18Q IQ Analyzer Normal (S1) & Emergency (S2) Switch Selectable Option-18V IQ Analyzer Load Option-18R IQ DP-4000 Normal (S1) Only Option-18S IQ DP-4000 Emergency (S2) Only Option-18T IQ DP-4000 Normal (S1) & Emergency (S2) Switch Selectable Option-18U IQ DP-4000 Load Option-18AN IQ 250/260 Normal (S1) Only Option-18AE IQ 250/260 Emergency (S2) Only Option- 8AL IQ 250/260 Load Optional Feature 23L: 24 Hour, 7 Day, 365 Day Programmable Plant Exerciser This plant exerciser has two channel electronic time switches with 365-day, 7-day, 24-hour programming. Each channel can be independently programmed and can provide up to 400 events. The plant exerciser offers daily, weekly or annual programming capability with up to 99 separate holiday periods of any duration and priority. An LCD display indicates load status, time-of-day, weekday & date. Optional Feature 26H: Phase Reversal Protection (Source 1) For a 3-phase wye or delta source, this feature monitors the phase sequence of the sources using an external reverse sensing relay. If a source does not have the same ABC or CBA sequence as the phase reversal setpoint, the source will be considered Unavailable. Optional Feature 26L: Source 1 All Phase Voltage Unbalance / Phase Loss Phase unbalance relay has two external user adjustable controls marked UNBAL & DELAY. The UNBAL control adjusts the relay trip point. The relay will trip when voltage becomes unbalanced by the percentage set by UNBAL control. The trip point is adjustable from 5% to 15% of nominal input. The delay control adjusts the time from when a fault is detected until the output contact changes state. The delay is adjusted from 0 to 10 seconds. Optional Feature 29G: Auto/Manual Operation (Available for 3-Position ATS only) This feature provides 2-position auto/manual selector switch marked Auto/Manual which permits the selection of automatic or manual operation. Once the selector switch is transferred to manual mode, manual transfer between Normal (S1), Neutral and Emergency (S2) can be achieved by operating 3-position selector switch marked Normal-OFF-Emergency. Optional Feature 29G: Auto/Manual Operation (Available for 2-Position ATS only) This feature provides 2-position auto/manual selector switch marked Auto/Manual which permits the selection of automatic or manual operation. Once the selector switch is transferred to manual mode, manual transfer between Normal (S1) and Emergency (S2) can be achieved by operating another 2-position selector switch marked Normal-Emergency.

13 Effective: August 2010 Page 13 Optional Feature 29J: Type of Operation (MANTR) This feature provides for a selection between an automatic transfer and re-transfer mode or a manual pushbutton re-transfer to Normal from the Emergency Source mode. If this option is not selected the factory default selection is automatic. Optional Feature 32A: Time Delay Neutral (TDN) (Available for Open Transition 3-Position ATS Only) This feature provides a time delay in the transfer switch Neutral position when both breakers are open. This delay takes place when the load is transferred in either direction to prevent excessive in-rush currents due to out-of-phase switching of large motor loads. This feature is not available with the Neutral Load Sense Delay (TDNLD) feature. Optional Feature 32B: Load Voltage Decay (LDCY) (Available for Open Transition 3-Position ATS Only) This feature utilizes the load voltage measurements to sense back EMF that is generated when the transfer switch is in the Neutral position. It provides a delay in transfer in either direction if an unacceptable level is sensed as established by a customer programmed level. The transfer will not take place until the back EMF decays below the acceptable programmed level. This feature has a separate setting of enabling or disabling the operation. If disabled, the transfer switch will not delay in the Neutral position and will transfer between the sources as fast as possible. This feature is not available with the Time Delay Neutral (TDN) Feature 32A. Optional Feature 32F: In-Phase Transition (Available for Open Transition 2-position ATS Only) Provides In-Phase transition, which is a feature that will permit a transfer or re-transfer between 2 available sources that have a phase angle difference of 8 degrees or less. The In-Phase transition feature includes permissible frequency difference and synchronization time setpoints. In the event Source 1 and Source 2 fail to synchronize within the permitted frequency difference and time, the Alarm relay will energize and Failed to Sync will be displayed on Line 1. After resetting the alarm, another in-phase transition may be attempted or a non-synchronized transfer may be initiated by failing the connected source. The adjustable frequency difference is 0.0 to 3.0 Hz. If the synchronization does not occur within a specified amount of time, the Alarm relay will energize and the failure will be logged into the Transfer History as either Sync Fail - Freq or Sync Fail - Phase depending on whether the frequency difference or the phase difference was excessive. Optional Feature 35: Pre-Transfer Signal (TPRE) Typically associated with elevator controls, this feature provides for the control of an addressable relay to remotely signal an elevator that a re-transfer is about to take place. A permissive report-back signal from the elevator, telling the ATC-800 that the elevator has reached the floor and opened its doors, is also recognized to facilitate faster transfer operation. Should the permissive signal not be used or does not occur, the ATC-800 has a programmed overriding pre-transfer delay timer that can be set from 0 to 5 minutes. Optional Feature 38: Stainless Steel Logic Cover Optional Feature 38A: Stainless Steel Cover for Device Panel Provides an added level of security by providing a pad lockable stainless steel cover for use with standard transfer switch device panel. The cover is designed for NEMA 1, 3R, 4X, and 12 applications. Optional Feature 38B: Stainless Steel Cover for Controller Provides an added level of security by providing a pad lockable stainless steel cover for use with standard transfer switch logic controllers and/or associated device panels. These covers function with Eaton s ATC series logic controllers and device panels. The covers are designed for NEMA 1, 3R, 4X, and 12 applications. Optional Feature 41: Space Heater With Thermostat This feature provides a space heater and non-adjustable thermostat. External control power is not required. Optional Feature 41A: Space Heater With Thermostat Watt This feature provides a 100 watt (W) space heater with a nonadjustable thermostat. Optional Feature 45: Load Sequencing Capability (TSEQ) This feature provides the sequential closure of up to 10 remote relays after a transfer. A customer programmed time delay is available to delay closure between each of the relays. Optional Feature 46: Potential Transformer (PT) Ratio This feature allows external voltage transformers to be used on the ATC-800 s source and load sense inputs. Once this option is enabled, the PT Ratio setpoint can be adjusted in steps of 1, between 2:1 and 500:1. Also when this option is enabled the Nominal System Voltage setting will be fixed at 120 or 110 volts, depending upon the Nominal System Frequency setting. If the Nominal System Frequency setting is 60Hz then the Nominal System Voltage will be fixed at 120 volts and all voltage pick-up and drop-out setpoints will be based upon the 120 volt level. The same is true of a Nominal System Frequency of 50Hz whose Nominal System Voltage will be fixed at 110 volts. The metering display will use the PT ratio value to calculate and display the load and source voltages with up to three significant digits. There will be four possible types of displays, as an example they could display 999K, 99.9K, 9.99K, or 999 volts.

14 Page 14 Effective: August 2010 Optional Feature 47D: Closed Transition Only (available for 3-position ATS only) Closed Transition is a feature that will temporarily parallel two live sources in a make-before-break scheme when performing a transfer. This achieves a transfer between sources with no power interruption. Both sources must be synchronized in frequency, phase, and voltage before the transfer is initiated. If the logic is forced into a fail safe mode (i.e. loss of connected source), the logic will perform a load voltage decay open transfer. Optional Feature 47F: Closed Transition/Time Delay Neutral Load Sense (available for 3-position ATS only) Closed Transition is a feature that will temporarily parallel two live sources in a make-before-break scheme when performing a transfer. This achieves a transfer between sources with no power interruption. Both sources must be synchronized in frequency, phase, and voltage before the transfer is initiated. Time Delay Load Voltage Decay utilizes the load voltage measurements to sense back EMF that is generated when the transfer switch is in the Neutral position. It provides a delay in transfer in either direction if an unacceptable level is sensed as established by a customer programmed level. The transfer will not take place until the back EMF decays below the acceptable programmed level. This feature has a separate setting of enabling or disabling the operation. If disabled, the transfer switch will not delay in the Neutral position and will transfer between the sources as fast as possible. This feature is not available with the Time Delay Neutral Optional Feature 32A. Optional Feature 47G: Closed Transition/Time Delay Neutral (available for 3-position ATS only) Closed Transition is a feature that will temporarily parallel two live sources in a make-before-break scheme when performing a transfer. This achieves a transfer between sources with no power interruption. Both sources must be synchronized in frequency, phase, and voltage before the transfer is initiated. Time delay neutral provides a time delay in the transfer switch neutral position when both breakers are open. This delay takes place when the load is transferred in either direction to prevent excessive in-rush currents due to out of phase switching of large motor loads. Optional Feature 48A: IPONI Module (INCOM Communication) Provides communications modules for the ATC-800 transfer switch controllers. These controllers are PowerNet and Modbus compatible devices. A separately mounted communications module will enable the automatic transfer controller to be remotely monitored controlled and programmed via the network. Optional Feature 48F: RS-232 and RS-485 with Modbus Provides communications for the ATC-800 via RS-232 or Modbus through an RS-485 port. Registers are available to read back status, voltages, frequencies, and historical data. Registers are also available for transfer switch control. Setpoints may be read back. Optional Feature 48D: PXG Gateway This Feature provides communication by using IPONI (INCOM communication module) at the back of ATC-800 controller. PXG400 Gateway serves as a communication protocol translator taking in INCOM, QCPort and MODBUS RTU and present data via Ethernet TCP/IP or Modbus TCP/IP. The data can then be accessed via the built-in web server, Power Xpert software or 3 rd party building management systems. PXG400 Gateway has a limit of 32 INCOM devices. For more information, refer to Eaton IB E. 24VDC is provided to PXG400 Gateway via ELC-PS02 power supply. Optional Feature 48R: Remote Annunciator This feature displays status information of a remotely located ATC-600/800 controller. The ATC Remote Annunciator will serially communicate with the ATC-600/800 over the INCOM subnetwork using a twisted shielded pair cable. External 120VAC power supply is required for operating ATC Remote Annunciator. Optional Feature 49B: Sensing Isolation Transformer (Up to 600 VAC only This feature provides 3-phase, 4-wire for Source-1 and Source-2 sensing input on ATC controller for a high resistance grounded delta system. Optional Feature 51D1: 50kA CVX Surge Device This feature gives protection for surge current capacity rating 50kA, upto 480VAC by providing a low impedance surge path to ground while supporting rated voltage. It provides LED indication. Optional Feature: 51F1:100kA CVX Surge Device This feature gives protection for surge current capacity rating 100kA, upto 480VAC by providing a low impedance surge path to ground while supporting rated voltage. It provides LED indication.

15 Effective: August 2010 Page Enclosure The rugged steel ATS enclosure is supplied with three door hinges, regardless of enclosure size. They ensure proper support of the door and door mounted devices (see Figures 11 and 12). The hinges have removable hinge pins to facilitate door removal. Certain procedures, such as switch mounting, are simplified with the door removed. The doors are supplied as standard with padlockable latches. The door is used to mount a variety of lights, switches, and push-buttons, depending upon the options required for a particular ATS. All lights and switches are mounted in the plastic doormounted panel. The rear of the enclosure is supplied with teardrop shaped holes in the top and bottom mounting flanges to facilitate mounting. It is also supplied with two positioning bolts and various pre-tapped inserts to insure proper positioning of the power panel anytime the power panel must be repositioned to accommodate a different cable entry position. Cable entry holes are the responsibility of the customer. ATS enclosures and all internal steel mounting plates, such as the power panel mounting plate, go through a pretreatment cleaning system prior to painting to ensure a durable finish. The standard ATS enclosure is NEMA 1 Type for general use. However, a variety of enclosures are available to address almost any environmental circumstance (see Table 3). Table 3. Transfer Switch Equipment Enclosures NEMA TYPE DESIGN PROTECTION Open Indoor 1 Indoor Enclosed Equipment 3R Outdoor Rain, Ice Formation 12 Indoor Dust, Dirt, and Non-Corrosive Liquids 3.7 Standards Figure 11. Typical Type 1 Open Transition ATS Enclosure (Door Closed). Eaton ATS equipment, enclosed in any of the enclosures listed in Table 3, is listed for application by UL and ULC. In addition, Eaton ATSs are listed in File E38116 by Underwriters Laboratories, Inc. under Standard UL This standard covers requirements for automatic transfer switches intended for use in ordinary locations to provide lighting and power as follows: a. In emergency systems, in accordance with articles 517 and 700 in the National Electrical Code, ANSI/ NFPA 70, and the National Fire Protection Association No. 76A; and/or b. In standby systems, in accordance with article 702 of the National Electrical Code; and/or c. In legally required standby systems in accordance with article 701 of the National Electrical Code. Eaton ATSs are available to meet NFPA 110 for emergency and standby power systems, and NFPA 99 for health care facilities when ordered with the appropriate options. Standard UL 1008 for ATSs lists devices under the reexamination program which only require a continual physical reexamination of the components used in the product to ensure consistency with the originally submitted device. Follow-up testing is not required by UL Figure 12. Typical Type 1 Closed Transition ATS Enclosure (Door Closed).

16 Page 16 Effective: August 2010 Section 4: 4.1 General Installation and Wiring Eaton ATSs are factory wired and tested. Installation requires solidly mounting the enclosed unit and connecting power cables and auxiliary pilot circuits. Physical mounting procedures and power cable connections are covered in this section. All other required wiring or electrical connection references are covered in a separate Customer Wiring Booklet packaged with the ATS. Locate the wiring schematic, review it, and keep it readily available for reference purposes during installation and testing. Once an ATS is properly installed and wired, it should be mechanically and electrically checked for proper installation and operation. The procedures for these initial mechanical and electrical checks are outlined in Section 6 of this instruction manual. WARNING BE CERTAIN THAT THE SOLID STEEL DOOR IS PROPERLY INSTALLED BEFORE THE TRANSFER SWITCH EQUIPMENT IS PUT INTO SERVICE. THE DOOR PROVIDES PROTECTION FROM DAN- GEROUS VOLTAGES AT THE LINE AND LOAD TERMINALS WHEN THE EQUIPMENT IS IN OPERATION. FAILURE TO DO SO COULD RESULT IN PERSONAL INJURY OR DEATH. 4.3 Mounting Procedure CAUTION SINCE THE ENCLOSED ATS MUST BE LIFTED INTO PLACE FOR MOUNTING, BE CERTAIN THAT ADEQUATE RESOURCES ARE AVAILABLE FOR LIFTING TO AVOID PERSONNEL INJURIES OR EQUIPMENT DAMAGE. All equipment enclosures and power panels are of the same design. Only the overall physical dimensions change. Note that the enclosure is provided with four teardrop (elongated) mounting holes, two in the top mounting flange and two in the bottom. Cable entry holes are not part of the enclosure when shipped from the factory and must be provided in the field, either before or after mounting the enclosure. Cable access may be from the top, bottom, and/or side. CAUTION EXTREME CARE SHOULD BE TAKEN TO PROTECT THE TRANSFER SWITCH FROM DRILL CHIPS, FILINGS, AND OTHER CONTAMI- NANTS WHEN MAKING THE CABLE ENTRY HOLES. EXTREME CARE SHOULD ALSO BE TAKEN WHEN MOUNTING THE ENCLO- SURE TO PREVENT COMPONENT DAMAGE OR A FUTURE MAL- FUNCTION. 4.2 Mounting Location Choose a location that offers a flat, rigid mounting surface capable of supporting the weight of the enclosed ATS equipment. For standard ATSs, avoid locations that are moist, hot, or dusty. However, Eaton offers optional enclosure designs that can be used in special environments. If there are any doubts as to a location s suitability, discuss them with your Eaton representative. Check to make certain that there are no pipes, wires, or other mounting hazards in the immediate mounting area that could create a problem. Carefully remove all packing material from the ATS at the mounting location. Even though an equipment inspection should have been made when the equipment was received, make another careful inspection of the enclosure and the enclosed ATS components as the packing material is removed and the enclosure readied for mounting. Be especially alert for distorted metal, loose wires, or damaged components. Figure 13.Typical (40A-400A) Open Transition Contactor Based ATS Equipment (Door Open).

17 Effective: August 2010 Page 17 Figure 14. Typical (40A-400A) Closed Transition Contactor Based ATS Equipment (Door Open). With the enclosed ATS equipment unpacked and ready for mounting, proceed with the following steps. Step 1: The ATS enclosure door is hinge mounted with removable hinge pins. To simplify the mounting procedure and avoid damaging the door-mounted logic panel, it is strongly suggested that the door be carefully removed and put it in a safe place until mounting is complete. To remove the door, open the door and disconnect the connectors at the back of the ATC-800 logic panel. Remove the wire ties securing the harness to the inside of the door. Carefully remove the hinge pins then the door from the enclosure. Step 2: Install the required upper and lower mounting bolt anchors and the two upper mounting bolts in the mounting surface. Step 3: Gently lift the enclosure and guide the teardrop holes in the upper mounting flange over the upper mounting bolts. Do not completely tighten the bolts at this time. Step 4: While still supporting the enclosure, install the two lower mounting bolts in the lower mounting flange. Again, do not completely tighten the bolts at this time. Use shims, if required, to prevent deformation of the enclosure if the mounting surface is distorted. Step 5: Tighten all four mounting bolts after any required shimming is completed. Figure 15.Typical Mounting of the ATS to a Mounting Surface. Step 6: Double check to ensure that all packing and shipping materials have been removed. 4.4 Power Cable Connections WARNING POWER CONDUCTORS MAY HAVE VOLTAGE PRESENT THAT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. DE-ENERGIZE ALL POWER OR CONTROL CIRCUIT CONDUCTORS TO BE CONNECTED TO THE ATS EQUIPMENT BEFORE BEGINNING TO WORK WITH THE CONDUCTORS AND/OR TERMINATING THEM TO THE EQUIPMENT. CAUTION USE OF CABLE LUGS NOT DESIGNED FOR THE ATS MAY CAUSE HEATING PROBLEMS.

18 Page 18 Effective: August 2010 CAUTION TO HELP PREVENT COMPONENT DAMAGE OR FUTURE MALFUNC- TIONS, USE EXTREME CARE TO KEEP CONTAMINANTS OUT OF THE ATS EQUIPMENT WHEN MAKING POWER CABLE CONNEC- TIONS. CAUTION RUN THE POWER CABLE THROUGH THE GUTTER SPACE PROVIDED TO THE RIGHT OR LEFT OF POWER PANEL. Test all power cables prior to connection to the unit to ensure that the conductors or cable insulation have not been damaged while being pulled into position. Power cables are to be connected to solderless screw type lugs located on the ATS switching devices. Refer to the separate Customer Wiring Booklet supplied with the ATS equipment for power termination. Verify that the lugs supplied will accommodate the power cables being used. Also verify that the cables comply with local electrical codes. Standard ATS equipment, as supplied from the factory, will accommodate the wire sizes shown in Table 4. Carefully strip the insulation from the power cables to avoid nicking or ringing of the conductor strands. Prepare the stripped conductor termination end by cleaning it with a wire brush. If aluminum conductors are used, apply an appropriate joint compound to the clean conductor surface area. WARNING IMPROPER POWER CABLE CONNECTIONS CAN CAUSE EXCESSIVE HEAT AND SUBSEQUENT EQUIPMENT FAILURE. Tighten the cable lugs to the torque identified on the label affixed to the door of the unit. 4.5 Wiring Power sources, load conductors, and control wiring should be connected to locations as indicated in the Customer Wiring Booklet supplied with the ATS equipment. Once the ATS equipment has been installed and wired, perform the initial mechanical and electrical procedures as outlined in Section 6 to verify that the equipment is installed and operating properly. 4.6 Engine Start Connection WARNING POWER CONDUCTORS AND CONTROL WIRING MAY HAVE VOLT- AGE PRESENT THAT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. DEENERGIZE ALL POWER OR CONTROL CIRCUIT CON- DUCTORS BEFORE BEGINNING TO PERFORM ANY WIRING ACTIV- ITY TO OR WITHIN THE ATS EQUIPMENT. CAUTION ENSURE THE ATS VOLTAGE IS SET CORRECTLY. IT SHOULD BE THE SAME AS THE SOURCE 1 AND SOURCE 2 LINE VOLTAGES. OPERATING THE EQUIPMENT ON IMPROPER VOLTAGE CAN CAUSE EQUIPMENT DAMAGE. The engine control contact connections are located on the logic panel of the ATS. Connect the engine start wires to the terminals marked 1 and 2 on J-5 connector on the ATC-800 Controller (see Figure 16). A contact closes between these terminal when an engine start signal is provided by the ATS logic. The wiring diagram provides additional engine start connection information. Use the proper wire size as listed by the generator set (Genset) manufacturer. NOTICE PRIOR TO MAKING THE ENGINE START CONNECTION TO THE SWITCH, SET THE ENGINE GENERATOR CONTROLS SELECTOR SWITCH IN THE OFF POSITION TO PREVENT AN UNWANTED ENGINE START. CONTROL WIRING, SUCH AS THE ENGINE START WIRES, MUST BE RUN IN A SEPARATE CONDUIT FROM THE POWER CABLES. Table 4. Transfer Switch Equipment Wire Sizes. TRANSFER SWITCH AMPERE RATING WIRE SIZE RANGES NUMBER OF CABLES PER PHASE TERMINAL TEMPERATURE RATING C ( F) 100 #14-2/ (167) 200 #6-250 KCMIL 1 75 (167) 320 #4-600 KCMIL or (2) 1/0-250 KCMIL 1 or 2 - depending on wire size used 75 (167) 400 #4-600 KCMIL or (2) 1/0-250 KCMIL 1 or 2 - depending on wire size used 75 (167) 600 #2-600 KCMIL 2 75 (167)

19 Effective: August 2010 Page 19 Communication Module Connector J4 (Inputs) Terminal Block (DC Wetted Contact) J5 (Outputs) Terminal Block (Dry Relay Contacts) Terminals J5-1 and J5-2 J1, J2, J3 Source/Load Program/Run Toggle Switch J7 Sources 1 and 2 Connector RIGHT SIDE VIEW LEFT SIDE VIEW Figure 16. Location of Terminals 1 and 2 on the J-5 Connector of ATC-800 Controller for Engine Start Connections.

20 Page 20 Effective: August Voltage Selection Adjustments Certain devices, such as the Voltage Selection Panel, sensing relays, and timers, need to be set and/or calibrated prior to placing the ATS equipment in service. Adjustments for logic devices are described in the separate instructional document dedicated to the specific logic being used. Voltage selection adjustments are described in this section. CAUTION BE SURE THAT THE CORRECT VOLTAGE IS SELECTED TO MATCH THE SYSTEM VOLTAGE. AN IMPROPER SELECTION AND/OR CON- NECTION COULD RESULT IN EQUIPMENT DAMAGE Standard Voltage Selection Panels (208, 240, 480, 600 V, - 60 Hz & 220, 380, 415 V, - 50 Hz) The standard voltage selection panel consists of multi-tap transformers, contained in a steel case mounted in the enclosure. To change the voltage from the factory default 600 Vac, follow the steps detailed below. Step 1: Loosen the six screws securing the cover of the Voltage Selection Transformer case. Slide the cover up, then away from the case. Step 2: Remove the wires from the primary taps of both transformers and installed them on the taps for the desired voltage (Figure 17B). Note that only one wire per transformer is moved since the second wire is the zero reference. Step 3: Reinstall the cover and tighten the six screws. Figure 17A. Standard Voltage Selection Panel. CAUTION WHEN CHANGING THE VOLTAGE, ONE WIRE MUST BE MOVED ON THE PRIMARY TAPS OF BOTH TRANSFORMERS. Figure 17B. Standard Voltage Selection Panels. Figure 17.Figure

Instructions for Installation, Operation and Maintenance of the Eaton ATC-600 Automatic Transfer Switch Controller Instructional Booklet

Instructions for Installation, Operation and Maintenance of the Eaton ATC-600 Automatic Transfer Switch Controller Instructional Booklet Instructions for Installation, Operation and Maintenance of the Eaton ATC-600 Automatic Transfer Switch Controller Description Page 1 Introduction 2 Hardware Description 3 Operator Panel 4 Operation 5

More information

ATC-300 Automatic Transfer Switch Controller

ATC-300 Automatic Transfer Switch Controller ATC-300 Technical Data New Information Technical Data Page 2 Effective: May 2004 ATC-300 Introduction The Cutler-Hammer ATC-300 from Eaton s Electrical business is a comprehensive, multi-function, microprocessor-based

More information

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

ATC-900 Automatic Transfer Switch Controller

ATC-900 Automatic Transfer Switch Controller ATC-900 Automatic Transfer Switch Controller center industries. An intelligent control architecture allows the ATC-900 to address virtually any system requirements. Typical applications include utility-to-utility,

More information

GTEC transfer switch open transition

GTEC transfer switch open transition GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

Cutler-Hammer I.B. ATS-RM01. Instructions for Cutler-Hammer Residential Automatic Transfer Switch

Cutler-Hammer I.B. ATS-RM01. Instructions for Cutler-Hammer Residential Automatic Transfer Switch Cutler-Hammer I.B. ATS-RM01 Instructions for Cutler-Hammer Residential Automatic Transfer Switch Effective June, 1999 I.B. ATS-RM01 Page iii WARNING READ AND UNDERSTAND THE INSTRUCTIONS CONTAINED HEREINAFTER

More information

I.L.15.01.T.K. Instructions for Cutler-Hammer MP1 Series Automatic Transfer Switches 30-1200A

I.L.15.01.T.K. Instructions for Cutler-Hammer MP1 Series Automatic Transfer Switches 30-1200A I.L.15.01.T.K. Instructions for Cutler-Hammer MP1 Series Automatic Transfer Switches 30-1200A I.L.15.01.T.K. Page i Table of Contents 1. WARRANTY... 1 2. RECEIVING, HANDLING AND STORAGE... 1 2.1 RECEIVING...

More information

Transfer Equipment Controls

Transfer Equipment Controls Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment

More information

MTS Power Products MIAMI FL 33142 ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual

MTS Power Products MIAMI FL 33142 ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual MTS Power Products MIAMI FL 33142 ATS-22AG Automatic Transfer Switch And Control PLC Operator s Manual Dedicated Single Phase Transfer Switch With Touch Screen Controls Normal Power Connections Emergency

More information

O & M Manual for the 200A EGSU Automatic Transfer Switch with RTC-100 Control

O & M Manual for the 200A EGSU Automatic Transfer Switch with RTC-100 Control Contents Description Page 1. Introduction............................ 2 2. Receiving, Handling, and Storage........... 5 3. Equipment Description................... 6 4. Installation and Wiring....................

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply

How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator

More information

Eaton s E-Series protective relay family

Eaton s E-Series protective relay family E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family

More information

Zenith Controls ISO 9001 50R-1000C 5/99

Zenith Controls ISO 9001 50R-1000C 5/99 OPERATION AND MAINTENANCE MANUAL TRANSFER SWITCH CONTROL PANEL MX100 MICROPROCESSOR CONTROLLER g GE Zenith Controls ISO 9001 50R-1000C 5/99 Table of Contents Page Safety... 1 Final Equipment Inspection...

More information

Automatic Transfer Switch Controller

Automatic Transfer Switch Controller Automatic Transfer Switch Controller Decision-Makerr MPAC 1500 Model KBS with Decision-Makerr MPAC 1500 Controller Applicable Models Model Description KCS Standard-Transition Any Breaker ATS ] KCP Programmed-Transition

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS 1. Description and Phone Number Dialing: The dialer shall be a solid state component capable of dialing up to 16 telephone numbers, each up to 60 digits

More information

TSC 800 TRANSFER SWITCH CONTROLLER INSTALLATION, OPERATING & SERVICE MANUAL

TSC 800 TRANSFER SWITCH CONTROLLER INSTALLATION, OPERATING & SERVICE MANUAL TSC 800 TRANSFER SWITCH CONTROLLER INSTALLATION, OPERATING & SERVICE MANUAL Software Version 2.2 PM049 REV 11 14/01/23 9087A 198 th Street, Langley, BC Canada V1M 3B1 Telephone (604) 888-0110 Telefax (604)

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,

More information

INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04 I.L. 32-693 A INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04 DANGER DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTE- NANCE ON EQUIPMENT

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

How To Test A Power Switch On A Power Supply

How To Test A Power Switch On A Power Supply transfer switches Soft load Innovative, reliable, integrated solution Built with years of experience Powered with innovation Delivered with reliability A history of experience, innovation and reliability

More information

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

More information

Generator Differential Relay Electrical Apparatus

Generator Differential Relay Electrical Apparatus Generator Differential Relay Electrical Apparatus MD3G Rotating Machine Differential Relay 150-3 The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

Parallel Redundant Uninterruptible Power Supply

Parallel Redundant Uninterruptible Power Supply 9 315 Parallel Redundant Uninterruptible Power Supply Installation/Operation Manual 164202013 Rev. D ------------------------------------------------------------------------ ------------------------------------------------------------------------

More information

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

O & M Manual for the 50-400A EGSX Transfer Switch

O & M Manual for the 50-400A EGSX Transfer Switch Contents Description Page 1. Introduction...2 2. Receiving, Handling, and Storage... 5 3. Equipment Description... 6 4. Installation and Wiring... 6 5. Functional Testing... 18 6. Maintenance and Component

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

Single Phase Soft Starter

Single Phase Soft Starter Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................

More information

THERMAL MANAGEMENT SOLUTIONS

THERMAL MANAGEMENT SOLUTIONS t2000 Series Electronic heat-tracing controller Product Overview /COMMUNICATIONS INTERACE CARRIER REQ TO SEND The DigiTrace heat trace controller is designed to provide the benefits associated with single

More information

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual Master Time Clock MTC-200 MTC-400 MTC-600 Users Manual Toll Free (888)713-0373 Phone (972)987-4408 FAX (877)720-9291 www.midwest-time.com sales@midwest-time.com TABLE OF CONTENTS TOPIC PAGE GENERAL DESCRIPTION

More information

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1930-61 FTA1930 Digital Solid State Starting Electric Fire Pump Controllers Product Description Fire Pump Controllers for Business-Critical Continuity

More information

Applied Electronics. Commercial Dimming System UPDATE NOTICE

Applied Electronics. Commercial Dimming System UPDATE NOTICE REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with

More information

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch

More information

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence

More information

Product Specification instalert Rapid Messenger Variable Message Sign

Product Specification instalert Rapid Messenger Variable Message Sign instalert 2 units to cover any application instalert 18 (ia18): 18 x 28 full matrix instalert 24: (ia24): 24 x 60 full matrix Size, Weight without battery ia18: 30 x 20 x 2.74, 29 lbs ia24: Folds to fits

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS + Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,

More information

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply

User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply User Manual English APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC Tower Uninterruptible Power Supply 990-1587A 12/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent

More information

SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches

SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches PART 1 GENERAL 1.01 Scope SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches Division 16 - Electrical Standby Power Generator Systems A. Furnish and install service entrance automatic

More information

SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown

920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown Self-Regulating 920 Series Dual-point heat-tracing control system Power-Limiting Mineral Insulated 920*E4FWL*SIS302*SS3102 shown Product overview The DigiTrace 920 is a compact, full-featured, microprocessor-based,

More information

Series TS 870 100-1200 Amp. Automatic Transfer Switches

Series TS 870 100-1200 Amp. Automatic Transfer Switches Series TS 870 100-1200 Amp Automatic Transfer Switches A Regal Brand TS 870 AUTOMATIC TRANSFER SWITCHES THOMSON POWER SYSTEMS TS 870 AUTOMATIC TRANSFER SWITCHES OFFER THE FOLLOWING OUTSTANDING FEATURES:

More information

TOSHIBA G9000 80/100/160/225 kva

TOSHIBA G9000 80/100/160/225 kva CORPORATE OFFICE 13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041 PHONE: (713) 466-0277 (800) 231-1412 FACSIMILE: (713) 896-5226 TOSHIBA G9000 80/100/160/225 kva GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE

More information

Product Guide. Low voltage grounding system. Answers for industry.

Product Guide. Low voltage grounding system. Answers for industry. Product Guide Low voltage grounding system Answers for industry. Advanced switchgear solutions for process industries In today s high-tech manufacturing world, profitability can be greatly impacted by

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

Installation instructions for Series NRX INCOM communications adapter module

Installation instructions for Series NRX INCOM communications adapter module 4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply

More information

ALPHA Meter Installation Information

ALPHA Meter Installation Information October 006 IL4-400Q ALPHA Meter Installation Information General This instructional leaflet contains general installation instructions for the following single phase and polyphase watthour meters: socket-connected

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions

More information

Installation and Operation Back-UPS 1250, 1300, 1500

Installation and Operation Back-UPS 1250, 1300, 1500 Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with

More information

DLP-PU/E Instruction Manual

DLP-PU/E Instruction Manual Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Series 427. 1/16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

Series 427. 1/16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS Series 427 1/16 DIN Multi-Mode Bar Graph Display Timer PRODUCT HIGHLIGHTS Digital Setting with 0.1% Accuracy Unique LED Bargraph Indicates Time Cycle in 20% Increments 8 Field Selectable Modes of Operation

More information

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

Limited Service Fire Pump Controllers Features

Limited Service Fire Pump Controllers Features Must Be Installed Per Applicable Code and Manufacturers Recommendations Limited Service Fire Pump Controllers Features 1-1 FD20 Full Voltage - Limited Service with Plus Microprocessor Power I/O Board Transformers

More information

EATON Diesel Plus Diesel Engine Fire Pump Controller

EATON Diesel Plus Diesel Engine Fire Pump Controller O & M Manual IM05805019K-002 Effective April 2015 EATON Diesel Plus Diesel Engine Fire Pump Controller Powering Business Worldwide O & M Manual IM05805019K-002 Effective April 2015 EATON Diesel Plus Diesel

More information

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications

SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

Operation and Installation Manual

Operation and Installation Manual Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

Continuous Power... Continuous Protection

Continuous Power... Continuous Protection Series 165 We Keep Your Power On Continuous Power... Continuous Protection An Automatic Transfer Switch helps prevent... Your business or home from losing power during bad weather or utility power equipment

More information

E-Series protective relay family

E-Series protective relay family E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays E-Series protective relay family Reliable protection for every application Eaton s E-Series relay

More information

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

TC-9102 Series Surface Mount Temperature Controllers

TC-9102 Series Surface Mount Temperature Controllers TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Specification Requirements DBL 700MX and 1000MX Series UPS

Specification Requirements DBL 700MX and 1000MX Series UPS Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without

More information

CAPTAIN 6. USER GUIDE System ver. 6.0. 6 Zones Intruder Alarm System. PIMA Electronic Systems Ltd. www.pima-alarms.com

CAPTAIN 6. USER GUIDE System ver. 6.0. 6 Zones Intruder Alarm System. PIMA Electronic Systems Ltd. www.pima-alarms.com CAPTAIN 6 6 Zones Intruder Alarm System USER GUIDE System ver. 6.0 PIMA Electronic Systems Ltd. www.pima-alarms.com P/N 4410049, G2 XX en, Jan. 2010 2 CAPTAIN 6 User Guide SAFETY INSTRUCTIONS Your CAPTAIN-i

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM Section TELEPHONE AUTOMATIC DIALER SYSTEM PART 1 GENERAL 1.01 SYSTEM DESCRIPTION A. Design Requirements: 1. Electronic monitoring system shall interface plant alarms to public telephone system or cellular

More information

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy. Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com

More information

Medium Voltage Motor Control Assemblies

Medium Voltage Motor Control Assemblies Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

Disturbance Recoder SPCR 8C27. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power

More information

Back-UPS Pro 1300/1500 Installation and Operation

Back-UPS Pro 1300/1500 Installation and Operation Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a

More information

±15 V Current-Limited Power Supply

±15 V Current-Limited Power Supply USER S GUIDE ±15 V Current-Limited Power Supply Model 0901 Newport Corporation 3635 Peterson Way Santa Clara, CA 95054 www.newport.com/newfocus Warranty Newport Corporation guarantees its products to be

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE Series Circuit Breaker Monitors CONSOLIDATED Electronics, Inc. MONITORING THE FUTURE Why SF Gas Density Monitors? 6 Cut Maintenance Costs Your capital investment may be recovered with the elimination of

More information