General Safety Information. Document Packaged DX Module. As used in Greenheck models DGX IGX MSX
|
|
|
- John Palmer
- 9 years ago
- Views:
Transcription
1 Document Packaged DX Module Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! As used in Greenheck models DGX IGX MSX Recognized Component General Safety Information Only qualified personnel should install and maintain this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward. 1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada. 2. Unit must be securely and adequately grounded. 3. Verify that the power source is compatible with the equipment. 4. Never open access doors to the unit while it is running. DANGER Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up. If this unit is equipped with optional gas accessories, turn off gas supply whenever power is disconnected. CAUTION This unit is equipped with a compressed refrigerant system. If a leak in the system should occur, immediately evacuate and ventilate the area. An EPA Certified Technician must be engaged to make repairs or corrections. Refrigerant leaks may also cause bodily harm. CAUTION When servicing the unit, the internal components may be hot enough to cause pain or injury. Allow time for cooling before servicing. Packaged DX Module for Make-Up Air 1
2 Receiving This module is installed as a component of a makeup air unit and does not require any special handling. Refer to the Receiving portion of the unit Installation, Operation and Maintenance (IOM) Manual for complete instructions on receiving, unpacking and handling. Unpacking The unit is shipped as a complete installed unit. Protective coverings have been installed on the face of the condenser coil that should be left in place until installation of the unit is complete. The only item that was shipped loose with the unit is the P Trap kit. Verify that the P Trap kit has been received. Refer to Unpacking instructions in unit IOM. Handling Units are to be rigged and moved by the lifting brackets provided. Do not forklift. Refer to the Handling portion of the unit IOM for complete instructions on handling. Storage Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories during storage. The manufacturer will not be responsible for damage during storage. The following suggestions are provided solely as a convenience to the user. Inspection and Maintenance During Storage While in storage, inspect units once per month. Keep a record of inspection and maintenance performed. If moisture or dirt accumulations are found on the parts, the source should be located and eliminated. At each inspection, rotate all moving parts by hand ten to fifteen revolutions to distribute lubricant on motor and bearings. If paint deterioration begins, consideration should be given to touch-up or repainting. Units with special coatings may require special techniques for touch-up or repair. Machined parts coated with rust preventative should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventative coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from the surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe clean thoroughly with Tectyl 506 (Ashland, Inc.) or the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl 511M Rust Preventative or WD-40 or the equivalent. Table of Contents General Safety Information...1 Receiving, Unpacking, Handling, Storage....2 Inspection and Maintenance During Storage...2 Product Overview...2 Subassemblies Coils....3 Dampers....3 DX System....3 Installation Service Clearances....4 Additional Clearances for Packaged DX Units....4 Lifting....4 Condensate Drain (P Trap)....4 Switch S Component Operation Compressor Components....5 Electrical Components....5 Refrigerant Components....5 Additional Control Components....5 Factory-Installed Refrigeration System Components....6 Sequence of Operation without Microprocessor Controller Control Sequence....7 Optional Variable Air Volume....7 Sequence of Operation with Microprocessor Controller...8 Start-Up Unit Warnings and Cautions....7 Model and Serial Number....8 Pre-Start-Up Checklist....9 Special Tools Required....9 Start-Up Procedure....9 Voltage Imbalance....9 Start-Up Checklist Troubleshooting Refrigeration Circuit Routine Maintenance Monthly Annually Maintenance Procedures Reference Component Location Maintenance Log...Backcover Our Commitment...Backcover 2 Packaged DX Module for Make-Up Air Unit
3 Product Overview The Packaged DX Module for make-up air is a horizontally configured unit that is installed as a complete package that has been designed for outdoor installations. The Packaged DX Module is used to temper the air that is supplied to the building. The make-up air unit is designed to provide supply air to replace the air that is exhausted from the building. The PDX module is designed to provide only cooling. The DX system comes fully charged with R-410A refrigerant from the factory and is ready for operation upon arrival. Units may be supplied with one or two compressors based on required cooling capacity. All units with multiple compressors allow for staging of compressors to meet a wider range of outdoor air loads while reducing the number of cycles per compressor. Compressed Refrigerant All packaged DX modules are charged with environmentally friendly R-410A compressed refrigerant. Do not use tools or parts designed for other refrigerants on this unit. Safety Listing Make-up air units are listed per ANSI/UL 1995, Heating and Cooling Equipment and are ETL Certified. Supplemental Installation, Operation and Maintenance Manuals Refer to the Installation, Operation and Maintenance manual for the Make-Up Air unit for additional information. Models and Capacities The Packaged DX Module for make-up air units is manufactured in three different platform sizes, each of which has several different output tonnage options. Examine shipping Platform Tonnage Circuiting documents to H12 2.5, 4, 5, 8 Single verify correct H22 7, 10 Two model of the module as H32 10, 12, 16 Two received. Model Number A metal plate is located on the fixed panel access to the control center. The plate is marked with the Platform type and Tonnage. Record the model number here: Subassemblies Coils Every module is supplied with a single DX evaporator coil. If there is only one cooling circuit, then the DX coil is not divided. If two cooling circuits are specified, then the DX coil will be a split-face. A single condenser coil is attached to the exterior of the module. If more than one cooling circuit is present, that condenser coil will be of split-face configuration. Dampers Only an inlet damper may be installed in a PDX module and it will only be found when the module is installed in either model IGX or MSX that was not ordered with an inlet damper module. DX System The DX system in the module is a complete, sealed unit with compressed R-410A refrigerant. It consists of one or two compressors, evaporator and condenser coils and the following integral components: expansion valves liquid line filter-drier service / charging valves moisture indicating sight glass crankcase heater on each compressor hot gas bypass valve (optional, single circuit units only) Each DX system incorporates the following: high pressure manual reset cutout low pressure auto-reset cutout DGX H Model Parent Fan Quantity 1 Wheel Diameter (in.) 8-36 Example of Model Name Cooling Tonnage Housing Size Packaged DX Module for Make-Up Air Unit 3
4 Installation Service Clearances All make-up air units require minimum clearances on all sides for routine maintenance. Filter replacement, drain pan inspection and cleaning, fan bearing lubrication and belt adjustment are all examples of routine maintenance that must be performed. Blower and motor assemblies and coil and filter sections are always provided with a service door or panel for proper component access. Clearances for component removal may be greater than the service clearances. Refer to submittal drawings for these clearance dimensions. Additional Clearances for Packaged DX Units Packaged DX units require additional service clearance because they must have unrestricted air movement around the condenser coil and condenser fans. Hot air is being discharged from the condenser fans during operation and the more clearance available, the better as this avoids the chance of recirculation or coil starvation. This unit should never be placed under an overhang or inside a building. A minimum of 48 inches above the condenser fans is recommended. Lifting All units equipped with this module are provided with either four or six lifting lugs. When the unit is being hoisted, all of the provided lugs must be used for support. Four lifting lugs are on the four corners of the unit, located at the base. In addition, there may be two more lifting lugs located at the top of the unit. The locations of those two top lugs varies somewhat from unit to unit. Use spreader bars as shown to prevent damage to the cabinet. If top-mounted lifting lugs are present, they must be used in conjunction with the bottom-mounted lifting lugs when hoisting the unit. Condenser Fans Minimum 48 inches clearance Use lifting lugs on all four corners. Minimum 42 inches clearance Lifting Details 48 inches clearance Condenser Fans and Condenser Coil Outdoor Air Intake End view of make-up air unit with Packaged DX 42 inches clearance 42 inches clearance Condenser Coil Indirect Gas-Fired Furnace Unit Control Center 36 inches clearance Install Condensate Drain (P Trap) The only installation step that is specific to the DX module is installation and priming of the engineered P trap. Locate the P trap kit that was shipped with the unit and install the kit in accordance with the enclosed instructions. Provide and Install Switch S4 Each Packaged DX unit requires an contact closure to enable the unit to run. This can be a user-supplied switch that may be a toggle switch mounted in a 2 x 4 inch electrical box (mounted in a position chosen by the user), or it may be a simple jumper or even a control switch installed in a remote control panel supplied by the factory. See also Additional Control Components on page 5 of this manual. 4 Packaged DX Module for Make-Up Air Unit
5 Component Operation Compressor Components Each Packaged DX module has a complete set of compressor contactors, condenser fan contactors, relays and certain integral safety controls located in the module. 4 Additional Control Components In addition to the control components located in the PDX module, various high- and low-voltage circuits are found in the make-up air unit control center. See the unit-specific wiring diagram (found in the unit control center) for complete information. 7 3A Typical Unit Control Center Electrical Components 1. Compressor Relays 2. Condenser Fan Contactor 3A. Compressor Contactor (Circuit A) 3B. Compressor Contactor (Circuit B) (not shown) 4. Low Voltage Terminal Strip 7B 8B 7B 8B 9 Refrigeration Components 5A. Compressor (Circuit A) 5B. Compressor (Circuit B) 6A. High Pressure Sensor (Circuit A, Manual Reset) (not shown) 6B. High Pressure Sensor (Circuit B, Manual Reset) (not shown) 7A. Thermostatic Expansion Valve (TXV) (Circuit A) 7B. Thermostatic Expansion Valve (TXV) (Circuit B) 8A. Refrigerant Distributor (Circuit A) 8B. Refrigerant Distributor (Circuit B) 9. Condensate Drain (P trap here) 10. Hot gas bypass valve - single circuit variable air volume units only (not shown) 5A 5B 1. Power Distribution Block - field-supplied power from main disconnect switch is terminated here. 2. Phase Monitor has jumpers going to power distribution block). It constantly checks for loss of a phase or phase reversal. It requires 24 VAC to operate. When a fault is detected, it cuts off the power supply to the low voltage terminal strip, disabling all motors. It has one red LED indicator light. Constant ON indicated properly applied power, If the LED is flashing, this indicated a fault connection. 3. Transformer provides 24 VAC to various low voltage devices including the Phase Monitor and to Low Voltage Terminal Strip in compressor compartment. 4. Relays RC1 and RC2 are wired to the control center in the compressor compartment. 5. Low Voltage Terminal Strip - Switch S4 terminates here. 6. Thermostat (Inlet Air Sensor) - TS5 monitors outdoor air temperature. It is field-adjustable. If there is more than one cooling circuit, an additional controller for the second stage will be provided. The TS5 will turn the DX cooling stages on or off. 7. Dirty Filter Switch - optional air proving switch and it is field-adjustable to monitor filter loading. Packaged DX Module for Make-Up Air Unit 5
6 Factory-Installed Refrigeration System Components Circuit A 7 Condenser Coil 6 Evaporator Coil Pressure Port for Troubleshooting Reheat Valves High Side Pressure Drop Service Valve for Superheat and Low Side Pressure Optional Service Valve for Subcooling Gauge/ High Side Pressure Drop Thermostatic Expansion Valve (TXV) Each unit is equipped with a Thermal Expansion Valve on each refrigerant circuit. The valve controls the flow of liquid refrigerant entering the evaporator coil by maintaining a constant, factory set superheat of 10 F. The valve is adjustable and is located on the side of the evaporator coil and can be accessed through the coil panel access door. 2. Refrigerant Distributor Attached to the TXV is a refrigerant distributor. The refrigerant distributor evenly distributes the refrigerant to each circuit of the evaporator coil to provide optimum performance. 3. Evaporator Coil The coil is located in the supply airstream. In the DX system, the liquid refrigerant is expanded in the TXV and it then flows through the evaporator coil. The refrigerant enters the coil as a low temperature liquid/gas where it eventually boils into a low temperature, low pressure gas prior to going into the compressor. As the refrigerant passes through the evaporator coil, it absorbs heat from the airstream. To ensure proper operation, the coil surface must be cleaned so that air movement over the coil provides the necessary heat transfer. 4. Low Limit Pressure Switch The switch is installed in the suction line and disables the DX system when the suction pressure drops below the set point. The switch will autoreset when the pressure rises above the auto-reset set point. 5. Compressors 6. Condensing Coil 7. Condenser Fans 8. High Limit Pressure Switch The switch opens when refrigerant pressure increases above the set point in the liquid line and it then requires a manual reset. 9. Liquid Line Filter-Drier The liquid line filter-drier prevents moisture and foreign matter from entering the expansion valve. 10. Moisture Indicating Sight Glass During normal operating conditions, the sight glass should typically be liquid. Some gas is acceptable, but excessive bubbles may indicate improper charge or a leak in the system. A green dot indicates the moisture level in the refrigerant, while a yellow dot indicates moisture in the system and needs to be dealt with Access Ports 15. Hot Gas Bypass Manual Shut Off Valve (optional) Used to disable hot gas bypass for service and troubleshooting procedures. 16. Hot Gas Bypass Valve (optional) On units equipped with hot gas bypass, hot gas from the compressor is injected into the liquid line of the evaporator coil after the TXV. Valve Adjustment - To adjust the valve, connect a pressure gauge to the suction line and block the entering air to the evaporator coil. The valve should begin to open when the suction pressure drops to approximately 115 PSIG for R-410A (the valve will feel warm to the touch). Adjustments are made by first removing the cap on the bottom of the valve and then turning the adjusting stem clockwise to increase the setting pressure (counterclockwise to decrease). Allow several minutes between adjustments for the system to stabilize. When adjustment is complete, replace the cap on the valve. 6 Packaged DX Module for Make-Up Air Unit
7 Sequence of Operation without Microprocessor Controller The compressors are energized by an outdoor air thermostat TS5, located in the unit control center. The thermostat sensor is located in the intake airstream upstream of the DX coil. The thermostat can be a single or dual stage thermostat depending on the number of compressors. The first stage of cooling will energize when the outdoor air temperature rises above the thermostat set point plus the differential. The thermostat is factory set at 80 F with a differential of 5 F but can be field adjusted. The second stage of cooling will energize when the outdoor air temperature rises above the second stage offset plus the differential. The second stage offset is factory set at 10 F and the second stage differential is set at 5 F. See the chart below for a graphical representation of the control operation. To summarize the cooling controls, the first stage of cooling will turn on at 85 F and the second stage of cooling will turn on at 95 F. The second stage of cooling will turn off at 90 F and the first stage of cooling will turn off at 80 F. (+10 F) (+5 F) Setpoint Temperature (factory set at 80 F) Adjustable Differential Adjustable Differential Control Sequence 1. Fan switch needs to be closed (S3) between terminals R and G. 2. Heating/Cooling switch (S4) is closed between terminal R and Y1. 3. N.O. contact on fan relay (RF) is energized and closed. 4. When the outdoor air temperature is above the set point plus the differential power passes through N.O. contacts on outdoor air thermostat (TS5) and energizes the cooling relay (RC1). 5. When the pressure switches LPS (refrigerant low pressure switch) and HPS (refrigerant high pressure switch) are in their normal state relay R10 will energize. Starting the first stage compressor contactor. 6. When the outdoor air temperature is above the second stage offset plus the differential power passes through N.O. contacts on outdoor air thermostat (TS5) and energizes the cooling relay (RC2). 7. When the pressure switches LPS and HPS (refrigerant high pressure switch) are in their normal state relay R11 will energize, starting the second stage compressor contactor. ON OFF FIRST STAGE COOLING ON OFF OFFSET (factory set at 10 F) SECOND STAGE COOLING Control Sequence - Two Circuit Variable Air Volume (optional) 1. Fan switch needs to be closed (S3) between terminals R and G. 2. Heating/Cooling switch (S4) is closed between terminal R and Y1. 3. N.O. contact on fan relay (RF) is energized and closed. 4. When the outdoor air temperature is above the set point plus the differential power passes through N.O. contacts on outdoor air thermostat (TS5) and energizes the cooling relay (RC1). 5. When the pressure switches LPS (refrigerant low pressure switch) and HPS (refrigerant high pressure switch) are in their normal state relay R10 will energize. Starting the first stage compressor contactor. 6. When the outdoor air temperature is above the second stage offset plus the differential power passes through N.O. contacts on outdoor air thermostat (TS5) and energizes the cooling relay (RC2). 7. When the pressure switches LPS (refrigerant low pressure switch) and HPS (refrigerant high pressure switch) are in their normal state relay R11 will energize, starting the second stage compressor contactor. 8. When the discharge air temperature drops below the low temperature set point (TS9) factory set at 55 F, the second stage compressor contactor will deenergize, turning off the second stage compressor. 9. The second stage compressor will re-energize when the discharge air temperature rises above 75 F. Control Sequence - Single Circuit Variable Air Volume (optional) 1. Fan switch needs to be closed (S3) between terminals R and G. 2. Heating/Cooling switch (S4) is closed between terminal R and Y1. 3. N.O. contact on fan relay (RF) is energized and closed. 4. When the outdoor air temperature is above the set point plus the differential power passes through N.O. contacts on outdoor air thermostat (TS5) and energizes the cooling relay (RC1). 5. When the pressure switches LPS (refrigerant low pressure switch) and HPS (refrigerant high pressure switch) are in their normal state relay R10 will energize. Starting the first stage compressor contactor. 6. When the suction gas temperature falls below 28ºF, which is 32-34ºF coil surface temperature, the hot gas bypass valve opens injecting hot gas from the compressor into the liquid line of the evaporator coil. Packaged DX Module for Make-Up Air Unit 7
8 Sequence of Operation with Optional Microprocessor Controller If the unit is equipped with a microprocessor controller it will be located in the units main control center. NOTE Similar Carel hardware is used for the network interfacing and indirect furnace control options. Only the microprocessor controller will contain keypad buttons on both the left and right side of the display. For any other hardware, please reference the previous section Sequence of Operation without Optional Microprocessor. If the unit is equipped with a microprocessor controller it will be located in the units main control center. With a microprocessor controller, the compressors will be energized by the microprocessor. When the outside air temperature rises above the cooling lockout temperature set point (plus the differential), the microprocessor will energize the cooling stages as required to maintain the supply temperature set point. The cooling lockout temperature set point is factory set to 80ºF with a 2ºF differential. The supply temperature set point is factory set to 70ºF. The set points and cooling lockout differential are field-adjustable using the microprocessor keypad. For additional information on the microprocessor controller, please reference the Microprocessor Controller Installation, Operation and Maintenance Manual. Start-Up Unit DANGER Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies. CAUTION Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur. CAUTION Do not operate without the filters and birdscreens installed. They prevent the entry of foreign objects such as leaves, birds, etc. CAUTION Do not run unit during construction phase. Damage to internal components may result and void warranty. WARNING Unit was factory tested. All blowers, fans, and compressors are set-up to run correctly when supplied power. If any one fan is running backwards or the compressor is making loud noises, immediately turn off the power. Switch two leads on the incoming power to the disconnect. This will ensure proper operation of the unit. Failure to comply may damage the compressors and void the warranty. Do not jumper any safety devices when operating the unit. This may damage components within or cause serious injury or death. Do not operate compressor when the outdoor temperature is below 40ºF. Do not short-cycle the compressor. Allow 5 minutes between on cycles to prevent compressor damage. DX system is charged with refrigerant. Start-up must be performed by EPA Certified Technician. WARNING Prior to starting up the unit, power must be energized for 24 hours without a call for cool to allow the compressor crankcase heaters time to boil off any liquid refrigerant present in the compressor. 8 Packaged DX Module for Make-Up Air Unit
9 Every installation requires a comprehensive start-up to ensure proper operation of the unit. As part of that process, the following checklist must be completed and information recorded. Starting up the unit in accordance with this checklist will not only ensure proper operation, but will also provide valuable information to personnel performing future maintenance. Should an issue arise which requires factory assistance, this completed document will allow unit experts to provide quicker resolve. Qualified personnel should perform start-up to ensure safe and proper practices are followed. Unit Model No. Unit Serial No. Compressor 1 Model No. Compressor 2 Model No. Start-Up Date Start-Up Personnel Name Start-Up Company Phone Number Pre-Start-Up Checklist Disconnect and lock-out all power switches. Remove any foreign objects that are located in the unit. Check all fasteners, set-screws, and locking collars on the fans, bearings, drives, motor bases and accessories for tightness. Rotate the fan wheels by hand and ensure no parts are rubbing. Filters can load up with dirt during building construction. Replace any dirty pleated filters and clean the aluminum mesh filters in the intake hood. Verify that non-motorized dampers open and close properly. Check the tightness of all factory wiring connections. Verify control wire gauge. Verify proper drain trap installation. Check condensing fans for any damage or misalignment. Spin the blades and make sure they don t contact any parts and are free turning without any resistance. Look over the piping system. Inspect all coils within the unit. Fins may get damaged in transit or during construction. Carefully straighten fins with a fin comb. If there is an indirect gas-fired furnace in this unit, refer to the manual provided with this unit for Pre- Start-Up information. This unit contains a crankcase heater for each compressor which needs power supplied to it 24 hours prior to start-up. If start-up is scheduled in 24 hours, unlock the disconnect power and energize unit. SPECIAL TOOLS REQUIRED Voltage Meter (with wire probes) Amperage Meter Pressure Gauges (refrigerant) Tachometer Thermometer Incline manometer or equivalent Start-Up Procedure The unit will be in operational mode during start-up. Use necessary precautions to avoid injury. All data must be collected while the unit is running. Ensure the Pre-Start-Up checklist is complete. Jumper R to G, R to Y1, and R to Y2 (if applicable) on the control board. Turn the disconnect on. After 3 minutes compressors will come on. Make sure all fans and compressors are rotating the correct direction. Allow the unit to run until the refrigerant system stabilizes. Approximately 5-10 minutes. Voltage Imbalance In a 3-phase system, excessive voltage imbalance between phases will cause motors to overheat and eventually fail. Maximum allowable imbalance is 2%. To determine voltage imbalance, use recorded voltage measurements in this formula. Key: V1, V2, V3 = line voltages as measured VA (average) = (V1 + V2 + V3) / 3 VD = Line voltage (V1, V2 or V3) that deviates farthest from average (VA) Formula: % Voltage Imbalance = [100 x (VA-VD)] /VA Packaged DX Module for Make-Up Air Unit 9
10 Start-Up Checklist Line Voltage. Check at unit disconnect. L1-L2 Volts L2-L3 Volts L1-L3 Volts Condensing Fans Condensing Fan 1 L1 Amps L2 Amps L3 Amps Condensing Fan 2 L1 Amps L2 Amps L3 Amps Condensing Fan 3 L1 Amps L2 Amps L3 Amps Compressors Outdoor Air Temperature Deg F Outdoor Air Relative Humidity % RH Return Air Temperature Deg F Return Air Relative Humidity % RH Compressor 1: L1 amps L2 amps L3 amps Crankcase Heater Superheat Deg. F. Should be between 8º and 12ºF. Subcooling Deg. F. Should be between 12º and 17ºF. Discharge Pressure PSIG Should be between 300 and 500 PSIG Suction Line Pressure PSIG Should be between 100 and 135 PSIG Liquid Line Temperature Deg. F. Suction Line Temperature Deg. F. Moisture Indicating Sight Glass Liquid Visible Yes / No Color of Center Dot Green / Yellow Hot Gas Bypass Operational Yes / No Compressor 2: L1 amps L2 amps L3 amps Crankcase Heater Superheat Deg. F. Should be between 8º and 12ºF. Subcooling Deg. F. Should be between 12º and 17ºF. Discharge Pressure PSIG Should be between 300 and 500 PSIG Suction Line Pressure PSIG Should be between 100 and 135 PSIG Liquid Line Temperature Deg. F. Suction Line Temperature Deg. F. Moisture Indicating Sight Glass Liquid Visible Yes / No Color of Center Dot Green / Yellow Hot Gas Bypass Operational Yes / No 10 Packaged DX Module for Make-Up Air Unit
11 Troubleshooting Refrigeration Circuit TROUBLESHOOTING NOTE Before any components are changed on the refrigeration system, the cause of the failure must be determined. Further problems will exist unless the true cause or problem is identified and corrected. IMPORTANT Do not release refrigerant to the atmosphere! If required service procedures include the adding or removing of refrigerant, the service technician must comply with all federal, state and local laws. The procedures discussed in this manual should only be performed by a qualified EPA Certified Technician. NOTE: Unit is equipped with a phase loss/phase reversal control. If system does not start, check phase of electrical supply. The first step is to check airflow conditions. (e.g. improper ductwork, atypical wet bulb / dry bulb, etc.) After these steps have been eliminated, proceed with troubleshooting by following this guide: Symptom Possible Cause Corrective Action Compressor will not run or does not start Compressor starts but cuts out on low pressure Low pressure switch activates at 50 PSIG Open disconnect switch or circuit breaker. Compressor contactor not closing. Blown fuse or tripped breaker. Low line voltage. Compressor motor protector open. Compressor defective. High pressure switch open or defective. Low pressure switch open or defective. Open room thermostat or control. (No cooling required). Loose wiring. Low or loss of refrigerant charge. Airflow restricted. Restriction in refrigerant line. Defective low pressure switch. Close switch and/or breaker. Check voltage to contactor coil, transformer, slave relay, system. Replace parts as necessary. Check for shorted wire or motor. Replace fuse after correcting problem. Check line voltage. If the voltage varies more than 10% from the nameplate voltage of the compressor, the incoming voltage must be corrected. Motor thermal protector automatically resets. Allow time (2 hours) for compressor to cool down so protector will reset. Restart and check for reason overheat occurred. Check motor for open circuit, short circuit, grounded windings, or burn out. Compressor may be seized; check refrigerant. If necessary, replace compressor. If manual reset (high pressure), reset switch. (Switch opens at 600 psi and will not reset above 420 psi for R-410A). Replace if defective. Switch will open at 50 psi and auto-close at 90 psi. Replace if defective. Check room temperature. If temperature is proper, wait for thermostat to close. Check all wire terminals and tighten as necessary. Check refrigerant pressures and temperatures (subcooling.) Check for dirty evaporator coil, dirty filters, dampers closed, iced evaporator coil, improper belt, check motor amps, check duct design. Check refrigerant pressures, look for frosted tubing and components indicating a restriction. Check pressure drop across the filter drier. Replace. Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information. Packaged DX Module for Make-Up Air Unit 11
12 Troubleshooting Refrigeration Circuit (continued) Symptom Possible Cause Corrective Action Compressor starts but cuts out on high pressure switch High pressure activates at 600 PSIG Compressor cuts out on thermal overload Compressor hums, but will not start Compressor noisy or vibrating Refrigerant overcharge. Condenser fan motor defective. Condenser coil inlet obstructed or dirty. Air or non-condensables in system. Defective high pressure switch. Restriction in discharge or liquid line. Condensing fan relay not pulling in. Low voltage. Sustained high discharge pressure. High suction and discharge pressures. Defective compressor overload. Improper refrigerant charge. Improperly wired. Loose wiring. Defective start relay. Motor windings damaged. Improperly wired. Low line voltage. Loose wiring. Defective start relay. Motor winding damaged. Internal compressor mechanical damage. Refrigerant overcharge. Liquid floodback. Tubing rattle. Scroll compressor rotating in reverse. (3-phase) Damaged compressor. Improper mounting on unit base. Check pressures, charge by subcooling. Check fan motor. Check coil and clearances. Clean coil if necessary. Check high side equalized pressures, check thermal expansion valves. Replace. Check refrigerant line pressures, check thermal expansion valves, replace any defective component. Replace. Check voltage. Check running amperage and conditions described under low suction pressure symptoms. Check thermal expansion valve setting, check for air in system. Check air conditions and cfm. If compressor is hot, allow compressor to cool for two hours. Recheck for open circuit. Check subcooling. Review wiring schematics. Check all connections. Replace relay. Verify amp draw. Review wiring schematics. Check voltage. Check all connections. Replace relay. Verify amp draws. Replace compressor if necessary. Replace. Check pressures and subcooling. Check thermal expansion valve setting. Check for refrigerant overcharge. Dampen tubing vibration by taping or clamping. Carefully bend tubing away from contact where possible. Check high and low side pressures during operation to confirm. Rewire for opposite rotation. Replace the compressor. Check that compressor is properly isolated and mounting bolts are tight. Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information. 12 Packaged DX Module for Make-Up Air Unit
13 Troubleshooting Refrigeration Circuit (continued) Symptom Possible Cause Corrective Action High suction pressure High discharge pressure Low suction pressure Excessive load on evaporator coil. Expansion valve sensing bulb not secured to suction line. Thermostatic expansion valve. Overfeeding. Overcharged. Thermal expansion valve setting. Air inlet to condenser dirty or obstructed. Condenser fan motor defective. Too much refrigerant. Non-condensable in system. Dirty condenser coil. Condenser fan not running or running backwards. High load conditions. Refrigerant undercharge/loss of refrigerant charge. Blower running backward. Loose blower, pulley or belts. Low entering air temperature. (Low load conditions). Refrigerant leak. Evaporator dirty or iced-up, or airflow restricted. Plugged liquid line filter-drier. Improper hot gas bypass setting. Expansion valve defective, superheat too high or valve too small. Moisture in system, check sight glass. Check for high entering wet bulb temperature, check for excessive air flow. Check the thermal expansion valve, ensure bulb is insulated. Check superheat. If superheat is high, then valve is choking refrigerant flow. Check bulb for contact. Adjust valve for superheat ~10 F. Replace valve power head or valve. Check bulb location and clamping. Adjust superheat. Replace expansion valve power head. Check pressures and subcooling. Check thermal expansion setting and calibrate superheat / subcooling. Check for proper clearances and possible air recirculating. Clean coil. Check condenser fan motor. Check subcooling. Remove excess refrigerant. Remove non-condensable from system. Clean condenser coil. Check electrical circuit and fuse. Check fan cycling controls. Add more equipment or reduce load. Check pressures and subcooling. Confirm blower rotation. If reversed, interchange any two wires from 3-phase disconnect. Check drive pulley alignment, belt tension. Check entering air wet bulb conditions. Check system for leaks. Repair leaks and add refrigerant. Clean the coil. Check fan operation. Check airflow. Replace filter-drier, check psi across filter. Check setting and correct as required. Adjust valve for proper superheat or replace the expansion valve if too small or defective. Reclaim refrigerant, check for leaks, recharge. Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information. Packaged DX Module for Make-Up Air Unit 13
14 Troubleshooting Refrigeration Circuit (continued) Symptom Possible Cause Corrective Action Low discharge pressure Compressor short cycles Compressor loses oil Not enough cooling or lack of cooling Liquid line is frosted or wet Suction line is frosting Frost on evaporator coil Insufficient refrigerant charge. Defective or improperly adjusted expansion valve. Low suction pressure. Faulty condenser temperature controls. (Condensing fan cycle switch). Thermostat location or controls malfunction. Improper refrigerant charge. Defective high or low pressure control. Poor air distribution. High discharge pressure. Low airflow at evaporator(s). Incorrect unit selection (oversized). Refrigerant leak. Short cycling. Refrigerant flood back. Refrigeration undercharged. Dirty filter or evaporator coil. Dirty or clogged condenser coil. Air or other non-condensables in system. Restriction in suction and liquid line. Control contacts stuck. Excessive load. Restriction in liquid line. Insufficient evaporator airflow. Malfunctioning or defective expansion valve. Hot gas bypass valve not functioning properly. Manual hot gas bypass valve closed. Low load or airflow. Check subcooling, check for leak. Repair leak and add refrigerant. Check superheating and adjust thermal expansion valve. See low suction pressure. Check condenser controls and reset to obtain desired condensing temperature. Check thermostat, check heat anticipator setting. Check subcooling, verify superheat. Check high or low pressure switch. Check ductwork for recirculating. See high discharge pressure. Check blower operation and airstream restrictions. Contact factory. Check system for leaks. Repair leaks and add refrigerant. Check low pressure control settings. Check thermal expansion valve setting. Check for refrigerant overcharge. Check crankcase heater operation. Check subcooling. Adjust charge, if necessary. Check filter, coil and airflow. Check coil and airflow. Check equalized high side pressure with equivalent outdoor temperature. Check for restrictions in refrigerant circuit. Check wiring. Add more equipment or reduce room load. Clear restriction upstream of point of frosting. Check airflow, check filters, check drive for loose parts or belts. Check VFD control signal for proper operation. Check bulb of thermal expansion valve. Check valve. If defective, replace. Open valve. Increase airflow, check filters. Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service information. 14 Packaged DX Module for Make-Up Air Unit
15 Routine Maintenance DANGER Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to the unit to OFF at disconnect switch(es). Unit may have multiple power supplies. CAUTION Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur. This unit requires minimal maintenance to operate properly. To ensure proper operation and longevity, the following maintenance schedule should be followed. The items in this list assume a relatively clean air environment and may require attention more frequently in a dusty or dirty area. If this unit contains an indirect gas-fired heater, refer to the Installation, Operation and Maintenance manual provided with the unit for maintenance purposes. An EPA Certified Technician should complete all refrigeration systems checks. Maintenance Frequency: Monthly 1. Condensate Drain Inspect and clean. Refill with water or glycol. Annually It is recommended that the annual inspection and maintenance occur at the start of the cooling season. After completing the checklist, follow the unit start-up checklist provided in the manual to ensure the refrigeration system operates in the intended manner. 1. Door Seal Check if intact and pliable. 2. Wiring Connections Check all connections for tightness. 3. Cabinet Check entire cabinet, inside and out, for dirt build-up or corrosion. Remove accumulated dirt, remove any surface corrosion and coat the area with appropriate finish. 4. Evaporator Coil Maintenance Check for cleanliness. Clean if required. 5. Condenser Coil Maintenance Check for cleanliness. Clean if required. 6. Condensate Drain Inspect and clean. Refill with water. 7. Condensing Fan Blades and Motors Check for cleanliness. Check all fasteners for tightness. Check for fatigue, corrosion and wear. Maintenance Procedures: Lubrication Check all moving components for proper lubrication. Apply lubricant where required. Any components showing excessive wear should be replaced to maintain the integrity of the unit and ensure proper operation. Dampers Check damper (if present) to ensure it opens and closes properly and without binding. Apply power to motorized dampers to ensure the actuator opens and closes the damper as designed. Reference Component Location Outdoor Air Intake Evaporator Coil Direct Gas-Fired Burner Outdoor Air Intake Unit Control Center Evaporator Coil Outdoor Air Intake Condenser Fans and Condenser Coil Model DGX Make-Up Air Unit Condenser Fans and Condenser Coil Model IGX Make-Up Air Unit Evaporator Coil Condenser Fans and Condenser Coil Model MSX Make-Up Air Unit with Electric Heat Indirect Gas-Fired Furnace Unit Control Center Unit Control Center Packaged DX Module for Make-Up Air Unit 15
16 Maintenance Log Date Time AM/PM Notes: Date Time AM/PM Notes: Date Time AM/PM Notes: Date Time AM/PM Notes: Date Time AM/PM Notes: Date Time AM/PM Notes: Date Time AM/PM Notes: Date Time AM/PM Notes: Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. AMCA Publication , Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at Phone: Fax: Parts: [email protected] Website: Packaged DX for Make-Up Units, Rev. 3, August 2016 Copyright 2016 Greenheck Fan Corporation
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Table Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
LOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: [email protected] Website: www.centrair.ca
Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
First irst Co. Products
First irst Co. Products Recommended Maintenance Program PM1193 FIRST OPERATIONS,LP - P.O. Box 270969 - Dallas, Texas 75227 - www.firstco.com Table of Contents Introduction... 3 General Precautions... 3
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR
3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
Compressor Service & Maintenance Manual
Compressor Service & Maintenance Manual C Series COMPRESSOR (D)C1103 (D)C1203 (D)C2106 (D)C2206 (D)C3210 Copyright 2006 DCI. All Rights Reserved. 92311, Rev. C, 08/13 1 C1000 Series Service & Maintenance
UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for
Dehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning
CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.
I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is
T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200
INSTRUCTION MANUAL FOR: T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleanthermal.com INSTRUCTION MANUAL TABLE OF CONTENTS
PC1130 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1130 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
COMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units.
R Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL for SPLIT SYSTEM Bus Air Conditioning Units T--326 Rev -- OPERATOR S MANUAL BUS AIR CONDITIONING UNITS GEN IV & GEN V CONTENTS
PC1131 Electric Air Compressor
Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6
AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2
POLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls
Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
Refrigeration System Installation & Operation Manual
Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3
Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00
E Refrigerant Charging Unit ICOGD 020AH1000 Operating Manual FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00 Contents Technical Specifications... 20 Safety... 21 A/C System... 22 Components... 23 Control Panel...
Installation Instructions
CNPVU CNRVU Uncased Coils Upflow - Downflow Heating - Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...
Panel Mounted Air Conditioners by Dantherm, Inc.
Panel Mounted Air Conditioners by Dantherm, Inc. CS020020A/B with USACG-6 Control PRODUCT INFORMATION MANUAL AC-2 CS020020 USACG-6 Manual Rev H Page 1 of 17 Dantherm, Inc. 110 Corporate Drive, Suite K
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor
INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:
Training Syllabus to Instruct/Prepare for the ASE Transit Bus HVAC Test
APTA STANDARDS DEVELOPMENT PROGRAM RECOMMENDED PRACTICE American Public Transportation Association 1666 K Street, NW, Washington, DC, 20006-1215 APTA BTS-BMT-RP-001-10 Approved October, 2010 APTA Bus Maintenance
Technical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
BMG/TMG -27, 48, 52, 74, 80 LAE CONTROLLER Installation & Operations Manual
BMG/TMG -27, 48, 52, 74, 80 LAE CONTROLLER Installation & Operations Manual Master-Bilt Products 908 Highway 15 North New Albany, MS 38652 Phone: (800) 684-8988 PN 075-90000 Rev 4-26-11 1 2 TABLE OF CONTENTS
SINGLE PHASE MOTORS. INSTALLATION AND MAINTENANCE MANUAL March 21, 2006
SINGLE PHASE MOTORS INSTALLATION AND MAINTENANCE MANUAL March 21, 2006 Irvine, California (800) 474-0520 Indianapolis, Indiana (800) 866-7973 Hamilton, Ontario (800) 809-0330 e-mail: [email protected]
Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
T-Series Air Conditioner T62 Model
INSTRUCTION MANUAL T-Series Air Conditioner T62 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
CE6500 Energy Recovery Ventilator
ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge
MP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
SECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
1 For All Non-Programmable Digital Thermostat
OWNER'S MANUAL P/N P474-0100 1 For All Non-Programmable Digital Thermostat TOTALINE 68 Dual Setpoint Very easy to program Thermoglow Backlight No batteries required Auto-Changeover Locking Keypad Meets
Single Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
FOXAIR 60/50 ALL MODELS
FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,
12V Portable Diaphragm Compressor Operating and Maintenance Instructions
12V Portable Diaphragm Compressor Operating and Maintenance Instructions (Part No. DC2) Part No. Serial Number Date Purchased Table of Contents Page Safety Messages...2 Guidelines for Product Use...2 Operation
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
WINDOW ROOM AIR CONDITIONER
WINDOW ROOM AIR CONDITIONER Installation and Operation Manual Electromechanical Remote Control CAPACITIES 220V - 60 HZ. 12,000; 18,000; 24000 BTU/HR 220V-240V - 50 HZ. 12,000; 18,000; 24000 BTU/HR Please
Instructions For SF 6 Refill Kit
S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Instructions For SF 6 Refill Kit TABLE OF CONTENTS Section Page Section Page INTRODUCTION..................................
ENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. This Troubleshooting Guide covers the electric coolant valve and control
ice 3 FLUID TO FLUID HEAT PUMP
ice 3 FLUID TO FLUID HEAT PUMP SUBMITTAL DATA (888) 530-7713 P O Box 5, Wentworth, H 03282 Rev.3 (5-30-14) ice 3, IC-2040 Fluid-to-Fluid R-410a Heat Pump Engineering Guide Specifications General otes:
JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator
JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator The Janus Pantheon mini operator does not typically require the provision of any additional site requirements other than
Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400
Owners Manual Refrigerated Air Dryer HX75 thru HX2400 IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS INFORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILIAR WITH THE PROPER INSTALLATION
A/C refrigerant system, overview
Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL Service Information If service or parts are required, contact the nearest Norcold Service Center. To find an authorized Norcold Service Center
HEAT RECOVERY VENTILATORS MODELS 90H-V ECM HRV, 90H-V+, 60H-V+ AND ENERGY RECOVERY VENTILATOR MODEL 90H-V ECM ERV
USER GUIDE HEAT RECOVERY VENTILATORS MODELS 90H-V ECM HRV, 90H-V+, 60H-V+ AND ENERGY RECOVERY VENTILATOR MODEL 90H-V ECM ERV PLEASE READ AND SAVE THESE INSTRUCTIONS These products earned the ENERGY STAR
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI Page 2 / 16 CONTENTS 1 GENERAL... 3 2 SAFETY... 3 2.1 Safety instructions... 3 2.2 Correct use... 3 3 DESCRIPTION
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC
Portable Evaporative Air Cooler OWNER S MANUAL Read and save these instructions before use Model: CL30XC Power rating: 250 Watts Voltage rating: 230 Volt, 50Hz Made in P.R.C. QUICK START GUIDE Fill with
Miami Heat Pump HP Series Installation Guide
CAUTION- THIS UNIT IS FOR INDOOR USE ONLY!! WARNING BEFORE ANY INSTALLATION OR MAINTANCE IS STARTED PLEASE READ COMPLETE INSTLLATION GUIDE. INSTALLATION START-UP AND SERVICE INSTRUCTION- The HP Water Source
T-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177
T-SERIES Air Conditioners T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177 88043249 TABLE OF CONTENTS RECEIVING THE AIR CONDITIONER...3 HANDLING AND
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW
Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as
IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.
THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to
