HEPA FILTER DEFECTS ARE COMMON
|
|
|
- Cameron Robertson
- 9 years ago
- Views:
Transcription
1 HEPA FILTER DEFECTS ARE COMMON Kenneth F. Cherry 1 and Kenneth A. Smigielski 2 1 NCEC Inc. 2 First Solar LLC. ABSTRACT HEPA filters (High Efficiency Particulate Air) filters are claimed by vendors to have % collection efficiency for particles down to 0.3 microns. We have found that relying on this claim may lead to employee exposures and emissions far in excess of those anticipated. In an attempt to comply with a corporate goal of zero detectible emissions for both in plant and stack discharges high quality HEPA filter holders and filters were purchased. After installation unexpected particulates were found in routine sampling. Our response included trying filters from several vendors and having filters installed by both the vendor s representative and our staff. This did not totally eliminate the problem and further investigation revealed that there were inadequacies in the certified HEPA filters delivered by several manufacturers. A relatively novel testing method was employed for testing both the HEPA filter material and gaskets seals. HEPA filters, as delivered, can t be relied on to perform as advertised. A test method for the evaluation of performance, although expensive, is available. With appropriate diligence HEPA quality filtration can be obtained, but not consistently using manufacturer certified filters and common HEPA filter holders.
2 A combination of inspection methods and special filter mounting methods is required in any critical application of HEPA filtration technology. Design principles, testing methodologies and results of tests on various vendors filters will be presented. Key Words: HEPA filtration, filter leaks, HEPA defects, and air filtration systems. INTRODUCTION HEPA filters were chosen as a means to assure compliance with a corporate goal of no detectable cadmium particles in the plant environment. A review of past and current cadmium levels demonstrated that the measured levels were always well below OSHA standards. Measurements of in-plant air showed occasional low levels substantially below the OSHA requirements. The corporate goal of no detectable metallic particulates was not consistently achieved. A comprehensive evaluation to determine sources of cadmium dust particles resulted in the correction of numerous potential small contributors. A Scanning Electron microscope and a combination of settling plates as well as NIOSH sampling methods indicated the likelihood of particulates from HEPA filtration units potentially sometimes in the plant air. An investigation to determine the root cause of the apparent failures was initiated. A basic assumption was that HEPA filters would remove all metallic particles at the rated efficiency.
3 PROBLEM AND HYPOTHESIS Minute traces of metallic dust in the plant environment at the facility did not meet a corporate goal of no detectable cadmium in the workplace air. A structured evaluation program using atomic absorption and scanning electron microscope methods to analyze samples from the plant apparently eliminated all sources except the HEPA air filtration units which served as an exhaust on some equipment. These HEPA filtration units discharged into the plant atmosphere. A reputable manufacturer for the equipment and filters had been chosen and there were no visually obvious problems with the systems. ASSUMPTIONS 1. The investigation of sources eliminated all potential in plant contributors to the metallic particulates found except the HEPA air filtration system. 2. Cadmium was not present in the ambient air outside the plant used as makeup air for the facility. 3. The sampling and analytical technique used was adequate for detection of cadmium at the levels reported. 4. The HEPA filters would remove all detectable cadmium particulates if operating at design efficiencies. REVIEW OF BACKGROUND INFORMATION HEPA filters are advertised as 99.97% effective on particulates of 0.3 microns or larger. Several filter vendors were contacted and their literature reviewed. It was apparent that the testing methods of the various manufacturers differed.
4 Discussions with manufacturers representatives and the review of periodical literature did not revel a common industrial problem recognized which would obviously cause the finding of particulates in our in-plant atmosphere. PROCEDURES An extensive investigation of all potential metallic sources was initiated. This investigation included sampling and developing a method to recognize various species of cadmium compounds using a scanning electron microscope (SEM). The results of the SEM examination were compared to resulting uses NIOSH sampling methods and atomic absorption analysis for cadmium. Some minor potential contributors were found and corrected. The problem of measurable cadmium, well below OSHA limits, in the plant environment occasionally continued. 1. Filter housing used in the facility were constructed having all internal seems sealed with silicon adhesive and the filter mounting mechanism was designed to apply 600 lb force to the gasketed filter structure. 2. Subsequently filters were obtained from three vendors 3. These filters were all gasketed and rated by manufacturers as HEPA filters at the 99.97% 0.3 micron rated. A visual inspection of the filters, which arrived at the facility, shows that there was some variance in the methods selected by the manufactures for the mounting of the filter media and the filter case as well as the gasketing of the filter case. The filter vendors assured us that the filters were all compatible with the equipment used on-site. Filters from some
5 vendors even came with certificates of inspection and testing from the manufacturing facility. A testing service known as Mechanical Testing Service Inc from Grandville, MI was eventually selected to come on site to perform tests of the filters in service. The testing protocol chosen was in conformance with federal standards 209E and the Institute of Environmental Sciences Standard IES-RP-CC006.2 testing clean rooms. A Thompson model BC700 photometer along with a model TDA-5B aerosol generator was used to challenge the media and the test for leaks. In this system a known aerosol size distribution is generated and injected into the air stream entering the filter. The probe is then used to scan the entire filter surface for leaks. TEST 1: SCAN METHOD LOGARITHMIC PROCEDURE This test is performed by introducing specified aerosol upstream of the HEPA filter and searching for leaks by scanning the downstream side of the filters with the photometer probe. The design airflow velocity is set prior to performing the filter installation leak test. The HEPA and pre-filters are pictured below in Figure 1. This HEPA unit is 24 x 24 x 12 in size and weighs 41 pounds. A pre-filter is place in front of the HEPA filter to capture large particles and reduce the loading on the HEPA filters.
6 HEPA Filter Pre-Filter Figure 1 HEPA and Pre-filter DESCRIPTION I) Aerosol is introduced into the air supplied to the HEPA filters in a manner, which will produce a uniform challenge concentration at the HEPA filter. II) The aerosol generator air supply pressure is set at 20 psig minimum. The number of nozzles operated is determined by the necessity to produce a concentration for detection by the photometer. III) The logarithmic readout photometer is adjusted using the instrument calibration curve, and the upstream aerosol challenge concentration is measured.
7 IV) Passing the probe in slightly overlapping strokes so that the entire area of the filter is sampled the probe is used to scan the filter face and perimeter of the filter pack. The probe should be held approximately 1inch (2.5cm) from the area of testing during the scanning. Separate passes were made around the entire periphery of the filter, along the bond between the filter pack and the frame, and around the seal between the filter and the device, at a traverse rate of not more than 10 feet/min (3 m/min). Reference Figure 2 (below) V) The logarithmic photometer results are indications of detected leaks greater than one scale division or less than 0.01 percent leakage. Scan probe HEPA housing HEPA filter Figure 2 Logarithmic Testing Procedure
8 TEST 2: LINEAR TESTING PROCEDURE This test is performed by introducing aerosol upstream of the HEPA filter and monitored on the downstream side to determine the percent efficiency of the filter. DISCUSSION I) Aerosol is introduced into the air supplied to the HEPA filters in a manner, which will produce a uniform challenge concentration of the HEPA filter. II) The aerosol generator air supply pressure is set at 20 psig minimum. The upstream concentration should be established using one or more nozzles adjusted to read 10 to 20 micrograms of air on the upstream concentration. The photometer is adjusted to read 100 percent. Reference Figure 2 (below). III) IV) Access to the duct system downstream from the filters must be established. The system to be tested will maintain a flow rate (CFM) set at normal operation conditions. V) Passing is specified as a measurement of less than 0.3 percent of upstream challenge for HEPA filters rated at percent.
9 Figure 3 Log/Linear Photometer PRESENTATION OF SUMMARY OF RESULTS A total of 34 HEPA filters were tested for this report. Out of the 34 tested filters only 12 filters (35%) passed on the initial testing. The 22 filters that failed the initial testing for a variety of reasons. Some filters contained poor gasketing (gaps in the gaskets material) resulting in leaks around the edges of the filter. Some of the gaskets were repaired using a gasket sealant and the filters were capable of being used. Other filters failed due to a poor seal with the filter housing. Some of these filters were retightened and passed a second test. Several of the filters tested had holes or poor filter media. These filters were not repaired they were discarded or returned to the vender. The filter testing included both systems with a single HEPA filter and systems with multiple HEPA filters in one housing. Failures of these systems were determined in a combined result of the entire
10 system, which resulted in less than 99.97% efficiency. The following graphs highlight the results of this test. HEPA FILTER TESTING RESULTS NOTE: A failure is the detection of any particles passing through the filter, not an evaluation of the 99.7% efficiency claimed for the HEPA filters. HEPA Filter Test Results filters Passed 22 filters Fail
11 HEPA FILTER FAILURE ANALYSIS HEPA Filter Failures % 41% % 10 0 System Failures Media Holes Install/Gaske t HEPA FILTER VENDER ANALYSIS HEPA Filters- Passing First Test % 33% 0 Vender A Vender B Vender C
12 HEPA Filters - Percent Pass After "Fixing" % 71% 0 Vender A Vender B Vender C DISCUSSIONS Prior to conducting this evaluation of performance of HEPA filters we assumed that the manufacturer s representation and certification were correct. We improperly assumed that careful installation of filter from a reputable vendor into the filter holder design for HEPA filters would provide essentially complete removal of particulates. Based on our investigation we conclude the following: 1. HEPA filters as manufactured by many US companies have significant defects when shipped. 2. Manufacturers certification of tests performed on individual filters prior to shipment are not a reliable indicator of filter quality. 3. Current common filter gasketing used in state of the art filter holders may leak even when following the recommendations of the manufacturers.
13 4. In critical applications it is essential to have an ongoing filter test program to assure HEPA filter system performance meets the anticipated goals. Complying with corporate goals of zero detectible emissions is possible but requires extensive monitoring of the HEPA filtration system. To insure compliance, a testing Service is contracted twice a year to assist in installation and tests of filters. Installation and testing requires a staff including a maintenance employee, the EHS engineer, and a scissor lift operator for eight to ten hours. Also, it is necessary to keep a significant surplus of filters on site to compensate for the anticipated failed performance in a portion of the filters to be installed. The installation of filters is not only time consuming, it also impacts the manufacturing process. Shut down of equipment for the filter change out and testing can take as long as an hour per filter. Often times, one or possibly two or three filters are installed and tested to achieve acceptable performance.
EACO DOP / PAO TESTING GUIDELINE 2013
2013 Foreword The guideline promotes industry standards for training, equipment, and methodologies for HEPA filter integrity testing of negative air units, vacuums and any other HEPA filtered equipment
PERFORMANCE QUALIFICATION OF A CLEAN ROOM FROM A QUALITY PERSPECTIVE
PERFORMANCE QUALIFICATION OF A CLEAN ROOM FROM A QUALITY PERSPECTIVE Every facility design is unique for its specific needs, and validation programs must be customized to meet these challenges. While there
Guide to in situ leak testing of HEPA filter configurations that cannot be conventionally scan tested
DOP Solutions Technical Document: Guide to in situ leak testing of HEPA filter configurations that cannot be conventionally scan tested Issue 1: Prepared by Neil Stephenson and Tim Triggs and edited by
Laminar Flow Cabinets
Laminar Flow Cabinets The World s Most Practical Selection of Benchtop Laminar Flow Cabinets. 24 36 48 Simple, Effective Protection for Samples and Work Processes, Uncompromised Performance, Economical
Environmental Monitoring
Chapter 10 Environmental Monitoring By the end of this chapter, you will be able to: l List the types of environmental testing l Name three types of checks that are carried out to ensure the isolator is
ASBESTOS MANAGEMENT PROGRAM
ASBESTOS MANAGEMENT PROGRAM Prepared By: Triumvirate Environmental Program Approval Developed: August 2011 Updated: June 2015 Associate Vice President of Public Safety & Administrative Services Date Associate
HVAC Design Requirements
Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements
1.0 What Are the Purpose and Applicability of Performance Specification 11?
While we have taken steps to ensure the accuracy of this Internet version of the document, it is not the official version. Please refer to the official version in the FR publication, which appears on the
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace Our thanks to OK International for allowing us to reprint the following. Why do we need fume extraction? Today s Electronics workplace
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
Stack Sampling Stack sampling or source sampling
Stack Monitoring Stack Sampling Stack sampling or source sampling may be defined as a method of collecting representative samples of pollutant laden air/gases at the place of origin of pollutants to determine
HEPA Filters for Pharma Applications Cleanrooms & Safety Applications. Gordon Farquharson June 2012
HEPA Filters for Pharma Applications Cleanrooms & Safety Applications Gordon Farquharson June 2012 1 Air Filters at work Images courtesy of CamfilFarr 2 How filters work Sieving Effect Straining 3 Filter
Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project
Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project The Watergate Community is currently in the process with the fire suppression and interior renovations
HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests
FOREMOST IN AIR FILTRATION HEPA Filters and Filter Testing PB-2007-1203 HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests A Wholly Owned Subsidiary of Flanders Corporation
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material Revised November 21, 2013 Application Code of Practice Where asbestos is present or believed to be present in a workplace
HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests Bulletin: PB2007-0504
HEPA Filters and Filter Testing A Comparison of Factory Tests and In-Service Tests Bulletin: PB2007-0504 Introduction HEPA filters, once known as absolute filters, were originally developed as the particulate
S300 Series Dust Monitors
S301 DustGuard S303 Trend Monitor S304 Emission Monitor S305 Stack Monitor Intrinsically Safe (ATEX) Dust Monitors Split Architecture (Remote)Models Data Logging Software S300 Series Dust Monitors Dust
Medical Air Systems: Scroll
GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing
SPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
What is a successful Steam Trap Management Program?
What is a successful Steam Trap Management Program? With today s energy costs, it is extremely important to have a proactive steam trap-testing program included with the overall Steam System Management
Specification. Indoor Air Quality Management
GREENGUARD Environmental Institute 2211 Newmarket Parkway, Suite 110 Marietta, GA 30067 1.800.427.9681 Specification Indoor Air Quality Management This Master Specification section is intended for use
Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health
Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class
Energy Efficient Operations and Maintenance Strategies for Boilers
Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must
Installation and Operating Manual Model F1800C Model F1800PG Model F1802C Model F1802PG Model F1806C Model F1806PG
Installation and Operating Manual Model F1800C Model F1800PG Model F180C Model F180PG Model F1806C Model F1806PG www.ipsystemsusa.com Contents Safety Warnings... Items supplied... Description... Installation...4
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory
CONTAMINATION CONTROL FOR ELECTRONIC AND SEMICONDUCTOR APPLICATIONS
CONTAMINATION CONTROL FOR ELECTRONIC AND SEMICONDUCTOR APPLICATIONS UNDERSTANDING, ACCELERATED TSI SETS THE STANDARD FOR PARTICLE COUNTING Performance Semiconductor, hard disk drive, and flat panel manufacturers
James M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard
MC² Market & Competitive Convergence Air Filters: New Facilities, New Standard Advances in testing procedures, coupled with greater pressure for better IAQ, leads to a new standard By Ron Wilkinson, P.E.
How To Install A Perfect 16 Id Series Filter System
IQAir Perfect 16 ID-Series MERV16 Micro-Particle Filtration System Perfect 16 Installation Manual Product Data High-Performance Medical-Grade Residential/Commercial Air Filtration System Application The
Installation and Operating Instructions Installation Instructions for SS EPE-316L Series
INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This
ASBESTOS SCIENCE TECHNOLOGIES, INC.
ASBESTOS SCIENCE TECHNOLOGIES, INC. P.O. Box 505 Bangor, CA 95914 Phone (530) 518-0934 Email - [email protected] Report for Lincoln Elementary School 1582 Lincoln Road Yuba City, Ca. 95993 Mold Report
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?
THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494
THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494 1. BEFORE YOU BEGIN IMPORTANT INSTRUCTIONS READ AND SAVE FOR THE CONSUMER WARNING: Risk of scalding or other severe injury. Before completing installation,
A Report of Air Sampling for Mercury Vapor and Particulates During Fluorescent Tubes Disposal Operation Maywood, Illinois Survey date: 9/28/2000
A Report of Air Sampling for Mercury Vapor and Particulates During Fluorescent Tubes Disposal Operation Maywood, Illinois Survey date: 9/28/2000 Prepared for: Air Cycle Corporation 2000 South 25 th Avenue,
SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR. www.sentryair.com 1.800.799.
SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR 1.800.799.4609 www.sentryair.com Pharmaceutical Compounding Safety Solutions Sentry Air Systems
A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
Reducing Injury and Damage Related to Electric Dryer Fires. Fire Containment Tests for the Second Edition of UL 2158
Reducing Injury and Damage Related to Electric Dryer Fires Fire Containment Tests for the Second Edition of UL 2158 Reducing Injury and Damage Related to Electric Dryer Fires: Fire Containment Tests for
AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller
January 2013 AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller Milliken Valve Company 190 Brodhead Avenue, Suite 100 Bethlehem, PA 18017 Phone: (610) 861-8803 Fax:
Wastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,
Scientific and analytical consultancy services for industry
Scientific and analytical consultancy services for industry EXPERTISE ON SITE AND IN THE LABORATORY Anchem Laboratories is a multi-disciplined accredited Laboratory offering a range of specialised environmental
Certification system of air filter quality (CAF mark)
Certification system of air filter quality (CAF mark) KOREA AIR CLEANING ASSOCIATION 1. Overview What is the certification system of air filter quality (CAF mark)? It is a mark granted by the KACL depending
TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation
GTRDD SERIES HEATLESS DRYER INSTALLATION, OPERATION & MAINTENANCE MANUAL TABLE OF CONTENTS SECTION 1 General Information: Pg 2 Description of Operation SECTION 2 Safety Instructions: Pg 3 Installation
SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING
SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air
Rotary Screw Compressors UP-Series 4 & 5.5 kw
Rotary Screw Compressors UP-Series 4 & 5.5 kw Rotary Screw Compressors UP-Series 4 & 5.5 kw Boost Your Profitability Boosting your company s profits was the main goal that Ingersoll-Rand had in mind when
Cartridge Filter Application Notes
Industrial Water Purification (800) CAL-WATER Cal Water 1961 Petra Lane Placentia, CA 92870 FAX: (714) 792-0794 Web Page / Email: www.cal-water.com Cartridge Filter Application Notes Cal Water offers a
NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS
NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS National Air Duct Cleaners Association 1518 K Street, N.W. Suite 503 Washington, DC 20005 (202)
3M Purification Inc. 3M Air Management Products for Your Commercial HVAC Needs. Create. Air. Confidence
3M Purification Inc. 3M Air Management s for Your Commercial HVAC Needs Create an Air of Confidence Pursuing Innovation 3M Company has long encouraged employees to pursue ideas and concepts that might,
PREFAULT MONITOR FOR AIR COOLED GENERATORS
PREFAULT MONITOR FOR AIR COOLED GENERATORS Steve Kilmartin Utility Products Specialist Environment One Corporation 2773 Balltown Road Schenectady, NY 129 518 346-6161 George F. Skala Senior Engineer Environment
Spetec Laminar Flow Systems. Operating Instructions
Spetec Laminar Flow Systems Operating Instructions 1 Spetec Laminar Flow Systems Operating Instructions Thank you for your trust in the Spetec clean room systems! Your chosen system is ideally suited for
Gerry Kaelin, FilterSense, USA, describes the ways in which optimising toward compliance with environmental regulations can reduce baghouse
Gerry Kaelin, FilterSense, USA, describes the ways in which optimising toward compliance with environmental regulations can reduce baghouse maintenance and operational expenses. Making Sense Introduction
ENVIRONMENTAL MONITORING / TESTING TO CONFORM WITH ISO14644 & TGA GMP REQUIREMENTS
ENVIRONMENTAL MONITORING / TESTING TO CONFORM WITH ISO14644 & TGA GMP REQUIREMENTS PRESENTATION TO RACI 20 TH APRIL 2016 PAUL MORGAN DIRECTOR CRITICAL CERTIFICATION PTY LTD CHANGES TO ISO14644 PART 1 CHANGES
ball valves Flomite 71 Series 2-way Integral Panel Mount Ball Valves
2-way Integral Panel Mount Ball Valves Used for quick on-off service with a visual indication of flow, HOKE s 2-way ball valves offer orifice sizes up to 0.25 (6.4mm). Flomite valves feature a floating
RULE 8-8 - ORGANIC COMPOUNDS - WASTEWATER COLLECTION AND SEPARATION SYSTEMS
BAY AREA AIR QUALITY MANAGEMENT DISTRICT RULE 8-8 - ORGANIC COMPOUNDS - WASTEWATER COLLECTION AND SEPARATION SYSTEMS (ADOPTED: January 17, 1979) (AMENDED: November 1, 1989; October 6, 1993; June 15, 1994;
Scotchgard Multi-Layer Protective Film 1004
Scotchgard Multi-Layer Protective Film 1004 3 Technical Bulletin September, 2008 Scotchgard Multi-Layer Protective Film 1004 Application Kit (3M Part No. 70-0710-4666-1) includes: (clockwise) Heavy Duty
BY MCI SOLUTIONS SECONDARY CONTAINMENT ADAPTOR
BY MCI SOLUTIONS SECONDARY CONTAINMENT ADAPTOR www.mcisolutions.ca Company Profile About Us MCI Solutions (MCI) is a manufacturing leader in chemical injection technologies, providing unique solutions
MARC5001A Employ tools, equipment and materials in a shipboard context
MARC5001A Employ tools, equipment and materials in a shipboard context Release 1 MARC5001A Employ tools, equipment and materials in a shipboard context Modification History Release 1 This is the first
APPENDIX A-1 SAMPLE CLEANROOM SPECIFICATIONS MICROELECTRONICS & SEMICONDUCTORS
APPENDIX A-1 SAMPLE CLEANROOM SPECIFICATIONS SECTION xxxxx CLEANROOM PERFORMANCE TESTING PART 1 -- GENERAL 1.1 WORK INCLUDED A. This Section specifies the requirements of the NEBB Certified Cleanroom Performance
ACC1-10, ACC1-25, ACC1-50, ACC1-125
FAN FILTER DIFFUSER PRODUCT OVERVIEW TABLE OF CONTENTS Page No. 92FFD Series Fan Filter Diffusers Aluminum or Stainless Steel 3 Dimensional Data 4 Performance Data 5 ECM Technology 7 RMBC (Room-Side Removable
Set-Up Instructions. (Liner-Based System) UL LISTED. Important Read set-up instructions before assembly. Report any shortages within 72 hours
INDUSTRIAL POWER Set-Up Instructions (Liner-Based System) UL LISTED Important Read set-up instructions before assembly. Report any shortages within 72 hours Specializing in Environmental and Fire-Life
APPLICATION COMPETENCY FIELD
UNIT CODE UNIT TITLE APPLICATION COMPETENCY FIELD ELEMENTS Elements describe the essential outcomes. 1 Follow safe work practices MARC018 Employ tools, equipment and materials in a shipboard context This
SELECTION, APPLICATION & MAINTENANCE
DIESEL PROTECTION SYSTEMS TPZ Engine Air Intake Shut Down Valves (Combined Automatic Overspeed and Air Pressure Operated Shut Down Bendix Types) SELECTION, APPLICATION & MAINTENANCE Valve Numbers TPZ-101
Cat S O SSM. Services. Reporting Particle Count by ISO Code. Management Guide. Two methods of reading particles
Cat S O SSM Services Management Guide Two methods of reading particles Measuring contamination ISO Codes ISO 11171:1999 Reporting Particle Count by ISO Code Introduction... 3 What ISO Means... 3 Two Methods
PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta
PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification Number: 3503-11.2.610 Rev. 2 Rubber Lined Steel Pipe and Fittings Mechanically Coupled Plain End Type System Issued Revised Approved
Robert McCabe Director, Health Care Solutions HTS Chicago. Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade
Robert McCabe Director, Health Care Solutions HTS Chicago Improved Air Quality and Energy Efficiency through Air Handler Filtration System Upgrade Biography Robert McCabe has been involved in commercial
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
IPACK2005-73273 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS
Proceedings of IPACK5 ASME InterPACK '5 July 17-, San Francisco, California, USA IPACK5-7373 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS Amir Radmehr Innovative Research, Inc. Plymouth, MN, USA
SFI SPECIFICATION 28.1 EFFECTIVE: SEPTEMBER 23, 2011 *
SFI SPECIFICATION 28.1 EFFECTIVE: SEPTEMBER 23, 2011 * PRODUCT: Polymer (Foam-Filled) Fuel Cells 1.0 GENERAL INFORMATION 1.1 This SFI Specification establishes uniform test procedures and minimum standards
Procedures for the Effective Use of Biological Safety Cabinets
Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum
Testing HEPA/ULPA filters at the manufacturer s facility and in situ on the user s premises
Publication Series Viledon Testing HEPA/ULPA filters at the manufacturer s facility and in situ on the user s premises Dipl.-Ing. Thomas Schroth Dr.-Ing. Thomas Caesar Lecture at 4th CLEANROOMS Europe
Scientific & Technical Report
Scientific & Technical Report A Comparison of Evaluative Test Methods for Cleanable Filter Elements Used in Polymer Applications Doug Elliott, Pall Corporation Mike Whitlock, Pall Corporation June 30,
CLASSIFICATION OF CLEANROOMS
CLASSIFICATION OF CLEANROOMS Cleanrooms are classified by the cleanliness of their air. The method most easily understood and most universally applied is the one suggested in the earlier versions (A to
Technical Services. Product MM INCH Installation direction Seams treatment GTI CONNECT (interlocking)
INSTALLATION INSTRUCTIONS FOR GTI CONNECT TILES This document refers to the following products: Product MM INCH Installation direction Seams treatment GTI CONNECT (interlocking) 635 X 635 mm 25.5 x 25.5
Desiccant Air Dryers Heatless, Heated and Heated Blower
Desiccant Air Dryers Heatless, Heated and Heated Blower Desiccant Dryers... Desiccant Our reliable high strength, non-acidic desiccant provides maximum performance and is easily stored and handled. Environmentally
THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS
THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS INDOOR AIR QUALITY INSTRUMENTS UNDERSTANDING, ACCELERATED BREATHE A LITTLE EASIER WITH TSI Indoor air quality is a growing concern. With the increasing
Method 202 Dry Impinger Method for Determining Condensable Particulate Emissions from Stationary Sources. By: Paul Ottenstein
Air Quality Issues in the Rocky Mountain Region PM2.5 Source Testing Method 201A Determination PM 10 and PM 2.5 Emissions from Stationary Sources (Constant Sampling Rate Procedure) Method 202 Dry Impinger
PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1
IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1 CHAPTER 44 ON-SITE CONTAINMENT OF PESTICIDES, FERTILIZERS AND SOIL CONDITIONERS [Prior to 7/27/88, see 21 Ch 9] PESTICIDES 21 44.1(206) Definitions.
Camfil Farr Technical Services Bulletin
Camfil Farr Technical Services Bulletin ASHRAE Testing for HVAC Air Filtration A Review of Standards 52.1-1992 & 52.2-1999 The American Society of Heating, Refrigeration, and Air Conditioning Engineers
MAC 10. Original & IQ FAMILY OF FAN FILTER UNITS
MAC 10 Original & IQ FAMILY OF FAN FILTER UNITS used in: microelectronics medical device semiconductor disk drive laboratory pharmaceutical markets hospitals clean rooms Table of Contents MAC 10 Original
Installation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of
APPENDIX 2-3 PCAPP EDS INSPECTION LOG SHEETS
APPENDIX 2-3 PCAPP EDS INSPECTION LOG SHEETS Pueblo Chemical Depot Pueblo Chemical Depot (This page intentionally left blank.) PCAPP EDS Daily (When in Use) Operational Inspection Checklist EXAMPLE Inspected
Signature and ISX CM870 Fuel System
Signature and ISX CM870 Fuel System Cummins Ontario Training Center HPI-TP Fuel System Heavy Duty High Pressure Injection - Time Pressure Fuel System The fuel system developed for the Signature and ISX
DATA CENTERS. Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS
DATA CENTERS Protect Your Best in Class Technology With Ours CLEAN AIR SOLUTIONS COSTLY FAN ENERGY REDUCED BY CAMFIL PREMIUM PRODUCTS = COST SAVINGS Power Usage Effectiveness (PUE) is an important metric
el-720 Carbon Dioxide Gas Leak Detector User s Guide
el-720 Carbon Dioxide Gas Leak Detector User s Guide Congratulations on the purchase of the AccuTools el-720 Carbon Dioxide Gas Leak Detector, the most technologically advanced instrument of its kind.
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
Best Practices for Handling Nanomaterials in Laboratories
Best Practices for Handling Nanomaterials in Laboratories Much of the toxicology of nanomaterials is currently uncertain or unknown. Some nanosized particles are more toxic than their respective micron
ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation
ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation Ohio Medical Corporation 1111 Lakeside Drive Gurnee, IL 60031 Phone: (800) 448-0770 Fax: (847) 855-6304 [email protected]
Air Filtration for. Indoor Firing Ranges
Air Filtration for Indoor Firing Ranges References, credits Lead Exposure at an Indoor Firing Range - NIOSH Lead Exposure & Design Considerations for Indoor Firing RAnges - NIOSH Standards - 29 CFR - OSHA
SELECTION, APPLICATION AND MAINTENANCE
DIESEL PROTECTION SYSTEMS D-Series Engine Automatic Overspeed Shut Down Valves (Spindle Types with Air Pressure and Manual Shut Down Options) SELECTION, APPLICATION AND MAINTENANCE Valve Numbers D92-AP
In-Place HEPA Filter Penetration Test
UCRL-JC-127230 PRBPRINT In-Place HEPA Filter Penetration Test W. Bergman K. Wilson J. Elliott B. Bettencourt J.W. Slawski Thispaperwaspreparedfor submittalto the 24th DOEliVRC Nuclear Air (Waning and Treatment
Diesel Fuel Systems. Injection Nozzles
Diesel Fuel Systems Injection Nozzles Unit Terms Injection nozzle Nozzle, nozzle holder, valve, spring assembly Nozzle assembly Valve, body, and spray valve Orifice Small hole Pintle Valve which the end
Mold Management Plan Operations & Maintenance
Document #: SAFETY_015 Revision Date: October 4, 2010 Mold Management Plan Operations & Maintenance Developed by: Environmental Health & Safety Approved by: Associate VP of Facilities & Campus Services
Mold Response and Remediation Plan
1.0 Policy Statement The University of New Haven has developed a mold response and remediation plan in accordance with best practices set forth by the Environmental Protection Agency (EPA), Occupational
ASBESTOS ENCLOSURE VENTILATION RESEARCH
FIELD OPERATIONS DIRECTORATE OCCUPATIONAL HYGIENE SPECIALIST GROUP REPORT ASBESTOS ENCLOSURE VENTILATION RESEARCH Author: Dr M J Gibson, HSE, Edinburgh Date: 22 August 2014 Distribution: For information:
HR Heated HB Blower. Smart Solutions for Drying Compressed Air. Dual Tower Heat Reactivated Desiccant Air Dryer
Smart Solutions for Drying Compressed Air Dual Tower Heat Reactivated Desiccant Air Dryer HR Heated HB Blower 800.943.794 www.engineeredairproducts.com Engineered Air Products Moisture in compressed air
MOLD RESPONSE AND REMEDIATION PLAN
MOLD RESPONSE AND REMEDIATION PLAN Prepared By: Triumvirate Environmental Developed: April 2011 Last Revised: March 2015 Program Approval Associate Vice President of Public Safety & Administrative Services
Experiment (13): Flow channel
Introduction: An open channel is a duct in which the liquid flows with a free surface exposed to atmospheric pressure. Along the length of the duct, the pressure at the surface is therefore constant and
Quartz Top Installation Instructions See separate installation instructions for installing your new Vanity.
Quartz Top Installation Instructions See separate installation instructions for installing your new Vanity. GOALS: The top will be positioned on the cabinet with finished edge towards the homeowner and