APPENDIX A-1 SAMPLE CLEANROOM SPECIFICATIONS MICROELECTRONICS & SEMICONDUCTORS
|
|
|
- Cynthia Powers
- 9 years ago
- Views:
Transcription
1 APPENDIX A-1 SAMPLE CLEANROOM SPECIFICATIONS SECTION xxxxx CLEANROOM PERFORMANCE TESTING PART 1 -- GENERAL 1.1 WORK INCLUDED A. This Section specifies the requirements of the NEBB Certified Cleanroom Performance Testing (CPT) Firm to measure and record the cleanroom conditions during a occupancy mode. B. Advise the Owner and the NEBB Certified Testing, Adjusting, and Balancing (TAB) Firm providing the TAB work on the adjustment and setting of dampers in access floor panels and cleanroom ceiling filters to achieve a final cleanroom certification. 1.2 RELATED WORK A. Use this section in conjunction with the following related Contract Documents to establish the total requirements for the testing of the cleanrooms: 1. Specifications: (List 2. Drawings: (List) 3. Standards: (List) 4. Other: (List) 1.3 SCOPE OF CLEANROOM PERFORMANCE TESTS A. Perform specific primary and secondary tests described in the Contract Documents. Report the test results in accordance with the acceptance criteria as stated in the Contract Documents. 1.4 REGULATORY AND STANDARD PRACTICES REQUIREMENTS A. Current edition of the NEBB Procedural Standards for Certified Testing of Cleanrooms (NEBB-PSCTC). This specification section contains multiple references to this acronym. When used or referenced in this specification, NEBB-PSCTC, is meant to identify the current publication and / or various sections, tables, equations, charts etc from the current publication. B. Other: (List) III
2 1.5 QUALITY ASSURANCE A. Firm shall be a NEBB Certified CPT Firm. B. Measurement: sampling based upon accepted NEBB sampling and statistical procedures. C. Equipment calibration: 1. Traceable by serial number to the National Institute for Standards and Technology (NIST) in accordance with the current edition of the NEBB Procedural Standards for Certified Testing of Cleanrooms. 2. Calibrate test equipment that requires calibration within the project work schedule, prior to any testing with the instrument. D. The reference standards for field tests and project record documents shall be in accordance with the current edition of the NEBB Procedural Standards for Certified Testing of Cleanrooms. 1.6 QUALIFICATIONS A. Firm Qualification: The Certified CPT Firm shall be current, certified, and in good standing with the National Environmental Balancing Bureau (NEBB). B. CPT Certified Professional: The Certified CPT Professional shall be current, certified and in good standing with the National Environmental Balancing Bureau (NEBB) and employed by the NEBB Certified CPT Firm. C. CPT Qualified Technician: The Qualified Technician shall be current, qualified and in good standing with the National Environmental Balancing Bureau (NEBB) and employed by the NEBB Certified CPT Firm and shall have completed previous training in cleanroom operations and certifying procedures thorough, demonstrable knowledge of test procedures and equipment. 1.7 COORDINATION A. Jobsite visits: Provide at least jobsite visits by the CPT Certified Professional during strategic construction phases for the period that the finished cleanroom envelope is being constructed. B. Schedule work activities with the Owner and the General Contractor / Construction Manager. Schedule may require that crucial tests be completed in an alternate sequence to allow selective partial occupancy. IV
3 1.8 SUBMITTALS A. Submit the following: 1. Qualifications of the NEBB Certified CPT Firm project specific staff. 2. Outline of the testing and certification procedures. 3. Schedule for the performance tests on this project. 4. List of instrumentation and test equipment and specimen certificates of calibration. 5. Samples of field reports, charts, and forms proposed to document measurements. B. Submit the following to the Owner within 10 working days after completion of work: 1. Preliminary field reports compiled from each of the certification steps. 2. One copy of the working field logs for review and evaluation. 3. Evaluation of any problems which may affect final certification results. 1.9 PROJECT RECORD DOCUMENTS A. Submit the final NEBB Certified CPT Report within 30 working days after completion. 1 Typed, hand-written or computerized field reports, charts, and forms complete with measured data referenced to sample location. 2. Written description of operating condition of each cleanroom. 3. Reduced set of architectural floor plan drawings, maximum size 280 mm x 432 mm (11-by-17 inches), made from the project CADD Contract Documents, obtained from the Owner, showing test and sample locations referred to on other field data sheets. 4. Separate narrative section outlining any operating or anomalies at the end of the testing procedures. 5. A list of instrumentation and test equipment used in the certifying process, including manufacturer, model and serial numbers, and NIST-traceable calibration certificate. 6. Written description of tests performed, including the purpose, instrumentation, procedure, results, date tests were taken, names of field technicians performing the tests, and analysis of the data. Present data in tabular form and display graphically to permit full understanding of the tests. 7. Electronic copies of the Final NEBB Certified CPT Report shall be submitted in pdf format. 8. A narrative outline with recommendations relating to test results and. operating conditions of each area tested. 9. A statement that cleanroom testing was performed in accordance with the NEBB Procedural Standards for Certified Testing of Cleanrooms. B. Provide one hard-bound copy and one unbound reproducible copy of the Final NEBB Certified CPT Report for the Owner s use. PART 2 -- PRODUCTS V
4 2.1 CLEANROOM PERFORMANCE TEST FIRM A. The Certified CPT Firm shall be certified by the National Environmental Balance Bureau to provide cleanroom performance testing. 2.2 MATERIALS A. Supply necessary personnel, materials, tools, test equipment, aerosol generators, instrumentation, and computers required to perform and analyze the cleanroom testing procedures described in this Section. B. Cleanroom garments and accessories will be furnished and laundered by the Owner. 2.3 INSTRUMENTATION A. All instrumentation requirements are based on standard temperature and pressure conditions (STP). Test Equipment / Instrumentation Airflow Velocity Anemometer and Uniformity Test (Direct Air Velocity Measurement) Airflow Velocity and Uniformity Test (Indirect Air Velocity Measurement) Airflow Volume and Uniformity Test Manometer Tube Array Pitot Tube or Single-Point Probe Direct Reading Hood Description A digital anemometer capable of meeting the following requirements: Range: m/s ( fpm) Accuracy: ± 5% of reading 0.50 m/s (100 fpm) or greater Accuracy: ± 10% of reading 0.50 m/s (99 fpm) or less Resolution: m/s (1.0 fpm) A digital manometer capable of meeting the following requirements: Range: m/s ( fpm) (Based on conversion of velocity pressure to velocity) Accuracy: ± 5% of reading Resolution: 0.1 m/s (20 fpm) Multi-point velocity pressure measurement sensing device to be used with a digital manometer as specified above. Range: Not Applicable Accuracy: Not Applicable Resolution: Not Applicable Single point velocity pressure measurement sensing device to be used with a digital manometer as specified above. Range: Not Applicable Accuracy: Not Applicable Resolution: Not Applicable A flow capture hood with an integral analog or digital manometer capable of meeting the following requirements: Range: L/s ( cfm) Accuracy: ± 5% of reading, ± 2.5 L/s (± 5% of reading, ± 5 cfm) Resolution (Digital): 0.5 L/s (1.0 cfm) Resolution (Analog): 2.5 L/s (5.0 cfm) Calibration Interval Not Required Not Required VI
5 Test Equipment / Instrumentation Airflow Volume Manometer and Uniformity Test Leak Testing (w/photometer) Leak Testing (w/particle Counter) Pitot Tube or Single-Point Probe Aerosol photometer Aerosol Generator Scanning Probes Particle Counter (Scanning) Particle Counter (Upstream Verification) Scanning Probes Description A digital manometer capable of meeting the following requirements: Range: m/s ( fpm) Accuracy: ± 5% of reading Resolution: 0.1 m/s (20 fpm) Single point velocity pressure measurement sensing device to be used with a digital manometer as specified above. Range: Not Applicable Accuracy: Not Applicable Resolution: Not Applicable The instrument shall have a threshold sensitivity of 10-4 micrograms per liter of challenge aerosol particles and be capable of measuring concentrations over a range of 10 5 times the threshold sensitivity. Sample flow rate shall be 28.3 L/min (1.0 cfm) with a probe inlet sized to provide isokinetic sampling. Readout shall be either linear or logarithmic with an accuracy of 1% of full scale of the selected range. A device that can aerosolize either a polydispersed or a monodispersed artificial particle medium for filter integrity testing, including Laskin nozzle type, thermal generator, atomizer, etc. Isokinetic (square or rectangular) scanning probe fitted with a sampling tube no longer than a length recommended by the aerosol photometer manufacturer or 8.0 mm (25 feet). A light scattering instrument with display or recording means to count and size discrete particles in air, as defined by ASTM F Instruments of this type shall provide for a sampling flow rate of 28.3 L/min (1.0 cfm) and a threshold size discrimination of a minimum of 0.2 micrometer in size. The unit shall be provided with an isokinetic sampling probe to maintain the probe inlet velocity at the test airflow rate. A light scattering instrument with display or recording means to count and size discrete particles in air, as defined by ASTM F Instruments of this type shall provide for a sampling flow rate of L/min (0.01 cfm) and a threshold size discrimination of a minimum of 0.2 micrometer in size. Isokinetic (square or rectangular) scanning probe fitted with a sampling tube no longer than a length recommended by the particle counter manufacturer. Calibration Interval Not Required Not Required Not Required Not Required VII
6 Test Equipment / Instrumentation Description Diluter A device that allows a ratio sample of 10:1, 100:1, or as required to achieve a minimum of 80% counting efficiency with the scanning particle counter 10% of upstream challenge. Airborne Particle Particle Counter A light scattering instrument with display or Count Cleanliness recording means to count and size discrete Classification Test particles in air, as defined by ASTM F Instruments of this type shall provide for a sampling flow rate of 28.3 L/min (1 cfm) and a threshold size discrimination of a minimum of 0.2 micrometer in size. The unit shall be provided with an isokinetic sampling probe to maintain the probe inlet velocity at the test airflow rate. Sampling Probes Isokinetic (square or rectangular) scanning probe fitted with a sampling tube no longer than a length recommended by the particle counter manufacturer or 8.0 m (25 ft). Room Pressurization Test Airflow Parallelism Test Enclosure Integrity Test Manometer Change Resolution to equal 10 Pa (0.25 in.w.g.) for magnehelic Test Medium Support Stand & Support Stand with Pointer Plumb Bob or Spirit Level Tape Measure Aerosol Generator Particle Counter An analog or digital manometer capable of meeting the following requirements: Range: Pa ( in.w.g.) Accuracy: ± 2% of reading Resolution: 2.5 Pa 250 Pa (0.01 in.w.g. <1 in.w.g.) 25 Pa > 250 Pa (0.1 in.w.g. >1 in.w.g.) A non-contaminating smoke vapor source, streamers, thread or string A device for positioning the test medium at the specified location and height that is aerodynamically designed to yield the least impact to room airflow. A small mass of heavy material suspended by a line and used to ascertain a vertical line. Linear measurement device with a minimum resolution of 1.0 mm (1/16 inch) A device that can aerosolize either a polydispersed or a monodispersed artificial particle medium for filter integrity testing, including Laskin nozzle type, thermal generator, ultrasonic humidifier, atomizer, etc. A light scattering instrument with display or recording means to count and size discrete particles in air, as defined by ASTM F Instruments of this type shall provide for a sampling flow rate of 28.3 L/min (1 cfm) and a threshold size discrimination of a minimum of 0.2 micrometer in size. The unit shall be provided with an isokinetic sampling probe to maintain the probe inlet velocity at the test airflow rate. Calibration Interval Not Required Not Required Not Required Not Required Not Required VIII
7 Test Equipment / Instrumentation Recovery Test Aerosol Generator Lighting Level and Uniformity Test Sound Level Test (performed w/slm) Sound Level Test (performed w/real Time Analyzers) Particle Counter Light Meter Sound level meter (SLM) Full and Third Octave Filters Acoustic Calibrators Real Time Analyzer Full and Third Octave Filters Description A device that can aerosolize either a polydispersed or a monodispersed artificial particle medium for filter integrity testing, including Laskin nozzle type, thermal generator, ultrasonic humidifier, atomizer, etc. A light scattering instrument with display or recording means to count and size discrete particles in air, as defined by ASTM F Instruments of this type shall provide for a sampling flow rate of 28.3 L/min (1 cfm) and a threshold size discrimination of a minimum of 0.2 micrometer in size. The unit shall be provided with an isokinetic sampling probe to maintain the probe inlet velocity at the test airflow rate. A portable photo-electric illumination meter approved for field measurement in accordance with the Illumination Engineering Society Lighting Handbook (IES). Sound level meter (SLM) for sound pressure measurements shall meet the Type 1 or Type 2 requirements specified in the most current version of ANSI S1.4 American National Standard Specification for Sound Level Meters. Filters for sound pressure measurements shall meet the requirements specified in the most current version of ANSI S1.11 American National Standard Specification for Octave-Band and Fractional-Octave-Band Analog and Digital Filters. Calibrators for sound pressure calibration shall meet the requirements specified in the most current version of ANSI S (R2001) American National Standard Specification for Acoustical Calibrators. Real Time Analyzer for sound pressure measurements shall meet the minimum requirements as specified in ANSI S1.4 and S1.11 and, Lines of resolution: 400 Frequency range capability: khz True dynamic range: 70 db Sum and exponential averaging Peak hold function Memory for storage of measurements Full and Third Octave Filters for sound pressure measurements shall meet the requirements specified in the most current version of ANSI S1.11 American National Standard Specification for Octave-Band and Fractional-Octave-Band Analog and Digital Filters. Calibration Interval IX
8 Test Equipment / Instrumentation Acoustic Calibrators Vibration Level Tests (performed w/slm) Sound level meter (SLM) Accelerometers / Transducers Vibration Integrators Vibration Calibrators Description Acoustic Calibrators for sound pressure calibration shall meet the requirements specified in the most current version of ANSI S (R2001) American National Standard Specification for Acoustical Calibrators. Sound level meter (SLM) for sound pressure measurements shall meet the Type 1 or Type 2 requirements specified in the most current version of ANSI S1.4 American National Standard Specification for Sound Level Meters. Accelerometers / Transducers for vibration measurements shall have the following minimum specifications: Sensitivity: (± 10%) 100 mv/g Measurement Range: ± 490 m/s² (50 G) peak Frequency Range: 1 to 1000 Hz at ± 5 % Mounted Natural Frequency: 30,000 Hz Vibration Integrators for SLM for vibration measurements shall meet the minimum requirements as specified below: Displacement: mm (0.1 to 100mils) Velocity: mm/s (0.005 to 100 in/sec) Acceleration: m/s² (0.01 to 100 G s) Frequency Range: 1 to 10,000 Hz Frequency Resolution: 1/3-Octave 12.5 to 20,000 Hz Vibration Calibrators for vibration calibration of SLM shall have the following minimum specifications: Operating Frequency: Hz Acceleration Output: 9.82 m/s² (1 G rms) ± 3% Distortion (with 0 to 100 gram load) 3% Calibration Interval Vibration Level Tests (performed w/ Vibration Meter) Vibration Meter Vibration Meter for vibration measurements shall meet the minimum requirements as specified below: Displacement: mm to 2.54 mm (0.1 to 100 mils), Velocity: mm/s (0.005 to 100 in/sec) Acceleration: m/s² (0.01 to 100 G s) Frequency Range 1 to 200 Hz (0 to 12,000 CPM) Frequency Resolution Narrowband 1 Hz Accelerometers / Transducers Accelerometers / Transducers for vibration measurements shall have the following minimum specifications: Sensitivity: (± 10%) 100 mv/g Measurement Range: ± 490 m/s² (50 G) peak Frequency Range: (1 to 1000 Hz) at ±5% Mounted Natural Frequency: 30,000 Hz X
9 Test Equipment / Instrumentation Vibration Integrators General Temperature and Moisture Uniformity Test Comprehensive Temperature and Moisture Uniformity Test Electrostatic Tests Vibration Calibrators Air Temperature Measurement Instrument Humidity Measurement Instrument Data Recorder - Temperature Data Recorder - Humidity Electrostatic Voltmeter Electrostatic Field meter Ohmmeter Description Vibration Integrators for SLM for vibration measurements shall meet the minimum requirements as specified below: Displacement: mm (0.1 to 100 mils) Velocity: mm/s (0.005 to 100 in/sec) Acceleration: m/s² (0.01 to 100 G s) Frequency Range: 1 to 10,000 Hz Frequency Resolution: 1/3 Octave Band: 12.5 to 20,000 Hz Vibration Calibrators for vibration calibration of SLM shall have the following minimum specifications Operating Frequency: Hz Acceleration Output: 9.82 m/s² (1 G rms) ± 3% Distortion (with 0 to 100 gram load) 3% An analog or digital thermometer capable of meeting the following requirements: Range: 4.5 C - 38 C (40 F to 100 F), Accuracy: ± 1% of reading, Resolution: 0.1 C (0.2 F) An analog or digital hygrometer capable of meeting the following requirements: Range: 10% - 90% RH, Accuracy: ± 2% RH, Resolution: 1% RH Electronic thermometers and temperature sensors with readout devices capable of meeting the following requirements: Range: 4.5 C - 38 C, (40 F F) Accuracy: ± 0.05 C, (±0.1 F) Resolution: ± 0.05 C. (±0.1 F) Instruments shall be capable of recording temperature and humidity or dew point at specified time intervals and time periods. Humidity measuring instruments and sensors used with readout devices capable meeting the following requirements: Range: 10% - 90%, Accuracy: ±0.1%, Resolution: ±0.1% Instruments shall be capable of recording temperature and humidity or dew point at specified time intervals and time periods. Voltmeter or field meter shall have a range of ± kv/cm (±19.99 kv/inch) with an accuracy of ± 5% and a response time of less than 2 seconds for 0 kv to ± 5 kv Ohmmeter shall have an open circuit voltage of 500 volts (DC) and a nominal internal resistance of not less than 100,000 ohms Calibration Interval 12 months 12 months XI
10 Test Equipment / Instrumentation Electrodes Charged Plate Monitor Description Electrodes shall weigh 2.27 kg (5 pounds) and have a flat, circular contact area 64 mm (2.5 inches) in diameter, which shall comprise of a surface of aluminum or tin foil to mm (0.005 inch to inches) thick, backed by a layer of rubber 6.4 mm (1/4 inch) thick and measuring 40 and 60 durometer hardness as determined with a Shore Type A durometer (ASTM D ). Device shall have a measuring range of -5 kv to + 5 kv with an error of ± 5% of full scale and a response time of 0.1 seconds short circuit current shall be between 2.5 ma and 5 ma. At any value of connected resistance, Rx, the terminal voltage (V) shall be: Calibration Interval 12 months 12 months Rx V = x 500 V ( ± 15%) Rx + internal resistance Conductivity Tests Ohmmeter Ohmmeter shall have an open circuit voltage of 500 volts (DC) and a nominal internal resistance of not less than 100,000 ohms. Electrodes Electrodes shall weigh 2.27 kg (5 pounds) and have a flat, circular contact area 64 mm (2.5 inches) in diameter, which shall be comprised of a surface of aluminum or tin foil to mm (0.005 inch to inch) thick, backed by a layer of rubber 6.4 mm (1/4 inch) thick and measuring 40 and 60 durometer hardness as determined with a Shore Type A durometer Electromagnetic Interference (EMI) Test Magnetic Field Meter Magnetic Field Sensor (ASTM D ). A magnetic field meter with a dynamic range of 0.1 to 4000 milligauss A magnetic field sensor with an external, multiturn loop. 12 months 12 months 12 months 12 months PART 3 EXECUTION 3.1 INSPECTION A. The NEBB Certified CPT Firm and the NEBB Certified CPT Professional shall be responsible to inspect the facility to verify that the construction of the cleanroom spaces shall be in a condition ready for the specified test occupancy state. Inspection should include, but not limited to, the following items: 1. Building perimeter walls, roof, and accessories installed to create a pressurized envelope around the cleanroom. XII
11 2. Cleanroom perimeter walls, ceiling, raised floor panels, doors, and necessary interior partitions installed that are essential to successful system performance. If approved by the Construction Manager or Owner, use temporary barriers for area isolation. 3. Permanent personnel gowning area in operation. 4. Final wipe down cleaning procedures complete on: a. Cleanroom finished surfaces. b. HVAC system ducts, plenums, and air handler surfaces exposed to airflow. c. Wall and floor cavities used as part of the cleanroom air handling strategy. d. Building structural elements and utility systems in contact with the cleanroom airstream. 5. Tool hookup or miscellaneous construction activities curtailed in the test area. B. The NEBB Certified CPT Firm and the NEBB Certified CPT Professional shall be responsible to inspect the facility to verify that the building environmental systems shall fully operational, under control and commissioned and shall be in a condition ready for the specified test occupancy state. Inspection should include, but not limited to, the following items: 1. Air-handling systems serving the cleanroom installed and operating under automatic controls and fully commissioned. 2. Testing, adjusting and balancing work complete for both the air and the hydronic systems serving the cleanroom air-handling systems. 3. Process exhaust systems and pressurization control fans installed and operating to simulate cleanroom pressurization. 4. Cleanroom lights, sprinklers, and safety devices installed and operational. 5. Housekeeping vacuum system operational. 6. Support systems required to perform certification tests operating normally for a minimum stable period of 5 days. 3.2 PREPARATION A. Confirm that activities within the facility comply with the requirements of the specified cleanroom occupancy test state. B. Inspect the entire cleanroom, accompanied by the Construction Manager or Owner, and note existing conditions that could jeopardize the certification results. Obtain the Construction Manager or Owner's written release before proceeding with certification steps. C. Coordinate field certification activities with the Construction Manager or Owner to permit observation of any test procedure. XIII
12 3.3 CLEANROOM PRIMARY AND SECONDARY TEST PROCEDURES A. Airflow Velocity Test: a. Determine the average supply airflow velocity delivered through each ceiling filter. b. Determine the airflow velocity uniformity throughout the cleanroom. c. Determine air velocity profile 50 mm,150 mm or 300 mm (2 in, 6in. or 12 in.) below the face screen of each ceiling filter. a. Measure and record the supply airflow velocity delivered through the filter using thermal anemometer or a tube array with a digital manometer. b. Measure and record the airflow velocity profiles. c. Measure and record the air velocity profile for 5 seconds. Select the average of the two values for the recorded reading. a. The average supply airflow velocity for each filter should be within ±10% of the design airflow supply velocity. b. The average or total airflow velocity for the cleanroom shall be within ±10% of the design. c. The relative standard deviation shall not exceed 15%. d. Sample Location Documentation e. As Left Data: Minimum airflow velocity, Maximum airflow velocity, Average airflow velocity f. Test Results Data g. Report all airflow measurements with corresponding grid locations. h. Relative Standard Deviation i. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. B. Airflow Volume Test: a. Determine the supply airflow volume delivered through each ceiling filter. b. Determine the airflow volume uniformity throughout the cleanroom. XIV
13 a. Measure and record the supply airflow volume delivered through the filter using a flow hood. Use appropriate size capture enclosure for each filter application. b. Measure and record the airflow volumes. a. The average supply airflow volume for every ceiling filter should be within ±10 % of the design airflow supply volume. b. The average or total airflow volume for the cleanroom shall be within ±10% of the design. c. The relative standard deviation shall not exceed 15%. d. Sample Location Documentation e. Duct Size and Individual Velocities f. As Left Data: Total Airflow Volume g. Test Results Data h. Report all airflow measurements with corresponding grid locations. i. Relative Standard Deviation (If multiple airflow volume measurements are made on multiple devices). j. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. C. Cleanroom Ceiling System / Filter Leakage Test: a. Determine integrity of cleanroom ceiling system / filters after installation. b. Determine leakage through any component in the ceiling system assembly. a. Verify that the design airflow velocity has been balanced by the NEBB Certified TAB Firm prior to performing the filter installation leak test. b. Test the entire ceiling system assembly. c. Provide optical laser particle counters, PSL aerosol generator, and accessories. d. Introduce microspheres from the generator into the recirculation air system. A minimum challenge of 35,300,000 particles per cubic meter 1,000,000 particles per cubic foot) is required at each filter. e. Measure and record the upstream challenge within the localized ceiling system at least once every 4 hours. XV
14 f. Calculate the scan rate per Equation 10-2 in the NEBB Procedural Standards for Certified Testing of Cleanrooms. Prior to calculating the scan rate, obtain the Construction Manager s or Owner's written approval to the Np value that will be used in the calculation. g. Scan the entire downstream filter face area isokinetically in overlapping strokes, moving the probe at the calculated scan rate, the scan rate is to be no more than 0.05 m/s (10 fpm), at a distance 25 mm (1 inch) below the filter face. Scan the entire perimeter, center support mullions, and corners. Provide filter shrouds in partial filter coverage ceilings to block air entrained from adjacent non-airflow components. h. Scan joints in the ceiling system assembly, including the gap between the ceiling grid and filter, wall-to-ceiling joint, sprinkler pipe and electrical conduit penetrations, and blank panel edge seals. i. A particle count detection exceeding Np will indicate a significant leak. Extend test duration under any portion of the ceiling system where Np is exceeded to a minimum sample volume of 14.2 L (0.5 ft 3 ). j. Repairs, leaks and retesting of cleanroom ceiling systems shall be performed in accordance with the requirements as stated in the contract documents or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. a. Reject any component of the cleanroom ceiling system where the leak exceeds 0.01% percent of the measured upstream challenge concentration. b. Reject any filter where one dimension exceeds 38 mm (1.5 inch) in length or with an accumulative total repair area of 3 percent of media pleated face area. d. Challenge Medium e. Upstream Challenge Concentration / Particle Size f. Leak: 1. Location 2. Percent of Penetration 3. Type (Media, Grid, Gel, Etc.) g. Test Results Data h. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. i. Scan Rate XVI
15 j. Repairs (Individual): 1. Number 2. Size 3. Location 4. Area 5. Repairs: Total percentage of repair area D. Airborne Particle Count Cleanliness Classification Test: The airborne particle count cleanliness classification test is performed to determine the actual particle count level within the facility at the specified occupancy state. a. Complete the installed ceiling cleanroom filter leakage scan test, makeup air handler cleanroom final filter media test, parallelism test, pressurization test, air velocity uniformity test, and the enclosure induction leak test before starting airborne particle count sampling. b. Measure and record the particle count at a distance 1066 mm (42 inches) above the floor on a sample location grid and sample volume basis as defined in ISO Standard c. Retesting of failed particle count sample locations shall be performed in accordance with the requirements as stated in the contract documents or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. a. The air in a cleanroom or controlled environment shall have met the acceptance criteria for an airborne particulate cleanliness class (see Table 10-1 of the NEBB Procedural Standards for Certified Testing of Cleanrooms (PSCTC). The cleanroom cleanliness classification is acceptable when the averages of the particle concentrations measured at each of the locations fall at or below the class limit. Additionally, if the total number of locations sampled is greater than one and less than ten, the mean of these averages must fall at or below the class limit with a 95% UCL. b. If the results are non-compliant based on the 95% UCL calculation due to a single outlier value, it does not need to be included in a recalculation of the 95% UCL analysis provided that the outlier is due to procedural error or equipment malfunction. Additionally, the calculation is repeated with all remaining sample locations and at least three samples remain in the calculation. Additionally the cause of the outlier is documented. Deletion of the outlier in the 95% UCL calculation shall be as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. c. Clean work zones within the cleanroom may also be allowed. These clean work zones shall be classified based on the maximum allowable particle count within that clean work zone. XVII
16 d. Standard Operating Procedure e. Test Occupancy State f. Test Results Data g. Particle Size(s) of Interest h. Actual Room Classification i. UCL 95 calculation of preformed j. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. E. Pressurization Test: a. Confirm capability of cleanroom air-handling systems to maintain cascaded air pressure differentials between the cleanroom and the adjacent support areas per the design requirements. a. Measure and record the relative pressure differentials between each cleanroom and the adjacent area. b. Measure and record the relative pressure differentials sequentially from the area with the highest cleanliness requirement outward through contiguous spaces to the outdoors. a. Compare actual pressure differential to design requirements. d. Test Results Data e. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. F. Airflow Parallelism Test: a. Verify parallel vertical flow paths of supply airflow. a. Measure and record the parallel vertical flow path. b. Divide the cleanroom into equal area grids. The maximum grid spacing shall be 3m x 3m (10 ft x 10 ft). Perform the test in the middle of each grid. XVIII
17 c. Secure the plumb line, spirit level or straight edge as required, mark the plumb line at 305 mm (12 inch) intervals, the distance from the plumb line to the streamer or vapor is determined at a distance of 915 mm and 1525 mm (36 inches and 60 inches) above the floor, introduce the test medium using a support stand at the specified height. Calculate the angle of deflection. a. The angle of deflection should not be greater than 14 from center when measured higher than 915 mm (36 inches) above the floor. d. Test Results Data e. Test Location Diagram f. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. G. Recovery Test: a. Determine ability of cleanroom air-handling system to recover cleanliness levels after an internal particle upset. a. Measure the particle counts at an initial condition in the cleanroom b. Generate the particulate challenge at the supply air inlet to the cleanroom to raise the particle count to following levels: ISO Class 5 and Cleaner: 100 times the established target cleanliness level. ISO Class 6 and Above: 10 times the established target cleanliness level. c. Shutoff the aerosol challenge d. Take particle counts for 6 second sample periods for each minute until the particle count is returned to the target cleanliness level measured prior to the introduction of the challenge particles. g. Document the recovery time. a. Acceptance of the facility is subject to approval of satisfactory recovery rate as agreed to by the Owner. XIX
18 d. Initial Particle Counts at Particle Size(s) of Interest e. Challenge Medium f. Challenge Concentration g. Test Results Data: Recovery Time h. Ending Particle Count at Particle Size(s) of Interest i. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. H. Lighting Level Test: a. Determine that the installed lighting levels and lighting uniformity meet the specified requirements. a. For high intensity, or fluorescent systems, in relatively new lamp installations, verify that lamps have been in operation for a minimum of 100 hours before measurements are taken. b. Verify that high intensity discharge or fluorescent systems have been illuminated for at least two hours before measurements are taken. c. Luminance measurements should be made under actual working conditions. All lighting in the area including general lighting, task lighting and supplementary lighting should be in normal use. d. Measurements shall be made at work surface elevation and from a specified work point location with the combinations of daylight and electric lighting facilities available. e. Prepare a measurement grid based on room size and luminaries type, spacing and location. f. Measure lighting intensity at 915 mm (36 inches) above the finish floor using Equations 11-1, 11-2, 11-3, 11-4, or 11-5 of the NEBB Procedural Standards for Certified Testing of Cleanrooms. Use the appropriate equation for the cleanroom lighting layout. a. Compare actual lighting levels to design criteria requirements. d. Test Location Diagram e. Test Results Data XX
19 f. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. I. Sound Level Test: a. Determine the operating sound level in the cleanroom produced by the facility support systems based on the specified occupancy state during the test. a. Measure and record the operating noise in the cleanroom when the cleanroom is at the specified occupancy test state. b. Place pickup sensors to achieve a direct line of sight between the sound source and the sound meter at 1220 mm (48 inches) above the floor and at least 915 mm (36 inches) from a wall, column, or any other large surface capable of altering the sound measurements. c. Record sound pressure data in all eight-octave bands. a. Compare actual sound pressure levels to design noise criteria requirements. d. Test Location Diagram e. Test Results Data: Operating Sound Pressure Levels: NC Curve, RC Curve or A-Weighted Value f. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. J. Vibration Level Test a. Determine vibration impact of normal activities, functions and operations in the cleanroom. a. Measure and record vibration displacement, velocity, and acceleration at test stations selected by the Owner in the specified occupancy state. b. Place accelerometers on top of structural and building support members, equipment bases, and raised floor tiles as directed by the owner. c. Measure and record the vibration levels in rms for peak-to-peak displacement, zero-to-peak velocity, and zero-to-peak acceleration. XXI
20 a. Acceptance of the facility is subject to approval of satisfactory vibration levels as agreed to by the Owner. d. Test Location Diagram e. Test Results Data: (data stated in appropriate units (SI or IP) and reported in terms of displacement, velocity, acceleration and / or frequency based on scope requirements) f. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. K. Comprehensive Temperature and Humidity Uniformity Test: a. Confirm the capability of the facility support systems to control temperature and relative humidity to meet the project criteria. b. Verify uniformity of environmental conditions throughout contiguous areas of the cleanroom. c. Confirm stability of environmental conditions at control sensing points. a. Designate a minimum of one temperature and relative humidity measurement location in each temperature control zone. b. Verify that the HVAC system(s) TAB work has been completed prior to performing this test. c. Verify that the airflow uniformity test have been competed and accepted. d. Allow the HVAC system to operate under automatic control for a minimum of 24 hours prior to beginning this test. Support systems shall have been in normal automatic operation under control of calibrated permanent controllers for at least 7 days. e. Uniformly place each temperature and humidity sensor at each designated work level sampling location, allow the sensor to stabilize. f. Measure and record the temperature and humidity measurement simultaneously at each location every 6 minutes for a minimum period of 2 hours. a. Acceptance of the facility is subject to approval of satisfactory temperature and humidity uniformity as agreed to by the Owner. XXII
21 d. Test Location Diagram e. Work Height Level f. Test Results Data g. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. L. Electrostatic Test: a. Benchmark the airborne positive and negative ion densities at strategic locations within the cleanroom. a. Surface Voltage Level: The measuring point(s) or the object to be measured shall be as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. 1. Hold the probe to a grounded metal plate and adjust the output of the electrostatic voltmeter to zero. 2. Hold the probe parallel to the plate and at a distance that is in accordance with the manufacturer s recommendations. 3. The metal plate should have a surface area large enough for the required probe aperture and be large enough for the probe to surface spacing ratio. 4. Hold the probe in the same position as for zero adjustment. Then place the probe near the object surface which has the charge and measure the surface voltage. b. Static Dissipative Test: The electrodes should be set at the correct distance from the surface in accordance with the manufacturer s recommendations. 1. Hold the probe to a grounded metal plate and adjust the output of the electrostatic voltmeter to zero. 2. Specific test conditions should be as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. c. Ion Generator Test: An Ion generator performance is evaluated by taking the discharge time and measurements of the offset voltages. The imbalance of positive and negative ions that are in the ionized airflow can result are determined by the offset voltage measurements. The efficiency of eliminating static charges that are caused by using ion generators is determined by measuring the discharge time. The measuring point(s) or the object to be measured should be as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. XXIII
22 1. Using isolated conductive plates of a known capacitance. 2. From a power source, the isolated conductive plates are charged to a known positive voltage. 3. Expose the isolated conductive plates to the airflow that is being ionized by the bipolar ion generator. 4. Measure the change in static charge of the plates. 5. Measure the time in which it takes the static voltage on the plate to be reduced to 10% of the initial voltage condition which is the discharge time. 6. Repeat this procedure with the plates charged to a known negative voltage. d. Offset Voltage Tests: The measuring point(s) or the object to be measured should be as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. 1. Using isolated conductive plates of a known capacitance. 2. Ground the isolated conductive plates. 3. Confirm that the voltage is zero. 4. Connect an electrostatic voltmeter to the plate. 5. Expose the isolated conductive plates to the airflow that is being ionized by the bipolar ion generator until the voltage becomes stable. 3. Acceptance Criteria - Acceptance of the facility is subject to approval of satisfactory electrostatic tests as agreed to by the Owner. Note: The owner s criteria will depend on the electrostatic sensitivity of devices that are located in the work area. d. Test Location Diagram e. Test Parameters f. Test Results Data g. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. M. Conductivity Test: a. Determine resistance between specified points on the floor. b. Determine resistance from the floor covering to building ground at strategic locations within the building. a. Tile-to-Tile: Perform conductivity tests at the specified number of tile pairs. XXIV
23 1. Floor shall be tested with temperature and relative humidity maintained as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. 2. Measure five (5) pair of test stations as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. 3. Measure resistance with a suitably calibrated ohmmeter. 4. Measurements on raised floor tiles shall be made between pairs of points and may include some, or all, of the following: a. Center of test tile to center of adjacent tile. b. Corner of test tile to corner of any tile two positions away. c. Center of test tile to any supporting pedestal. d. Center of test tile to conductive paint finish covering main structural concrete floor. b. Floor-to-Building Ground: Perform conductivity tests from the floor covering to the building ground (raised floors only). 1. Floor shall be tested with temperature and relative humidity maintained as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. 2. Measurements shall be made at twenty (20) tests locations as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. 3. Measurements shall be made at each of the 20 test locations in each room and the results averaged. 4. Measure resistance with a suitably calibrated ohmmeter. 5. Measurements shall be made with the one electrode on the floor connected to the ohmmeter. The other terminal of the ohmmeter shall be connected to the nearest building column or exposed grounding conductor. a. The floor tile-to-tile test shall achieve an average value of less than 1 megaohm. b. The floor-to-building ground test shall achieve an average value of less than 1 megaohm. Provide tabularized data with individual data and averaged values and record for each test station mapped on a building layout. d. Test Location Diagram e. Test Parameters f. Test Results Data XXV
24 g. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. N. Electromagnetic Interference Test: determine electromagnetic interference caused by the 60-hertz magnetic field levels at strategic locations within the facility. a. Measure and record magnetic field intensity at 5 critical test stations selected by the Owner. b. Take measurements 1067 mm (42 inches) above the finished floor. c. Measure magnetic field intensity level without any process equipment located in the cleanroom but with the lights and fans operating. d. Measure and record magnetic field intensity (flux density) in milligauss. a. Acceptance of the facility is subject to approval of satisfactory EMI Tests as agreed to by the Owner. Normal acceptance values are less than 1 milligauss. d. Test Location Diagram e. Test Parameters f. Test Results Data g. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. O. Room Air Change Rate Test: a. Determine the number of times the air is being exchanged within the cleanroom on an hourly basis. The room air change rate per hour (ACH) is determined by measuring the total airflow volume being supplied or returned from the cleanroom (whichever is greater) and by calculating the overall volume of the cleanroom. a. Determine if the cleanroom is under a positive or negative pressure. b. If the pressure is positive, measure and record the supply airflow volume delivered through the filter using a flow hood. Use appropriate size capture enclosure for each filter or supply diffuser application. XXVI
25 c. If the pressure is negative, measure and record the return / exhaust airflow volume being captured by all return openings and process exhaust devices using a flow hood for return openings and appropriate traverse points on all process exhaust devices. Use appropriate size capture enclosure for each return opening application. Use appropriate traverse locations and traverse grid spacing for each process exhaust device. d. Measure the volume of the cleanroom space. e. Calculate the ACH by dividing the airflow volume by the cleanroom volume. a. Acceptance of the facility is subject to approval of satisfactory ACH rate as agreed to by the Owner. d. Room Identification e. As Left Data: Total Airflow Volume per Hour, ACH f. Test Results Data g. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. P. Bench-Scan Filter Leakage Test: a. Determine integrity of each filter shipment by spot testing random statistical samples. a. Test every filter, or if owner approved, develop a statistical sample based on the following: 1. Test all filters which show signs of damage. 2. Test every fifth filter and upon failure, test additional untested filters as agreed to between the NEBB Certified CPT Firm and the Owner. b. Provide flow test bench, optical laser particle counter, microsphere generator and a particle controlled environment. c. Introduce microsphere challenge upstream of the filter. A minimum challenge shall be at least 211,800,000 particles per cubic meter (6,000,000 particles per cubic foot). d. Measure the upstream challenge of each filter. e. Scan the entire downstream filter face area in overlapping strokes, moving at XXVII
26 the calculated scan rate (See NEBB-PSCTC) spaced a distance of 25.4 mm (1 inch) from the filter face. f. Repairs, leaks and retesting of filters shall be performed in accordance with the requirements as stated in the contract documents or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. a. Reject any component of the cleanroom ceiling system where the leak exceeds 0.01% percent of the measured upstream challenge concentration. b. Reject any filter where one dimension exceeds 38 mm (1.5 inch) in length or with an accumulative total repair area of 3 percent of media pleated face area. 4. Documentation (Failed Filters only): d. Challenge Medium e. Upstream Challenge Concentration / Particle Size f. Leak: 1. Location 2. Percent of Penetration 3. Type (Media, Frame, Etc.) g. Test Results Data h. Identify all performance data that exceeds the acceptance criteria as specified herein or as agreed to between the Owner / Buyer and the NEBB Certified CPT Firm. i. Scan Rate j. Repairs (Individual): 1. Number 2. Size 3. Location 4. Area k. Repairs (Total): 1. Total percentage of repair area XXVIII
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Air and Water Balancing - Sound and Vibration Testing - Cleanroom Services - Building Commissioning Building Envelope Testing Thermal Imaging
NEUDORFER ENGINEERS, INC. provides our customer with unbiased, professional, performance testing of Cleanrooms. We are committed to providing you, our customer, with value-added expertise in an effort
ENVIRONMENTAL MONITORING / TESTING TO CONFORM WITH ISO14644 & TGA GMP REQUIREMENTS
ENVIRONMENTAL MONITORING / TESTING TO CONFORM WITH ISO14644 & TGA GMP REQUIREMENTS PRESENTATION TO RACI 20 TH APRIL 2016 PAUL MORGAN DIRECTOR CRITICAL CERTIFICATION PTY LTD CHANGES TO ISO14644 PART 1 CHANGES
DRYER VENTING SPECIFICATIONS DRYER SAFETY
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
PROCEDURAL STANDARDS FOR CERTIFIED TESTING OF CLEANROOMS
PROCEDURAL STANDARDS FOR CERTIFIED TESTING OF CLEANROOMS 2009 THIRD EDITION National Environmental Balancing Bureau 8575 Grovemont Circle Gaithersburg, Maryland 20877 301-977-3698 301-977-9589 FAX www.nebb.org
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Guide to in situ leak testing of HEPA filter configurations that cannot be conventionally scan tested
DOP Solutions Technical Document: Guide to in situ leak testing of HEPA filter configurations that cannot be conventionally scan tested Issue 1: Prepared by Neil Stephenson and Tim Triggs and edited by
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Exhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: [email protected] ADC Part No. 450450 Exhaust
A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.
SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel
SECTION 15950 - TESTING, ADJUSTING, AND BALANCING
SECTION 15950 - TESTING, ADJUSTING, AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory
SUMMARY of PRODUCTS. HVAC Systems Control Airflow, Space, & Building Pressurization. Accurate airflow measurement for demanding applications
SUMMARY of PRODUCTS HVAC Systems Control Airflow, Space, & Building Pressurization Accurate airflow measurement for demanding applications Airflow Measuring Stations FAN-E AIRFLOW MEASURING STATION. The
International Standard ISO 14644
International Standard ISO 14644 Cleanrooms and associated controlled environments Praphon Angtrakool Food and Drug Administration 1 International Standard : ISO 14644 ISO 14644 consists of the following
plenum slot diffusers
light powered Redefine your comfort zone. www.titus-hvac.com dual-function smart logic light powered energy solutions Table of Contents PLENUM SLOT IFFUSERS products Plenum Slot iffusers Products... 4
Acoustical Design Guidelines for HVAC Systems in Schools
Acoustical Design Guidelines for HVAC Systems in Schools Seminar 9, ASHRAE Summer Meeting Albuquerque, New Mexico Sponsor: TC 2.6 Sound and Vibration Robert M. Lilkendey Associate Principal Consultant
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
HEPA FILTER DEFECTS ARE COMMON
HEPA FILTER DEFECTS ARE COMMON Kenneth F. Cherry 1 and Kenneth A. Smigielski 2 1 NCEC Inc. 2 First Solar LLC. ABSTRACT HEPA filters (High Efficiency Particulate Air) filters are claimed by vendors to have
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
ANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals
ANSI/AHRI Standard 880 (I-P) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:
Description. Specifications and Ordering Information 330400 and 330425 Accelerometer Acceleration Transducers
Specifications and Ordering Information 330400 and 330425 Accelerometer Acceleration Transducers R Description These accelerometers are intended for critical machinery applications where casing acceleration
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
Generic - Hearing Loop - (AFILS) U.S. System Specification
This document is a generic specification for any Hearing Loop (Audio Frequency Induction Loop System). For the remainder of the document, we will refer to using the term Hearing Loop rather than Audio
HVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
Lightweight Partition Design for Residential and Commercial Buildings
Lightweight Partition Design for Residential and Commercial Buildings Stanley D. Gatland II, CertainTeed Corporation, Valley Forge, Pennsylvania Guidelines are presented for the design and proper installation
SAM HOUSTON STATE UNIVERSITY
PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the
Environmental Monitoring
Chapter 10 Environmental Monitoring By the end of this chapter, you will be able to: l List the types of environmental testing l Name three types of checks that are carried out to ensure the isolator is
Instructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version
instrumentation for fluids Electromagnetic sensor Series FLOMID FX Instructions Manual! Conforms with the Pressure Equipment Directive 97/23/EC. 0830 This equipment is considered as being a pressure accessory
Troubleshooting accelerometer installations
Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.
CHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update
Specification of 5 Wire Analog Touch Panel
Specification of 5 Wire Analog Touch Panel 5 WIRE ANALOG RESISTIVE TOUCH PANEL A. Application This specification applies to the 5 Wire Analog Resistive Touch Panel. B. Environmental Conditions 1. Operating
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS
METHODS FOR THE CALIBRATION OF ELECTROSTATIC MEASURING INSTRUMENTS Contents Foreword --------------------------------------------------------------------------------------------------------------------
Building Design for Advanced Technology Instruments Sensitive to Acoustical Noise
Building Design for Advanced Technology Instruments Sensitive to Acoustic Noise Michael Gendreau Colin Gordon & Associates Presentation Outline! High technology research and manufacturing instruments respond
Duct Leakage Testing. Ken Helfers, TSI Inc. 2011, TSI Incorporated
Duct Leakage Testing Ken Helfers, TSI Inc. Agenda Need for duct leakage testing Duct leakage testing standards and regulations Performing duct leakage testing Why Test Ducts for Leakage? Conserve energy
Current Probes. User Manual
Current Probes User Manual ETS-Lindgren L.P. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
Environmental Monitoring of Clean Rooms
Environmental Monitoring of Raul Duarte President DDK Scientific, Corp. Copyright DDK Scientific, Corp. 2008, 2009, DDK Scientific, Corp. Proprietary A manufacturing facility for pharmaceutical products
IPACK2005-73273 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS
Proceedings of IPACK5 ASME InterPACK '5 July 17-, San Francisco, California, USA IPACK5-7373 DISTRIBUTED LEAKAGE FLOW IN RAISED-FLOOR DATA CENTERS Amir Radmehr Innovative Research, Inc. Plymouth, MN, USA
Outer Diameter 23 φ mm Face side Dimension 20.1 φ mm. Baffle Opening. Normal 0.5 Watts Maximum 1.0 Watts Sine Wave.
1. MODEL: 23CR08FH-50ND 2 Dimension & Weight Outer Diameter 23 φ mm Face side Dimension 20.1 φ mm Baffle Opening 20.1 φ mm Height Refer to drawing Weight 4.0Grams 3 Magnet Materials Rare Earth Size φ 9.5
How to Measure HVAC System Airflow
How to Measure HVAC System Airflow About National Comfort Institute National Comfort Institute is an international training Since our and beginning development in 1994 company we have trained with and
Particle Monitoring Requirements in Pharmaceutical Cleanrooms
Particle Monitoring Requirements in Pharmaceutical Cleanrooms All drugs must be manufactured in accordance with the current Good Manufacturing Practice (cgmp) regulations. Pharmaceutical manufacturers
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by
24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL ENERGY CONSERVATION CODE (1) The Department of Labor and Industry adopts and incorporates by reference the International Code Council's International
WTW SWANTM. Linear slot air diffusers of wall-to-wall design for ceilings
SWANTM WTW Linear slot air diffusers of wall-to-wall design for ceilings Quick facts Wall-to-wall installation Diffuser face of light aluminium design 2, 3 or slots Horizontal/vertical air distribution
Fundamentals of Acoustics & Practical HVAC Design Considerations. Demir Doken Acoustic Engineer
Fundamentals of Acoustics & Practical HVAC Design Considerations Demir Doken Acoustic Engineer What is sound? Sound is a mechanical wave that is an oscillation of pressure transmitted through some medium
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
Under sill units. Type FSL-B-ZAS
.1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract
The entire document shall be read and understood before proceeding with a test. ISTA 3B 2013 - Page 1 of 35
Packaged-Products for Less-Than-Truckload (LTL) Shipment ISTA 3 Series General Simulation Performance Test PROCEDURE VERSION DATE Last TECHNICAL Change: NOVEMBER 2012 Last EDITORIAL Change: JANUARY 2013
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
ACL 395 Resistivity Meter
ACL 395 Resistivity Meter OPERATION MANUAL Meter is warranted for one year from the date of purchase on parts and labor. Calibration is recommended every 12 months. 840 W. 49 th Place Page 1 of 13 [email protected]
Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract
Commissioning of Exterior Building Envelopes of Large Buildings for Air Leakage and Resultant Moisture Accumulation using Infrared Thermography and Other Diagnostic Tools Mario D. Gonçalves, Patenaude-Trempe
Rain Penetration Tests on Manthorpe Mini Castellated Vent Tile with 15" x 9" Format Roof Tiles. Prepared for: Ben Hales
Rain Penetration Tests on Manthorpe Mini Castellated Vent Tile with 15" x 9" Format Roof Tiles Prepared for: Ben Hales Manthorpe Building Products Ltd. 24 th June 2014 Report number 295-318 1 Rain Penetration
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
How To Test A Fume Cupboard
Jürgen Liebsch WALDNER Labor EN 14175 Requirements for Fume Cupboards DIN 12924 EN 14175 The contents of the DIN 12924 part 1 standard is divided into 5 parts in the EN 14175 standard: 14175-1 Terms and
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
Help. Help Software Tutorial. Building a load sizing project with an ME Series Humidifier
Help Help Software Tutorial Building a load sizing project with an ME Series Humidifier 502-B 18 Aug 2015 Help Tutorials provide step-by-step examples of complete load sizing projects and browser projects
Indoor air quality monitoring made easy
Indoor air quality monitoring made easy with the Fluke 985 Particle Counter Application Note Introduction Energy savings is top of facilities owners agenda. HVAC system tends to be the largest contributor
E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex
FIRERAY 2000 Installation Guide
FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health
Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class
PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING
PERFORMANCE EVALUATION OF WATER-FLOW WINDOW GLAZING LI CHUNYING DOCTOR OF PHILOSOPHY CITY UNIVERSITY OF HONG KONG FEBRUARY 2012 CITY UNIVERSITY OF HONG KONG 香 港 城 市 大 學 Performance Evaluation of Water-flow
How to Estimate the Cost of a. Laboratory Renovation. Candidate Number: 0714144
How to Estimate the Cost of a Laboratory Renovation Candidate Number: 0714144 December 15, 2014 1 Table of Contents Cover Page Page 1 Table of Contents Page 2 Introduction Page 3 Types & Methods of Measurements
Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP
Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s
BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES
Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE
Sample Company SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES
SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES A. The Owner will contract separately and directly for the majority of the commissioning work
Enclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes
Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes Jonathan Coulter, Bruce Davis, Cyrus Dastur, Melissa Malkin-Weber and Tracy Dixon Advanced Energy,
Performance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
Laminar Flow Elements
Laminar Flow Elements Meriam Laminar Flow Elements (LFEs) are excellent for measuring low gas flow rates from 0.2 SCCM up to 2250 SCFM. They are inherently accurate and repeatable and are calibrated traceable
O C M III. Open Channel Flow Monitor
O C M III Open Channel Flow Monitor Part 1. General 1.1 Scope A. This section describes the requirements for an ultrasonic flow transmitter with sensor and temperature compensation probe. B. Under this
Periodic Verification System Model 775PVS
Periodic Verification System Model 775PVS Instruction Manual Contents 1 Description... 1 775PVS System... 1 Model 775 Fieldmeter... 2 Model 775C Charger... 2 Model 775P Plate Assembly... 3 2 Operation...
IECC Compliance Guide for Homes in Virginia
IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,
The CEETHERM Data Center Laboratory
The CEETHERM Data Center Laboratory A Platform for Transformative Research on Green Data Centers Yogendra Joshi and Pramod Kumar G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
Packaging Guidelines Version Date: 11/6/12. ABB Inc. Packaging Guidelines. Version 1.0. Page 1. 3.04.P08.W03 Rev 0
ABB Inc. Packaging Guidelines Version 1.0 Page 1 Contents Master Carton:... 3 Data Requirements... 3 Barcodes... 5 Label Placement... 6 Packing List... 7 Page 1 Contents... 7 Page 2 Contents... 9 International
THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES
TSI and TSI logo are registered trademarks of TSI Incorporated. SmartTune is a trademark of TSI Incorporated. THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES IFA 300 Constant Temperature Anemometry
Element D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
1.0 What Are the Purpose and Applicability of Performance Specification 11?
While we have taken steps to ensure the accuracy of this Internet version of the document, it is not the official version. Please refer to the official version in the FR publication, which appears on the
EACO DOP / PAO TESTING GUIDELINE 2013
2013 Foreword The guideline promotes industry standards for training, equipment, and methodologies for HEPA filter integrity testing of negative air units, vacuums and any other HEPA filtered equipment
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has
SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS
July 14, 2015 1.0 GENERAL BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS This work shall consist of furnishing all materials, equipment, labor, and incidentals necessary for conducting bi-directional
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
PIEZOMETER AIRFLOW MEASURING RING
PIEZOMETER AIRFLOW MEASURING RING M.K. Plastics is pleased to introduce The Piezometer Airflow Measuring Ring, now available as an accessory for our steel Axijet fans. The system consists of a Piezometer
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids
Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids Dr. J. M. Meyers Dr. D. G. Fletcher Dr. Y. Dubief 1. Introduction Last lab you investigated flow loss in a pipe due to the roughness
ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems
ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems Content Introduction Preventing unauthorized access by perimeter surveillance Monitoring unauthorized access by indoor surveillance
TRANSPORT OF DANGEROUS GOODS
Recommendations on the TRANSPORT OF DANGEROUS GOODS Manual of Tests and Criteria Fifth revised edition Amendment 1 UNITED NATIONS SECTION 38 38.3 Amend to read as follows: "38.3 Lithium metal and lithium
Acoustic Design Practices for Sustainable Buildings
Acoustics 2008 Geelong, Victoria, Australia 24 to 26 November 2008 Acoustics and Sustainability: How should acoustics adapt to meet future demands? Acoustic Design Practices for Sustainable Buildings Danny
Chapter 12 Industrial Ventilation
Chapter 1 Industrial Ventilation Introduction Industrial Ventilation is an important method for reducing employee exposures to airborne contaminants. Ventilation is used to reduce or remove contaminates