Using Carbon Dioxide as a Tracer Gas to Measure Air Change Rate in a Single Zone
|
|
|
- Barbara Walters
- 9 years ago
- Views:
Transcription
1 Using Carbon Dioxide as a Tracer Gas to Measure Air Change Rate in a Single Zone C. Simmons, F. Boelter, G. Crawford, Boelter & Yates, Inc., Park Ridge, IL Presented by: Catherine E. Simmons, CIH
2 Situation Ventilation information was needed to perform a retrospective exposure assessment. Procedure was needed to determine the ventilation rate in air changes per hour (ACH) for representative boiler rooms and an isolation test chamber.
3 Boiler Room Ventilation Research Published Information on Boiler Room Air Change Rates ASHRAE, BOCA and NFPA reviewed for ventilation requirements in ACH Ventilation Models Using Tracer Gas Published Ventilation Models using Tracer Gas Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution ASTM E
4 Problem Existing methods allow for the use of a variety of tracer gases to be used. Each has advantages and disadvantages. Selected method highly portable easily measured non-toxic or very low toxicity inexpensive Tracer gas acceptable to school district personnel.
5 Research Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution ASTM E Tracer gases (examples) CO 2 PEL 5000 ppm SF 6 PEL 1000 ppm CO PEL 50 ppm Selection of test method Concentration Decay Constant Injection Constant Concentration
6 Resolution Selection of tracer gas Carbon dioxide Relatively high PEL Inexpensive Easy to obtain and measure Acceptable to School personnel Selection of method Concentration Decay Test Method Measures the decay rate of carbon dioxide over time to calculate the air exchange rate. Regression Analysis InC(t) = -At + C(0)
7 Sample Time Air Change Rate (1/hr) Minimum Duration (hour) Minimum sample duration based on 10% uncertainty at the 95% confidence level in the detection of air change rate, a tracer gas concentration measurement precision error of 5% of reading and various air change rate. Using the regression method reduces the minimum test duration due to more than 2 data points.
8 Boiler Room Ventilation Testing Using Tracer Gas Representative Boiler Rooms Elementary School - IN Elementary School - IL Middle School - IL
9 Gas Injection and Distribution
10 Direct Reading Equipment TSI Q-Trak Log Data
11 School Indiana 5500 ft 3 Boiler Room Volume of gas needed Calculated based on room size and target concentration of 4000 ppm V tracer = C target X V zone 2 boilers Input BTU/hr ,000 Input BTU/hr. 156,000 Both boilers operating during the testing No mechanical ventilation
12 Average CO2 Concentration vs Time Indiana Boiler Room - 2 Boilers Operating March 26, 2003 Carbon Dioxide Concentration in Parts Per Million (PPM) Trial 1 - Average CO2 Concentration (PPM) 5.2 Air Changes Per Hour Trial 2 - Average CO2 Concentration (PPM) 5.3 Air Changes Per Hour Time in Minutes Trial ACH Trial ACH Average 5.2 ACH
13 Elementary School Illinois Measured Volume 24,322 ft 3. 2 Boilers Ventilation tracer gas testing conducted with boilers on and off.
14 Elementary School Ventilation Rate - Boilers Off 1.8 Air Changes Per Hour March 27, 2003 Average CO2 Concentration vs Time March 27, Time in Minutes Carbon Dioxide Concentration (ppm) Carbon Dioxide Concentration (ppm) Time in Minutes Trial 2 - Average Carbon Dioxide Concentrations with 2 Boilers Operating Trial 3 - Average Carbon Dioxide Concentrations with 2 Boilers Operating Trial 1 Boilers On Boilers Off ACH Trial ACH Trial ACH Average 3.7 ACH
15 Middle School Illinois 16,372 ft 3 Boiler Room 2 Identical Boilers
16 Middle School Average Carbon Dioxide Concentration (ppm) vs Time Middle School March 21, Time in Minutes Carbon Dioxide Concentration (ppm) Carbon Dioxide Concentration (PPM) Average CO2 Concentration vs Time Boiler Room - 2 Boilers March 31, Time in Minutes Boilers On (1 boiler on part time): Trial 2 - Average CO2 Concentration 4.4 Air Changes Per Hour, GlenCrest School March 31, 2003 Boilers On: Trial 3 - Average CO2 Concentration 5.3 Air Changes Per Hour, GlenCrest School March 31, 2003 Boilers Off Boilers On 1.2 ACH Trial ACH Trial ACH Average 4.9 ACH
17 Measured Range of Boiler Room Ventilation Summary Boilers Off Range: 1.2 to 1.8 ACH Boilers On Range: 3.7 to 4.9 ACH
18 Isolation Test Chamber Approximately 20 x 20 x 9 (3600 ft 3 ) Wood Frame Polyethylene sheeting on walls and floors 2 viewing windows Entrance airlock Decontamination Shower (if needed) HEPA filtered exhaust machines for ventilation
19 HEPA Filtered Exhaust Machines for Chamber Ventilation System Note: Using various configurations, both machines operated as exhaust (tubing was attached to machines to exhaust outside the building).
20 Installation and Measurement of Ventilation System Various configurations to achieve approximately 1, 3, 5 and 10 ACH Carbon dioxide tracer gas used to measure ventilation rate. Each rate tested twice to assure repeatability. Final ventilation rates were: 1.2, 2.9, 5.7, 10.7 ACH.
21 Carbon Dioxide Concentration (ppm) vs Time B & Y Test Chamber 5.7 Air Changes Per Hour April 29, :28 16:30 16:32 16:34 16:36 16:38 16:40 16:42 16:44 16:46 16:48 16:50 Carbon Dioxide Concentration (ppm) Trial 1 - high Trial 1 - low Trial 2 - high Trial 2 - low Time Trial ACH Trial ACH Average 5.7 Trial ACH Trial ACH
22 Conclusions Ventilation rates for representative boiler rooms were between 1 and 5 ACH. Using carbon dioxide as a tracer gas and following ASTM E , Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution met the objectives and goals of the project.
23 Benefits Carbon Dioxide as a tracer gas Inexpensive, reliable procedure for IH s to determine ventilation rates. Measuring Equipment is readily available The method provides an additional tool for industrial hygienists to better characterize workplace conditions during the initial stages of an exposure assessment. Ventilation information is critical to the ability to perform and validate mathematical modeling for exposure estimation.
24 C(t) Well Mixed Room Model - Constant Contaminant Emission Rate G + C Q Q + k V Q + k V IN L + L = 1 exp t C exp t Q + k V V 0 V L Input Variables C IN mg/m 3 Concentration in incoming air G mg/min Q m 3 /min Generation Rate Exhaust air flow V m 3 Volume of Room K L per min Loss Pathway (sinks) C 0 mg/m 3 Initial concentration
25 Predicted Concentration at 0.01, 0.1, 1, 3, 4, 5 and 10 Air Changes Per Hour 12 Effect of Ventilation Rate on Concentration of Contaminant ACH 0.1 ACH 1 ACH 3 ACH 4 ACH 5 ACH 10 ACH
26 Thank you! Questions? Speaker Contact Information: Catherine E. Simmons, CIH Boelter & Yates, Inc. Park Ridge, IL
Exposure and Control of Ten High Priority MSHA Contaminants in Metal Mines. Presented by: Shannon E. Newton, MPH, CIH
Exposure and Control of Ten High Priority MSHA Contaminants in Metal Mines Presented by: Shannon E. Newton, MPH, CIH Topics What are these hazards? How can they harm you? Why do we care? How do we tell
Measuring Air Changes per Hour with Carbon Dioxide
Measuring Air Changes per Hour with Carbon Dioxide Dr Rod Escombe MRCP DTM&H PhD Honorary Research Fellow, Wellcome Centre for Clinical Tropical Medicine & Department of Infectious Diseases & Immunity,
Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program
Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality
HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.
HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains
Exposures to Coal Fly Ash During Maintenance of Air Cleaning Devices in Power Plants
Exposures to Coal Fly Ash During Maintenance of Air Cleaning Devices in Power Plants Harry J Beaulieu, PhD, CIH, CSP President & Senior Scientist Industrial Hygiene Resources Boise, ID Arlen W Siert, PhD,
THE EFFECTS OF LAMINAR AIRFLOW IN SEMICONDUCTOR FABS ON THE VENTILATION DESIGN FOR EXHAUSTED ENCLOSURES
THE EFFECTS OF LAMINAR AIRFLOW IN SEMICONDUCTOR FABS ON THE VENTILATION DESIGN FOR EXHAUSTED ENCLOSURES Presented By: John Hatfield, CIH John O Hehir Global Semiconductor Safety Services 1365 Adams Court
Calculations and OELs
Calculations and Dr. Peter Bellin, PhD, CIH EOH 466A The Occupational Environment Definitions Particulates: dust, fume, mist Vapors Gases Particle size considerations Inspirable Particulate Mass (IPM)
Risk Assessment of Lab Bench Top Processes to Ensure Safety in Smart Labs
Risk Assessment of Lab Bench Top Processes to Ensure Safety in Smart Labs Presented by Lisa Mahar, CIH, CSP, RN, EH&S UC/CSU Laboratory HVAC Design for Energy Efficiency Workshop 2012 Page 1 Learning Objectives
THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS
THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS INDOOR AIR QUALITY INSTRUMENTS UNDERSTANDING, ACCELERATED BREATHE A LITTLE EASIER WITH TSI Indoor air quality is a growing concern. With the increasing
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material Revised November 21, 2013 Application Code of Practice Where asbestos is present or believed to be present in a workplace
Using Assigned Protection Factors (APFs) for Respirator Selection Use with Chapter 296-842 WAC, Respirators
How to use this tool: Follow guidance in this tool if you need help using the APFs in Table 5 of Chapter 296-842 WAC, Respirators. When you finish using this guidance, return to WAC 296-842-13005 to complete
A Report of Air Sampling for Mercury Vapor and Particulates During Fluorescent Tubes Disposal Operation Maywood, Illinois Survey date: 9/28/2000
A Report of Air Sampling for Mercury Vapor and Particulates During Fluorescent Tubes Disposal Operation Maywood, Illinois Survey date: 9/28/2000 Prepared for: Air Cycle Corporation 2000 South 25 th Avenue,
A Series of Negative Exposure Assessments Related to Asbestos Containing Components Still Used in Railroad Equipment Today
A Series of Negative Exposure Assessments Related to Asbestos Containing Components Still Used in Railroad Equipment Today - PO108 - American Industrial Hygiene Association s 66th Annual Conference and
How To Test For Residual Dust
Experience on Measurement of Residual Dust as Quality Assurance Documentation During Mold Remediation AIHCE - Chicago, Illinois May 16, 2006 P. Morey & G. Crawford Boelter & Yates, Inc. Gettysburg, PA
Specification. Indoor Air Quality Management
GREENGUARD Environmental Institute 2211 Newmarket Parkway, Suite 110 Marietta, GA 30067 1.800.427.9681 Specification Indoor Air Quality Management This Master Specification section is intended for use
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
Trace Gas Exchange Measurements with Standard Infrared Analyzers
Practical Environmental Measurement Methods Trace Gas Exchange Measurements with Standard Infrared Analyzers Last change of document: February 23, 2007 Supervisor: Charles Robert Room no: S 4381 ph: 4352
Introduction to Industrial Hygiene
This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike License. Your use of this material constitutes acceptance of that license and the conditions of use of materials on this
Unit 3.4 Decontamination (Core)
INSTRUCTOR GUIDE Unit 3.4 Decontamination (Core) INSTRUCTOR GUIDE TERMINAL OBJECTIVE Given scenarios involving hazardous materials/wmd incidents, the participant shall identify when emergency decontamination
WATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts
WATER DAMAGE INVESTIGATION Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor
Technical Cleaning Ó
Technical Cleaning JUSTIFICATION Cleaning of Data Centers and Communications Rooms should be performed by qualified personnel who will use techniques and equipment designed to clean without re-contaminating
Excerpts from EPA s Mold Remediation in Schools and Commercial Buildings
www.epa.gov/mold/mold_remediation.html Compiled by SUNY Office for Capital Facilities, May 2014 Page 1 Compiled by SUNY Office for Capital Facilities, May 2014 Page 2 Compiled by SUNY Office for Capital
Case Study: Successful Decontamination of an HVAC System s Ductwork Using Chlorine Dioxide Gas
Canadian Biosafety Symposium Date: June 1, 2009 Place: Delta Halifax, Halifax Nova Scotia Case Study: Successful Decontamination of an HVAC System s Ductwork Using Chlorine Dioxide Gas Mark A. Czarneski
Course Guidelines. Occupational Health and Safety for the Asbestos Worker
Course Guidelines Occupational Health and Safety for the Asbestos Worker February 2013 Table of Contents 1.0 Introduction...................................................... 1 2.0 Course Criteria...................................................
Asbestos Abatement Management Program. Facilities Operations and Development Environmental Health & Safety
Asbestos Abatement Management Program Facilities Operations and Development Environmental Health & Safety November 7, 2012 INTRODUCTIONS David Kos (EHS) Director of Environmental Affairs David Kehl (EHS)
SLMA Meeting. Boiler MACT and Related Rules. Atlanta, GA March 2, 2011. Martin Rollins, P. E. H. M. Rollins Company, Inc. Gulfport, Mississippi
SLMA Meeting Atlanta, GA March 2, 2011 Boiler MACT and Related Rules Martin Rollins, P. E. H. M. Rollins Company, Inc. Gulfport, Mississippi Boiler MACT and Related Rules EPA Had Requested 15 Month Delay
Performance Assessment of EAGLE 5000 in Tobacco Smoke Environment. REPORT
Performance Assessment of EAGLE 5000 in Tobacco Smoke Environment. REPORT Reference 943/78357 Carried out by: Ainhoa Mendivil Martínez IAQ CONSULTANT October 2006 Borrador 02 ÍNDEX 1. INTRODUCTION... 3
APPENDIX B. EPA s Investigating, Evaluating, and Remediating Moisture and Mold Problems (see EPA website for complete details)
APPENDIX B. EPA s Investigating, Evaluating, and Remediating Moisture and Mold Problems (see EPA website for complete details) Table 1: Water Damage - Cleanup and Mold Prevention Table 1 presents strategies
Principles of Ventilation. Patrick N. Breysse, PhD, CIH Peter S.J. Lees, PhD, CIH Johns Hopkins University
This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike License. Your use of this material constitutes acceptance of that license and the conditions of use of materials on this
SAFETY AND HEALTH PROGRAM
PROGRAM NUMBER NO. PAGES 05-005 10 REVISION ISSUE DATE Revision 2 11/1/2005 SAFETY AND HEALTH PROGRAM Confined Space Entry 1.0 INTRODUCTION Confined Space Entry is a serious workplace hazard, capable of
READ FIRST. Confined Space Entry Procedure. San José State University Environmental Health and Safety. Confined Space Entry Procedure
READ FIRST 1. The purpose of a is to save lives by controlling the inherent hazards of a confined space prior to entry. a. If possible, avoid entering a confined space. Every consideration should be given
Mould Mould A Basic Guide
Mould A Basic Guide Summary Mould is a fact of life. Moulds will grow practically everywhere people live and work. Mould is recognized as an occupational hazard for indoor workers as well as outdoor workers
Radford University. Indoor Air Quality Management Plan
Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings
CAT CG132. Series Gas Generator Sets
CAT CG132 Series Gas Generator Sets CAT CG132 SMARTER ENERGY SOLUTIONS COMMERCIAL AND INDUSTRIAL FACILITIES Facilities such as manufacturing plants, resorts, shopping centers, office or residential buildings,
CeramClean II Aluminum Safe
1. Identification of substance: MATERIAL SAFETY DATA SHEET DIVISION Reviewed on 07/01/2004 Product details: Trade name: CeramClean II Ink Cleaner Product Code: 332506 Manufacturer/Supplier: Harper Corporation
Comparison of Analytical Methods for Evaluating Mold in Carpet Dust
Comparison of Analytical Methods for Evaluating Mold in Carpet Dust R. Rottersman, MS, CIH & G. Crawford, CIH Boelter & Yates, Inc. Park Ridge, IL P. Fallah, PhD EMLab San Diego, CA Carpet & Indoor Mold
International Refrigerant Standards and their Influence on the Global HVAC Industry and Refrigerant Replacement
International Refrigerant Standards and their Influence on the Global HVAC Industry and Refrigerant Replacement Tom Watson, P.E. Fellow ASHRAE, Life Member President ASHRAE Issues Choosing a refrigerant
Quantifying the energy and carbon effects of water saving summary report
Quantifying the energy and carbon effects of water saving summary report Domestic water use in the UK is around 150 litres per person per day. Taking water from the environment, treating it, distributing
SUMMARY OF ASHRAE S POSITION ON CARBON DIOXIDE (CO 2 ) LEVELS IN SPACES. Stephen Petty, P.E., C.I.H.
SUMMARY OF ASHRAE S POSITION ON CARBON DIOXIDE (CO 2 ) LEVELS IN SPACES Stephen Petty, P.E., C.I.H. Purpose of the Summary Statement: It is widely reported by the technical community involved in indoor
Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION
Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION LARS OLANDER, LORRAINE CONROY, ILPO KULMALA, RICHARD P. GARRISON, MICHAEL ELLENBECKER, BERNHARD BIEGERT, BERNARD FLETCHER, HOWARD D.
Standardized Terminology for Combustion Appliances and. Combustion Safety Testing
Standardized Terminology for Combustion Appliances and Combustion Safety Testing Air-Free Carbon Monoxide A measurement of CO in an air sample or flue gas that takes into account the amount of excess air
Decontamination Units
Decontamination Units 1 DECON The worker/personal decontamination system (commonly called the "decon unit or Decon") is specially designed to allow passage to and from the work area during the abatement
Training Requirements for the Revised Hazard Communication Standard
www.alterisus.com Training Requirements for the Revised Hazard Communication Standard As of December 1, 2013 OSHA revised its Hazard Communication Standard (HCS) to align with the United Nations Globally
XYZ Contract Company Industrial Hygiene Program
[This is an example of a general Industrial Hygiene program intended to help Industrial Hygienists in the development of a specific contractor IH program if one is not yet developed. It is not intended
Not All 3A Recovery Wheels Limit Contaminant Transfer
Not All 3A Recovery Wheels Limit Contaminant Transfer A Comparison of Laboratory Test Data Shows Substantial Differences Between Products Claiming to Use a 3A Desiccant and the SEMCO 3 Angstrom Wheel By
Occupational Health and Safety. Course Guidelines. for the Asbestos Worker
Occupational Health and Safety Course Guidelines Occupational Health and Safety for the Asbestos Worker CG001 Asbestos 0 Table of Contents 1.0 Introduction...2 2.0 Course Criteria..3 3.0 Course Content
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
Benzene Exposures from Petroleum- Derived Solvents Containing Trace Levels of Benzene in Occupational Settings
Benzene Exposures from Petroleum- Derived Solvents Containing Trace Levels of Benzene in Occupational Settings P. Williams, J. Panko, K. Unice, J. Brown, and D. Paustenbach Presented by: Julie Panko, CIH
Mechanical and Natural Ventilation
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
UNIVERSITY OF KENTUCKY CONFINED SPACE PROGRAM
SCOPE AND APPLICATION: The University of Kentucky has developed a written policy for safe entry into confined spaces. The University recognizes that certain environmental conditions within confined spaces
Hazardous Drug. Cleanroom. Standards
Hazardous Drug Cleanroom Standards Module 3 Table of Contents Section A... 1 A.1 International Standards Organization (ISO) Classifications... 1 A.2 Hazardous Drug Cleanroom and Anteroom... 1 A.2.1 Location
Case Studies: Infrared Heating in Industrial Applications
Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000
Ammonia Detection System Codes and Design Specifications. Brian EuDaly, P.E. Calibration Technologies, Inc.
Ammonia Detection System Codes and Design Specifications Brian EuDaly, P.E. Calibration Technologies, Inc. Ammonia Detection Code Requirements IIAR-2A-2008 ASHRAE 15-2010 NFPA 1 2012 UMC 2012 Preprint
************************************************************************ *** SECTION 1 PRODUCT IDENTIFICATION
MATERIAL SAFETY DATA SHEET Pure Tech Emergency Phone Numbers: P.O. Box 1950 CHEMTREC: 800/424-9300 Brewster, New York 10509-8950 POISON CENTER: 800/562-8236 845/279-0900 Date of Last Revision: 03-21-97
White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen
White Paper Best Practices for Gas Monitoring in the Commercial Kitchen Enhancing Kitchen Safety through Strategic Gas Monitoring Overview Commercial kitchens are one of the most hazardous commercial building
MOLD REMEDIATION KEY STEPS
MOLD REMEDIATION KEY STEPS The EPA has developed the following guidelines for mold remediation managers. These guidelines are generally helpful, but we believe an expert in the industry should be consulted
Sandblasting & Silica Exposure Control Plan
Safety & Health Program 10627 Midwest Industrial Boulevard, St. Louis, MO Phone: 314-785-6425 Fax: 314-785-6426 Sandblasting & Silica Exposure Control Plan The purpose of this program is to inform interested
CONFINED SPACE ENTRY (PROJECT STANDARDS AND SPECIFICATIONS) KLM Technology Group
Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENTS Purpose 2 Scope
CSA Z317-13-12 Infection Control during Construction, Renovation and Maintenance of Health Care Facilities Overview and Case Studies
CSA Z317-13-12 Infection Control during Construction, Renovation and Maintenance of Health Care Facilities Overview and Case Studies Grant Rogers, BSc. Principal 1 North West Environmental Group Industrial
Confined Space Air Monitoring
November 2008 Vol. 26. No. 3 Confined Space Air Monitoring Scott Shinn, C.I.H. Scott Shinn is a Certified Industrial Hygienist with 3M OH&ESD Technical Service and Regulatory Affairs. Summary Over the
Guide Specification for Laboratory Fume Hood Commissioning
Guide Specification for Laboratory Fume Hood Commissioning 3 February, 1997 Application notes: This specification is intended to be used by qualified, experienced engineers and industrial hygienists as
WHMIS Material Safety Data Sheet Product Information VP-TECH CHEMICAL PRODUCT AND COMPANY IDENTIFICATION. Water Soluble Metalworking Fluid Concentrate
WHMIS Material Safety Data Sheet Product Information VP-TECH SECTION 1: MATERIAL IDENTIFICATION CHEMICAL PRODUCT AND COMPANY IDENTIFICATION Emergency: Chemtrek Telephone: 1-800-424-9300 General Information:
A practical guide to restrictive flow orifices
Safetygram 46 A practical guide to restrictive flow orifices Restrictive flow orifices (RFOs) installed in cylinder valve outlets provide a significant safety benefit for users of hazardous gases, especially
Generation of Vapor-Phase Hydrogen Peroxide Test Atmospheres for the Evaluation of Respirator Cartridges and Air Samplers
Generation of Vapor-Phase Hydrogen Peroxide Test Atmospheres for the Evaluation of Respirator Cartridges and Air Samplers C.R. (Gus) Manning, PhD, CIH Hydrogen Peroxide Common substance with unusual properties
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?
Visualisation and control of solder fume exposure
Health and Safety Executive Visualisation and control of solder fume exposure A quantitative assessment of LEV effectiveness Prepared by the Health and Safety Laboratory for the Health and Safety Executive
Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project
Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project The Watergate Community is currently in the process with the fire suppression and interior renovations
Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
LANCOM4 PORTABLE FLUE GAS MONITORING. NO NO2 NOx CO2 H2S SO2 CxHy. CO low CO high O 2 QUALITY CUSTOMER SOLUTIONS WWW.LANCOM4.COM
PORTABLE FLUE GAS MONITORING WWW.LANCOM4.COM i CO low CO high O 2 NO NO2 NOx CO2 H2S SO2 CxHy QUALITY CUSTOMER SOLUTIONS AMETEK LAND HAS BEEN BUILDING PRECISION MEASURING EQUIPMENT SINCE 1947. WE ARE SPECIALISTS
GUIDELINES ON SAMPLING STRATEGY AND SUBMISSION OF AIR MONITORING / SAMPLE ANALYSIS REPORT
GUIDELINES ON SAMPLING STRATEGY AND SUBMISSION OF AIR MONITORING / SAMPLE ANALYSIS REPORT MINISTRY OF MANPOWER OCCUPATIONAL HEALTH DEPARTMENT 18 HAVELOCK ROAD #05-01 SINGAPORE 059764 FAX: 539 5140 EMAIL:
Information paper 20. Prepared by: David Clark. book:
Information paper 20 Ventilation rates in offices and natural mechanical Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information
Selective Catalytic Reduction (SCR) and Diesel Exhaust Fluid (DEF) Training Module
Selective Catalytic Reduction (SCR) and Diesel Exhaust Fluid (DEF) Training Module DEF SCR Training Module Welcome to the Cummins Filtration DEF SCR training module. DEF & SCR systems are key to Cummins
SAP 2012 IN A NUTSHELL
SAP 2012 IN A NUTSHELL The consultation version of the SAP 2012 methodology was published by the Department of Energy and Climate Change (DECC) on January 4th 2012. This article from Dyfrig Hughes of National
Lead Exposure Management Plan
Lead Exposure Management Plan 1.0. Policy CSUF has developed the Lead Exposure Management Plan to reduce occupational and environmental exposure to lead, a potent neurotoxin and carcinogen that causes
Indoor Air Quality Issues for Hotels
Indoor Air Quality Issues for Hotels Chai chen Chao DEA 670 Spring, 2000 Thermal Control Relative Humidity Winter Temperature Summer Temperature 30% 68.5 F - 76.0 F 74.0 F - 80.0 F 40% 68.5 F - 75.5 F
9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration
OSHA Combustible Dust Inspections Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration Overview Background Information OSHA Combustible
Alternative to Fossil Fuel
Alternative to Fossil Fuel Biodiesel Emissions Biodiesel Biodiesel is made from any vegetable oil such as Soya, Rice bran, Canola, Palm, Coconut, Jatropha or peanut,from any animal fat and recycled cooking
Nitrous Oxide: Hazards and Proper Use
1 Nitrous Oxide: Hazards and Proper Use James Kaznosky Manager, Env. & Occ. Safety Environmental Health and Safety What is Nitrous Oxide? 2 Nitrous oxide (N20) is nonflammable, colorless gas with pleasant,
Ammonia Detection System Codes and Design Specifications
Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion
DUST AND DEBRIS MANAGEMENT PROCEDURES HPD HOUSING REHABILITATION PROGRAMS
DUST AND DEBRIS MANAGEMENT PROCEDURES HPD HOUSING REHABILITATION PROGRAMS Dust and Debris Management Procedures refers to preventive measures that shall be undertaken by the contractor to prevent exposure
A Multi-Application, Multi-Industry Asbestos Exposure Assessment During Maintenance of Surfaces and Joints Sealed with Gaskets and Packing
A Multi-Application, Multi-Industry Asbestos Exposure Assessment During Maintenance of Surfaces and Joints Sealed with Gaskets and Packing - PO115 - American Industrial Hygiene Association s 66th Annual
A Comparison of Tchebycheff, Equal Area and Tracer Gas Air Flow Rate Measurements
A Comparison of Tchebycheff, Equal Area and Tracer Gas Air Flow Rate Measurements P.L. Lagus, Ph.D., CIH Lagus Applied Technology, Inc. Escondido, California P. W. Butler Entergy Russellville, AR K. M.
Mold and Mildew Mold and mildew can be detected by sight, smell and touch.
Mold and Mildew Mold and mildew can be detected by sight, smell and touch. Molds are usually black (not unlike the molds that grow in showers and between grout), green or tan in color, but can be in various
Real-Time DPM Ambient Monitoring in Underground Mines
Real-Time DPM Ambient Monitoring in Underground Mines Hsin Wei Wu, A.D.S. Gillies 2, J. D Volkwein 3 and J Noll 4 Director, Gillies Wu Mining Technology, [email protected] 2 Union Pacific/Rocky Mountain
BEST PRACTICE IN DESIGN AND TESTING OF ISOLATION ROOMS IN NORDIC HOSPITALS
TR 564 Approved 2005-11 BEST PRACTICE IN DESIGN AND TESTING OF ISOLATION ROOMS IN NORDIC HOSPITALS James P. Rydock Pål Kjetil Eian Conny Lindqvist Irma Welling Egil Lingaas September 2004 Nordic Innovation
Independent Forensics of Illinois
Independent Forensics of Illinois RSID -Semen Lab kit Universal Buffer #0230 Material Safety Data Sheet Date Updated: 01/2014 SECTION 1 - CHEMICAL PRODUCT AND COMPANY IDENTIFICATION MSDS Name: RSID -SEMEN
Plumbing Code in Commercial Kitchens
Plumbing Code in Commercial Kitchens City of Concord Code Administration 225-8580 Dan Clark Plumbing Inspector Tedd Evans, Chief Building Inspector Code References from the 2009 edition of the International
Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
ANSI/BPI-1200-S-2015:
Guidelines for Home Energy Professionals Project Standard Work Specifications (SWS) Update to Align SWS with the Combustion Appliance Section of ANSI/BPI-1200-S-2015: Standard Practice for Basic Analysis
MONITORING SCHOOL ENERGY CONSUMPTION
MONITORING SCHOOL ENERGY CONSUMPTION Goal(s): The mains goal of the energy monitoring activity are: To make the pupils and all school staff aware of school energy consumption; and To show how changes in
Veterinary Clinics and Hospitals
Anesthetic Gases: Guidelines for Workplace Exposure Veterinary Clinics and Hospitals Inhalation anesthesia in veterinary hospitals is practiced in a manner similar to that in human hospitals. Generally,
How Sensors Work. How Oxygen, Electrochemical Toxic, and Metal Oxide Semiconductor Sensors Work *
How Oxygen, Electrochemical Toxic, and Metal Oxide Semiconductor Sensors Work * 1. Oxygen sensor detection principle Most portable or survey instruments used for workplace evaluation of oxygen concentrations