Case Study: Successful Decontamination of an HVAC System s Ductwork Using Chlorine Dioxide Gas
|
|
|
- Ezra Preston
- 10 years ago
- Views:
Transcription
1 Canadian Biosafety Symposium Date: June 1, 2009 Place: Delta Halifax, Halifax Nova Scotia Case Study: Successful Decontamination of an HVAC System s Ductwork Using Chlorine Dioxide Gas Mark A. Czarneski Director of Technology 1
2 Overview 1. Reasons, Requirements & Choices 2. Equipment / Facility Setup 3. Pictures of Setup 4. Readings 5. Concerns & Conclusions 2
3 New Developments in Chlorine Dioxide Chlorine Dioxide Gas has been approved by NSF International under Annex G of NSF/ANSI 49 for the decontamination of BSC s Only 2 methods are approved for BSC decontamination 1983 Formaldehyde was approved 2008 Chlorine dioxide gas was approved. NO other method approved for BSC decontamination 3
4 Reason for Decontamination Ductwork was undersized and had to be modified BSL-2 & 3 work in lab Ductwork and Biological Safety Cabinets possibly contaminated with HIV - Human Immunodeficiency Virus HCV - Hepatitis C Virus Costly and time consuming for contractors to demolish / work in proper PPE if NOT decontaminated 4
5 Requirements for Decontamination Sterilant must travel long distances From 3 rd floor BSL-2/3 lab space up to 5 th floor HEPA housing Over 200 ft (61m) of hose to re-circulate gas from 3 rd floor to 5 th floor Sterilant must not be affected by temperature difference Hoses traveling through un-conditioned space, Mezzanine and stairwell not temperature controlled (50-60deg F / deg C) Lab space 70 deg F (21 deg C) Fully decontaminate duct work and BSC s and demonstrate 6 log reduction of BI s Biological Indicator Placed in each Exhaust Point to test process ( Positive control = 16 Ttl) 5
6 Choices Requirements Chlorine Dioxide Formaldehyde Hydrogen Peroxide True Gas NO (reaches all surfaces) Travel Long Distances NO Temperature effect NO (Fallout / re-polymerize) (Condense) Demonstrate 6 log reduction Carcinogen NO NO Residue NO NO Odor Detection (Safety) NO OSHA 8 hr TWA (time weighted average) 0.1 ppm 0.75 ppm 1.0 ppm Typical Concentrations 360 ppm ,000 ppm 750 ppm 6
7 What is Chlorine Dioxide (CD)? Properties: Yellow-Green Gas 1 Water Soluble 2 Boiling Point 11 o C 3 Tri-atomic Molecule Molecular Weight Ability to be monitored in real time with a photometric device. Not subject to condensation or affected by temperature gradients. 2. Ability to penetrate water (not all sterilants can penetrate water, vapors can not) 3. Chlorine dioxide is a true gas at room temperatures; which means excellent distribution and penetration. 7
8 Chlorine Dioxide Time Line Aqueous Germicide (Water Treatment Longest User) Chlorine Dioxide Recognized as a Gaseous Chemosterilizing Agent CSI CD-Cartridge Registered with US-EPA Mar 2004 Time 1811 First Preparation of Chlorine Dioxide 1940 Bleaching Agent (Pulp & Paper Industry Largest User) 1988 First Registered with the US-EPA for use as a sterilant World wide consumption of chlorine dioxide 4.5 million lbs/day (2.04million kg/day). 743,000 lbs (337,000 kg) released to atmosphere in Example: Maine allows 3 lb s / hour (1.4kg / hour)of CD to be emitted 8
9 Decontamination Cycle Typical Concentration and exposure 60-75% RH (10 min for rooms, 30 min for small chambers) 1 mg/l for 2 hours = 720 ppm hours (rooms) 5 mg/l for 30min = 900 ppm-hrs (small chambers) 400 ppm-hrs successful at University of Pennsylvania Example Cycle (small chamber) Concentration (mg/l) Pre-Condition Condition Charge Exposure Aeration Relative Humidity (%) 1 5 9
10 Total Equipment on Site 1 Chlorine Dioxide Generators 1 Chlorine cylinder 1 EMS Chlorine Dioxide Gas Sensor Module 4 Steam Fast Humidity Generators 15 Recirculation Blowers 200 ft (61m) 2 (51mm) hose (BSL-2 area) 200 ft (61m) 1/1/2 (38mm) hose (BSL-3 area) 800 ft (244m) 1/1/4 hose (From Tee assemblies to BSC s) Extension Cords Duct Tape 2 ft (0.6m) Wide Tape 3/8 (10mm) gas inject tubing ¼ (6mm) gas sample tubing 10
11 Time Line (How Long is the whole Process?) Day 1 arrive in afternoon and setup Uncrate generator and sensor module Place Tee assemblies Run Hoses to 5 th floor HEPA Housing from 3 rd floor Lab Run Hoses from Tee assembly to BSC s and Ceiling drops Run Gas injection and sample tubing Seal 13 BSC s (MOST OF WORK) Day 2 arrive in morning Start Decon process 10am Finish Decon process 12:30pm Breakdown equipment and re-crate 11
12 CD Gas Generation Technology Cl 2(g) + 2NaClO 2(s) 2ClO 2(g) + 2NaCl (s) Performed in solid phase (no liquids) Gas generated on demand Self-Contained reagents Simple to replace consumables Small portable generators Photometric measurement of concentration Real Time Repeatable Accurate Validated 12
13 BSL-2 Area Equipment 11 BSC s 1 CD gas injection point 3 sensing points 3 steam inject points 3 (4pt Tee assemblies) 1 (3pt Y assembly) 13
14 BSL-3 Area Equipment 2 BSC s 1 CD gas injection point 1 sensing points 1 steam inject points 1 (4pt Tee assemblies) 14
15 BSL-2 Area Hose from 5 th floor HEPA Housing Air Flow Direction 15
16 BSL-3 Area Air Flow Direction Air Flow Direction Air Flow Direction Hose from 5 th floor HEPA Housing 16
17 Connections to BSC s Pressure Relief Gas Injection Re-Circulation Hose 17
18 Connections Blowers to BSC s and Exhaust Grill Gas Sample & Steam Inject Air Flow Direction 2 Pipe Tee Assembly Hose from 5 th floor HEPA Housing 18
19 Connections to BSC s Air Flow Direction 19
20 Concentration Readings (mg/l) 20
21 Concerns Was Gas getting to each BSC (gas only injected into one BSC) Biological Indicators will Test Leakage from BSC s 21
22 Conclusions Complete kill of all Biological Indicators No physical residue observed Had Leakage, Leakage contained in BSL-2/3 labs (need to seal BSC s better) No visible indication of material degradation on any electronics Low Chlorine Dioxide Concentrations Average concentration 500 ppm for BSL-2 area Average concentration 830 ppm for BSL-3 area 1021 Lowest PPM-Hrs 1701 Highest PPM-Hrs 22
23 For more information contact: Mark A. Czarneski PO Box 549 Lebanon, NJ Phone: Fax: Revision Date: April 27,
Thermo Scientific Biological Safety Cabinets Fumigation Methodologies
Thermo Scientific Biological Safety Cabinets Fumigation Methodologies Due to its use in hazardous processes, the biological safety cabinet (BSC) is a highly regulated device. Generally speaking, regulatory
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory
BIOLOGICAL SAFETY CABINET PROGRAM
BIOLOGICAL SAFETY CABINET PROGRAM TABLE OF CONTENTS: 1. INTRODUCTION 2. PURPOSE AND SCOPE 3. SELECTION AND INSTALLATION 4. USE OF BIOLOGICAL SAFETY CABINETS 5. CERTIFICATION OF BIOLOGICAL SAFETY CABINETS
Procedures for the Effective Use of Biological Safety Cabinets
Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum
Decontamination and Waste Management www.biosecurity.sandia.gov
Decontamination and Waste Management www.biosecurity.sandia.gov SAND No. 2006-3684C Sandia is a multiprogram laboratory operated by Sandia Corporation, a Lockheed Martin Company, for the United States
Generation of Vapor-Phase Hydrogen Peroxide Test Atmospheres for the Evaluation of Respirator Cartridges and Air Samplers
Generation of Vapor-Phase Hydrogen Peroxide Test Atmospheres for the Evaluation of Respirator Cartridges and Air Samplers C.R. (Gus) Manning, PhD, CIH Hydrogen Peroxide Common substance with unusual properties
Fumigation of Safety Cabinets
Fumigation of Safety Cabinets General Microbiological safety cabinets should always be fumigated if a large spillage of infectious material occurs within them, before filters are changed or before any
Fume Hood Questions and Answers
Fume Hood Questions and Answers 1. When should I use a fume hood? Use a chemical fume hood anytime your work involves: Chemicals with a National Fire Protection Association (NFPA) Health rating of 3 or
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
Risk Assessment: Biosafety Cabinet
Risk Assessment: Biosafety Cabinet Biosafety cabinets (BSCs) serve as primary containment devices for operations involving potential splashes, spills or aerosolization of hazardous biological materials.
Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health
Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class
Biosafety Level 2 (BSL-2) Safety Guidelines
BLS-4 Biosafety Level 2 (BSL-2) Safety Guidelines BSL-3 BSL-2 BSL-1 BSL-2 builds upon BSL-1. If you work in a lab that is designated a BSL-2, the microbes used pose moderate hazards to laboratory staff
How To Control A Medical Device With A Pc System
Clean room monitoring and disinfection FMS 5.0, the Leading Facility Monitoring Software TSI FMS system is an advanced, reliable, and user-friendly monitoring software suite that features a truly open
Technical Specifications for West Campus Data Center HVAC System
Technical Specifications for West Campus Data Center HVAC System I. Mechanical Systems Requirements A. HVAC Primary Data Centers, Automation HVAC is to be provided on a 24 hours per day, 365 days per year
PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3)
PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3) Yes No 1. Is access to the laboratory limited or restricted at the discretion of the laboratory director when experiments are in progress? Yes No
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
Laboratory Design & Construction Guidelines
Laboratory Design & Construction Guidelines Department of Environmental Health & Safety EHS-M-35 Page 1 Issue Date: 03/01/10 General Health and Safety The USC Environmental Health and Safety Department
The Breather Box. High Performance Grade-D Breathing Air Filtration system. BB50-cO
The Breather Box High Performance Grade-D Breathing Air Filtration system Specifications Filter change Indicators Incoming Air Plug 1/2 Industrial Interchange 2 Automatic Drains with Discharge tubes 3
AUTOCLAVE PROGRAM. SOP Bio-006 FOR THE USE OF AUTOCLAVE FOR STERILIZATION OF MATERIALS AND BIOLOGICAL WASTE SOP
ENVIRONMENTAL AND EMERGENCY MANAGEMENT ENVIRONMENTAL HEALTH AND SAFETY 175 Cabot St. Wannalancit Suite 311 Lowell MA 01854 Ruth Medina, Ph.D. Tel: 978-934-2778 Senior Biosafety Specialist/Biosafety Officer
Remediation of Mold Contaminated Ductwork
Remediation of Mold Contaminated Ductwork Roger G. Morse AIA, Paul Haas CSP, CIH, Dean Zehnter, Andrea Grdina Morse Zehnter Associates The Problem Visible mold growth on interior of liner inside air handling
IX. Decontamination and Spills
IX. Decontamination and Spills IX.1. Definitions Sterilization: the act or process, physical or chemical, which destroys or eliminates all forms of life, especially microorganisms. Decontamination: reduction
Steam Sterilization Cycles for Lab Applications
Steam Sterilization Cycles for Lab Applications Presented by Gary Butler STERIS Life Sciences August 2009 Early Steam Sterilizers Koch Upright Sterilizer First Pressurized Sterilizer First built by Pasteur-Chamberlain
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Storage-stable Aqueous Solutions of Chlorine Dioxide
White Paper Storage-stable Aqueous Solutions of Chlorine Dioxide Tom McWhorter November 14, 2014 Abstract Chlorine dioxide is a powerful, selective biocide. Aqueous solutions of chlorine dioxide have many
DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE
1.0 Introduction DESERT RESEARCH INSTITUTE This Desert Research Institute (DRI) Mold Assessment and Remediation Procedure was established to assure that consistent and uniform information is provided to
HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.
HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains
Water Incursion Standard Operating Procedure
Water Incursion Standard Operating Procedure Purpose: To provide a standardized procedure in the event of water incursion into any Penn State University facility. References: A Brief Guide to Mold, Moisture
University of Toronto Office of Environmental Health and Safety Biosafety Containment Level 3
University of Toronto Office of Environmental Health and Safety Biosafety Containment Level 3 Emergency Response Susan Fern-MacDougall Director, Environmental Health and Safety Agenda The University Observation
Containment Challenges & Engineering Solutions for Low Containment. National Centers for Animal Health Ames, Iowa Dennis Jones, Facility Engineer
Containment Challenges & Engineering Solutions for Low Containment National Centers for Animal Health Ames, Iowa Dennis Jones, Facility Engineer 1 NCAH Missions Conduct basic and applied research on selected
MANAGING A STERILE PROCESSING DEPARTMENT IN CRISIS: HOW TO STAY COOL WHEN YOUR SPD GETS TOO HOT
MANAGING A STERILE PROCESSING DEPARTMENT IN CRISIS: HOW TO STAY COOL WHEN YOUR SPD GETS TOO HOT FRANK MYERS, MA, CIC INFECTION PREVENTIONIST III UC SAN DIEGO HEALTH SYSTEM POTENTIAL CONFLICT: MR. MYERS
Fundamental Autoclave Techniques
Fundamental Autoclave Techniques Version 3, September 2010 Veronika Tatarinoff GSBmE University of NSW Brandy Nelson University of Kentucky The following information is directed at aseptic/sterile surgical,
RULE 1102. DRY CLEANERS USING SOLVENT OTHER THAN PERCHLOROETHYLENE
(Adopted January 6, 1978)(Amended August 3, 1979)(Amended July 11, 1980) (Amended August 3, 1990)(Amended December 7, 1990) (Amended November 17, 2000) RULE 1102. DRY CLEANERS USING SOLVENT OTHER THAN
Revised 4-3-2012 EHS Biosafety. 1 Select appropriate containers/bags for autoclaving.
Requirements for Decontamination by Autoclaving Summary: Steam sterilization (autoclaving) is one of the most effective methods for decontaminating biohazardous material. Autoclaves use saturated steam
AGENDA. Technical Biosafety Concepts in Laboratories and Animal Facilities. 1. Comprehension of BioSafety and BioSecurity
AGENDA Technical Biosafety Concepts in Laboratories and Animal Facilities VCCN Cleanroom Symposium in s Hertogenbosch, Session 4, 15:30 16:30 1. Comprehension of BioSafety and BioSecurity 2. High Containment
Decontamination Showers
Decontamination Showers PBSC Operator Over suit Decontamination: API powders from routine operations contaminate over suit / work ware/ppe: Your Facility Could be at Risk: Risk 1: Cross contamination to
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
Nick s Inspection Services
Nick s Inspection Services 909 Shorthorn Grain Valley Mo. 64029 Phone: 816-355-0368 Cell: 816-225-5783 Email: [email protected] Building Inspection Report and Protocol Inspection Date: 08-20-14
CHAPTER V: DISPOSAL OF WASTES CONTAMINATED WITH INFECTIOUS AGENTS
CHAPTER V: DISPOSAL OF WASTES CONTAMINATED WITH INFECTIOUS AGENTS These biohazard waste disposal guidelines are designed to not only protect the public and the environment, but also laboratory and custodial
GenStore Archive Cabinet
GenStore Archive Cabinet Setup and Maintenance Manual Version A April 2014 Two GenStore Archives shown mounted on optional table stand. 2 Contents Getting Started... 4 Using this Manual...4 Safety Precautions...4
Key words: Low temperature Sterilization (LTS), Single-Use Cardio Catheterization (SUCC). Ethylene Oxide (ETO), Royal Medical Services (RMS).
Using the Low temperature Sterilization (Ethylene oxide and Plasma sterilization) in reuse of a single-use Cardio Catheters Devices: A study Case at RMS Maj. Engineer Ghassan Alghizzawi, Maj. Engineer
THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM
1 Application Note AT-102 THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM Lawrence B. Kilham 1 and Randall M. Dodd 2 1 Eco Sensors, Inc. Santa Fe, New Mexico, USA [email protected]
CelCulture. CelCulture CO2 Incubator Model CCL-170_-_. CO2 Incubator with Integrated Cooling System Solution for Highly Specialized Applications
1 CO2 Incubator Model CCL-170_-_ CO2 Incubator with Integrated Cooling System Solution for Highly Specialized Applications Welcome to Esco Esco s Vision is to provide enabling technologies for scientific
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Using Carbon Dioxide as a Tracer Gas to Measure Air Change Rate in a Single Zone
Using Carbon Dioxide as a Tracer Gas to Measure Air Change Rate in a Single Zone C. Simmons, F. Boelter, G. Crawford, Boelter & Yates, Inc., Park Ridge, IL Presented by: Catherine E. Simmons, CIH Situation
THE ECOLOGICAL IMPLICATIONS OF TRENCHLESS PIPE REHABILITATION
THE ECOLOGICAL IMPLICATIONS OF TRENCHLESS PIPE REHABILITATION Bridget Donaldson Research Scientist Virginia Transportation Research Council Transportation Infrastructure Deterioration of pipes is a growing
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Appendix J IBC Biohazard Spill Management Plan
OVERVIEW Prevention is the most important part of any spill management plan. Be sure to read and understand standard operating procedures (SOP s) and protocols for safe manipulation of biohazards before
Sterilization methods and equipment Lab 1-2
Sterilization methods and equipment Lab 1-2 PHT 434 Sterilization Sterilization a process that by which all viable M.O are removed or destroyed, based on a probability function. Sterilization concept Sterilization
3. It is recommended that the water supply into the facility can be obtained from two (2) separate water lines if possible.
PART VIII SANITATION AND MEDICAL WASTE 132 SANITATION 132.01 Water Supply. 1. If at all possible, all water shall be obtained from a public water supply. If not possible to obtain water from a public water
Kompressoren. Adsorption Dryer AD
Kompressoren Adsorption Dryer AD Adsorption Drying: why? Modern industries require compressed air that is increasingly filtered with low dew point and condensate. Today, the equipment is more sophisticated
Administrative Procedure
Administrative Procedure Number: 410 Effective 1/30/98 Supercedes: 1 of Subject: MEDICAL WASTE MANAGEMENT PLAN 1.0. PURPOSE: The purpose of the California State University Los Angeles Medical Waste Management
Professional Certification in Biological Waste Management Examination Content, Sample Questions & References
Professional Certification in Biological Waste Management Examination Content, Sample Questions & References The IFBA s Professional Certification (PC) in Biological Waste Management identifies individuals
The Supplier Perspective: Sterilization. Presented by: Thad Wroblewski STERIS Isomedix Services
The Supplier Perspective: Sterilization Presented by: Thad Wroblewski STERIS Isomedix Services Agenda Introduction Contractor selection criteria Pre-planning with sterilization in mind Key elements of
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson
Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology HWEA 2011 Conference Craig S. Johnson Presentation Overview Introduction Aeration Air & Digester gas challenges Gas flow metering
7. 1.00 atm = 760 torr = 760 mm Hg = 101.325 kpa = 14.70 psi. = 0.446 atm. = 0.993 atm. = 107 kpa 760 torr 1 atm 760 mm Hg = 790.
CHATER 3. The atmosphere is a homogeneous mixture (a solution) of gases.. Solids and liquids have essentially fixed volumes and are not able to be compressed easily. have volumes that depend on their conditions,
Rusty Walker, Corporate Trainer Hill PHOENIX
Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat
Air Conditioner Maintenance
Central air conditioning systems are wonderful features of many homes in the US. In hot and humid climates it s hard to imagine living without AC, although this convenience has been common in only the
= 1.038 atm. 760 mm Hg. = 0.989 atm. d. 767 torr = 767 mm Hg. = 1.01 atm
Chapter 13 Gases 1. Solids and liquids have essentially fixed volumes and are not able to be compressed easily. Gases have volumes that depend on their conditions, and can be compressed or expanded by
Protocol for Disinfection of Cell Culture and Tissue Culture in Media:
Protocol for Disinfection of Cell Culture and Tissue Culture in Media: Location: Hickory Hall 001 Director: Dr. Guido Verbeck DECONTAMINATION OF CELL CULTURE WASTE Cell culture has become a common laboratory
Standard Operating Procedure
Standard Operating Procedure FLAMMABLE LIQUIDS This standard operating procedure (SOP) is intended to provide general guidance on how to safely work with flammable liquids. This SOP is generic in nature
STERILIZATION AND DISINFECTION
STERILIZATION AND DISINFECTION Importance of hand washing shown by Semmelweis STERILIZATION A physical or chemical process that destroys or eliminates all forms of microbial life, including spores. A satisfactory
CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping
BUILDING TECHNOLOGIES PROGRAM Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping The intent of the pipe insulation requirements is to reduce temperature changes
Clinic Washer-Disinfectors. Washer-Disinfector Line
Clinic Washer-Disinfectors Washer-Disinfector Line Easy-to-Use Washer-Disinfectors for Clinics The Clinic Range of Washer Disinfectors provides superior cleaning and disinfection combined with innovative
RULE 8-8 - ORGANIC COMPOUNDS - WASTEWATER COLLECTION AND SEPARATION SYSTEMS
BAY AREA AIR QUALITY MANAGEMENT DISTRICT RULE 8-8 - ORGANIC COMPOUNDS - WASTEWATER COLLECTION AND SEPARATION SYSTEMS (ADOPTED: January 17, 1979) (AMENDED: November 1, 1989; October 6, 1993; June 15, 1994;
Detailed Design Review. P15611: Digital Microfluidics Packaging
Detailed Design Review P15611: Digital Microfluidics Packaging Presentation Summary - 1 Requirements/Test Plan Risk Assessment Individual Solutions System and Drawings Bill of Materials Schedule Questions/Discussion
Air Shower Biosafety Changing Station with Pass-Through Box Pass-Through Box Automatic atomizer for no-contact hand disinfection
Air Shower Biosafety Changing Station with Pass-Through Box Pass-Through Box Automatic atomizer for no-contact hand disinfection A wide range of products to meet the needs of transferring animals, operators,
Standard Operating Procedure for Dacarbazine in Animals
Standard Operating Procedure for Dacarbazine in Animals 1. Health hazards Dacarbazine, also known as DTIC, DIC, and Imidazole Carboxamide, is an antineoplastic chemotherapy drug used in the treatment of
"EC" Series Electric Humidifier
EC-1 Standard Water "EC" Series Electric The Electric from PURE Co. is loaded with features and options. All you need is tap water, electricity, and a sanitary drain. The humidifier does the rest. These
SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING
SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air
Mould Mould A Basic Guide
Mould A Basic Guide Summary Mould is a fact of life. Moulds will grow practically everywhere people live and work. Mould is recognized as an occupational hazard for indoor workers as well as outdoor workers
What is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere
Green AAON for What is LEED? Sustainability and green have recently become terms used within the building industry (and others) to refer to a construction project that has low environmental impact, or
Oxivir Tb and Accelerated Hydrogen Peroxide (AHP) Frequently Asked Questions
Oxivir Tb and Accelerated Hydrogen Peroxide (AHP) Frequently Asked Questions What is Accelerated Hydrogen Peroxide (AHP)? AHP is a patented synergistic blend of commonly used, safe ingredients that when
Aurora Mall. Aurora (Denver), Colorado
is the largest superregional mall in the city of Aurora, and it s only getting bigger and better. The mall is currently undergoing a significant interior and exterior renovation, scheduled for completion
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
BSL 1 Laboratory Biosafety Manual
BSL 1 Laboratory Biosafety Manual Version 1.0 Idaho State University, Office for Research Institutional Biosafety Committee (IBC) 1651 Alvin Ricken Drive, Pocatello, ID 83201-8046 Phone: 208-282-2179 Fax:
CSA Z317-13-12 Infection Control during Construction, Renovation and Maintenance of Health Care Facilities Overview and Case Studies
CSA Z317-13-12 Infection Control during Construction, Renovation and Maintenance of Health Care Facilities Overview and Case Studies Grant Rogers, BSc. Principal 1 North West Environmental Group Industrial
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
STANDARD OPERATING PROCEDURES Safe Autoclave Operations
Department of Environmental Health & Safety Biosafety & Biosecurity STANDARD OPERATING PROCEDURES Safe Autoclave Operations The purpose of this document is to provide standard operating procedures for
Sterilization A REVIEW OF THE BASICS. By Gayla Tilton and Myrna Kauffman 66 MANAGING INFECTION CONTROL
Sterilization A REVIEW OF THE BASICS By Gayla Tilton and Myrna Kauffman 66 MANAGING INFECTION CONTROL Although sterilization has been performed in healthcare facilities for many decades, the process is
Infection Control in the Dental Practice through Proper Sterilization
Midmark Corporation 60 Vista Drive P.O. Box 286 Versailles, Ohio 45380-0286 937-526-3662 midmark.com Infection Control in the Dental Practice through Proper Sterilization In today's world, the need for
Fact Sheet on Steam Sterilizers at Stanford University
Fact Sheet on Steam Sterilizers at Stanford University By: Environmental Quality and Water Efficiency Group, Stanford University; December 2013 Jennifer Fitch, Marty Laporte, Julia Nussbaum, Adam Kern,
Vapor Corrosion Inhibitors (VCIs) for Storage Tanks Corrosion Controlled Cost Controlled
Vapor Corrosion Inhibitors (VCIs) for Storage Tanks Corrosion Controlled Cost Controlled Presented by Kelly Baker, Zerust Oil & Gas Efim Lyublinski, Monique Posner, Terry Natale, Yefim Vaks, Ronnie Singh
MOLD REMEDIATION KEY STEPS
MOLD REMEDIATION KEY STEPS The EPA has developed the following guidelines for mold remediation managers. These guidelines are generally helpful, but we believe an expert in the industry should be consulted
Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
KGI MEDICAL WASTE MANAGEMENT PLAN
1revised 2012 I. Facility Information KGI MEDICAL WASTE MANAGEMENT PLAN a. Contact Person: Barbara Erwin Director Research Operations/Chemical and Biological Laboratory Safety/Chair. 909-607-0160 i. Facility:
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
Case Studies. Disaster Recovery Restoration Remediation Decontamination 800.808.1553 www.rolyncompanies.com
Case Studies 800.808.1553 www.rolyncompanies.com Property Type: College Loss Type: Water and Flood Location: Hyattsville, Maryland Once Rolyn received clearance from the insurance adjuster, crews began
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment. Larry Zanko Project Manager STERIS Corporation
Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment Larry Zanko Project Manager STERIS Corporation Agenda Brief overview of multiple-effect water stills (MWS) Lean advancements
Carefully to Carry. Fumigation of ships and their cargoes
Carefully to Carry Fumigation of ships and their cargoes Introduction Fumigation is a procedure that is used throughout the world to eradicate pests that infest all types of goods, commodities, warehouses,
Indoor Air Quality Issues for Hotels
Indoor Air Quality Issues for Hotels Chai chen Chao DEA 670 Spring, 2000 Thermal Control Relative Humidity Winter Temperature Summer Temperature 30% 68.5 F - 76.0 F 74.0 F - 80.0 F 40% 68.5 F - 75.5 F
MATERIAL SAFETY DATA SHEET FOR OZONE GAS Ozilla Ozone Sterilizer SECTION 1. CHEMICAL IDENTIFICATION
SECTION 1. CHEMICAL IDENTIFICATION PRODUCT NUMBERS: E400110, E400220 NAMES: Ozilla Ozone Sterilizer, 110 volts. Ozilla Ozone Sterilizer, 220 volts. COMMON SYNONYMS: Triatomic Oxygen, Trioxygen, O 3 CHEMICAL
How To Clean Up A Reactor Water Cleanup
General Electric Systems Technology Manual Chapter 2.8 Reactor Water Cleanup System TABLE OF CONTENTS 2.8 REACTOR CLEANUP SYSTEM... 1 2.8.1 Introduction... 2 2.8.2 System Description... 2 2.8.3 Component
EH&S. Sheet. Fact. Safe and Effective Use of Autoclaves. What are autoclaves? Factors for effective sterilization. Dry heat cycle - when to use
Please post or circulate Fact heet nvironment, ealth and afety Information for the Berkeley Campus No. 33 Revised 04/04/11 afe and ffective Use of Autoclaves Autoclaves are easy to use but can pose a safety
Guidance on safe use of Autoclaves
Safety Office Reviewed: Dec 2013 Reviewed: DD Month Year Guidance on safe use of Autoclaves 1. Hazards & Uses There are several different types of hazard associated with the use of autoclaves. The main
DETERMINE THE HAZARD VOLUME. The first step is to calculate the total volume of the hazard being protected.
SUBFLOOR PROTECTION CO 2 DESIGN GUIDE The Subfloor Application Profile (AP 006) provides guidance on fire protection requirements for spaces beneath raised floors. In the event of a fire, the Fike Carbon
CONTROL METHODS. There are five ways to control the release of asbestos fibers:
Control Methods CONTROL METHODS When asbestos containing materials are found in a building, the owner must decide which method or methods will be used to deal with the asbestos. The decision will be based